User Guide for TOSHIBA models including: LF654-LF620F Electromagnetic Flowmeter, LF654-LF620F, Electromagnetic Flowmeter, Flowmeter

Electromagnetic Flowmeter

[PDF] Electromagnetic Flowmeter - Toshiba

Introduction. The electromagnetic flowmeter uses Faraday's Law of electromagnetic induction to measure the process flow. The device consists of two units: a ...


File Info : application/pdf, 14 Pages, 893.20KB

PDF preview unavailable. Download the PDF instead.

TIC-LF654U
Mount Anywhere Series - Flanged
Electromagnetic Flowmeter

LF654 /LF620F LF654 /LF622F 1/2" to 18" (15 to 450 mm)

Introduction
The electromagnetic flowmeter uses Faraday's Law of electromagnetic induction to measure the process flow. The device consists of two units: a detector, through which the fluid measured flows and in which low-level signals proportional to flow rates are obtained; and a converter, which supplies excitation current to the detector, and amplifies the signals from the detector and then processes and converts the signals into the 4­20 mAdc current signal or communication signal*1&2. The meter features a Mount-Anywhere magnetic field distribution technology, the meter is highly immune to upstream flow disturbances. Combined with a multi-functional converter LF620 (combined type) or LF622 (separate type) equipped with its Noise-Sentry original noise-suppression circuit and advanced algorithms. The LF654 has a very high tolerance to noise, giving the unit a very stable output even for slurry fluid measurement. IR (Infrared) switches enable parameter setting of the converter without removing the cover. Flow direction can be set in either way, and its unique 128 x 128 dot matrix LCD display allows the LCD to be rotated electronically to 90, 180, and 270 degrees without opening the cover.
*1: HART protocol (Highway Addressable Remote Transducer) is a communication protocol for industrial sensors recommended by the HCF (HART Communication Foundation).
*2: Modbus is the communication protocol. Physical layer is RS485.

Combined type

Separate type

Figure1. Configuration

LF654/LF620F

LF654

LF622F

Figure2. LF654 Mount-Anywhere Series Flowmeters

For NSF certified products (see Table 4)
Cable gland openings have only dust caps which are not water tight. Water tight status is not met until properly wired and connected.
Specifications
 Overall Specifications Measurement range in terms of flow velocity:
1.0 ft/s to 32.8 ft/s (0.3 m/s to 10 m/s).
0.3 ft/s to 1.0 ft/s (0.1 m/s to 0.3 m/s) range is available optionally. Accuracy: < 1/2" to 18" ( 15mm to 450mm) > ±0.2 % of Rate*
* This pulse output error result is established under standard operating conditions at Toshiba admitted flow calibration facility. (NIST Traceable)
* Individual meter measurement error may vary up to ±0.5% of Rate at 1.64 ft/s (0.5m/s) or more and ±0.3% of rate ±0.039 inch/s (1mm/s) at 1.64 ft/s or less.
* Current output: plus ± 8µA (0.05% of span.) * Refer to individual calibration data for each individual meter's
measurement error.

TIC-LF654U

TIC-LF654U
Fluid conductivity:
3µS/cm minimum
Fluid temperature:
-4 to 248 °F (-20 to +120 °C): PFA lining -4 to 104 °F (-20 to +40 °C): Polyurethane lining * Consult Toshiba before using the meter at the high temperature, because the product lifetime may be shortened. Ambient temperature: -40 to 140 °F (-40 to +60 °C):
Separate type for PFA lined flowmeter -4 to 140 °F (-20 to +60 °C):
Combined type for PFA lined flowmeter
-4 to 140 °F (-20 to +60 °C): PU lined flowmeters
Structure: Standard -- IP 67 and NEMA 4X Option -- IP68 and NEMA 6P Submersible type allow for accidental submergence up to 15m for 48 hours. PFA and Polyurethane lined detector tubes are NEMA 6P/IP68 compliant when a TOSHIBA-approved Potting kit is properly Field or Factory installed.
NOTE: PFA lining detector shall become valid for the IP68/NEMA 6P function after being connected to the pipeline. It needs to avoid being put under the rain or water by itself before connecting. Power consumption:
AC100-240:MAX12W(27VA)
DC24: MAX16W
With communication function Approved hazardous location certifications:
Model: LF654/LF620F and LF654/LF622F
cFMus Nonincendive for use in hazardous (classified) locations:
Class I, II, III, Division 2, Groups A-G Detector and converter combination:
LF654/LF620F: Combined type with Ex approval of Class I, II, III, Division 2 (cFMus).
LF654/LF622F: Separate type with Ex approval of Class I, II, III, Division 2 (cFMus).
Mount-Anywhere Technology: With TOSHIBA's unique magnetic field distribution technology, the meter is highly immune to upstream flow disturbances.
A minimum of 1D (one diameter) length of upstream straight pipe from the flange and 0D (zero diameter) length of downstream straight pipe from the flange are required to maintain the specification performance.
2

