5012-0016 MA aV160 ALD EN
Installation instructions
aV160 ALD

Ventilation device
without heat recovery

www.inventer.eu

Trademarks, copyrights and industrial property rights
inVENTer® is a protected trademark of inVENTer GmbH. The copyright to this document remains with the manufacturer. Rights to all content and images: © inVENTer GmbH 2022. All trademarks used in this document are the property of their respective manufacturers and are hereby acknowledged.

Disclaimer
This documentation represents a translation of the original German installation instructions. It must be passed on to the user (tenant, owner, property management, etc.) after completion of the installation. The contents of this documentation have been checked for conformity with the hardware and software described. Nevertheless, deviations cannot be excluded, so that no guarantee can be given for complete conformity.
This documentation describes the functionality of the standard range. For reasons of clarity, the documentation does not contain all detailed information on all types of the product and cannot take into account every conceivable case of operation, installation and assembly.
The illustrations in this documentation may differ slightly from the design of the product you have purchased. The function remains the same despite the difference in detail.
This documentation is updated regularly. Necessary corrections and appropriate supplements are always included in subsequent editions. You can also find the latest version at www.inventer.eu/downloads.

Company Information

Publisher:

inVENTer GmbH Ortsstraße 4a D-07751 Löberschütz Germany

Telefon: Fax: E-Mail: Web:

+49 (0) 36427 211-0 +49 (0) 36427 211-113 info@inventer.de www.inventer.eu

CEO: Annett Wettig VAT ID number: DE 815494982 Jena District Court HRB 510380

2

Ventilation device aV160 ALD | Installation instructions

TaBLE OF CONTENTS
Table of contents
1 User and Safety instructions.................................................................................................. 4 1.1 User information............................................................................................................. 4 1.2 Safety instructions.......................................................................................................... 5
2 System overview: Ventilation device 2.1 Construction ................................................................................................................... 8 2.2 Functions........................................................................................................................ 9
3 Preparing for installation ........................................................................................................ 10 3.1 Installation Position ........................................................................................................ 10 3.2 Position of the wall opening ........................................................................................... 12 3.3 Sectional drawings ventilation device ............................................................................ 13 3.4 Dimensional drawings of the components ..................................................................... 15 3.5 Dimensions .................................................................................................................... 16
4 Installation and assembly....................................................................................................... 17 4.1 Check the scope of supply ............................................................................................. 17 4.2 Create wall opening ....................................................................................................... 18 4.3 Installing the wall sleeve ................................................................................................ 19 4.4 External termination Ventilation device Variante Standard montieren ........................... 22 4.5 Installing inner panel Light ............................................................................................. 27
5 Technical Data ......................................................................................................................... 28 5.1 General specifications.................................................................................................... 28
6 Scope of supply....................................................................................................................... 29
7 Troubleshooting ...................................................................................................................... 30
8 Warranty and guarantee.......................................................................................................... 30
9 Service...................................................................................................................................... 31

Ventilation device aV160 ALD | Installation instructions

3

USER AND SAFETY INSTRUCTIONS

1 User and Safety instructions

Thank you for purchasing this high quality product from inVENTer!
This section provides an overview of the basic safety precautions for safe and proper operation of your ventilation system.

1.1 User instructions

Safety and warning instructions

The safety and warning instructions in these installation instructions have a uniform structure and are marked with a symbol on the left side of the instruction. A signal word in front of the text also indicates the hazard level. If several hazard levels occur, the safety note for the highest level is always used.

The safety instructions and warnings contain the following information:

SIGNAL WORD: Type and origin of the hazard. Possible consequences of the danger! · Measures to avoid hazard.

The signal word indicates the severity of the potential hazard unless the preventive measures are taken:

DANGER means: Imminent danger of serious injury or death.

WARNING means: Possible danger of serious injury or death.

CAUTION means: Direct danger or minor/significant injury.

NOTICE Means: Direct or possible risk of property damage due to an adverse event/state.

If you see these signs, follow the measures described to avoid possible danger and damage.

Other symbols used in this documentation

In addition to the safety and warning instructions, the following symbols are used:

i

A TIPsymbol indicates practical and useful tips for handing your ventilation device.


 !

Additional tools and aids are required.
Red bar over a graphic: Illustration shows the outer wall.
Blue bar over a graphic: Illustration shows the outer wall.
Action required: This prompts the user to perform a specific action. Action results: Requires user to check results ofthe action performed. Actions focus: To be taken into account in the corresponding assembly step.

