DC Variable-Frequency Barrier Gate CB01VF-I (DC24V) Manual
Preface
Symbol Stipulations
Symbols | Meanings |
---|---|
!Danger | Indicates that there is a high level of potential danger, if not avoided, it may cause casualties or serious injuries. |
! Warning | Indicates that there is a medium or low level of potential danger. If not avoided, it may cause minor or moderate injury to personnel. |
! Attention | Indicates potential risks. If you ignore the information, it may cause equipment damage, data loss, equipment performance degradation, or unpredictable results. |
Tips | Indicates that it can help you solve a problem or save your time. |
Explanation | Indicates that it is the additional information of the main text, which emphasizes and supplements the main text. |
Revision Records
Version No. | Revision Content | Release Date |
---|---|---|
V1.0.0 | First Release | 2021.07 |
V.1.0.1 | Adding "4.7 Auto-calibrating at limit position” | 2021.09 |
V1.0.2 | Adding "3.5.2 Quick Adjustment Instruction" | 2022.08 |
Adding "RS485 Communication Protocol" |
Safety Instructions
The following is the correct methods of using the product, in order to prevent danger, prevent property damage, etc., please read this manual carefully before using the equipment and strictly follow it during use. Please keep the manual properly after reading.
Operating Environment Requirements
- Please transport, use and store the device within the allowable humidity and temperature range.
- Please do not let any liquid flow into the device.
- Please install the device in a well-ventilated place, and do not block the vents of the device.
- Please do not press hard, vibrate violently or soak the equipment.
- Please use the factory packaging or materials of the same quality when shipping the equipment.
- It is recommended to ground via the grounding hole on the device to improve the reliability.
Operation and Maintenance Requirements
Warning
- Please do not disassemble the device privately.
- Please use the accessories or attachments of the manufacturer for installation and maintenance by professional service personnel.
- Please do not provide two or more power supply methods to the device at the same time, otherwise the device may be damaged.
- The self-contained boom is not allowed to be lengthened or cut off, and it is also not allowed to add weight to the boom privately.
Contents
- Preface
- Safety Instructions
- Production Overview
- Functions and Features
- Technical Data
- Product Structure
- Mechanism Structure
- Installation Direction Definition
- Mechanical Part Installation and Adjustment
- Cabinet Installation
- Boom Installation
- Spring Installation and Adjustment
- Mechanism Installation Direction Change
- Controller Explanations and Instructions
- Controller Interface Explanations
- Quick Adjustment Instruction
- Controller Parameter Setting
- "Regular Menu" Command List
- "Advanced Menu" Command List
- Common Malfunctions and Solutions
- Warranty and Service Items
- Maintenance
- Packing List
- Spring Selection Table
- Appendix
- RS485 Communication Protocol
1. Production Overview
1.1. Functions and Features
- DC variable frequency control motor drive, equipped with connecting rod transmission mechanism, balance spring, stable and reliable operation, motor life up to 6 million times, spring life 500,000 times.
- With auto-reversing on obstacle function, the boom will auto reverse when it meets obstacle during the closing process.
- Support external radar, coil, infrared anti-smashing function, built-in DC 12V power output, can be used for external radar power supply.
- Support RS485 communication or RS485 off-line connection.
- Optional Bluetooth module, convenient debugging of barriers through small programs.
- Large LCD screen display, English visual menu, easy function selection and debugging.
- Left-installation and right-installation can be changed.
1.2. Technical Data
- Working temperature (motor): -30℃~ + 70℃
- Power supply input voltage: AC110±10%, or AC220V±10%
- Controller input voltage: DC24V±10%, 10A
- Motor power: 240W MAX
- Relative Humidity: 30%~80%, No condensation
- Distance of remote control: L≥30M
- Running Speed: 2~6 seconds adjustable
- MTBF: 6,000,000 times
2. Product Structure
2.1. Mechanism Structure
The mechanism includes the following components:
- Spring Strength Regulating Screw
- Spring Lock-nut
- Boom Holder
- Balance Spring
- DC Motor
- Motor Hand-wheel
(See Figure 1 for visual representation)
2.2. Installation Direction Definition
When placing an order, please confirm “left-installed" or "right-installed". Figures as below:
(See Figure 2 for visual representation of left and right installation)
Left-installed: Cabinet fixed at the left side of the entrance.