Note: The test results were obtained and demonstrated at TOSHIBA's flow calibration facility, Fuchu Japan.
Drinking water approvals: NSF/ANSI standard 61 (see Table 4)
 Model LF654 Detector Mounting style: Flange connection type Fluid pressure:
-15 psi or -1.0 bar (-0.1 MPa) to the nominal pressure of the connection flange (see Figure 2)
Figure 2 Nominal pressure and fluid temp Connection flange standards:
ASME B16.5 class 150, ASME B16.5 class 300 EN1092-1 PN10, EN1092-1 PN16 Principal materials: Case -- carbon steel Flange material -- carbon steel Linings --
1/2" to 18" (15 to 450mm): PFA (NSF certified) 1/2" to 18" (15 to 450mm): PU (NSF certified : over 4"(100mm))
Note: PFA liners are mechanically retained for full vacuum service (2 1/2" to 18" (65mm to 450 mm)).
Electrodes -- Type-Super smooth, polished with self-cleaning finish, and non-stick shape 316L stainless steel (std. for PU lining) Hastelloy C equivalent (std. for PFA lining)
Note: Electrodes are mechanically buffed and electro-chemically polished.
Grounding rings -- 316 stainless steel (std.)
Note: See Table 4 for optional materials and other

related information.
Measuring tube material -- 304 stainless steel Terminal box material -- Aluminum alloy (for
separate type)
Coating: Corrosion-resistant resin coating (std.) gray colored
Dimensions and weights: See Figure 3, 4, 5, and 6.
Cable connection port: for separate type detectors. Cable gland -- LF654(with cFMus):Not provided, 1/2­14NPT male screws are required.
 Model LF620 and LF622 converters Input signals
Analog signal -- the voltage signal from detector, proportional to process flow rate (for LF622 separate type converter).
Digital input DI Signal type: 20 to 30Vdc voltage signal Input resistance: 10k Number of inputs: one point
Note: DI cannot be used with the Modbus communication.
DI function -- One of the following functions can be assigned to the DI signal.
·Range switching -- Selects either the higher or lower range in the unidirectional or bidirectional 2-range setting.
·Totalizer control -- `Starts/Stops' or `Resets /Starts'operation in the built-in totalizer.
·Fixed-value outputs --Outputs fixed-values for current and pulse outputs for loop check.
·Zero adjustment -- Executes zero adjustment (on-stream at zero flow rate).
Output signals
Current output: 4­20mAdc (load resistance 0 to 750)
Digital outputs -- Two points are available as follows.
Digital output DO1: Output type: Transistor open collector Number of outputs: One point Output capacity: 30Vdc, 200mA maximum
Note: DO1 cannot be used if Modbus communication connection is 3 lines. (Refer to table 6 for details)
Digital output DO2 :

TIC-LF654U
Output type: Solid-state relay output (non-polarity)
Number of outputs: One point Output capacity: 150Vdc, 150mA maximum or 150Vac (peak to peak), 100mA maximum
Note: DO2 cannot be used with the Modbus communication. (Refer to table 6 for details)
DO1 and DO2 functions -- One of the following functions can be assigned to DO1 and/or DO2 .
· Pulse output (available only for DO1, DO2) Pulse rate: MAX 10kHz (10000pps)(DO1) MAX 100Hz (100pps)(DO2) (Over 1kpps, auto-setting) Pulse width: 0.3 to 500ms (but it is 40% or less of the full-scale cycle. )
Note: The same and simultaneous pulse is not available between DO1 and DO2.)
· Multi-range selection outputs (Note 1)
· High, High high, Low, and/or Low low alarm outputs (Note 2)
· Empty pipe alarm output (Note 2)
· Preset count output
· Converter failure alarm output
Note 1: Two outputs (DO1 and DO2) are needed for 4-range switching and forward/reverse 2-range switching.
Note 2: Normal Open (default set) or Normal Close is selected for alarm outputs when programming. When power failure occurs, unit will be fault to Normal Open.
Communications output: · HART (std.) -- Digital signal is superimposed on 4­20mAdc current signal as follows: Conforms to HART protocol Load resistance: 240 to 750 Load capacitance: 0.25µF maximum Load inductance: 4mH maximum
· MODBUS (opt.) Physical layer : RS485 Protocol : Modbus Mode : RTU Baudrate : 4800, 9600, 19200bps Data length : 8bit Parity bit : None, Odd, Even Stop bit : 1bit, 2bit Error check : CRC-16 Max. station number : 32(with Master device) Max. cable length : 1.2km (Note)
Note: This length is the specification of 3 line
3

connection.