4

Ventilation device aV160 ALD | Installation instructions

USER AND SAFETY INSTRUCTIONS

1.2 Safety instructions

The operating instructions are part of your ventilation device and must be available at all times (see www.inventer.eu/downloads). When handing over the device/system to third parties, the information on access to the installation instructions must also be handed over. Be sure to read through the installation instructions carefully before carrying out any work on the unit/system and observe all the instructions for installation given in this chapter. In addition, observe the safety instructions that precede the instructions described. Failure to observe the safety instructions may result in personal injury and/or damage to property.
Intented use
The external wall air diffuser aV160 ALD is used for the supply of fresh air according to DIN 18017-3 or DIN 1946-6 in residential spaces and supplements the extract air device.
Use contrary to the intended purpose leads to the exclusion of any liability claims.
General information
· Observe the applicable standards, regulations and directives when carrying out work. In particular, also applicable building regulations, the fire protection ordinance and accident prevention regulations of the employers' liability insurance association.
· Only use the components in accordance with the applications described in this documentation. Changes or conversions to the components are not permitted.
· Your ventilation device/system is exclusively designed for use in ambient temperatures between -20 and 50°C.
· Faultless and safe operation of the unit/system requires proper transport, storage and assembly as well as careful maintenance.
Installation and assembly
· CAUTION: The system may only be installed by qualified personnel. Before starting work, you should have a project plan showing the number of ventilation devices, the location of the ventilation devices and the ventilation principle (cross-ventilation, individual room ventilation, exhaust ventilation). The exact positioning of the individual units and control units must be checked on site and, if necessary, adapted to the conditions on site with the involvement of the responsible planner or the user. For optimal functioning, it is recommended that the unit be installed at an appropriate location in the upper wall area.
· WARNING:For the joint operation of a ventilation unit with fireplaces, securing measures must be taken to prevent the occurrence of negative pressure in the building. The decision as to which measures should be carried out is made by the responsible chimney sweep and/or building planner.
· NOTICE: The ventilation unit is not suitable for drying out buildings. Do not operate the device until all construction work has been completed.
· NOTICE: Contamination of components by e.g. plaster residues will damage the components! Seal the ventilation unit/air outlets of the ventilation unit dust-tight during the entire construction work. Do not remove any thread locks until final assembly.

Ventilation device aV160 ALD | Installation instructions

5

USER AND SAFETY INSTRUCTIONS
· NOTICE: Do not install the unit near room air thermostats or in the immediate vicinity/above sensitive pictures or furniture.
· NOTICE:Observe the specified minimum distances on both sides of the wall and frontally to avoid unintentional mixing of different air volume flows and to ensure access to the device and its components. A minimum distance of 1.2 m must be maintained between adjacent air openings. (, page 11).
· NOTICE: The wall sleeve must be integrated into the building envelope (airtightness level) in accordance with the current state of the art, taking into account constructional and physical specifications ("RAL installation"). The material for this is to be provided by the customer.
· NOTICE: Install the wall sleeve with a slope of 1 - 2° to the outer wall to ensure that any condensation that may occur is drained off.
· NOTICE: Store components upright outside the wall sleeve and do not throw them to avoid damage and breakage of the components.
· NOTICE: To prevent algae from settling around the outer closures, the installation instructions must be followed exactly (apply all sealing tapes!). We recommend a biocide pre-setting/ water-repellent pre-treatment of the façade surface around the exterior finishes. Ask your planner about this!
· NOTICE: When mounting components in (exterior) walls with insulation, use insulation anchors to ensure secure fastening of the components. Insulation anchors are not included in the scope of delivery, they are optionally available!
· NOTICE: Use only permanently elastic sealing compound suitable for outdoor use to seal the joints at all outdoor terminations!
· NOTICE: The device has plastic surfaces that are sensitive to scratches. Do not touch components with oily and/or dirty hands. Avoid contact with sharp or pointed objects e.i Rings.
If your device has a defect, contact the factory representative responsible for you or our technical service.
Improper use
Any use that is not mentioned in the chapter Intended use is considered improper use.
Do not install/operate the equipment in areas where the following may enter or occur:
· Environment with high oil or grease content. · Flammable gases, liquids or vapours. · Extreme dust exposure. · Enviroment temperatures outside -20 ­ 50 °C · Obstacles preventing access to or removal of components of the ventilation device.
The ventilation device is not to be used as an opening to the outside and/or for the purpose of smoke discharge/smoke extraction in basements without windows.
Qualified personnel
Qualified personnel in the sense of the safety instructions in this documentation are persons who are authorized to install, commission and label devices, systems and circuits in accordance with safety engineering standards.

