Installation Guide for ABB models including: ACS480 Inverter Drive, ACS480, Inverter Drive

EN / ACS480 drives quick installation and start-up guide

FIDRI / EIF200

EN / ACS480 drives quick installation ...

EN / ACS480 drives quick installation and start-up guide

Jul 20, 2021 — Do not do work on the drive, motor cable, motor, or control cables when the drive is connected to the input power. Before you start the work, isolate the.


File Info : application/pdf, 2 Pages, 2.19MB

PDF preview unavailable. Download the PDF instead.

EN ACS480 QISG D A3
H
B+ ADGND B+ ADGND B+ ADGND

--
ABB GENERAL PURPOSE DRIVES
ACS480 drives Quick installation and start-up guide

 To install the drive with screws

1. Make marks onto the surface for the mounting holes. Refer to Dimensions and weights. Use the included mounting

template for frames R3 and R4.

2. Drill the holes for the mounting screws. If M2 necessary, install suitable plugs or

MW1

anchors into the holes.

3. Install the mounting screws into the holes. Leave a gap between the screw head and installation surface.

4. Put the drive onto the mounting screws.

5. Tighten the mounting screws.

 To install the drive to a DIN rail
1. Move the locking part to the left. If necessary, use a flat-head screwdriver.
2. Push and hold the locking button down.
3. Put the top tabs of the drive onto the top edge of the DIN rail.
4. Put the drive against the bottom edge of the DIN rail.
5. Release the locking button.
6. Move the locking part to the right.
7. Make sure that the drive is correctly installed.
To remove the drive, open the locking part and lift the drive from the DIN rail.

6. Connect the phase conductors of the motor cable to terminals T1/U, T2/V and T3/W.
7. If used, connect the brake resistor cable to terminals R- and UDC+. Use a shielded cable and ground the shield under the grounding clamp.
8. Make sure that the R- and UDC+ terminal screws are tightened. Do this step also if you do not connect cables to the terminals.
9. Strip the input power cable.
10. If the input power cable has a shield, ground the shield under the grounding clamp. Then twist the shield into a bundle, mark it and connect it to the grounding terminal.
11. Connect the PE conductor of the input power cable to the grounding terminal. If necessary, use a second PE conductor.
12. In 3-phase drives, connect the phase conductors of the input power cable to terminals L1, L2 and L3. In 1-phase drives, connect the phase and neutral conductors to terminals L1 and L2.
13. Mechanically attach the cables on the outside of the drive.

9. Install the communication module

To install the communication module (I/O module or fieldbus module):

1. Pull out the locking tab of the communication module.

2. Align the communication module

1

contacts with the contacts on the drive.

Carefully push the module into position.

3. Push in the locking tab of the

communication module.

4. Tighten the locking screw to fully attach

2

and electrically ground the

communication module.

Safety instructions
WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If you are not a qualified electrical professional, do not do electrical installation or maintenance work.
· Do not do work on the drive, motor cable, motor, or control cables when the
drive is connected to the input power. Before you start the work, isolate the drive from all dangerous voltage sources and make sure that it is safe to start the work. Always wait for 5 minutes after disconnecting the input power to let the intermediate circuit capacitors discharge.
· Do not do work on the drive when a rotating permanent magnet motor is
connected to it. A rotating permanent magnet motor energizes the drive, including its input and output terminals.
1. Unpack the delivery
Keep the drive in its package until you are ready to install it. After unpacking, protect the drive from dust, debris and moisture. Make sure that these items are included:
· drive · assistant control panel · options, if ordered · RIIO-01 I/O & EIA-485 module. Note: If a fieldbus adapter is ordered, it
replaces the RIIO-01 module of the standard delivery.
· mounting template (frames R3 and R4 only) · installation accessories (cable clamps, etc.) · multilingual warning sticker sheet (residual voltage warning) · safety instructions · quick installation and start-up guide · hardware and firmware manuals, if ordered.
Make sure that there are no signs of damage to the items.
2. Reform the capacitors
If the drive has not been powered up for a year or more, you must reform the DC link capacitors. The manufacturing date is on the type designation label. Refer to Capacitor reforming instructions (3BFE64059629 [English]).
3. Select the cables and fuses
· Select the power cables. Obey the local regulations. · Input power cable: ABB recommends to use symmetrical shielded cable
(VFD cable) for the best EMC performance.
· Motor cable: Use symmetrical shielded cable (VFD cable) for the best EMC
performance. Symmetrical shielded cable also reduces bearing currents, wear, and stress on motor insulation.
· Power cable types: In IEC installations, use copper or aluminum cables (if
permitted). In UL installations, use only copper cables.
· Current rating: max. load current. · Voltage rating: min. 600 V AC. · Temperature rating: In IEC installations, select a cable rated for at least
70 °C (158 °F) maximum permissible temperature of conductor in continuous use. In UL installations, select a cable rated for at least 75 °C (167 °F).
· Size: Refer to Fuses and typical power cable sizes for the typical cable
sizes and to Terminal data for the power cables for the maximum cable sizes.
· Select the control cables. Use double-shielded twisted-pair cable for analog
signals. Use double-shielded or single-shielded cable for the digital, relay and I/O signals. Do not run 24 V and 115/230 V signals in the same cable.
· Protect the drive and input power cable with the correct fuses. Refer to
Fuses and typical power cable sizes.
4. Examine the installation area
The drive is intended for cabinet installation and has a degree of protection of IP20 / UL open type. Examine the site where you will install the drive. Make sure that:
· The installation site is sufficiently ventilated and hot air does not recirculate. · There is sufficient free space around the drive for cooling, maintenance, and
operation. For the minimum free space requirements, refer to Free space requirements.
· The ambient conditions meet the requirements. Refer to Ambient
conditions.
· The installation surface is as close to vertical as possible and strong enough
to support the weight of the drive. Refer to Dimensions and weights.
· The installation surface, floor and materials near the drive are not flammable. · There are no sources of strong magnetic fields, such as high-current single-
core conductors or contactor coils near the drive. A strong magnetic field can cause interference in the operation of the drive.
5. Install the drive
You can install the drive with screws, or to a DIN rail (top hat type, width × height = 35 mm × 7.5 mm [1.4 in × 0.3 in]).
· Install R0 drives vertically. R0 drives do not have a cooling fan. · You can install drives with frame size R1...R4 tilted by a maximum of
90 degrees, from vertical to fully horizontal orientation.
· Do not install the drive upside down. · You can install several drives side by side.