LCD display:
Full dot-matrix 128×128 dot LCD display (backlight provided) A parameter change will rotate the display.
Parameter settings -- Parameters can be set as follows:
· IR Switches: Three key switches are provided to set configuration parameters.
· Digital communication: HART, or Modbus is needed to set parameters.
Counter control: If the digital input is set for counter control, counter control is available for the integrated value and the pulse output.
Zero adjustment: Zero point adjustment can be started by pressing the switch in the converter.
Damping: 0.5, 1 to 60 seconds (selectable in 1 second increments)
"Converter Field re-verification" Mag-Prover ­ Toshiba's Zero span verification tool allows unit to be re-verified using an internal software program. The meter's excitation current is a NIST traceable parameter. This parameter can be verified in the field through the converter to verify the meter is still within factory calibration. (For more information contact Toshiba International Corp.)

Conditions when power fails:

Parameter setting values are stored in non­volatile memory and the values will be restored when the power returns to normal condition. The outputs and display will remain as follows when power fails.

· Current output: 0mAdc

· Digital output: OFF

· LCD display: No display

· HART:

No communication

· Modbus:

No communication

Power supply: One of the following can be selected:

TIC-LF654U
100 to 240Vac (allowable voltage range: 80 to 264Vac 50/60Hz)
24Vdc (allowable voltage range: 18 to 36Vdc) or 110Vdc (allowable voltage rangel:90 to 130Vdc)
Surge protection: Arresters are installed in the power supply, digital input/outputs circuit and current signal output circuit to help protect the meter from lightning and improve personnel safety.
Confirmed by following tests
IEC 61000-4-2 Electrostatic discharge immunity test
IEC 61000-4- Electrical first transient/burst immunity test
IEC 61000-4-5 Serge immunity test
Case: Aluminum alloy (equal to IP 67)
Coating: Acrylic resin-baked coating, pearl­gray colored
Cable connection port: Cable glands -- LF620F and LF622F with cFMus Approval: Not provided, 1/2­14NPT male threads are required.
Vibration resistance: No resonance to the following levels of vibration: · 10 to 150Hz with acceleration of 9.8m/s2 · Vibration of 30Hz with 29.4 m/s2 in 4h in each direction will not cause any defect to unit.
Note: Avoid using the flowmeter in an environment with constant vibration.
Dimensions and Weights: See Figure 7 (for Separate type)
MTBF: Converter: 220,000 hours (25 years) at 77 °F (25 °C) based on strict military specification MIL-HDBK-217F Detector: 350,000 hours (40 years) at 77 °F (25 °C) based on strict military specification MIL-HDBK-217

4

Installation
 Dimensions

TIC-LF654U

Unit: inch (mm)

Note1: Eye bolts are provided at the top for flowmeters sized 8" (200mm) or above, and further, a roll-prevention base is provided for flowmeters sized 10" (250mm) or larger.
Note2: Cable glands are not provided for LF654 of cFMus approved type. Refer to the cable connection port at converter. Note3: 1 inch = 25.4mm

ASME B 16.5 class 150 dimensions:

Meter size L1

L2

L3 No. of

(inch) (inch) (inch) (inch) bolts

1/2

5.51 8.07 9.82

4

1

6.30 8.31 10.43

4

1-1/4

7.87 8.62 10.95

4

1-1/2

6.69 8.66 11.16

4

2

7.09 9.09 12.09

4

2-1/2

7.87 9.29 12.80

4

3

9.06 9.69 13.42

4

4

9.45 10.28 14.77

8

5

9.84 10.71 15.71

8

6

10.24 11.34 16.83

8

8

11.81 12.24 18.99

8

10

13.78 13.15 21.14 12

12

15.75 14.65 24.14 12

14

17.72 14.88 25.35 12

16

19.69 15.79 27.18 16

18

21.65 16.69 29.17 16

Weight (lbs)
approx. 11.0 approx. 16..0 approx. 20.0 approx. 20.0 approx. 29.0 approx. 38.0 approx. 45..0 approx. 64.0 approx. 73.0 approx. 93.0 approx. 139.0. approx. 207.0 approx. 315.0 approx. 403.0 approx. 509.0 approx. 617.0