Right-installed: Cabinet fixed at the right side of the entrance.
3. Mechanical Part Installation and Adjustment
3.1. Cabinet Installation
According to the specific conditions of the site, select the barrier gate of the appropriate specification. Use expansion bolts to fix the cabinet on the ground with the dimensions shown in the figure below. Ensure the barrier foundation is made according to site conditions. For non-concrete ground, a cast-in-place foundation is needed.
(See Figure 3 for expansion bolts and cabinet fixing bar dimensions)
3.2. Boom Installation
Note: Installation pictures are for reference only; the product prevails in kind.
3.2.1 Straight Boom Installation
- Fix the boom fixing plate on the boom with 2pcs of M12*70mm hexagon screws.
- Hold the fixing plate by hand, lift the boom vertically, and install it on the boom holder.
- Install the flat washer, spring washer, and M12 nut on the screw in turn, and fix the screw with a wrench.
(See Figure 4 for visual representation)
3.2.2 Folding Boom Installation
- Fix the boom fixing plate on the boom with 2pcs of M12*70mm hexagon screws.
- Hold the fixing plate by hand, lift the boom vertically, and install it on the boom holder.
- Install the flat washer, spring washer, and M12 nut on the screw in turn, and fix the screw with a wrench.
- Fix the rod and connecting bearing on the support board components with screws.
- Loosen the bolsters with right-hand and left-hand screws, rotate the stainless steel pulling rod to adjust the horizontal and vertical position of the boom; after adjustment, lock the bolsters with right-hand and left-hand screws.
(See Figure 5 for visual representation)
3.2.3 Fence Boom Installation
- Fix the boom fixing plate on the boom with 2pcs of M12*70mm hexagon screws.
- Hold the fixing plate by hand, lift the boom vertically, and install it on the boom holder.
- Install the flat washer, spring washer, and M12 nut on the screw in turn, and fix the screw with a wrench.
- Fix the U-connecting unit to the cone axis on the barrier with screws.
- Fix the bottom fence to the U-connecting unit, then release the 2pcs screws of the unit and adjust them to make the fence perpendicular to the ground.
(See Figure 6 for visual representation)
3.3. Spring Installation and Adjustment
Note: The barrier gate is well adjusted before delivery. Please do not change the boom type and boom length at will. The length of springs prevails in kind; design is subject to change without prior notice. Regular maintenance and replacement are required for the spring due to its wear-tear feature.
Step 1: Spring installation, dis-assembly and replacement
Keep the boom in a vertical position. Loosen the spring fastening nuts, unscrew the M8x140mm spring adjusting screws with a hexagonal spanner, then take off the spring. The steps for installation and disassembly of the spring are the opposite.
Step 2: Spring force adjustment
When the power is off, turn the motor hand wheel to move the boom towards the closing direction. When the boom gets close to the horizontal position, if the hand wheel cannot be turned smoothly, the spring force is too small; tighten the spring. Turn the motor hand wheel to move the boom towards the opening direction. When the boom gets close to the vertical position, if the hand wheel cannot be turned smoothly, the spring force is too big; loosen the spring. Repeat these operations and adjustments until the hand wheel can be turned smoothly, indicating the spring force is at balance status.
Judging spring force by observing boom running situation also works. If the boom shakes when opening, the spring force is too strong. If the boom shakes when closing, the spring force is too low.
3.4. Mechanism Installation Direction Change
This barrier mechanism can be both left-installed and right-installed. Users can change the installation direction according to the actual situation. The following steps describe changing from left-installed to right-installed:
- Take out the 10MM screw by turning the 8MM Allen wrench counterclockwise.
- Push out the boom holder by turning the 14MM*150 screw clockwise.
- Disassemble the 6 sets of 8MM screws.
- Turn the mechanism 180 degrees vertically.
- Put the mechanism into the cabinet.
- Assemble the boom holder back, and fix the 10MM screw by turning the 8MM Allen wrench clockwise.
