Instruction Manual for Mircom models including: MIX-2351RAPA, Advanced Protocol Intelligent Photoelectric Smoke Sensor, MIX-2351RAPA Advanced Protocol Intelligent Photoelectric Smoke Sensor, Intelligent Photoelectric Smoke Sensor, Photoelectric Smoke Sensor, Smoke Sensor, Sensor

Click here to download

Mircom MIX-2351RAPA Installation Manual - English - Fire Alarm Resources - Free fire alarm PDF manuals, documents, installation instructions, and technical specifications


File Info : application/pdf, 2 Pages, 891.63KB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676770618
I56-6725-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

MIX-2351RAPA

Advanced Protocol

Mircom Technologies Ltd.

Intelligent Photoelectric Smoke Sensor

25 Interchange Way, Vaughan ON, L4K 5W3 Tel: 905-660-4655, FAX: 905-660-4113

with Remote Test Capability in Duct Applications

SPECIFICATIONS

Operating Voltage Range: Operating Current @ 24 VDC: Maximum Alarm Current: Maximum Current: Operating Humidity Range: Operating Temperature Range: Air Velocity: Height: Diameter: Weight: Isolator Load Rating:

15 to 32 VDC 200 uA (one communication every 5 seconds with green LED blink on communication) 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on) 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on) 10% to 93% Relative Humidity, Non-condensing 32°F to 122°F (0°C to 50°C), -4°F to 158°F (-20°C to 70°C) in duct applications 0 to 4000 ft./min. (0 to 1219.2 m/min.) 2.0 (51 mm) installed in B300A-6 Base 6.2 (156 mm) installed in B300A-6 Base; 4.1 (104 mm) installed in B501A Base 3.4 oz. (95 g) 0.0063*

*Please refer to your isolator base/module manual for isolator calculation instructions.

Listed to CAN/ULC S529.

This sensor must be installed in compliance with the control panel system installation manual. The installation must meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with CAN/ULC S524.

GENERAL DESCRIPTION

MIX-2351RAPA is a plug-in type smoke sensor that combines a photoelectronic sensing chamber with addressable-analog communications. When used in duct applications with a DNRA, testing can be done remotely using approved System Sensor test accessories, eliminating the need for a test coil. The sensors transmit an analog representation of smoke density over a communication line to a control panel. Rotary dial switches are provided for setting the sensor's address.

FIGURE 1. ROTARY ADDRESS SWITCHES

6 7 89

5

10

4

11

3

12

2 1

0

13 1514

TENS

6789 5 4 3 2
10
ONES

C0162-00

Two LEDs on the sensor are controlled by the panel to indicate sensor status. An output is provided for connection to an optional remote LED annunciator (P/N RA100ZA).

Note: Only System Sensor approved accessories may be used with the MIX-2351RAPA.

Mircom panels offer different features sets across different models. As a result, certain features of the photoelectric sensors may be available on some control panels, but not on others. MIX-2351RAPA supports Advanced Protocol and CLIP (Classic Loop Interface Protocol) mode. The possible features available if supported by the control panel are:

1. The sensor's LEDs can operate in three ways--on, off, and blinking­and they can be set to red, green, or amber. This is controlled by the panel.

2. The remote output may be synchronized to the LED operation or controlled independent of the LEDs.

3. Devices are point addressable up to 159 addresses.

Please refer to the operation manual for the ULC listed control panel for specific operation. The MIX-2351RAPA requires compatible addressable communications to function properly. Connect these sensors to listed-compatible control panels only.

SPACING

Mircom recommends spacing sensors in compliance with CAN/ULC S524. In low air flow applications with smooth ceilings, space sensors 30 feet apart (9.1 m). For specific information regarding sensor spacing, placement, and special applications, refer to CAN/ULC S524 or the System Smoke Detector Application Guide, available from Mircom.

NOTE: MIX-2351RAPA is also listed for use inside DNRA duct smoke detectors.

WIRING GUIDE
All wiring must be installed in compliance with the Canadian Electrical Code, applicable local codes, and any special requirements of the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mistakes and ease system troubleshooting. Improper connections will prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors. 1. Wire the sensor base (supplied separately) per the wiring diagram, Figure 2. 2. Set the desired address on the sensor address switches, see Figure 1. 3. Install the sensor into the sensor base. Push the sensor into the base while
turning it clockwise to secure it in place. 4. After all sensors have been installed, apply power to the control panel and
activate the communication line. 5. Test the sensor(s) as described in the TESTING section of this manual.