EN 1092-1 PN 16 dimensions:

Meter size L1

L2

L3

(mm)

(mm) (mm) (mm)

15

140

203

251

25

160

209

272

32

200

217

285

40

170

218

288

50

180

232

310

65

200

237

325

80

230

255

347

100

240

262

367

125

250

273

399

150

260

285

425

200

300

310

475

250

350

335

535

300

400

365

588

350

450

374

619

400

500

397

677

450

550

420

730

No. of bolts
4 4 4 4 4 4 8 8 8 8 12 12 12 16 16 20

Weight (kg)
approx. 6.0 approx. 7.5 approx. 10.0 approx. 10.5 approx. 14.5 approx. 16.5 approx. 21.5 approx. 26.5 approx. 31.0 approx. 37.5 approx. 54.0 approx. 78.0 approx. 117.0 approx. 156.5 approx. 202.5 approx. 249.5

Figure 3. LF654/LF620F combined type flowmeters Meter Sizes 1/2" (15) to 18" (450mm) for Toshiba lay length

5

TIC-LF654U

Unit: inch (mm)
Note1: Eye bolts are provided at the top for flowmeters sized 8" (200mm) or above, and further, a roll-prevention base is provided for flowmeters sized 10" (250mm) or larger.
Note2: Cable glands are not provided for LF654 of cFMus approved type. Refer to the cable connection port at converter.  Note3: 1 inch = 25.4mm

ASME B 16.5 class 150 dimensions:

Meter size L1

L2

L3 No. of

(inch) (inch) (inch) (inch) bolts

1/2

7.87 8.07 9.82

4

1

7.87 8.31 10.43

4

1-1/4

7.87 8.62 10.95

4

1-1/2

7.87 8.66 11.16

4

2

7.87 9.09 12.09

4

2-1/2

7.87 9.29 12.80

4

3

7.87 9.69 13.42

4

4

9.84 10.28 14.77

8

5

9.84 10.71 15.71

8

6

11.81 11.34 16.83

8

8

13.78 12.24 18.99

8

10

17.72 13.15 21.14 12

12

19.69 14.65 24.14 12

14

21.65 14.88 25.35 12

16

23.62 15.79 27.18 16

18

23.62 16.69 29.17 16

Weight (lbs)
approx. 11.0 approx. 16..0 approx. 20.0 approx. 20.0 approx. 29.0 approx. 38.0 approx. 45..0 approx. 64.0 approx. 73.0 approx. 93.0 approx. 139.0. approx. 207.0 approx. 315.0 approx. 403.0 approx. 509.0 approx. 617.0

EN 1092-1 PN16 dimensions:

Meter size L1

L2

L3

(mm)

(mm) (mm) (mm)

15

200

203

251

25

200

209

272

32

200

217

285

40

200

218

288

50

200

232

310

65

200

237

325

80

200

255

347

100

250

262

367

125

250

273

399

150

300

285

425

200

350

310

475

250

450

335

535

300

500

365

588

350

550

374

619

400

600

397

677

450

600

420

730

No. of bolts
4 4 4 4 4 4 8 8 8 8 12 12 12 16 16 20

Weight (kg)
approx. 6.0 approx. 7.5 approx. 10.0 approx. 10.5 approx. 15.0 approx. 17.0 approx. 21.5 approx. 26.5 approx. 31.0 approx. 38.0 approx. 55.5 approx. 83.5 approx. 125.5 approx. 166.0 approx. 215.0 approx. 257.0

Figure 4. LF654/LF620F combined type flowmeters Meter Sizes 1/2" (15) to 18" (450mm) for ISO lay length

6

TIC-LF654U

Unit: inch (mm)
Note1: Eye bolts are provided at the top for flowmeters sized 8" (200mm) or above, and further, a roll-prevention base is provided for flowmeters sized 10" (250mm) or larger.
Note2: Cable glands are not provided for LF654 of cFMus approved type. Refer to the cable connection port at converter. Note3: 1 inch = 25.4mm

ASME B 16.5 class 150 dimensions:

Meter size L1

L2

L3 No. of

(inch) (inch) (inch) (inch) bolts

Weight (lbs)