(See Figure 7, Step 1-5 for visual representation)
4. Controller Explanations and Instructions
Note: All electrical connections are done before delivery. Connect the power and grounding connection.
(See Figure 8 for controller interface diagram and Figure 9 for wire diagram)
- Motor Interface: DC24V Power Input Interface.
- Signal Input Indicator: Indicates the status of various signals.
- LCD Screen: Displays barrier gate information, working status, parameters, and menu items.
- Open Button: (Function Up-regulate)
- Close Button: (Function Down-regulate)
- Stop Button: (Function Quit)
- Set Button: (Function Confirm)
- Open/Close/Stop Wire Control Interface: For external control of the barrier gate.
- Radar/Loop Detector/Photocell Interface: Connects to external sensors for obstacle detection.
- RS485 Communication Interface: For communication with computers or other systems.
- Up Limit Relay Output Interface
- Down Limit Relay Output Interface
- R&G Light Output Interface (no power)
- Internal Diagram of Output Interface
4.1. Controller Interface Explanations
Item | Explanation |
---|---|
Wire Control Interface | This interface is available for parking systems and external controllers. UP: Short circuit "UP" and "GND". Down: Short circuit "Down" and "GND". Stop: Short circuit "Stop" and "GND". |
Anti-smashing Interface | Infrared Photocell: Boom lifts up when short-circuiting "Infrared photocell interface" and "GND" during boom down. Loop Detector: Boom lifts up when short-circuiting "loop detector interface" and "GND" during boom down. In up limit position, boom falls down automatically after these two interfaces are disconnected. |
RS485 Communication Interface | Used for controlling the barrier gate or checking its status via computer or system. Also used for online controlling paired barrier gates synchronously. |
Limit Relay Output Interface | Used for checking the barrier gate status by opening and closing times. Users can also change to other output modes via option 4 of the advanced menu. |
DC12V Power Output Interface | Provides 1A current output, available for radar or small light strips. |
R&G lights | Available to connect with R&G lights to indicate the working status of the barrier gate. |
Function Buttons | The 4 buttons have two working statuses: normal working status and menu setting status. Normal status: "▲" for opening, "▼" for closing, "■" for stopping. "=" is invalid when short-pressed. Long press "=" for 2 seconds to enter menu setting status. In menu setting status, "▲" and "▼" adjust menu items/parameters, "■" cancels or exits, "=" enters the next menu or saves. |
LCD Screen | Displays barrier gate information such as working status, parameters, and menu items. |
4.2. Quick Adjustment Instruction
This barrier gate is well adjusted before delivery. If there are any changes in boom length, spring, or control board, adjust as follows in an environment without roofs:
Step | Name | Operation | Speed Choice |
---|---|---|---|
1 | Choose "CB01VF-I" from the menu "3. Quick Operation Parameter" | Long press "=" button for 3s to enter setting status, then choose "CB01VF-I". | |
2 | Open and close | Press the remote controller button to open and close the barrier gate stably. | |
3 | Boom shakes during running | Well adjust the parameters of 4.4.1 and 4.4.2 in the regular menu. | |
4 | Horizontal limit position | After entering the menu, enter "4.4.4. Position Setting" to adjust it to "4.5 Horizontal Fine Adjustment". | Refer to "5. Common Malfunctions and Solutions on page 15". |
Note: If the boom is too long, it is normal for it to shake when it first learns the horizontal and vertical limit position.
4.3. Controller Parameter Setting
Long press "=" for 2 seconds to enter the regular menu setting status. Select menu items by short or long pressing "▲" and "▼". Short press to increase/decrease by one; long press for continuous increase/decrease. When the required value is displayed, press "=" to enter the setting. Press "■" to return to the previous level or exit. Press "=" to confirm the setting. Pressing "■" without confirming will make the set parameters invalid.