6. Measure the insulation resistance

Drive: Do not do voltage tolerance or insulation resistance tests on the drive, because this can cause damage to the drive.

Input power cable: Before you connect the input power cable, measure the insulation of the input power cable. Obey the local regulations.

Motor and motor cable:
1. Make sure that the motor cable is connected to the motor and disconnected from the drive output terminals T1/U, T2/V and T3/W.

2. Use a voltage of 1000 V DC to measure the

insulation resistance between each phase conductor and the protective earth conductor. The insulation resistance of an ABB motor must be more than 100 Mohm (at ohm 25 °C [77 °F]). For the insulation resistance of

U1

V1

M 3~

W1 PE

other motors, refer to the manufacturer's

documentation. Moisture in the motor

U1-PE, V1-PE, W1-PE

decreases the insulation resistance. If you

think that there is moisture in the motor, dry the motor and do the

measurement again.

7. Make sure that the drive is compatible with the grounding system

You can connect all drive types to a symmetrically grounded TN-S system (center-grounded wye). The drive is delivered with the EMC and VAR screws installed. The material of the screws (plastic or metal) depends on the product variant. The table shows when to remove the metal EMC screw (disconnect the internal EMC filter) or metal VAR screw (disconnect the varistor circuit).

Screw Factory default label screw material

EMC VAR

Metal Plastic 1) Metal
Plastic

Symmetrically grounded TN-S systems (centergrounded wye) Do not remove Do not remove 2) Do not remove
Do not remove

Grounding systems
Corner-grounded delta, midpointgrounded delta and
TT systems Remove
Do not remove Do not remove Do not remove

IT systems (ungrounded or high-resistance
grounded) Remove
Do not remove Remove
Do not remove

1) UL (NEC) types have a plastic EMC screw. 2) Can install the metal screw (included in the drive delivery) to connect the internal EMC filter.

8. Connect the power cables  Connection diagram (shielded cables)
ACS480

L1 L2 L3 PE

R+ R- UDC+ UDC-

T1/ T2/ T3/ U VW

5

3 4

6

2 1

U1 V1 W1 M PE
3

PE L1 L2 L3 (L) (N)
1. Disconnecting device 2. Two protective earth (ground) conductors. Drive safety standard
IEC/EN 61800-5-1 requires two PE conductors, if the cross-sectional area of the PE conductor is less than 10 mm2 Cu or 16 mm2 Al. For example, you can use the cable shield in addition to the fourth conductor.
3. Use a separate grounding cable or a cable with a separate PE conductor for the line side, if the conductivity of the fourth conductor or shield does not meet the requirements for the PE conductor.
4. Use a separate grounding cable for the motor side, if the conductivity of the shield is not sufficient, or if there is no symmetrically constructed PE conductor in the cable.
5. 360-degree grounding of the cable shield is required for the motor cable and brake resistor cable (if used). It is also recommended for the input power cable.
6. Brake resistor and resistor cable (optional).
 Connection procedure (shielded cables)
For the tightening torques, refer to Terminal data for the power cables.
1. Loosen the screw on the front cover. Then lift the front cover up.
2. Attach the residual voltage warning sticker in the local language to the drive.
3. Strip the motor cable.
4. Ground the motor cable shield under the grounding clamp.
5. Twist the motor cable shield into a bundle, mark it and connect it to the grounding terminal.