6

Ventilation device aV160 ALD | Installation instructions

SYSTEM OVERVIEW VENTILATION DEVICE AV160 ALD

2 System overview Ventilation device aV160 ALD

The external wall air diffuser aV160 ALD is used for the supply of fresh air according to DIN 18017-3 or DIN 1946-6 in residential spaces. They are installed in the supply air room.

It consists of a slide-in unit with adjustable inner screen, integrated wind protection and filter, as well as a wall sleeve, a sound-absorbing liner and a freely selectable outer closure. The installation is generally carried out in the outer wall.

The ALD insert, including all filters and wind protection, is easily accessible on the inside. The air volume is regulated on the inner panel, where there is a mechanism for changing the opening an-
gle. The integrated filter cartridge with dust filter ensures that pollen and dust from outside do not penetrate the interior. The filter cartridge with dust filter ensures that pollen and dust from outside do not penetrate the interior. The sound insulation lining must be installed along the entire length
of the wall sleeve.

If required, the aV160 ALDs can be retrofitted as ventilation devices with heat recovery (diameter of wall installation sleeves 160 mm, observe wall thicknesses). The standard length of the wall sleeve is 495 mm. For larger wall thicknesses, a wall sleeve with a length of 745 mm can be ordered. Both versions can be shortened on site.
Components

· Inner panel Light · Filter cartridge incl. filter ISO Coarse (G1) · Wall sleeve
Models

· Sound insulation lining · External termination1) · Pollen filter (optional)

The ventilation devices of the aV160 ALD product series differ in their external terminations. This documentation only contains information on the Light and Plus variant of the ventilation device. Information on the variants can be found in the separate installation instructions for the respective components.

· Light variant: Ventilation device aV160 ALD with round weather protection grille Light (hereinafter referred to as the "Light").
· Plus variant: Ventilation device aV160 ALD Plus (hereinafter referred to as the "Plus") with driving rain-proof weather protection hood Flex (white/grey/anthracite/special colour/north).
· Corner variant:Ventilation device aV160 ALD Corner (hereinafter referred to as the "Corner variant") for integration of the external closure in the window reveal (white/grey/anthracite/special colour/ nord)
· Nordic variant:Ventilation devices aV160 ALD Nordic (in the further text "Variant Nordic") for integration of the external closure in clinker brick walls (white/grey/anthracite/special colour/ nord).

1) External closure "Weather protection hood Flex" available in stainless steel or optionally in aluminium [increased salt resistance].

Ventilation device aV160 ALD | Installation instructions

7

SYSTEM OVERVIEW VENTILATION DEVICE AV160 ALD
2.1 Construction
2 4
3 5
6
Figure 1: Ventilation device aV160 ALD Plus
Components 1 External closure1)
1a) Base plate WPH2)Flex 1b) Drip edge top 1c) Cover WPH2) Flex 1d) Weather protection grille Light 2 Wall sleeve

1

180°

Light variant

Plus variant

1c 1a

1d WPG Light2)

1b WPH Flex2)

3 Sound insulation lining
4 Filter cartridge with wind protection 5 Filter cartridge incl. filter ISO Coarse (G1)
[pre-assembled] 6 Inner panel Light

SYSTEM OVERVIEW VENTILATION DEVICE AV160 ALD

2.2 Functions

Exhaust device and air vents
The aV160 ALDs are installed in the supply air room, which forms a room compound with the extract air unit.
Due to the negative pressure generated by the extract air unit, the outside air flows in automatically. They are installed in the supply air room.
The fresh air outlets have a filter system to ensure minimum hygienic requirements and are equipped with a wind protection as standard.
The air volume is regulated in the lower area of the inner panel. There is a mechanism for changing the opening angle.

aV160 ALD

Exhaust air system

Supply air

Exhaust air

aV160 ALD

Supply air

aV160 ALD
Supply air

aV160 ALD
Figure 2: Installation example: Aventus extract air system in conjunction with aV160 ALD as fresh air supply

1) The description of the components of all other possible external finishes can be found in the separate installation instructions of the respective external finish.
2) WPH: Weather protection hood | WPG = Weather protection grille

8

Ventilation device aV160 ALD | Installation instructions

Ventilation device aV160 ALD | Installation instructions

9

PREPARING FOR INSTALLATION
3 Preparing for installation
3.1 Installation Position
· The installation location can be derived from the positioning proposal of the ventilation planning. The exact positioning of the individual units and control units must be checked by the customer and adjusted on site if necessary. Consult the responsible planner about this! For optimum function, it is recommended that the ventilation device is installed at an appropriate point in the upper wall area (e.g. 1.80 m UEFF [upper edge of finished floor]).
· Do not place the ventilation unit above radiators, room thermostats, sensitive furniture and/or pictures.
Minimum distances of the wall opening for the ventilation device:
NOTICE: Malfunction due to incorrect positioning of the ventilation device. · Note insulation thickness and possible shutters! · Do not install near radiators! · Observe minimum distance of 1.2 m to adjecent air openings!