4.4. "Regular Menu" Command List
4.4.1. Opening operation parameters
Sub-menu | Defaults | Range | Remarks |
---|---|---|---|
1.1 Acceleration Time | 8 | 1-20 | The smaller the value, the faster the speed. |
1.2 Opening Speed | 40 | 15-100 | The bigger the value, the faster the opening speed. |
1.3 Deceleration Angle | 60 | 10-80 | The angle at which deceleration begins in the opening process. If the boom shakes after it is opened, reduce this value. |
1.4 Angle of Low-speed Area | 90 | 45-90 | The angle at which the boom enters a low-speed area in the opening process. If the boom shakes after it is opened, reduce this value. |
1.5 End Speed | 8 | 1-50 | The minimum speed at which the barrier gate is opened. If the boom shakes after it is opened, reduce this value. |
1.6 Learning Speed | 25 | 10-50 | The speed at which the barrier gate begins to learn the down limit position after power-on. |
(See speed schematic diagrams for opening and closing parameters)
1.3. The Deceleration Angle
Sets the angle at which deceleration begins during the opening process. The angle is 0 degrees when the boom opens to the up limit position and 90 degrees when it closes to the down limit position. This parameter indicates that deceleration begins when the barrier gate opens to this angle. If the boom shakes after it is opened, reduce this value.
1.4. The Angle of Low-speed Area
Sets a low-speed area in the opening process. When the opening angle reaches the set angle, the barrier gate will run at the end speed set in 1.5 until it opens to the up limit position. If the value is 90, the function is invalid. If the boom shakes after opening to the up limit position, reduce this value.
1.5. The End Speed
The minimum speed at which the barrier gate opens to the up limit position. The barrier gate will run at this speed until it opens to the up limit position. If the parameter is set too large, the boom may shake when it opens to the up limit position.
4.4.2. Closing operation parameters
Sub-menu | Defaults | Range | Remarks |
---|---|---|---|
2.1 Acceleration Time | 8 | 1-20 | The smaller the value, the faster the speed. |
2.2 Closing Speed | 40 | 15-100 | The bigger the value, the faster the closing speed. |
2.3 Deceleration Angle | 40 | 10-80 | The angle at which deceleration begins in the closing process. If the boom shakes after it is closed, increase this value. |
2.4 Angle of Low-speed Area | 0 | 0-45 | The angle at which the boom enters a low-speed area in the closing process. If the boom shakes after it is closed, reduce this value. |
2.5 End Speed | 4 | 1-50 | The minimum speed at which the barrier gate is closed. If the boom shakes after it is closed, reduce this value. |
2.6 Learning Speed | 25 | 10-50 | The speed at which the barrier gate begins to learn the down limit position after power-on. |
4.4.3. Quick operation parameter
Sub-menu | Model Type | Remarks |
---|---|---|
Auto setting of opening and closing operating parameter according to different models | CB01VF-I | Quickly set parameters according to different models. Notice: this device can quickly set the opening and closing operating parameters according to the model types, which shortens the debugging time. If the effect is still not good after setting, you can adjust the corresponding parameters appropriately. |
4.4.4. Position setting
Sub-menu | Range | Remarks |
---|---|---|
4.1 Position learning mode | Find up and down limit/ find up limit only/ find down limit only | Learning mode after power-on for the first time. For straight booms over 5 meters or fence booms, select "Find up limit only". When the barrier gate is installed under an eaves, select "Find down limit only". |
4.2 Manual learning of up and down Limit | None; prompts on the screen. | In manual mode, learn the up and down limit. |
4.3 Manual learning of up limit | None; prompts on the screen. | In manual mode, learn the up limit only. |
4.4 Manual learning of down limit | None; prompts on the screen. | In manual mode, learn the down limit only. |
4.5 Horizontal fine adjustment | 1-3000 | Boom horizontal fine adjustment. |
4.5. "Advanced Menu" Command List
Warning: Advanced menu is for professional technicians; general users should use it with caution!