3

4

10. Connect the control cables

Do the connections according to the application macro that you select. The ABB standard macro is the default macro. Keep the signal wire pairs twisted as near to the terminals as possible to prevent inductive coupling. The tightening torque for the terminal connections is 0.5 ... 0.6 N·m (4.4 ... 5.3 lbf·in).

1. Strip a part of the outer shield of the control cable for grounding.

2. Use a cable tie to ground the outer shield to the grounding tab.

3. Strip the control cable conductors.

4. Connect the conductors to the correct control terminals.

5. Connect the shields of the twisted pairs and grounding wires to the SCR terminal.

6. Mechanically attach the control cables on the outside of the drive.
 Default I/O connections (ABB standard macro)

Terminal

Description

1)

1 ... 10 kohm

Reference voltage and analog I/O 1 SCR Signal cable shield (screen)

2 AI1 Output freq./speed reference: 0 ... 10 V

3 AGND Analog input circuit common

4 +10 V Reference voltage 10 V DC

5 AI2 Not configured

6 AGND Analog input circuit common

7 AO1 Output frequency: 0 ... 20 mA

8 AO2 Output current: 0 ... 20 mA

Max. 500 ohm

9 AGND Analog output circuit common Aux. voltage output and programmable digital inputs

10 +24 V Aux. voltage output +24 V DC, max. 250 mA



11 DGND Aux. voltage output common



12 DCOM Digital input common for all



13 DI1 Stop (0)/Start (1)



14 DI2 Forward (0)/Reverse (1)



15 DI3 Constant frequency/speed selection

16 DI4 Constant frequency/speed selection

17 DI5 Ramp set 1 (0)/Ramp set 2 (1)

18 DI6 Not configured

Relay outputs

19 RO1C

Ready run



20 RO1A

250 V AC / 30 V DC



21 RO1B

2A



22 RO2C

Running

23 RO2A

250 V AC / 30 V DC

24 RO2B

2A

25 RO3C

Fault (-1)

26 RO3A

250 V AC / 30 V DC

27 RO3B

2A

Safe torque off

34 SGND Safe torque off (STO). Both circuits must be closed for the 

35 IN1 drive to start. The drawing shows the simplified



36 37

IN2 OUT1

connection of a safety circuit through safety contacts. If STO is not used, leave the factory-installed jumpers in place. See also section Safe torque off (STO).

 

1) × = on base unit, empty = on RIIO-01 I/O extension module
 Embedded fieldbus connection
You can connect the drive to an EIA-485 serial communication link through the embedded fieldbus interface on the RIIO-01 module. The embedded fieldbus interface supports the Modbus RTU protocol. To configure Modbus RTU communication with the embedded fieldbus: 1. Connect the fieldbus cables and the necessary I/O signals. 2. Use the termination switch to set the correct termination settings. 3. Power up the drive and set the necessary parameters. A connection example is shown below.

3)

2)

GR - +

ON

ON

ON

Automation controller
Termination ON1)

1
Drive Termination OFF

1
Drive Termination OFF

1
Drive Termination ON1)

1) The devices at the ends of the fieldbus must have termination set to ON. All other devices must have termination set to OFF (1).
2) Attach the cable shields together at each drive, but do not connect them to the drive. Connect the shields only to the grounding terminal in the automation controller.
3) Connect the signal ground (DGND) conductor to the signal ground reference terminal in the automation controller. If the automation controller does not have a signal ground reference terminal, you can connect the signal ground to the cable shields through a 100 ohm resistor, preferably near the controller.

11. Install the control panel
To install the control panel: 1. Close the front cover and tighten the
screw. 2. Put the bottom edge of the control panel
into position. 3. Push the top of the control panel until it
locks into position.
12. Start up the drive
WARNING! Before you start up the drive, make sure that the installation is completed. Make sure also that it is safe to start the motor. Disconnect the motor from other machinery, if there is a risk of damage or injury.
The control panel has softkeys below the display to access the related commands, and arrow keys to navigate the menu and change parameter values. Push the "?" button to open the help function. Make sure that you have the motor nameplate data available. 1. Power up the drive. The set up assistant runs automatically. Wait until the
control panel shows the language selection list. 2. Select the user interface language with
the arrow keys, then push the right softkey (OK).
3. Select Start set-up and push the right softkey (Next).

