EL-QE-E Quantum Edge Installation Guide

Antenna Installation

When selecting an antenna, consider radio proximity. Use Figure 1 as a guide for installing an antenna and attaching it to the EL-QE-E.

Figure 1. Antenna Installation

For maximum range, install the antenna above local obstructions. For short-range applications, install the antenna directly to the connector on top of the unit.

Antenna*

Connect Coax to building earth in accordance with 6.2 g) and 6.2 i) of IEC60728-11:2005

Stress Relief Loop

Surge Arrestor (recommended)

Coaxial Cable

EL-QE-E

GND

Mast

HAZLOC NOTICES

The EL-QE-E is suitable for use in hazardous locations that are rated Class I Division 2, Groups A, B, C, D or Zone 2 Group IIA, IIB, IIC.

The RF coaxial cable must be installed in a metallic conduit, per the US National Electrical Code (NEC) or NFPA.

The EL-QE-E must only be powered from an NEC Class 2 circuit or from a Class 2 power supply.

Internal Switches SW1 to SW6 Do not open the side access panel or operate any internal switches unless the area is known to be non-hazardous.

Specific Conditions of Use (X): The EL-QE-E must be installed in an enclosure that complies with the requirements of IEC60529 for IP54 and meets the enclosure requirements of EN50014 or EN60079-0.

To ensure effective heat dissipation, the EL-QE-E must be installed vertically with at least 25mm clearance on the right side.

WARNING - EXPLOSION HAZARD

Do not disconnect equipment while the circuit is live unless the area is known to be free of ignitable concentrations.

Substitution of any component may impair suitability for UL Class I Division 2 and for IEC Ex Zone 2.

NOTE

All connections must be SELV <50 Vac and <60Vdc.

Connecting to the module for configuration

Ports on the EL-QE-E

The following illustrations show the ports on the EL-QE-E:

Battery Temperature Monitoring

The EL-QE module monitors the temperature and disables battery charging at low temperatures. An internal temperature sensor can be used when the battery is located close to the EL-QE module.

For applications where the battery is remote from the module, connect an NTC thermistor to the Battery Temp Sense. Recommended type: Vishay NTCLE400E3103H.

Select battery type (LiFePO4 Lithium Iron Phosphate or PbSO4 Lead-Acid) using the switches under the side access panel. Battery charging is disabled when the measured temperature falls below the temperature threshold for the battery.

Battery Type SelectionDisable TemperatureThermistor ResistanceSW6 Position
PbSO4 (Lead-Acid)-20 °C96,500 ΩA (up)
LiFePO4 (Lithium-Iron)0 °C32,500 ΩB (down)

Expansion I/O connection

115S Modules connect via the RS-485 connection. The +12V supply connection can also be used to power the 115S modules directly from the EL-QE module.

Power supply wiring

The "BAT-" and "SUP -" terminals are connected internally to the ground terminals and to the module enclosure.

Connect the Earth Screw terminal on the rear of the module left side to ground for surge protection. Torque to 0.5-0.6Nm.

Connect SUP- and SUP+ terminals to main supply or solar input.

Connect BAT- and BAT+ terminals to a 13.8V battery for back-up supply.

Configuration switches

Use the Slide switches in the side access panel to select analog input voltage, current, RS-485 termination, Battery type and Module boot settings.

SwitchDESCRIPTION
RESModule Reset
SW1Al1/2 A - SE Current
SW2Al3/4 B - Diff Current
SW3Al5/6 C - SE Voltage
SW4RS485 Term (Position A)
SW5Factory Boot (Position B)
SW6Battery A-PbSo4; B-LiFePo4

Input and output connections

The digital input/output channels can be wired as inputs or outputs.

Digital input

Voltage-free Contact

TTL CMOS Output from other device

Digital output

Transistor Switch Device (NPN)

DC Load (Relay) Max 400mA

High Current Digital output (BottomPanel)

Analog connections

Single-ended current input (Position A)

Externally Powered Sensor

Loop-Powered Sensor

Differential current inputs (Position B)

Externally Powered Sensor

Loop-Powered Sensor

Single-ended voltage input (Pos C)

0-20V Sensor

Switch for Al3 and Al4 Voltage Input

Analog output

Serial Connections

RS-485 serial connection

The RS-485 port is isolated for long cable runs. The three terminals: A+, B-, and COM are isolated to 60V.