1/2

5.51

6.77

8.54

4

approx. 9.0

1

6.30

7.01

9.13

4

approx. 14.0

1-1/4

7.87

7.32

9.65

4

approx. 18.0

1-1/2

6.69

7.36

9.88

4

approx. 18.0

2

7.09

7.80 10.79

4

approx. 27.0

2-1/2

7.87

7.99 11.50

4

approx. 36.0

3

9.06

8.39 12.13

4

approx. 42.0

4

9.45

8.98 13.50

8

approx. 62.0

5

9.84

9.41 14.41

8

approx. 71.0

6

10.24 10.04 15.55

8

approx. 91.0

8

11.81 10.94 17.72

8

approx. 137.0

10

13.78 11.85 19.84

12

approx. 205.0

12

15.75 13.35 22.83

12

approx. 313.0

14

17.72 13.58 24.09

12

approx. 401.0

16

19.69 14.49 25.91

16

approx. 507.0

18

21.65 15.39 27.91

16

approx. 614.0

Meter size (mm) 15 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450

EN1092-1 PN 16 dimensions:

L1 (mm)

(L2) (mm)

L3 (mm)

No. of bolts

140

170

218

4

160

176

239

4

200

184

252

4

170

185

255

4

180

199

277

4

200

204

292

4

230

222

314

8

240

229

334

8

250

240

366

8

260

252

392

8

300

277

442

12

350

302

502

12

400

332

555

12

450

341

586

16

500

364

644

16

550

387

697

20

Weight (kg)
approx. 4.0 approx. 5.5 approx. 8.0 approx. 8.5 approx. 12.5 approx. 14.5 approx. 19.5 approx. 24.5 approx. 29.0 approx. 35.5 approx. 52.0 approx. 76.0 approx. 115.0 approx. 154.5 approx. 200.5 approx. 247.5

Figure 5. Separate type detectors LF654 Meter sizes 1/2" (15) to 18" (450mm) for Toshiba lay length

7

TIC-LF654U

Unit: inch (mm)
Note1: Eye bolts are provided at the top for flowmeters sized 8" (200mm) or above, and further, a roll-prevention base is provided for flowmeters sized 10" (250mm) or larger.
Note2: Cable glands are not provided for LF654 of cFMus approved type. Note3: 1 inch = 25.4mm

ASME B 16.5 class 150 dimensions:

Meter size L1

L2

L3 No. of

Weight

(inch) (inch) (inch) (inch) bolts

(lbs)

1/2

7.87

6.77

8.54

4

approx. 9.0

1

7.87

7.01

9.13

4

approx. 14.0

1-1/4

7.87 7.32

9.65

4

approx. 18.0

1-1/2

7.87 7.36

9.88

4

approx. 18.0

2

7.87 7.80 10.79

4

approx. 27.0

2-1/2

7.87 7.99 11.50

4

approx. 36.0

3

7.87 8.39 12.13

4

approx. 42.0

4

9.84 8.98 13.50

8

approx. 62.0

5

9.84 9.41 14.41

8

approx. 71.0

6

11.81 10.04 15.55

8

approx. 91.0

8

13.78 10.94 17.72

8

approx. 137.0

10

17.72 11.85 19.84

12

approx. 205.0

12

19.69 13.35 22.83

12

approx. 313.0

14

21.65 13.58 24.09

12

approx. 401.0

16

23.62 14.49 25.91

16

approx. 507.0

18

23.62 15.39 27.91

16 approx. 614.0

Meter size (mm) 15 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450

EN1092-1 PN 16 dimensions:

L1

(L2)

L3

No. of

Weight

(mm) (mm) (mm) bolts

(kg)

200

170

218

4

approx. 4.0

200

176

239

4

approx. 5.5

200

184

252

4

approx. 8.0

200

185

255

4

approx. 8.5

200

199

277

4

approx. 13.0

200

204

292

4

approx. 15.0

200

222

314

8

approx. 19.5

250

229

334

8

approx. 24.5

250

240

366

8

approx. 29.0

300

252

392

8

approx. 36.0

350

277

442

12

approx. 53.5

450

302

502

12

approx. 81.5

500

332

555

12

approx. 123.5

550

341

586

16

approx. 164.0

600

364

644

16

approx. 213.0

600

387

697

20 approx. 247.5

Figure 6. Separate type detectors LF654 Meter sizes 1/2" (15) to 18" (450mm) for ISO lay length