4. Select the localization and push the right softkey (Next).
5. To complete the set up assistant, enter the settings and values when you are prompted.

You can also use Primary settings in the Main menu to configure the unit. In Primary settings, you can select a macro, set operation limits (speed), acceleration and deceleration ramps as required by the application. In I/O, you can define external control signal sources (IO or fieldbus).

WARNING! If you activate the automatic fault reset or automatic
restart functions of the drive control program, make sure that no dangerous situations can occur. These functions reset the drive automatically and continue operation after a fault or supply break. If
these functions are activated, the installation must be clearly marked as defined in IEC/EN 61800-5-1, subclause 6.5.3, for example, "THIS MACHINE STARTS AUTOMATICALLY".

 Fieldbus settings
If necessary, configure the drive for fieldbus communication. The table below shows the minimum set of parameters required to configure Modbus RTU communication through the embedded fieldbus interface. If you use a fieldbus adapter, refer to the applicable fieldbus adapter documentation.

No. 20.01 22.11 28.11 31.11 58.01 58.03 58.04 58.05

Name Ext1 commands Ext1 speed ref1 (vector) Ext1 frequency ref1 (scalar) Fault reset selection Protocol enable Node address Baud rate Parity

Value Embedded fieldbus EFB ref1 EFB ref1 DI1 1) Modbus RTU 1 (default) 19.2 kbps (default) 8 EVEN 1 (default)

1) If you select DI1, you must connect the reset signal to digital input DI1.

Warnings and faults

Warning A2A1
A2B1
A2B3
A2B4 -
A3A1
A3A2
A5A0
-
-
A7AB
AFF6 -

Fault 2281
2310
2330
2340 3130 3181 3210
3220
3381 5091 6681
7510
-
FA81 FA82

Description
Warning: Current calibration is done at the next start. Fault: Output phase current measurement fault.
Overcurrent. The output current is more than the internal limit. This can be caused by an earth fault or phase loss.
Earth leakage. A load unbalance that is typically caused by an earth fault in the motor or the motor cable.
Short circuit. There is a short circuit in the motor or the motor cable.
Input phase loss. The intermediate DC circuit voltage oscillates.
Cross connection. The input and motor cable connections are incorrect.
DC link overvoltage. There is an overvoltage in the intermediate DC circuit.
DC link undervoltage. There is an undervoltage in the intermediate DC circuit.
Output phase loss. All three phases are not connected to the motor.
Safe torque off. The Safe torque off (STO) function is on.
EFB communication loss. There is a problem with the embedded fieldbus connection.
FBA A communication. Communication is lost between drive and fieldbus adapter, or between controller and fieldbus adapter.
Extension I/O configuration failure. The I/O module is not installed, or ABB limited macro is not selected.
Identification run. The motor ID run occurs at the next start.
Safe torque off 1. The Safe torque off circuit 1 is broken.
Safe torque off 2. The Safe torque off circuit 2 is broken.

Ratings

IEC type Input ratings

ACS480- No

With

04-...

choke choke

I1N

I1N

A

A

1-phase UN = 230 V 1)

02A4-1

5.0

4.2

03A7-1

7.1

6.4

04A8-1

8.8

8.3

Max. current
Imax A

Output ratings

Nominal use Light-duty use

IN

PN

ILd

PLd

A kW A kW

3.2

2.4 0.37 2.3 2.4

4.3 3.7 0.55 3.5 3.7

6.7

4.8 0.75 4.6 0.75

Heavy-duty use
IHd PHd A kW

Frame size

1.8 0.25 R0 2.4 0.37 R0 3.7 0.55 R1

Related documents

ACS480 manual list

ACS480 online videos

Ecodesign information (EU 2019/1781)

3AXD50000047400 Rev D EN 2021-07-20 Original instructions. © Copyright 2021 ABB. All rights reserved.

IEC type Input ratings

ACS480- No

04-...

choke

With choke

I1N

I1N

A

A

06A9-1

12.0

11.9

07A8-1

14.2

13.5

09A8-1

18.7

17.0

12A2-1

24.6

21.1

3-phase UN = 230 V 1)

