ebm-papst R3G500-RA28-03 Operating Instructions

Manufacturer: ebm-papst Mulfingen GmbH & Co. KG

Address: Bachmühle 2, D-74673 Mulfingen

Contact: info1@de.ebmpapst.com | www.ebmpapst.com

1. Safety Regulations and Information

Read these operating instructions carefully before starting work on the device. Observe the following warnings to prevent malfunctions or danger to persons.

These operating instructions are to be regarded as part of the device. The device is only to be sold or passed on together with the operating instructions.

These operating instructions may be duplicated and distributed to inform about potential dangers and their prevention.

1.1 Hazard levels for warnings

DANGER: Indicates an imminently hazardous situation which will result in death or serious injury if the specified actions are not taken. Compliance with the instructions is imperative.

WARNING: Indicates a potentially hazardous situation which can result in death or serious injury if the specified actions are not taken. Exercise extreme caution while working.

CAUTION: Indicates a potentially hazardous situation which can result in minor or moderate injury or damage to property if the specified actions are not taken.

NOTE: A potentially harmful situation can occur and, if not avoided, can lead to property damage.

1.2 Staff Qualifications

The device may only be transported, unpacked, installed, operated, maintained and otherwise used by suitably qualified, trained and authorized technical staff. Only authorized specialists are permitted to install the device, to carry out a test run and to perform work on the electrical installation.

1.3 Basic Safety Rules

The safety hazards associated with the device must be assessed again following installation in the final product. The locally applicable industrial safety regulations are always to be observed when working on the device.

Keep the workplace clean and tidy. Untidiness in the work area increases the risk of accidents.

Note the following when working on the device:

  • Do not perform any modifications, additions or conversions on the device without the approval of ebm-papst.

1.4 Voltage

DANGER: Electrically charged device. Risk of electric shock.

  • When working on an electrically charged device, stand on a rubber mat.

WARNING: Live terminals and connections even with device switched off. Electric shock.

  • Wait five minutes after disconnecting the voltage at all poles before opening the device.

CAUTION: In the event of a fault, the rotor and the impeller will be energized. The rotor and the impeller have basic insulation.

  • Do not touch the rotor and impeller once installed.

CAUTION: If control voltage or a stored speed set value is applied, the motor will restart automatically, e.g. after a power failure. Risk of injury.

  • Keep out of the device's danger zone.
  • When working on the device, switch off the line voltage and ensure that it cannot be switched back on.
  • Wait until the device comes to a stop.
  • After working on the device, remove any tools or other objects from the device.

1.5 Safety and Protective Features

DANGER: Guard missing and guard not functioning. Without a guard, hands may become caught up in the device during operation for example, resulting in serious injury. Loose parts or items of clothing could be drawn in.

  • The device is a built-in component. As the owner, you are responsible for ensuring that the device is adequately safeguarded. Operate the device only with a fixed protective device and guard grill.
  • Stop the device immediately if a protective device is found to be missing or ineffective.

1.6 Electromagnetic Radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction with open- and closed-loop control devices. If impermissible radiation levels occur following installation, appropriate shielding measures have to be taken by the user.

NOTE: Electrical or electromagnetic interference after installing the device in customer equipment.

  • Verify that the entire setup is EMC-compliant.

1.7 Mechanical Movement

DANGER: Rotating device. Risk of injury to body parts coming into contact with the rotor or the impeller.

  • Secure the device against accidental contact.
  • Before working on the system/machine, wait until all parts have come to a standstill.

DANGER: Ejected parts. Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries.

  • Take appropriate safety measures.

WARNING: Rotating device. Long hair and dangling items of clothing, jewelry and the like can become entangled and be pulled into the device. Injuries can result.

  • Do not wear any loose-fitting or dangling clothing or jewelry while working on rotating parts.
  • Protect long hair with a cap.

1.8 Emissions

WARNING: Depending on the installation and operating conditions, the sound pressure level may exceed 70 dB(A). Risk of noise-induced hearing loss.