8

Attachment LCD display

TIC-LF654U
Unit : inch(mm) Weight: Approx. 7 lb (3.5 kg)
I/O cable ground Excitation cable ground

Plate

IR Switch

Power supply cable ground

Signal cable ground

Option cable ground

Note: Cable glands are not provided for LF622F cFMus approved type. Refer to the part Cable connection port at converter.
Note: 1 inch = 25.4mm

Figure 7. Separate type converter LF622F
 External Connections  Combined type LF654/LF620F flowmeters

Instrument panel : Ordered separately
Grounding with 100 or less ground resistance Power switch (External double-pole power switch)

Power supply Current output (420mAdc)

or Modbus

D(2i0gita3l 0inVpduct) Digital output 2

Signal common for DI and DO

Digital output 1

Grounding with 100 or less ground resistance

I/O cable Power cable

AWG wire 5.5mm2 or more
Grounding with 100 or less ground resistance
NOTE: In the case of the integral type, the signal line ( A, B, G ) and the excitation line ( E, X, Y ) are
the connector joints.

*1 Locate an external double-pole power switch on the power line near the flowmeter within easy reach of operation. Use the appropriate switch rating as shown below: Switch rating: 250Vac, 6A or more In rush current: 15A or more
Figure 8. Combined type LF654/LF620F flowmeters Wiring Diagram
9

 Separate type LF654/LF622F flowmeters

TIC-LF654U

Instrument panel : Ordered separately
Grounding with 100 or less ground resistance Power switch (External double-pole power switch)

Power supply Current output (420mAdc)

or Modbus

Digital input (2030Vdc) Digital output 2

Signal common for DI and DO Digital output 1

Grounding with 100 or less ground resistance

I/O cable Power cable

AWG wire 5.5mm2 or more Grounding with 100 or less ground resistance Thick walled steel conduit Signal cable (2-wire shielded hard-rubber sheathed cable)
Excitation cable (3-wire shielded Chloroprene rubber cable)
Connected detector

Figure 9. Separate type LF654/LF622F flowmeters wiring Diagram

Table 1. LF620F and LF622F Converters Signal Table

Symbol L1 () L2 () GND
FG DI DO1 DO2 COM

Description
Power supply
Ground (for arrester) Frame ground
Digital Input (2030Vdc) Digital Output 1 Digital Output 2
Signal Common for DI, DO1, DO2

Cable Power cable (CVV)
I/O cable (CVV-S)

 Current Output (420mAdc)



X Y E

Excitation Output

Excitation cable (for LF622F only)

A B G

Signal Input

Signal cable (for LF622F only)

T+

Modbus(+)

Twisted-pair polyethylene

T-

Modbus(-)

insulated vinyl sheath cable

TG

Modbus(GND)

(JKEV,AWG24(0.2mm2))

Note: The symbol of the terminal is changed as follows for Modbus.

DO2  T+, DI  T-, COM  TG

10

TIC-LF654U

 Wiring Precautions
(1) Explosion-proof type flowmeters are not provided with cable glands. Refer to the part Cable connection port at detector and converter.
(2) Connect the grounding wire (IV wire 5.5mm² or more) to a good earth ground (100 or less ground resistance). Make the wire as short as possible. Do not use a common ground shared with other equipment where earth current may flow. Independent earth ground is recommended.
(3) The allowable cable lengths between the detector and converter for the separate type flowmeter depend on the electrical conductivity of the object fluid. See Figure 10.
(4) DO1, DO2, and DI use the same common terminal (COM). This COM can not be connected to other equipments which have their own ground terminal. (Power supply for connecting to DI or DO, etc...) Need to wire separately.
 Wiring Precautions (Modbus)
(1) For the wiring path, avoid places near electrical equipment that may cause electromagnetic induction or electrostatic induction interference (such as a motor, transformer and wireless transmitter).
(2) General cables are designed for indoor use where cables are not exposed to humidity, rain, etc. When you install cables, make sure to check the operating conditions such as the operating temperature range of the cable by contacting its manufacturer.
(3) When you carry out cable end treatment, use a dedicated cable stripper to avoid the core wire of the cable being nicked or damaged. In addition, for cables, be careful of allowable maximum bend diameter. (Do not allow excessive twisting or bending of cables).

(4) The electromagnetic flowmeter is not equipped with terminating resistors. Use the terminating resistor unit for Modbus or junction box, if.
(5) Only one Modbus cable goes cable gland of the Electromagnetic Flowmeter. Please use the junction box at system configuration.
(6) Install a terminator to flowmeter that connected to the end of Modbus network.