02A4-2

3.6

2.4

03A7-2

5.1

3.7

04A8-2

6.3

4.8

06A9-2

8.4

6.9

07A8-2

10.1

7.8

09A8-2

13.8

9.8

12A2-2

17.3

12.2

17A5-2

22.2

17.5

25A0-2

29.1

25.0

032A-2

37.0

32.0

048A-2

50.0

48.0

055A-2

60.0

55.0

3-phase UN = 400 V

02A7-4

3.8

2.6

03A4-4

5.1

3.3

04A1-4

6.4

4.0

05A7-4

8.9

5.6

07A3-4

10.9

7.2

09A5-4

13.9

9.4

12A7-4

17.6

12.6

018A-4

25.2

17.0

026A-4

34.1

25.0

033A-4

43.4

32.0

039A-4

52.3

38.0

046A-4 56.0

45.0

050A-4 58.9

50.0

Max. current
Imax A 8.6
12.4 14.0 17.6

Output ratings

Nominal use Light-duty use

IN

PN

ILd

PLd

A kW A kW

6.9 1.10 6.6 1.10

7.8 1.5 7.4 1.5

9.8 2.2 9.3 2.2

12.2 3.0 11.6 3.0

3.2 4.3 6.7 8.6 12.4 14.0 17.6 22.0 31.5 45.0 57.6 86.4

2.4 0.37 2.4 0.37 3.7 0.55 3.2 0.55 4.8 0.75 4.6 0.75 6.9 1.1 6.6 1.1 7.8 1.5 7.5 1.5 9.8 2.2 9.3 2.2 12.2 3.0 11.6 3.0 17.5 4.0 16.7 4.0 25.0 5.5 24.2 5.5 32.0 7.5 30.8 7.5 48.0 11.0 46.2 11.0 55.0 15.0 52.8 15.0

3.2 4.7 5.9 7.2 10.1 13.0 16.9 22.7 30.6 45.0 57.6 68.4 81.0

2.6 0.75 2.5 0.75 3.3 1.1 3.1 1.1 4.0 1.5 3.8 1.5 5.6 2.2 5.3 2.2 7.2 3.0 6.8 3.0 9.4 4.0 8.9 4.0 12.6 5.5 12.0 5.5 17.0 7.5 16.2 7.5 25.0 11.0 23.8 11.0 32.0 15.0 30.5 15.0 38.0 18.5 36.0 18.5 45.0 22.0 42.8 22.0 50.0 22.0 48.0 22.0

Heavy-duty use
IHd PHd A kW 4.8 0.75 6.9 1.1 7.8 1.5 9.8 2.2

Frame size
R1 R1 R2 R2

1.8 0.25 R1

2.4 0.37 R1

3.7 0.55 R1

4.8 0.75 R1

6.9

1.1

R1

7.8 1.5 R1

9.8 2.2 R2

12.2 3.0 R3

17.5 4.0 R3

25.0 5.5 R4

32.0 7.5 R4

48.0 11.0 R4

1.8 0.55 R1

2.6 0.75 R1

3.3

1.1

R1

4.0 1.5 R1

5.6 2.2 R1

7.2 3.0 R1

9.4 4.0 R2

12.6 5.5 R3

17.0 7.5 R3

25.0 11.0 R4

32.0 15.0 R4

38.0 18.5 R4

45.0 22.0 R4

UL (NEC) Input ratings

type ACS48004-...

No choke
I1Ld

With choke
I1Ld

A

A

1-phase UN = 230 V 1)

02A3-1

4.8

4.0

03A5-1

6.8

6.1

04A6-1

8.2

8.0

06A6-1

12.0

11.4

07A4-1

13.0

12.8

09A3-1

18.0

16.1

11A6-1

20.6

20.1

3-phase UN = 230 V 1)

02A3-2

3.5

2.4

03A5-2

4.8

3.2

04A6-2

5.8

4.6

06A6-2

8.3

6.6

07A5-2

9.2

7.5

11A6-2

12.8

11.6

017A-2

20.5

16.7

024A-2

29.7

24.2

031A-2

36.0

30.8

046A-2

50.5

46.2

053A-2

57.6

52.8

3-phase UN = 480 V

02A1-4

3.0

2.1

03A0-4

4.3

3.0

03A5-4

4.9

3.5

04A8-4

6.7

4.8

06A0-4

6.7

6.0

07A6-4

10.6

7.6

011A-4

14.9

11.0

014A-4

20.2

14.0

021A-4

28.5

21.0

027A-4

35.8

27.0

034A-4 43.8

34.0

042A-4 49.4

42.0

Max. current
Imax A
3.2 4.3 6.7 8.6 12.4 14.0 17.6
3.2 4.3 6.7 8.6 12.4 17.6 22.0 31.5 45.0 57.6 86.4
3.2 4.7 5.9 7.2 10.1 13.0 16.9 22.7 30.6 45.0 57.6 81.0