· The aV160 ALD must not be covered by cabinets or porches The outside air must be able to flow freely .

 

250

· Keep a minimum distance of 250 mm all around.
· Installation should be close to the ceiling (better air distribution).

250
Figure 3: Installation Position aV160 ALD

· Fit the wall opening above radiators. This means that the incoming air is already preheated when it enters the interior.

· Position the ventilation unit so that there is no direct airflow into the occupied zone of the users. Keep a distance of 1 - 1.2 m from the user area.

· To ensure that the unit does not interfere with other ventilation and that its function is not disturbed by other ventilation operations, it must always be installed in its own wall sleeve.

· The flow velocity should be low in order to avoid draughts.

PREPARING FOR INSTALLATION

Minimum distances to components / building elements on the internal and external wall:

· on the interior and exterior walls:

Component termination
Weather protection grille Light Weather protection hood Flex
External termination Corner
External termination Nordic Inner panel Light

Distance from centre of hole at the

Outer wall [mm]

Inner wall [mm]

250

­

250

­

250 385 to Soffit

250 (above, below, side-

ways)

­

250 circumferential

­

250

frontal [mm] ­ ­
­ 300

· in between two neighbouring ventilation device in one room.

A Horizontal or vertical
on the same wall
1,2 m
B Installation over corner

C Installation with height offset
1,2 m ­ 0,75 y
y

1,0 m 1,4 m

1,0 m

10

Ventilation device aV160 ALD | Installation instructions

Ventilation device aV160 ALD | Installation instructions

11

PREPARING FOR INSTALLATION

3.2 Position of the wall opening

For the positioning of the wall sleeve of other variants of your ventilation unit see the installation instructions for your special external closure.

Ventilation device Light variant [Weather protection grille Light]

 2501,2) 100 100

Ø180

 250

5

1 2 4

43 Position of the wall opening

 2501,2) 100 100
249

 250

1

5

4

2

43

260

Position wall installation system Simplex

Ventilation device Plus variant [Weather protection hood Flex]

 2501)

 4502)

Ø180

 250 5
1 2 4

 4502)  2501)

148

1

 250 5

4

148

249

165

165

43 279

43

260

2

279

Figure 4: Dimensional drawing wall opening aV160 ALD (interior view) with weather protection grille Light [top] and weather protection hood Flex [bottom].

1 Wall opening (Fig. 4, left, above and below) Wall installation system Simplex (Fig. 4, right, above and below)

2 External termination3) 3 Soffit 4 Door-/Window frame 5 Bottom edge of lintel4)

1) Min. distance to adjacent building components on the inner wall 2) Min. distance to adjacent building components on the outer wall

3) Recomendation: Attach the outer finish at the height of the lintel 4) Consider insulation thickness and possibly roller shutters

12

Ventilation device aV160 ALD | Installation instructions

PREPARING FOR INSTALLATION

3.3 Sectional drawings ventilation device

For sectional drawings of other variants of your ventilation unit, see the installation instructions for your specific external closure.

Sectional drawings ventilation device aV160 ALD
10 1 ­ 2°

32 12

ø 200 Ø160 Ø100 160 210

30

5

4

D

C

6

3

112

40

138

B

A

Figure 5: Sectional drawings ventilation device aV160 ALD with weather protection grille Light

A Interior plaster/ interior structure B Masonry

C Insulation D Exterior plaster

1 Inner panel base plate 2 Inner panel cover 3 Wall sleeve R-D160 4 Sound insulation lining

5 Weather protection grille Light 6 Filter cartridge with dust filter
ISO Coarse (G1) and wind protection (pre-assembled)

Ventilation device aV160 ALD | Installation instructions

13

PREPARING FOR INSTALLATION

Sectional drawings ventilation device aV160 ALD, Plus variant

10

32

1 ­ 2°

12

313 Ø160 Ø100 160
210

6

5

4

88

D

C

3
B

7 112 138

40
A

Figure 6: Sectional drawings ventilation device aV160 ALD with weather protection hood Flex