4.5.1. Auto-aging test
Sub-menu | Defaults | Range | Remarks |
---|---|---|---|
1.1 Time Interval | OFF | 0-5, 0 is OFF | Time interval for auto aging test; unit: second. |
1.2 Boom up angle | 0 | 0-90 | Boom up angle after switching from off to on. If the value is odd, it will keep switching. If the value is even, it will turn from off to on once and then completely turn off once again, and repeat continuously. |
4.5.2. Auto-open when power off
Sub-menu | Defaults | Range | Remarks |
---|---|---|---|
2.1 Low voltage actuation time | OFF | 0-5000, 0 is OFF | The time when the voltage is lower than the set threshold and continues to exceed the threshold; unit: millisecond. |
1.2 Low voltage threshold | 21 | 15-23 | The operating voltage is lower than the threshold; unit: V. Note: This function needs a backup power module. |
4.5.3. Motor setting
Sub-menu | Defaults | Range | Remarks |
---|---|---|---|
3.1 Power value when closing | 0% | 0-12% | When the spring force is not enough and the boom sags down when closing at the down limit position, increase this value to get more force. |
3.2 Motor type | 129 Forward Rotation | 129 Forward/Reverse, -B03 Forward/Reverse | Used for matching the motor type. This model must be set as 129 forward rotation; otherwise, the operation will be abnormal. |
4.5.4. Relay output mode
The control board has two limit output relays. Users can set different output modes to meet different application requirements.
- Limit output: When the barrier gate opens to the up limit position, the open relay closes; when it closes to the down limit position, the down limit relay closes. During opening, closing, or stopping, these two relays are disconnected. This function can be used with the system to monitor the barrier gate's status.
- Alarm for boom swinging away: In this mode, "infrared signal input" and "GND" interface are used as the signal interface for boom installation. If they are short-circuited, the boom is working normally; if disconnected, the boom is swinging away. When the boom swings away, the barrier gate opens to the up limit position automatically, and the up limit relay stays closed. When the boom is installed correctly and works normally (signals are short-circuited), the up limit relay works normally. Note: This function requires an inductive switch for boom status detection.
- Alarm against artificial lifting boom: In this mode, the up limit relay serves as an alarm signal output. When the barrier gate closes at the down limit position, if the boom is artificially lifted to a certain angle, the up limit relay will be closed for 15 seconds as an alarm output. An external alarm can be connected.
- Down Limit Pulse Signal: After the boom reaches the down limit position, the down limit relay sends a closing signal for one second. This function can be used as the opening signal for another barrier gate or control system. The up limit relay
was closed when the boom fell down. The signal during boom falling and at the down limit position can be used as an R&G light signal or for detecting the barrier gate running status.
4.5.5. Buffer time for boom from closing to opening
When the open button is pressed during closing, this parameter sets the buffer time from receiving the command to starting the opening.
4.5.6. Buffer time of barrier gate stopping
When the stop button is pressed during opening or closing, this parameter sets a buffer time for the barrier to stop smoothly. This is the time from receiving the stop command to stopping completely.
4.5.7. Open the barrier gate by remote control to enter the motorcade mode
Opens the barrier gate by remote control to enter motorcade mode directly. The loop detector is invalid until the barrier gate closes. Closing the barrier gate by wire control or remote control exits motorcade mode. Opening by wire control does not enter motorcade mode. The default is "OFF". Tip: If set to "OFF" in the up limit position, long pressing the "UP" button of the remote controller for 4 seconds also enters motorcade mode. Alternatively, pressing the "STOP" button on the controller (program version "10824" or above) at the up limit position also enters this mode.
4.5.8. Valid time of loop detector signal
During opening or at the up limit position, the duration of the loop detector signal must exceed the set time. The auto-closing action is executed after the loop detector signal disappears, preventing the signal from being too short and triggering auto-closing, which could hit vehicles. The default time is 200ms. Range: 100ms-900ms.
4.5.9. Beep of Loop detector signal
When there is a loop detector signal (vehicle on the loop wire) and the boom is at the up limit position, the buzzer emits a hint tone. "ON" has sound, "OFF" has no sound. "ON" is default.
4.5.10. Failure angle of loop detector anti-smashing
During the closing process, when the boom reaches the setting angle from the horizontal level, it will not respond to the loop detector signal. This prevents vehicles from being followed by other vehicles and avoids misoperation of the loop detector triggering the barrier gate opening. The default value is 5 degrees.
4.5.11. Failure angle on obstacle
During the closing process, when the boom reaches the setting angle from the horizontal level, it will not respond to barrier gate opening if it meets an obstacle. The default value is 10 degrees.