Output ratings

Frame

Light-duty use

Heavy-duty use size

ILd

PLd

IHd

PHd

A

hp

A

hp

2.3

0.5

1.8

0.33

R0

3.5

0.8

2.3

0.5

R0

4.6

1.0

3.5

0.75

R1

6.6

1.5

4.6

1.0

R1

7.4

2.0

6.6

1.5

R1

9.3

3.0

7.4

2.0

R2

11.6

3.0

9.3

3.0

R2

2.4 3.2 4.6 6.6 7.5 11.6 16.7 24.2 30.8 46.2 52.8

0.5 0.75 1.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 20.0

1.8 2.4 3.2 4.6 6.6 9.3 11.6 16.7 24.2 30.8 46.2

0.33

R1

0.5

R1

0.75

R1

1.0

R1

1.5

R1

3.0

R2

3.0

R3

5.0

R3

7.5

R4

10.0

R4

15.0

R4

2.1

1.0

1.6

0.75

R1

3.0

1.5

2.1

1.0

R1

3.5

2.0

3.0

1.5

R1

4.8

3.0

3.5

2.0

R1

6.0

3.0

4.8

3.0

R1

7.6

5.0

6.0

3.0

R1

11.0

7.5

7.6

5.0

R2

14.0

10.0

11.0

7.5

R3

21.0

15.0

14.0

10.0

R3

27.0

20.0

21.0

15.0

R4

34.0

25.0

27.0

20.0

R4

42.0

30.0

40.0

30.0

R4

1) 230 V drives not available at the time of publication. For availability, contact ABB.

Fuses and typical power cable sizes

IEC type UL (NEC) ACS480- type 04-... ACS480-
04-...

gG ABB type

1-phase UN = 230 V 02A4-1 02A3-1 OFAF000H10

03A7-1 03A5-1 OFAF000H10

04A8-1 04A6-1 OFAF000H16

06A9-1 06A6-1 OFAF000H20

07A8-1 07A4-1 OFAF000H25

09A8-1 09A3-1 OFAF000H32

12A2-1 11A6-1 OFAF000H35

3-phase UN = 230 V 02A4-2 02A3-2 OFAF000H6

03A7-2 03A5-2 OFAF000H10

04A8-2 04A6-2 OFAF000H10

06A9-2 06A6-2 OFAF000H16

07A8-2 07A5-2 OFAF000H16

09A8-2 -

OFAF000H16

12A2-2 11A6-2 OFAF000H25

17A5-2 017A-2 OFAF000H32

25A0-2 024A-2 OFAF000H50

032A-2 031A-2 OFAF000H63

048A-2 046A-2 OFAF000H100

055A-2 053A-2 OFAF000H100

3-phase UN = 400 V or 480 V 02A7-4 02A1-4 OFAF000H6

03A4-4 03A0-4 OFAF000H6

04A1-4 03A5-4 OFAF000H10

05A7-4 04A8-4 OFAF000H10

07A3-4 06A0-4 OFAF000H16

09A5-4 07A6-4 OFAF000H16

12A7-4 011A-4 OFAF000H25

018A-4 014A-4 OFAF000H32

026A-4 021A-4 OFAF000H50

033A-4 027A-4 OFAF000H63

039A-4 034A-4 OFAF000H80

046A-4 -

OFAF000H100

050A-4 042A-4 OFAF000H100

Fuses gR
Bussmann type
170M2695 170M2695 170M2696 170M2697 170M2698 170M2698 170M2698
170M2694 170M2695 170M2695 170M2696 170M2696 170M2696 170M2697 170M2698 170M2699 170M2700 170M2702 170M2702
170M2694 170M2694 170M2695 170M2695 170M2696 170M2696 170M2697 170M2698 170M2699 170M2700 170M2701 170M2702 170M2702

UL class T 1) 2) 3)
Bussmann/ Edison type

Cable conductor Frame

sizes (Cu)