A Interior plaster/ interior structure B Masonry

C Insulation D Exterior plaster

1 Inner panel base plate 2 Inner panel cover 3 Wall sleeve R-D160 4 Sound insulation lining 5 Baseplate WSP1) Flex

6 Cover WSP1) Flex 7 Filter cartridge with dust filter
ISO Coarse (G1) and wind protection (pre-assembled)

1) WPH: Weather protection hood 14

Ventilation device aV160 ALD | Installation instructions

PREPARING FOR INSTALLATION

3.4 Dimensional drawings of the components

Weather protection grille Light

Ø 200

1
A

2
2 x Ø 4,8

A  A
1
2

Ø 200 100

4
3 3

A

30

134

Figure 7: Dimensional drawing weather protection grille Light
1 Frame 2 Slats 3 Condensate discharge 4 Mounting screws (2 x)

Weather protection hood Flex

A

5

A  A 23

4 x Ø 4,8

1

7

21

313 148

1
7
A 279
Weather protection hood cover Flex Flex

252

194,5

5
4 x Ø 4,8
4
3

Ø168 Ø211

2

88

6

194,5 221

Weather protection hood base plate

Figure 8: Dimensional drawing weather protection hood Flex

1 Weather protection hood base plate 2 Fixing hole outer wall (4x) 3 Simplex mounting hole (4x) 4 Sealing strip guide

5 Weather protection hood cover 6 Protective grid 7 Drip edge top

Ventilation device aV160 ALD | Installation instructions

15

184 160 210

PREPARING FOR INSTALLATION
Inner panel
7
Ø160

4 4 x Ø4.8

32 1

5

6

184 210

40 32

Figure 9: Dimensional inner panel Light V-220x220
1 Inner panel base plate 2 Connecting element 3 Snap-in hook 4 Inner panel cover

5 Filter holder 6 Mounting hole inside wall (optional) 7 Fastening connecting element

3.5 Dimensions
Designation Wall opening for wall sleeve Wall sleeve R-D160x495 (745) Weather protection grille Light Weather protection hood Flex Inner panel Light V-220x220

Depth/ Lenght [mm]

Wide [mm]

High [mm]

Wall thickness1)

Ø180

495 ­ 745

Ø160

43

Ø200

23 ­ 88

279

313

722)

220

220

1) with external rendering, insulation, brickwork and internal rendering 2) open, incl. spigot

16

Ventilation device aV160 ALD | Installation instructions

INSTALLATION AND ASSEMBLY
4 Installation and assembly
i Read this chapter carefully before installation to avoid installation errors. The installtion and connection of the ventilation device must be carried out by qualfied personnel.
4.1 Check the scope of supply
Check the delivery for completeness and transport damage on receipt, using the delivery note. Report missing items immediately. These assembly instructions describe the standard version of the product. For the scope of delivery of the external closure variants, please refer to the separately available installation instructions of the respective system component.

1a 2

1b 4x 4x 4x
2a

1c 1 External termination 1 a: WSP1) Flex

1 b: WPG2) Light

1 c: Sealing strip guide

1d

1 d: Fixing elements outer wall

1 e: Stop tape

1e

The weather protection hood Flex is

available in different colours and mate-

rials (stainless steel / aluminium [with

increased salt resistance]) and must be

ordered according to the desired colour

and texture.

2b

22 Wall sleeve R-D160

2a: Sound insulation lining

2c

2b: Styrofoam discs

2 c: Mounting wedges set

3a 3b 3c
3d

33 Inner panel Light 3 a: Inner panel base plate with connecting elements 3 b: Inner panel cover 3c: Filter cartridge 3 d: Filter ISO Coarse (G1)

1)WPH: Weather protection hood 2) WPG = Weather protection grille

Ventilation device aV160 ALD | Installation instructions

17

INSTALLATION AND ASSEMBLY

4.2 Create wall opening

CAUTION: Falling masonry when creating the wall opening can lead to physical injuries and /or damage to property! · Install protection against falling masonry on building exterior. · Remove objects from the inmediate vicinity of the building´s exterior.

In new buildings/constructions we recommend the use of the optional Simplex D160 wall mounting system, D180 wall block, or Woodplex for timber post and beam construction.

Observe the minimum deistances and the installation position of the ventilation device. If uncertain, consult your planner before installation!

Create the wall opening through core drilling

Drill with core drill attachment or milling drill Ø 180 mm,

Ø 180

Requirements: · The masonry must be dry and in a load-bearing
condition. · No load-bearing elements in the position of the drill
hole.
 Create a wall opening, Ø 180 mm, at the installation location of the ventilation unit.
! The wall sleeve must have a slope of 1 ­ 2° to the exterior wall side. Alternatively the drilling can be carried through with a slope.
 The wall opening for the ventilation device has been created.