An on-board RS-485 terminating resistor provides line termination for long runs. Switch SW4 to position "A" to enable line termination. Enable terminating resistors at the far end of the RS-485 cable.

Remote RS-485

RS-232 serial connection

The RS-232 port supports 3-wire connection with rates up to 230,400 baud.

You can use the +12 supply to power devices up to 500mA.

RS-232 device

SDI-12 on RS-485 port

SDI-12 devices connect to the B- pin of the RS-485 connector. Leave A+ pin unconnected. You can use the +12 supply to power SDI-12 devices.

Remote SDI-12

SDI-12 on RS-232 port

SDI-12 devices connect to the TX pin of the RS-232 connector. Leave RX pin unconnected. You can use the +12 supply to power SDI-12 devices.

Note: SDI-12 mode must be enabled in device configuration.

Remote SDI-12

Contact Information

Australia

ELPRO Technologies
29 Lathe Street
Virginia QLD 4014
T +61 7 3352 8600
E sales@elprotech.com
W elprotech.com

USA

ELPRO Technologies Inc
2028 East Ben White Boulevard
#240-5656 Austin, TX 78741-6931
T +1 855 443 5776
E sales@elprotech.com
W elprotech.com

How to Order

Simply send us an email at sales@elprotech.com, contact your local distributor, or phone +61 7 3352 8600.

Models: EL-QE-E_JAN25, EL-QE-E, EL-QE-E Industrial Wireless Ethernet, Industrial Wireless Ethernet, Wireless Ethernet, Ethernet

File Info : application/pdf, 4 Pages, 1.72MB

PDF preview unavailable. Download the PDF instead.

EL-inst-QE-E JAN25

References

Adobe PDF Library 17.0 Adobe InDesign 19.1 (Windows)

Related Documents

Preview ELPRO I/O Plus Logic: Instruction and Examples for Wireless I/O Products
This document provides detailed instructions and examples for configuring and using the I/O Plus logic feature available in ELPRO's Wireless I/O products, including models like 415U-2, 415U-E, 925U-2, 215U-E, and 115E-2. It covers overview, configuration steps, testing methods, and practical application examples.
Preview EL-ERTK-A2 ERRTS Field Test Set Operator Manual | ELPRO Technologies
This operator manual provides comprehensive guidance for the ELPRO Technologies EL-ERTK-A2 Field Test Set, designed for testing Event Reporting Radio Telemetry Systems (ERRTS) Field Stations and Store & Forward Repeaters. It covers setup, operation with the Surecom SW-102 VSWR Watt Meter, and the use of ERRTS Ranger Software for data analysis.
Preview ELPRO 115S Serial Expansion Modules User Manual
This user manual provides comprehensive information on the ELPRO 115S Serial Expansion Modules, covering installation, configuration, operation, and technical specifications. It details various module types, I/O capabilities, communication protocols (RS232, RS485, Modbus), and hazardous location notices.
Preview ELPRO 215U-2-BGN User Manual: Wireless Ethernet I/O and Gateway
Comprehensive user manual for the ELPRO 215U-2-BGN 802.11 WiFi Wireless Ethernet I/O and Gateway. Details installation, configuration, networking, and protocols like Modbus, DNP3, and MQTT for industrial automation.
Preview ELPRO LIBERO C PDF Logger & Indicator Operation Manual
Comprehensive operation manual for ELPRO LIBERO C PDF Loggers and Indicators, detailing configuration with liberoCONFIG and SmartStart, safety information, and product specifications for temperature monitoring during transport.
Preview ELPRO 415U-Ex-Cx Wireless Mesh Modem and Gateway Installation Guide
This guide provides instructions for installing and configuring the ELPRO 415U-Ex-Cx wireless mesh modem and gateway. It covers antenna installation, power supply wiring, and input/output connections.
Preview ELPRO LIBERO Cx PDF Logger & Indicator Operation Manual
Comprehensive operation manual for the ELPRO LIBERO Cx PDF data loggers and indicators, detailing setup, configuration with liberoCONFIG, quick start, safety, and SmartStart features for temperature monitoring during transport.
Preview ECOLOG-PRO Radio Modules Operation Manual: 2PTR & 1THR
Comprehensive operation manual for ELPRO ECOLOG-PRO 2PTR and ECOLOG-PRO 1THR radio modules, covering system overview, module specifications, connection instructions, sensor data, and disposal guidelines.