4.5.12. Switching angle of R&G light
When the boom opens to the setting angle, the relay of R&G light will close. The default value is 60 degrees.
4.5.13. Wire control signal type measurement
"Infrared photocell", "loop detector/radar", and "stop" signals of the wire control interface can be set to normal open input and normal close input. The default is normal open input.
5. Common Malfunctions and Solutions
Malfunction Phenomenon | Possible Causes | Solution |
---|---|---|
The opening and closing speed is too fast for the first time after power on | Regular menu 1.6/2.6 learning speed value is too large | Reduce the corresponding value. |
In manually finding limit, boom can't run to limit position, and the buzzer sounds | Regular menu 1.6/2.6 learning speed value is too small | Increase the corresponding value and try again. |
Prompt: The motor sensor is not detected | The motor sensor plug is not plugged in or the wire is loose | Plug well the motor sensor. |
Motor sensor failure | Measure the resistance of each two wires (white, yellow and red) of the motor phase line by a multimeter to check if the resistance numbers are the same. | |
The control board resets when the barrier gate is running | Short circuit inside the motor | Replace the motor. |
Control board failure | Replace the control board. | |
Auto reverse during the closing process. | Signal error of loop detector or radar | Check whether the loop detector or radar signal indicator flashes by mistake. |
Control board failure | Replace the control board. | |
Boom shakes a lot at up limit position | Opening speed in up limit position is large | Reduce the value of 1.5 in regular menu. |
Opening deceleration angle is large | Reduce the value of 1.3/1.5 in regular menu at the same time. | |
Opening speed is high | Reduce the value of 1.2 in regular menu. | |
Closing speed in down limit position is large | Reduce the value of 2.5 in regular menu. | |
Boom shakes a lot at down limit position | Closing deceleration angle is small | Reduce the value of 2.3/2.5 in regular menu at the same time. |
Closing speed is high | Reduce the value of 2.2 in regular menu. | |
The battery voltage of remote controller is too low | Replace the batteries. | |
Remote control distance is short | High-voltage wires or strong electromagnetic interference near the barrier gate | Replace the high-power remote controller. |
Remote control learning failed | The remote controller does not match the receiver | Contact the manufacturer. |
The order of the remote controller is wrong | Relearn after clearing the code of the remote controller. |
6. Warranty and Service Items
- Free service is offered for component parts in one year warranty time (not including the barrier boom or remote).
- Lifetime service with charge accordingly.
- Technical questions are supported.
- The below items and situations are not included in the range of free service:
- The user does not follow the instruction and causes any damage to the product.
- The power supply is not stable, over the range of permitted voltage, or not according to safety electric using standards.
- The user installs or uses the product in wrong methods, causing damage to the product's appearance.
- Natural disaster causes damage to the product.
- Warranty time has expired.
- Service items are out of our promises.
7. Maintenance
- Keep the barrier gate clean.
- Check the joints every month for loose parts.
- Check the spring balance status after the barrier gate has run 500,000 times or after 12 months (check if the boom shakes when moving). Readjust the balance. Change new springs after running 1,000,000 times or 18 months to avoid spring breaking due to excessive fatigue.
- Check the easily worn-out parts every half year and renew them.
- Remote control distance will be shortened or not work in cases like big object screening, battery exhausting, or extreme weather.