INSTALLATION AND ASSEMBLY

4.3 Installing the wall sleeve

Measuring tape, angle grinder, spirit level, non-pressing 2K polyurethane foam, cutter, mounting wedge set and styrofoam discs.

DC B

Y

X = ?

Requirements: · The wall opening Ø 180 mm is finished.

 Determine the exact thickness X:

A

D = Exterior rendering, incl. other superstructures if

applicable.

C = Insulation, if necessary inl. air gap (optional)

B = Masonry, incl. relining if necessary.

A = Interior plaster.

Y = Protrusion of the

wall sleeve in the outer area (depending on the

installation situation exterior rendering or masonry)

External termination Light Flex Corner

Inner panel

X in [mm] =
Light

A + B + C + D A + B + C + D A + B A + B

Nordic

double-skin Masonry (clinker)
single-skin Masonry (ETICS1))

A + B A + B

Y in [mm] =
10 10 10 UBP + 10
(for installation with substructure panel UBP)
C + D - 200
(min. 30 mm)
C + D - 95
(min. 30 mm)

1) ETICS = External thermal insulation composite system

18

Ventilation device aV160 ALD | Installation instructions

Ventilation device aV160 ALD | Installation instructions

19

INSTALLATION AND ASSEMBLY
X + Y

 Cut the wall sleeve to the determined dimension X + a protrusion of Y on the exterior wall.
 File the edges.

1 ­ 2°

 Remove the styrofoam discs from the wall sleeve.
 Insert the wall sleeve into the wall opening so it is flush with the interior wall. Note the thickness of the plaster.
.
NOTICE: An accumulation of condensation-water in the wall sleeve. Damage to the exterior wall and masonry and the building structure! · Insert wall sleeve with a slope of
1 - 2° to the outer wall.
 Attach the wall sleeve inside and outside with the mounting wedges so that there is a slope of 1 ­ 2° to the exterior wall.
 Check the angle of the wall sleeve using a spirit level.
NOTICE: Contamination of components by e.g. plaster residues will damage the components of the wall sleeve! · Before foaming the free space between
the wall sleeve and the masonry, insert Styrofoam discs.
 Insert the styrofoam discs into the wall sleeve from the inside and outside.

24 h

INSTALLATION AND ASSEMBLY
NOTICE: INTerruption of the thermal insulation composite system. Damage to teh building structure! · During installation, replace the wall
structure as far as the wall sleeve and if necessary guide the housing (flush-mounted inner covers) towards it. · Observe the necessary barrier levels.
 Foam-seal the gap between the wall sleeve and masonry all the way around with non-pressing 2K polyurethane foam.
 Cut off the excess, hardened assembly foam and protruding assembly wedges as follows: · Flush with the inner wall · Flush with the outer wall
 The wall sleeve set is installed.

20

Ventilation device aV160 ALD | Installation instructions

Ventilation device aV160 ALD | Installation instructions

21

INSTALLATION AND ASSEMBLY

4.4 Installing the external closure ventilation device Light and Plus variant

The assembly of any interior termination variants is not part of this documentation! It can be found in the installation instructions of the respective external closure.

NOTICE
Installing on an unfinished exterior wallleads to damage of the exterior wall! · Only install the external closure once the exterior wall is finished and fully dried .

NOTICE Penetration of condensation water and/or algae accumulation around the weather protection hood leads to damage to the masonry/exterior wall and/or discolouration of the façade! · Secure all sealing tapes on the weather protection hood circumferentially before installing the
external closure. · Attach the stop tape on the outside wall in the upper area of the wall sleeve. · Before installation, carry out a biocidal pre-treatment/ water-repellent pre-treatment of the sur-
face around the external termiantion (consult your planner regarding this!)
Weather protection grille Light
Spirit level, cordless screwdriver, permanently elastic exterior sealing compound, sealing tape, screws, scissors

210 mm

Requirements: · The exterior wall is completed and even. · The wall sleeve set is installed.
 Remove the styrofoam disc on the outside wall side from the wall sleeve.
 Kürzen Sie das Stop tape auf 210 mm.


22

 

 Fix the shortened stop tape, 210 x 15 mm, on the outside wall side exclusively in the upper area of the wall sleeve.
! Both ends of the stop band are above the horizontal centre line so that the fixing claws of the weather protection grille can hook into the wall sleeve on the left and right.

