User Manual for Winsen models including: ZP211 Refrigerant Gas Detection Module, ZP211, Refrigerant Gas Detection Module, Gas Detection Module, Detection Module, Module
File Info : application/pdf, 5 Pages, 756.10KB
DocumentDocumentZhengzhou Winsen Electronics Technology Co., Ltd www.winsen-sensor.com Refrigerant gas detection module ModelZP211 User's Manual Version: 1.1 Issue Date.2023-3-9 Zhengzhou Winsen Electronics Technology Co., Ltd Tel: 86-371-67169097/67169670 Fax: 86-371-60932988 Email: sales@winsensor.com Leading gas sensing solutions supplier in China Zhengzhou Winsen Electronics Technology Co., Ltd Statement www.winsen-sensor.com This manual's copyright belongs to Zhengzhou Winsen Electronics Technology Co., LTD. Without the written permission, any part of this manual shall not be copied, translated, stored in database or retrieval system, also can't spread through electronic, copying, record ways. Thanks for purchasing our product. In order to let customers use it better and reduce the faults caused by misuse, please read the manual carefully and operate it correctly in accordance with the instructions. If users disobey the terms or remove, disassemble, change the components inside of the sensor, we shall not be responsible for the loss. The specific such as color, appearance, sizes &etc., please in kind prevail. We are devoting ourselves to products development and technical innovation, so we reserve the right to improve the products without notice. Please confirm it is the valid version before using this manual. At the same time, users' comments on optimized using way are welcome. Please keep the manual properly, in order to get help if you have questions during the usage in the future. Zhengzhou Winsen Electronics Technology CO., LTD. Tel: 86-371-67169097/67169670 Fax: 86-371-60932988 Email: sales@winsensor.com Leading gas sensing solutions supplier in China Zhengzhou Winsen Electronics Technology Co., Ltd www.winsen-sensor.com ZP211 Refrigerant gas detection module Product Description ZP211 refrigerant gas detection module adopts advanced multi-layer thick film manufacturing process semiconductor gas sensor element. The gas sensor element contains a filter adsorption layer to reduce the interference of alcohol and other gases, and has extremely high sensitivity to refrigerant gas R290. The module has been aged , calibration, calibration, with good consistency and high sensitivity. Features High sensitivity, fast response, strong anti-interference ability, long life, stable operation, factory calibrated, sensor fault self-diagnosis Application Used for air conditioning, refrigeration system refrigerant leak detection. Parameters Model ZP211 Target Gas Refrigerant gas R290 Physical interface S05B-PASK-2 Output Data PWM Working Voltage 5.0±0.2V DC (No voltage reverse connect protection) Working Current 80mA Warm Up Time Recovery time 3 min 120s Set alarm concentration Initial alarm accuracy 2000ppm 13402660ppm Operating Temperature Operating Humidity Storage Temperature Storage Humidity Size -2055 95RH -2060 60RH 25×34×14.1mmL×W×H Weight 5g Figure 1:Structure(tolerance±0.2mm) Tel: 86-371-67169097/67169670 Fax: 86-371-60932988 Email: sales@winsensor.com Leading gas sensing solutions supplier in China Zhengzhou Winsen Electronics Technology Co., Ltd Terminal definition Pin Name Function G GND Input power - R / / T / / PWM signal output (need to O Output connect external pull-up resistor) V 5V Input power + www.winsen-sensor.com Figure 2: Module Pin Diagram Definition of output signal Status PWM output Preheating H75ms L: 300ms Work H75ms L: 300ms Alarm H225ms L: 150ms Fault H300ms L: 75ms Note: 1. After the module enters the alarm state, it will keep the alarm state and will not switch to other states. It needs to be powered on again to exit the alarm state. 2. If the sensor is exposed to high concentrations (above 10000ppm) of R290 gas, the sensor may be damaged and its performance may be affected. 3. The module fault signal takes priority over the alarm signal. Sensor basic testing circuit The module uses an MP511D sensor, and Figure 3 shows the basic testing circuit of the MP511D sensor. The sensor requires two voltages to be applied: heating voltage (VH) and testing voltage (VC). Tel: 86-371-67169097/67169670 Fax: 86-371-60932988 Email: sales@winsensor.com Leading gas sensing solutions supplier in China! Zhengzhou Winsen Electronics Technology Co., Ltd www.winsen-sensor.com Figure 3 Basic Test Circuit of MP511D Sensor Among them, VH is used to provide a specific operating temperature for the sensor, and the voltage is applied to both ends of the heating electrode using a DC power supply. VC is used to measure the circuit's loop voltage. VRL is the voltage on the load resistor (RL) connected in series with the sensor, which is the output voltage VOUT. The module determines the concentration of refrigerant R290 in the current environment by detecting the voltage of VOUT. On the premise of meeting the electrical characteristics of the sensor, VH and VC can share a common power supply circuit. Cautions Please do not put the module in organic solvent (include silica gel and other cementing compound), painting, medicament, oils and fuels, high concentration gas etc. Please do not impact or vibrate the module seriously. Please warm up for 5 min before first use. Please do not use the module related with personal safety. Please do not install the module in the severe convection environment. Please do not put in the module in high concentration organic gas for long time. Please supply the module with requested voltage as manual strictly, if voltage is higher than 5.5V, the module will be destroyed irreversibly. Zhengzhou Winsen Electronics Technology Co., Ltd Add: No.299, Jinsuo Road, National Hi-Tech Zone, Zhengzhou 450001 China Tel: +86-371-67169097/67169670 Fax: +86-371-60932988 E-mail: sales@winsensor.com Website: www.winsen-sensor.com Tel: 86-371-67169097/67169670 Fax: 86-371-60932988 Email: sales@winsensor.com Leading gas sensing solutions supplier in China!