  • Take appropriate technical safety measures.
  • Protect operating personnel with appropriate safety equipment such as hearing protection.
  • Also observe the requirements of local agencies.

1.9 Hot Surface

CAUTION: High temperature on electronics housing. Risk of burns.

  • Ensure sufficient protection against accidental contact.

1.10 Transport

WARNING: Transporting the fan. Injuries from tipping or slipping, damage to the fan.

  • Always transport the fan with care and in its original packaging. Impact, e.g. if set down too hard or at an angle, can lead to bearing damage or impeller deformations. It must be ensured that the fans cannot tip over during transportation and handling. Secure the fan(s) e.g. with a lashing strip to stop anything slipping or tipping.

1.11 Storage

  • Store the device, partially or fully assembled, in a dry place, protected against the weather and free from vibration, in the original packaging in a clean environment.
  • Protect the device against environmental effects and dirt until final installation.
  • We recommend storing the device for no longer than one year in order to guarantee trouble-free operation and the longest possible service life.
  • Even devices explicitly intended for outdoor use are to be stored as described prior to commissioning.
  • Maintain the storage temperature, see Chapter 3.6 Transport and storage conditions.
  • Make sure that all cable glands are fitted with dummy plugs.

2. Intended Use

The device is exclusively designed as a built-in device for conveying air according to its technical data. Any other usage above and beyond this does not conform with the intended purpose and constitutes misuse of the device. Customer equipment must be capable of withstanding the mechanical and thermal stresses that can arise from this product. This applies for the entire service life of the equipment in which this product is installed.

Intended use also includes:

  • The device is only to be used in power systems with grounded neutral (TN/TT power systems), in power systems with phase conductor grounding, or in IT power systems.
  • The device is to be used in networks with network quality characteristics as per EN 50160.
  • Using the device only in stationary systems.
  • Performing all maintenance work.
  • Conveying air at an ambient air pressure between 800 mbar and 1050 mbar.
  • Using the device within the permitted ambient temperature range; see Chapter 3.6 Transport and storage conditions and Chapter 3.2 Nominal data.
  • Operating the device with all protective devices.
  • Following the operating instructions.

Improper Use

In particular, operating the device in the following ways is prohibited and could be hazardous:

  • Operating the device in an unbalanced state, e.g. due to dirt deposits or ice formation.
  • Resonant operation, operation with severe vibration. This also includes vibration transmitted to the fan from the customer installation.
  • Operation in medical equipment with a life-sustaining or life-support function.
  • Conveying solids in the flow medium.
  • Painting the device.
  • Connections (e.g. screws) coming loose during operation.
  • Opening the terminal box during operation.
  • Conveying air that contains abrasive particles.
  • Conveying highly corrosive air, e.g. salt spray. Exception: devices designed for salt spray and correspondingly protected.
  • Conveying air with high dust content, e.g. suctioning off sawdust.
  • Operating the device close to flammable materials or components.
  • Operating the device in an explosive atmosphere.
  • Using the device as a safety component or to perform safety-related functions.
  • Operation with completely or partially disassembled or manipulated protective devices.
  • In addition, all applications not listed among the intended uses.

3. Technical Data

3.1 Product Drawing

Diagram showing the physical dimensions of the R3G500-RA28-03 fan. All dimensions are in mm.

Key Dimensions:

  • Overall diameter: Ø232 mm
  • Motor housing diameter: Ø70 mm
  • Mounting flange diameter: Ø257.5±2 mm
  • Impeller diameter: Ø334.5-0.5 mm
  • Overall length: 227 mm
  • Bolt circle for mounting: Ø275 mm
  • Mounting holes: Ø5.5 mm, 6x60° spacing
  • Connection thread for mounting: M10 (6x)
  • Detail view showing a 12 mm dimension.

References for drawing dimensions:

ItemDescription
1Accessory part: inlet ring 50901-2-2943 not included in scope of delivery.
2Max. clearance for screw 20 mm.
3Cable diameter min. 4 mm, max. 10 mm, tightening torque 4 ± 0.6 Nm. (The tightening torque is designed for PVC cables. If the cable materials are different, the tightening torque may have to be adjusted).
4Tightening torque 1.5 ± 0.2 Nm.