Ventilation device aV160 ALD | Installation instructions

INSTALLATION AND ASSEMBLY

i

TIP: B do not apply the sealing tape until immediately before mounting the weather pro-

tection grille. This prevents the sealing tape



from swelling too much and makes installation easier.

 Attach the sealing tape, 9 mm, above and below



the fixing claws to the inner ring on the back of the

weather protection grille.

! Do not apply sealing tape to the fixing claws.

NOTICE: DAMage to masonry/external wall due to misaligned condensate drain! · The condensate drain must be directed
towards the floor.

 Slide the weather protection grille onto the protruding wall sleeve.
! The slope of the condensate drain is directed towards the floor and positioned away from the façade.

 Align the fixing screws with a spirit level.

 Screw the weather protection grille with the
pre-mounted fastening screws. (1)  The fixing claws hook into the wall sleeve.

1

 Seal the joint between the cover and the exterior

wall all around with permanently elastic exterior

sealant. (2)

2

 The protective grille is mounted.

Ventilation device aV160 ALD | Installation instructions

23

INSTALLATION AND ASSEMBLY

Mounting the weather protection hood Flex
NOTICE · The projection of the wall sleeve on the outer wall is 10 mm!

Spirit level, pencil, power drill with Ø 8mm drill bit, cordless screwdriver, wall anchors (wallplugs for insulation for insulated exterior walls), permanently elastic external sealant, sealing tape, screws

ø 160 mm

Requirements: · The exterior wall is completed and even. · The wall sleeve set is installed.
 Remove the styrofoam disc on the outside wall side from the wall sleeve.

 Fix the shortened stop tape, 380 x 15 mm, on the

4 x

outside wall side exclusively in the upper area of

the wall sleeve.

! The recess in the circumferential stop band is placed in the lower area of the wall

sleeve.

Simplex

 Slide the base plate onto the projecting wall sleeve.
! The protective grille is directed towards the floor.

 Level the base plate inner panel with a spirit level.

ø 8 mm

 Mark the four drill holes: Outer holes (blue arrow) Masonry. Inner holes (green arrow) Simplex
 Drill the four holes Ø 8 mm, min 50 mm deep

i

TIP:Do not apply the sealing tape until inmediately before installing the base plate. This

prevents the sealing tape from swelling too

much and makes installation easier.

INSTALLATION AND ASSEMBLY

 Attach the sealing tape, 9 mm, outside wall side and circumferentially along the guide on the base plate: · flush with the opening for the wall sleeve · along the guide on the outer edge.
! Do not seal the fixing holes! The sealing tape must not protrude at the inner edge of the opening wall sleeve .
 Insert the wall anchors into the boreholes.
 Screw the base plate weather protection hood into the wall anchors with 4 screws.

i

TIP:When attaching the base plate of the Flex weather protection bonnet to external walls

with insulation or when using the Simplex wall

installation block/wall installation system, use

insulation dowels for fastening. These are

not included in the scope of supply, they are

available as an option.

NOTICE: Wrong sealing of the joint between the base plate and the outer wall prevents intallation of the cover. · Seal only the upper joint between the base
plate and the outer wall.
 Seal the joint between the base plate and the exterior wall with permanently elastic exterior sealant.

 Place the cover on the base plate from above.  Pull the cover down as far as it will go.
! The guides on the cover hook behind the base plate.
 The weather protection hood Flex is installed.

24

Ventilation device aV160 ALD | Installation instructions

Ventilation device aV160 ALD | Installation instructions

25

INSTALLATION AND ASSEMBLY

Inserting the sound insulation lining
NOTICE: The sound insulation lining absorbs sound waves from the outside and from the unit itself (sound transmission and inherent sound). · To ensure the sound-insulating function, handle the lining with care.

Blade knife

Requirements: · The external closure is mounted. · The wall sleeve set is installed.

 Remove the styrofoam discs from the wall sleeve.
 Place the end faces of the sound insulation lining against each other

 Push the sound insulation lining under slight tension into the wall sleeve as far as it will go (the ring insert, if present, is facing the outer wall).

 Cut the sound insulation lining to the length of the wall sleeve minus 20 mm.
 The sound insulation lining is mounted.

INSTALLATION AND ASSEMBLY

4.5 Installing inner panel Light

Requirements: · The exterior wall is completed and even. · The wall sleeve set is installed. · The sound insulation lining is mounted.
 Slide the pre-assembled inner panel into the wall sleeve.
! The inVENTer logo is located at the bottom right.
 Align the base plate inner panel with a spirit level.

i

If the inner panel does not fit tightly enough in the wall sleeve, it can optionally be screwed

to the inner wall. To do this, use the 4 corner

holes in the base plate inner panel.