8. Packing List
Name | Specification | Quantity | Unit | Application |
---|---|---|---|---|
Screws, Nuts, Flat Pad | M12*70 | 2 | sets | Fixing the boom |
Boom Fixing Bar | 1 | pcs | Fixing the boom | |
Boom Holder Plastic Cover | 1 | sets | Optional | |
Cabinet Fixing Bar | 2 | pcs | Fixing the cabinet | |
Expansion Screws | M16*150 | 4 | sets | Fixing the cabinet |
Support Post | 1 | pc | Optional | |
Radio Emitter | 1 | pcs | Optional | |
Keys | 2 | pcs | For cabinet door | |
Remote Controller | 2 | pcs | Optional | |
Manual | 1 | pcs | Optional |
9. Spring Selection Table
Boom Type | Boom Length (Meters: M) | Spring Diameter Φ (mm) | Quantity of Springs (pieces) | Remark |
---|---|---|---|---|
Straight Boom | 8≥L>6 | 3.8 | 6 | |
6≥L≥5.8 | 3.8 | 5 | ||
5.8≥L≥5 | 3.8 | 4 | ||
5≥L≥4.5 | 3.8 | 3 | ||
4.5≥L≥3.5 | 3.8 | 2 | ||
3.5≥L≥2.8 | 3.8 | 1 | ||
Articulated Boom | 5≥L≥4.8 | 3.8 | 4 | |
4.8≥L≥4.3 | 3.8 | 3 | ||
4.3≥L≥3.5 | 3.8 | 2 | ||
3.5≥L≥2.8 | 3.8 | 1 | ||
Fence Boom, Two-levels | 4≥L≥3.8 | 3.8 | 6 | |
4≥L≥3.5 | 3.8 | 5 | ||
3.5≥L≥3 | 3.8 | 4 | ||
3≥L≥2.5 | 3.8 | 3 | ||
Fence Boom, Three-levels | 4≥L≥3.8 | 3.8 | 6 | |
3.8≥L≥3.3 | 3.8 | 5 | ||
3.3≥L≥2.5 | 3.8 | 4 |
Appendix
I. RS485 Communication Protocol
This controller supports two types of protocols: new protocol (baud rate 19200) and old protocol (baud rate 9600). The baud rate can be selected via advanced menu H-25. H-26 sets the address.
New Protocol Communication Format: 16 hexadecimal, Baud rate: 19200.
Upper System Data Format: Data header (fd xx) + Address + Command + (data) + End code (fd fa). XX cannot be fd or fa (example: 00).
Controller Return Data Format: Data header (fd 00) + Address + Command + (data) + End code (fd fa).
Some commonly used command tables (example address: 01):
- Upper system sends search command: 00
Sending stream code: fd 00 01 00 fd fa
Barrier controller returns: 00 intermediate state
09 open to up limit position
Oc open to down limit position
If the barrier gate opens to up limit position, the returning stream code is: fd 00 01 09 fd fa - Upper system sends stopping command: 01
Sending stream code: fd 00 01 01 fd fa
Barrier controller return 01
returning stream code: fd 00 01 01 fd fa - Upper system sends opening command: 03
Sending stream code: fd 00 01 03 fd fa
Barrier controller return 03
returning stream code: fd 00 01 03 fd fa - Upper system sends closing command: 05
Sending stream code: fd 00 01 05 fd fa
Barrier controller return 05
returning stream code: fd 00 01 05 fd fa - Upper system sends locking command: 07
Sending stream code: fd 00 01 07 fd fa
Barrier controller return 07
returning stream code: fd 00 01 07 fd fa - Upper system sends unlocking command: 08
Sending stream code: fd 00 01 08 fd fa
Barrier controller return 08
returning stream code: fd 00 01 08 fd fa - Turn on proactive reporting command: a1
Barrier controller return a1
sending stream code: fd 00 01 a1 fd fa
returning stream code: fd 00 01 a1 fd fa
Data format for proactive reporting: fd 00 + Address + Characteristic code + fd fa
The list of proactive reporting content is as follows: - Characteristic code 02: Stop by remote control; Characteristic code 11: Stop by wire control
- Characteristic code 04: Open by remote control; Characteristic code 13: Open by wire control
- Characteristic code 06: Close by remote control; Characteristic code 15: Close by wire control
- Characteristic code 09: Open to up limit position; Characteristic code 16: Open by loop detector
- Characteristic code Oc: Close to down limit position; Characteristic code 17: Open by infrared photocell
- Characteristic code Oa: Auto-closing after vehicle passing through; Characteristic code 18: Delay auto-closing
- Characteristic code 12: Open by auto-reversing on obstruction; Characteristic code 14: Stop on obstruction
- Characteristic code e3: Motor sensor is not detected; Characteristic code e7: Alarm for artificially lifting boom or spring tension too high
- Turn off proactive reporting command: a0
Barrier controller return a0
sending stream code: fd 00 01 a0 fd fa
returning stream code: fd 00 01 a0 fd fa