size

mm2

AWG

JJN/TJN10 3×1.5 + 1.5 16 R0

JJN/TJN10 3×1.5 + 1.5 16 R0

JJN/TJN20 3×1.5 + 1.5 16 R1

JJN/TJN20 3×1.5 + 1.5 16

R1

JJN/TJN25 3×1.5 + 1.5 16

R1

JJN/TJN25 3×2.5 + 2.5 14 R2

JJN/TJN35 3×2.5 + 2.5 14 R2

JJS/TJS6 3×1.5 + 1.5 16 R1

JJS/TJS10 3×1.5 + 1.5 16 R1

JJS/TJS10 3×1.5 + 1.5 16

R1

JJS/TJS20 3×1.5 + 1.5 16 R1

JJS/TJS20 3×1.5 + 1.5 16

R1

JJS/TJS20 3×2.5 + 2.5 14 R1

JJS/TJS25 3×2.5 + 2.5 14 R2

JJS/TJS35 3×6 + 6

10

R3

JJS/TJS50 3×6 + 6

10

R3

JJS/TJS60 3×10 + 10 8

R3

JJS/TJS100 3×25 + 16 4

R4

JJS/TJS100 3×25 + 16 4

R4

JJS/TJS6 3×1.5 + 1.5 16 R1

JJS/TJS6 3×1.5 + 1.5 16 R1

JJS/TJS10 3×1.5 + 1.5 16 R1

JJS/TJS10 3×1.5 + 1.5 16 R1

JJS/TJS20 3×1.5 + 1.5 16 R1

JJS/TJS20 3×2.5 + 2.5 14 R1

JJS/TJS25 3×2.5 + 2.5 14 R2

JJS/TJS35 3×6 + 6

10

R3

JJS/TJS40 3×6 + 6

10

R3

JJS/TJS60 3×10 + 10 8

R4

JJS/TJS80 3×16 + 16 6

R4

JJS/TJS100 3×25 + 16 4

R4

JJS/TJS100 3×25 + 16 4

R4

1) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 listing.
2) The drive is suitable for use on a circuit capable of delivering not more than 100000 symmetrical amperes (rms) at 480 V (480 V drive types) or 240 V (240 V drive types) maximum when protected by the fuses given in this table.
3) As an alternative to Class T fuses, you can use Class J or Class CF fuses of the same voltage and current rating for branch circuit protection of 3-phase drives.

Terminal data for the power cables

Frame size
R0 R1 R2 R3 R4

L1, L2, L3, T1/U, T2/V, T3/W, R-, R+/UDC+, UDC-

Min. wire size (solid/
stranded) mm2 AWG

Max. wire size (solid/
stranded) mm2 AWG

Tightening torque
N·m lbf·in

0.5/0.5 18 4/2.5 10 0.5...0.6 5

0.5/0.5 18 4/2.5 10 0.5...0.6 5

0.5/0.5 18 4/2.5 10 0.5...0.6 5

0.5/0.5 18 10/6 6 1.2...1.5 11...13

0.5/0.5 18 25/16 2 2.5...3.7 22...32

PE

Max. wire size (solid/
stranded) mm2 AWG

Tightening torque
N·m lbf·in

6/4 10 1.2 11

6/4 10 1.2 11

6/4 10 1.2 11

6/4 10 1.2 11

25/16 4 2.9 26

Note: · The minimum specified wire size does not necessarily have sufficient current carrying

capacity at maximum load. · The terminals do not accept a conductor that is one size larger than the maximum
specified wire size. · The maximum number of conductors per terminal is 1.

Ambient conditions

Requirement Installation altitude
Surrounding air temperature
Relative humidity Contamination levels Shock or free fall

During operation (installed for stationary use)
230 V drives: 0 ... 2000 m (0 ... 6562 ft) above sea level.
400/480 V drives: 0 ... 4000 m (0 ... 13123 ft) above sea level. At altitudes above 2000 m (6562 ft): · only TN-S and TT grounding systems are permitted · the maximum permitted voltage for the integrated relay outputs
decreases. At 4000 m (13123 ft), it is 30 V.
Derating: The output current must be derated 1% for each 100 m (328 ft) above 1000 m (3281 ft).
Frame R0: -10 ... +50 °C (14 ... 122 °F). No frost permitted.
Frames R1...R4: -10 ... +60 °C (14 ... 140 °F). No frost permitted. The output current must be derated at temperatures above +50 °C (122 °F) as follows: · IEC types 055A-2, 039A-4, 050A-4 and UL (NEC) types 053A-2,
034A-4 and 042A-4: 2% for each added 1 °C (1.8°F) · Other types: 1% for each added 1 °C (1.8°F).
5 ... 95%. No condensation permitted. Maximum permitted relative humidity is 60% in the presence of corrosive gases.
No conductive dust permitted
Not permitted

Dimensions and weights
D

W

Ø 5 mm (0.2")

M1

Ø 10 mm (0.4")

H2 H1 H3

M2
Ø 5 mm (0.2")

Frame size
R0 R1 R2 R3 R4

H1
mm in 205 8.1 205 8.1 205 8.1 205 8.1 205 8.1

H2
mm in 223 8.8 223 8.8 223 8.8 220 8.7 240 9.5

Dimensions

H3

W

D

mm in mm in mm in 170 6.7 73 2.9 208 8.2

170 6.7 73 2.9 208 8.2

170 6.7 97 3.8 208 8.2

170 6.7 172 6.8 208 8.2

170 6.7 262 10.3 213 8.4

M1
mm in 50 2.0 50 2.0 75 3.0 148 5.8 234 9.2

M2
mm in 191 7.5 191 7.5 191 7.5 191 7.5 191 7.5

Weights
kg lb 1.70 3.74 1.77 3.90 2.35 5.19 3.52 7.76 6.02 13.3

Free space requirements

Frame size R0...R4

Above

mm

in

75

3

Below

mm

in

75

3

Sides 1)

mm

in

0

0

1) A side-mounted option requires approximately 20 mm (0.8 in) of space on the right side of the drive.