 Pull the top edge of the cover forwards until you feel the latch hook unhook.

 The inner panel is fitted.

26

Ventilation device aV160 ALD | Installation instructions

Ventilation device aV160 ALD | Installation instructions

27

TECHNICAL DATA
5 Technical Data
5.1 General specifications
Feature Operating range [°C] Minimum wall thickness Extract air/outdoor air Reference air flow [m³/h] Reference air flow [m³/h]
Standard sound level difference [dB] Standard filter class
ISO 16890 EN 779: 2012 Comformity

Value
-20 ­ 50
150 mm
Without aggresive gases, dust and oils 12 ­ 18 [Light variant] 13 ­ 17 [Plus variant] 18 ­ 24 [Light variant] 19 ­ 23 [Plus variant] 51 ­ 52 [Light variant] 54 ­ 55 [Plus variant]
ISO Coarse G1

28

Ventilation device aV160 ALD | Installation instructions

SCOPE OF SUPPLY

6 Scope of supply

Standard components
All standard components are also available as spare parts. Further accessories and spare parts can be found in the separate accessories overview. Contact your local distributor to order components for your ventilation system.

Component

Product Number

aV160 ALD

1001-0204

aV160 ALD Plus

1001-0205

aV160 ALD Corner aV160 ALD Nordic

1001-0215 1001-0236

External termination Light / Plus1) variants: Weather protection hood incl. sealing tapes

Weather protection grille Light, white  RAL 9010 Weather protection hood Flex, white  RAL 9016 Weather protection hood Flex, grey  RAL 9006 Weather protection hood Flex, Nord  RAL 7011 Weather protection hood Flex, anthracite  RAL 7016 Weather protection hood Flex, special colour

1508-0110 1508-0157 | 1508-01712) 1508-0158 | 1508-01722) 1508-0159 1508-0160 | 1508-01732) 1508-0161 | 1508-01742)

Wall sleeve with Styrofoam discs and mounting wedges

Wall sleeve R-D160x495 Wall sleeve R-D160x745

1506-0068 1506-0069

Inner panel

Inner panel Light V-220x220, white

1505-0039

Accessories
Component Flicker filter aV100 ALD Pollen filter aV100 ALD Dust filter aV100 ALD Simplex incl. WEH R-D160 Wall mounting block WEB D180 V-210x249x120

Product Number 1004-0165 1004-0163 1004-0164 1506-0106 3008-0078

1) Article numbers of the external closure variants in the separate installation instructions of the respective external closure 2) Variant special: consisting of aluminium, with increased salt resistance

Ventilation device aV160 ALD | Installation instructions

29

TROUBLESHOOTING

7 Troubleshooting

Troubleshooting

Fault

Possible cause

Air volume flow too low

Air volume flow control

Air volume flow too strong

Noises Supply air is cold

Foreign body in the fan No heat recovery possible

Remedy
Move the cover to a larger opening.
Move the cover to a smaller opening for a short time.
! The inner panel must not be permanently closed.
Remove foreign body from the ventilation device. Upgrade to a device/system with heat recovery

8 Warranty and guarantee
Warranty
The warranty covers all defects that were present at the time of purchase. Observe the intended use in order to maintain the warranty claim.
Outside Germany, the national warranty regulations of the country in which the system is sold apply. Contact the dealer of your home country. Guarantee:
inVENTer GmbH gives a 5-year guarantee on the wall sleeve. This covers premature product wear. Warranty and guarantee claim
For information on the guarantee provisions, see www.inventer.eu/garantie/guarantee.
In the event of a warranty or guarantee claim, contact the dealer or factory representative responsible for you.
In any case, send the complete unit back to the manufacturer.
The warranty claim is an additional offer by the manufacturer and does not affect applicable law in any way.

30

Ventilation device aV160 ALD | Installation instructions

SERVICE
9 Service
Complaints Check the delivery for completeness and transport damage on receipt, using the delivery note. Complain about missing items immediately, at the latest within 14 days, to your supplier, dealer or factory representative. Accesories and spare parts To order components for your ventilation unit, contact your dealer or factory representative. Technical customer service: For technical advice, please contact our technical service staff:
+49 (0) 36427 211-333 service@inventer.de

Ventilation device aV160 ALD | Installation instructions

31

inVENTer GmbH Ortsstraße 4a D-07751 Löberschütz www.inventer.eu
Subject to modifications No liability for printing errors
Product Number 5012-0016 Version: 1.0 ­ 09/2022