CAUTION
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers must be removed before the sensors can sense smoke. Remove sensors prior to heavy remodeling or construction.

FIGURE 2. WIRING DIAGRAM

Remote Annunciator
+-

CAUTION: Do not loop wire under terminal 1 or 2. Break wire run to supervise connections.

(+)

++

2­

RA
3

1

+2+ ­

RA
3

1

+2+ ­

RA

1

3

ULC Listed Compatible Control Panel

(­)

(­)

CLASS A OPTIONAL WIRING

(+)

TAMPER-RESISTANCE

C0129-11

MIX-2351RAPA includes a tamper-resistant capability that prevents removal from the base without the use of a tool. Refer to the base manual for details on making use of this capability.

1
firealarmresources.com

I56-6725-000 10/10/2020

TESTING
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when tested and maintained in compliance with CAN/ULC S536.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00) This sensor can be functionally tested with a test magnet. The test magnet electronically simulates smoke in the sensing chamber, testing the sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3. 2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor status. Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical documentation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry Sensitivity readings are available through the FACP. Refer to the manufacturer's published instructions for proper use.
Additionally, canned aerosol simulated smoke (canned smoke agent) may be used for smoke entry testing of the smoke detector. Tested and approved aerosol smoke products are:

Manufacturer HSI Fire & Safety SDi
No Climb

Model 25S, 30S (PURCHECK) SMOKE CENTURIAN, SOLOA4, SMOKESABRE, TRUTEST TESTIFIRE 2000

When used properly, the canned smoke agent will cause the smoke detector to go into alarm. Refer to the manufacturer's published instructions for proper use of the canned smoke agent.

CLEANING
Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
1. Remove the sensor to be cleaned from the system. 2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place. 3. Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7. 4. Remove the chamber cover/screen assembly by pulling it straight out. 5. Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber. 6. Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place. 7. Replace the cover using the LEDs to align the cover and then gently push-
ing it until it locks into place. 8. Reinstall the detector. 9. Test the detector as described in TESTING. 10. Reconnect disabled circuits. 11. Notify the proper authorities that the system is back on line.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
FIGURE 3. FEATURES OF THE PHOTO DETECTOR

Magnet Test
Marker
Base Alignment
Notch LED

CapRTaeebsmlteote

Base Alignment Notch

Magnet Test Marker

LED

FIGURE 4. CLEANING THE PHOTO DETECTOR

C2021-01

CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by manufacturer. Misuse or overuse of these products may have long term adverse effects on the smoke detector. Consult the canned smoke agent manufacturer's published instructions for any further warnings or caution statements.
C. Remote Test. MIX-2351RAPA can be remotely tested using the RTS151A or RTS151KEYA test accessories. Refer to the DNRA manual for wiring diagrams. Maximum test response time may be up to two communications from the panel.
A sensor that fails any of these tests may need to be cleaned as described under CLEANING, and retested. When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in operation.

Cover Removal
Tabs

Sensor Cover
Sensing Chamber Cover and Screen Sensing Chamber

C2022-00

SUPPLEMENTAL INFORMATION For Limitations of Fire Alarm Systems,
please go to: http://www.systemsensor.com/ en-us/Documents/I56-1558.pdf
Limitations of Fire Alarm Systems

FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: ­ Reorient or relocate the receiving antenna. ­ Increase the separation between the equipment and receiver. ­ Connect the equipment into an outlet on a circuit different from that to which the receiver is con-
nected. ­ Consult the dealer or an experienced radio/TV technician for help. This Class B digital apparatus complies with Canadian ICES-003.

Mircom® is a registered trademark of Mircom Technologies, Ltd. Testifire® is a registered trademark of SDi, LLC.

2

firealarmresources.com

DEVICE AND SYSTEM SECURITY Before installing this product ensure that the tamper seal on the packaging is present and unbroken and the product has not been tampered with since leaving the factory. Do not install this product if there are any indications of tampering. If there are any signs of tampering the product should be returned to the point of purchase. It is the responsibility of the system owner to ensure that all system components, i.e. devices, panels, wiring etc., are adequately protected to avoid tampering of the system that could result in information disclosure, spoofing, and integrity violation.
I56-6725-000 ©2020 Mircom. 10/10/2020



References

Adobe PDF Library 15.0 Adobe InDesign 15.1 (Windows)