Allowable cable length (m)

300 200 100
50 30 20
10

5

3
3 5 10 20 30 50 100 200 Conductivity (S/cm)

Figure 10. Electrical Conductivity and Cable Length

 Meter Size

To select the meter size:

See Table 2 and 3 to find meter sizes within the velocity of 0.3 to 39.4 ft/s (0.1 to12m/s) for a specified full-scale (measuring range high limit) flow. Select one that has its full-scale velocity between 3.0 and 10 ft/s (1 and 3m/s).
Note: Make sure the full-scale flow rate used for the final planning stage stays within 39.4ft/s (12m/s) in terms of flow velocity.

Size (inch)
1/2' 1 1 ¼ 1 ½ 2 2 ½ 3 4 5 6 8 10 12 14 16 18

Table 2. Flow Rate and Flow velocity

(English unit)

Unit: gal/min

Flow rate

0.328 ft/s 0.98 ft/s 3.0ft/s 10 ft/s 39.4 ft/s

0.2801 0.8403 2.561 8.532 33.61

0.7781

2.334 7.115 23.72 93.37

1.275

3.824 11.66 38.86 153.0

1.992

5.975 18.21 60.71 239.0

3.112

9.337 28.46 94.86 373.5

5.260

15.78 48.09 160.3 631.2

7.967

23.90 72.85 242.8 956.1

12.45

37.35 113.8 379.4 1,494

19.45

58.35 177.9 592.9 2,334

28.01

84.03 256.1 853.8 3,361

49.80

149.4 455.3 1,518 5,975

77.81

233.4 711.5 2,372 9,337

112.0

336.1 1,025 3,415 13,445

152.5

457.5 1,394 4,648 18,300

199.2

597.5 1,821 6,071 23,902

252.1

756.3 2,305 7,684 30,251

11

Table 3. Flow Rate and Flow velocity (SI unit)

Unit: m3/h

Flow rate

Size (mm)

0.1 m/s

0.3 m/s

1.0 m/s

3.0 m/s

12 m/s

15 0.06362 0.1908 0.6361 1.908 7.634

25

0.1767 0.5301 1.767 5.301 21.21

32

0.2895 0.8686 2.895 8.686 34.74

40

0.4523 1.357 4.523 13.57 54.29

50

0.7067 2.120 7.067 21.20 84.82

65

1.195 3.583 11.95 35.83 143.4

80

1.809 5.428 18.09 54.28 217.1

100

2.827 8.482 28.27 84.82 339.3

125

4.417 13.25 44.17 132.5 530.1

150

6.361 19.08 63.61 190.8 763.4

200

11.31 33.93 113.1 229.3 1,357

250

17.67 53.01 176.7 530.1 2,121

300

25.45 76.34 254.5 763.4 3,054

350

34.64 103.9 346.4 1,039 4,156

400

45.23 135.7 452.3 1,357 5,429

450

57.25 171.7 572.5 1,717 6,871

 About establishment environment
Do not store or install the flowmeter: · Where there is direct sunlight. · Where excessive vibration or mechanical shock occurs. · Where high temperature or high humidity conditions exist. · Where corrosive atmospheres exist. · Places that can be submerged under water. · When placing the flowmeter temporarily on the floor, support it, i.e., with a block so that the
flowmeter does not topple over.
In areas like the following, there may be the case that
infrared switches do not function correctly. (If these
are unavoidable, use an appropriate cover.)
(1) Where unit (operation panel) is exposed to direct
sunlight, reflection of light onto window pane
and diffused light reflection.
(2) Where smoke and steam may occur.
(3) Where exposed to direct snow, ice or mud.

TIC-LF654U
 Ordering Information 1. When ordering the LF654 series flowmeters, refer to Tables 4 and 5 (Type Specification Codes). An entry must be made for each of the columns in each of these tables. 2. Fluid characteristics: (1) Type of fluid to be measured and its characteristics (2) Fluid temperature (3) Fluid pressure (4) Electrical conductivity of the fluid 3. Measuring range 4. I/O function setting 5. Ordering scope Flow calibration data 6. Other items Specifications other than standard items
Consult a Toshiba representative when choosing materials for lining, electrodes, and grounding rings.
Toshiba International Corp. (Houston) stocks Hazardous location certification type flowmeters as standard inventory.