Markings
The applicable markings are shown on the type designation label of the drive.

CE

UL

RCM

UKCA EAC

KC EIP green WEEE TÜV Nord

Safe torque off (STO)

The drive has a Safe torque off function (STO) in accordance with IEC/EN 61800-5-2. It can be used, for example, as the final actuator device of safety circuits that stop the drive in case of danger (such as an emergency stop circuit). When activated, the STO function disables the control voltage of the power semiconductors of the drive output stage, thus preventing the drive from generating the torque required to rotate the motor. The control program generates an indication as defined by parameter 31.22. If the motor is running when Safe torque off is activated, it coasts to a stop. Closing the activation switch deactivates the STO. Any faults generated must be reset before restarting. The STO function has a redundant architecture, that is, both channels must be used in the safety function implementation. The safety data given is calculated for redundant use, and does not apply if both channels are not used.

WARNING! The STO function does not disconnect the voltage from the main and auxiliary circuits of the drive.

Notes:
· If stopping by coasting is not acceptable, stop the drive and machinery using
the appropriate stop mode before activating the STO.
· The STO function overrides all other functions of the drive.
 Wiring
The safety contacts must open/close within 200 ms of each other. Double-shielded twisted-pair cable is recommended for the connection. The maximum length of the cabling between the switch and the drive control unit is 300 m (1000 ft). Ground the shield of the cable at the control unit only.
 Validation
To ensure the safe operation of a safety function, a validation test is required. The test must be carried out by a competent person with adequate expertise and knowledge of the safety function. The test procedures and report must be documented and signed by this person. Validation instructions of the STO function can be found in the drive hardware manual.
 Technical data
· Minimum voltage at IN1 and IN2 to be interpreted as "1": 13 V DC · STO reaction time (shortest detectable break): 1 ms · STO response time: 2 ms (typical), 5 ms (maximum) · Fault detection time: Channels in different states for longer than 200 ms · Fault reaction time: Fault detection time + 10 ms · STO fault indication (parameter 31.22) delay: < 500 ms · STO warning indication (parameter 31.22) delay: < 1000 ms · Safety integrity level (EN 62061): SIL 3 · Performance level (EN ISO 13849-1): PL e
The drive STO is a type A safety component as defined in IEC 61508-2. For the full safety data, exact failure rates and failure modes of the STO function, refer to the drive hardware manual.
Declarations of conformity

Declaration of Conformity

Supply of Machinery (Safety) Regulations 2008

We Manufacturer: Address: Phone:

xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
ABB Oy Hiomotie 13, 00380 Helsinki, Finland. +358 10 22 11

declare under our sole responsibility that the following product:

xxxxxxxxxxxxxxxxxxxxxxxxxxx

Frequency converter ACS480-04
with regard to the safety function Safe Torque Off

is in conformity with all the relevant safety component requirements of the Supply of Machinery (Safety) Regulations 2008, when the listed safety function is used for safety component functionality.

The following designated standards have been applied: EN 61800-5-2:2007
EN 62061:2005 + AC:2010 + A1:2013 + A2:2015

Adjustable speed electrical power drive systems ­ Part 5-2: Safety requirements Functional Safety of machinery ­ Functional safety of safety-related electrical, electronic and programmable electronic control systems

EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 60204-1:2018 The following other standards have been applied: IEC 61508:2010, parts 1-2 IEC 61800-5-2:2016

Safety of machinery ­ Safety-related parts of control systems. Part 1: General requirements Safety of machinery ­ Safety-related parts of the control systems. Part 2: Validation Safety of machinery ­ Electrical equipment of machines ­ Part 1: General requirements
Functional safety of electrical / electronic / programmable electronic safetyrelated systems Adjustable speed electrical power drive systems ­ Part 5-2: Safety requirements Functional

The product(s) referred in this declaration of conformity fulfil(s) the relevant provisions of other UK statutory requirements, which are notified in a single declaration of conformity 3AXD10001324452.
Authorized to compile the technical file: ABB Limited, Daresbury Park, Cheshire, United Kingdom, WA4 4BT.

Helsinki, May 7, 2021 Signed for and on behalf of:
Tuomo Tarula Local Division Manager, ABB Oy
Document number 3AXD10001329531

Harri Mustonen Product Unit Manager, ABB Oy


Acrobat Distiller 21.0 (Windows)