14

TIC-LF654U

Table 4. Specification Code (Flange type detector LF654 Series)

Model

Specification Code

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Description

LF 6 5
4
D E S F G W H J U K L M N P Q R
L M
C D 1 2
B C D E F
C
P

Flange type electromagnetic flowmeter detector
Usage cFMus Division 2 Hazardous Location Meter size ½"(15mm) 1"(25mm) 1¼"(32mm) 1½"(40mm) 2"(50mm) 2½"(65mm) 3"(80mm) 4"(100mm) 5"(125mm) 6"(150mm) 8"(200mm) 10"(250mm) 12"(300mm) 14"(350mm)
16"(400mm)
18"(450mm) Mounting Style (Note1)
Detector/Converter combined type Detector/Converter separate type
Connection flange standard, Overall length ASME B 16.5 class 150, ISO length ASME B 16.5 class 300, ISO length (Note 5) ASME B 16.5 class 150, Toshiba length ASME B 16.5 class 300, Toshiba length Electrode Material (Note2)(Note 3) 316L stainless steel (Standard for Polyurethane lining) Ti (titanium) Pt-Ir (platinum/iridium) (Note 6) Ta (tantalum) (Note 6) Hastelloy C (Equivalent) (Standard for PFA lining) Lining Materials (Note2) (Note 4)
PFA
PFA (NSF certified)

N

Polyurethane (NSF certified)

U
C D E F G H
A

Polyurethane
Grounding Ring Material (Note 6) 316 stainless steel 316L stainless steel Ti (titanium) Ta (tantalum) (Note 6) Pt-Ir (platinum/iridium) (Note 6) Hastelloy C (Equivalent) Flow and calibration velocity range 1.0 to 32.8 ft/s (standard range calibration)

Excitation and Signal Cables

A

not provided

Coating

F PU coating pearl-gray colored

*Direct burial detector coating

Contact Toshiba International Corp. (Houston)

Lining

PU

PFA







































































































­













­



­



­





­



­





































Size code explanation:  : Object : Standard : Option ­: Not available Note1: In case of LF654 with cFMus approval, Cable glands are not provided. Note2: Consult with Toshiba and your customer when choosing wetted parts materials. Note3: 316L stainless steel electrodes are provided with NSF-approved PU liner, sizes 4" to 18".
Hastelloy C electrodes are provided with NSF-approved PFA liner. Note4: Potting kit is available for IP68/NEMA6P submersible option with remote type NPU/PU(1/2~18inch) & PFA(2-1/2~18 inch) lined Detector. Note5: ASME B 16.5 class 300 flange is NOT available in 3" & 5" ISO length. Note6: Pt-Ir are available for less than 2" (50mm). Ta available up to 6".

13

Table 5. Specification Code for converters

TIC-LF654U

Model

Specification Code

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Contents

LF6 2

Electromagnetic flowmeter converter

0

Combined (Integral) type

2

Separate (Remote) type

Purpose

F

cFMus class I, Division 2 approved

Shape

B

Standard type with case (2022 renewed version)

Converter mounting fitting

A

None

C

Panel, Accessory for wall mounting (BNP material: SUS304)

E

Accessory for pipe installation (BNP material: SUS304)

Digital input/output

2

Digital output points 2 (DO1+DO2) +Digital input point 1 (DI)

Current output and Communication function(Note1)

1

Current output + HART communication

3

Current output + Modbus (RS485) communication

LF620 LF622 type type



­

­















­



­















Power supply(Note2)

1

100Vac-240Vac 50/60Hz, 110Vdc

2

24Vdc

3

110Vdc













Instruction manual

E

English





Code explanation: : Standard : Option ­: Not available

Note 1:When Modbus communication is provided, digital output points 1(DO1) and digital output points (DO2),

digital input point 1(DI), HART communication cannot be used.

Refer to Table 6 for more details.

Note2: Select 110Vdc for test report inspected under the condition of 110Vdc.

Table6. Communication functions and output selection table

Selection of Function

Availability of outputs

Code (10th digit)

Selected

4-20mAdc DO1

DO2

DI

Communication

1

HART









3

Modbus









(Note)

Code explanation: :Available :Not Available

Note: When digital output 1 function and Modbus communication function are used at one time, TG (signal ground) of the Modbus communication function cannot be connected (2 line connection).

ISO9001 and ISO14001 are certified.
Misuse of this product can result in damages to property or human injury. Read related manuals carefully before using this product.

Specifications are subject to change without notice. Printed in Japan Feb., 2024