Additional dimensions for inlet ring (accessory part):

  • Outer diameter: Ø319.5 mm
  • Inner diameter: Ø470 mm
  • Flange width: 75 mm
  • Radii: R49, R28, R87
  • Mounting holes: Ø9 mm, 6x60° spacing
  • Bolt circle for mounting: Ø435 mm, Ø445 mm
  • Flange thickness: 3.5 mm

3.2 Nominal Data

ParameterValue
MotorM3G150-FF
Phase3~
Nominal voltage / VAC400
Nominal voltage range / VAC380.. 480
Frequency / Hz50/60
Method of obtaining dataml
Statusprelim.
Speed (rpm) / min⁻¹1900
Power consumption / W3600
Current draw / A5.5
Min. ambient temperature / °C-40
Max. ambient temperature / °C40

ml = Max. load, me = Max. efficiency, fa = Free air, cs = Customer specification, ce = Customer equipment. Subject to change.

Occasional start-up at temperatures between -40 °C and -25 °C is permitted. For continuous operation at ambient temperatures below -25 °C (such as refrigeration applications), a fan design with special low-temperature bearings must be used.

3.3 Data according to Commission Regulation (EU) 327/2011

ParameterActualReq. 2015
01 Overall efficiency ηes / %64.357.3
02 Measurement categoryA
03 Efficiency categoryStatic
04 Efficiency grade N6962
05 Variable speed driveYes
06 Year of manufactureThe year of manufacture is specified on the product's rating label.
07 Manufacturerebm-papst Mulfingen GmbH & Co. KG, Amtsgericht (court of registration) Stuttgart, HRA 590344, D-74673 Mulfingen
08 TypeR3G500-RA28-03
09 Power consumption Ped / kW3.58
09 Air flow qv / m³/h8125
09 Pressure increase total pfs / Pa979
10 Speed (rpm) n / min⁻¹1900
11 Specific ratio*1.01
12 Recycling/disposalInformation on recycling and disposal is provided in the operating instructions.
13 MaintenanceInformation on installation, operation and maintenance is provided in the operating instructions.
14 Additional componentsComponents used to calculate the energy efficiency that are not apparent from the measurement category are detailed in the CE declaration.

* Specific ratio = 1 + pfs / 100 000 Pa

Data obtained at optimum efficiency level. The efficiency values displayed for achieving conformity with the Ecodesign Regulation EU 327/2011 has been reached with defined air duct components (e.g. inlet rings). The dimensions must be requested from ebm-papst. If other air conduction geometries are used on the installation side, the ebm-papst evaluation loses its validity/the conformity must be confirmed again. The product does not fall within the scope of Regulation (EU) 2019/1781 due to the exception specified in Article 2 (2a) (motors completely integrated into a product).

3.4 Technical Description

  • Weight: 20.98 kg
  • Size: 500 mm
  • Motor size: 150
  • Rotor surface: Painted black
  • Electronics housing material: Die-cast aluminum
  • Impeller material: PP plastic
  • Number of blades: 7
  • Direction of rotation: Clockwise, viewed toward rotor
  • Degree of protection: IP55
  • Insulation class: "F"
  • Moisture (F) / Environmental (H) protection class: H1

Ambient temperature note: Occasional start-up at temperatures between -40°C and -25°C is permitted. For continuous operation at ambient temperatures below -25°C (such as refrigeration applications), use must be made of a fan design with special low-temperature bearings.

  • Installation position: Shaft horizontal or rotor on bottom; rotor on top on request.
  • Condensation drainage holes: On rotor side.
  • Mode: S1
  • Motor bearing: Ball bearing
  • Technical features: Operation and alarm display with LED; External 15-50 VDC input (parameterization); Alarm relay; Integrated PI controller; Configurable inputs/outputs (I/O); MODBUS V6.3; Motor current limitation; RS-485 MODBUS-RTU; Soft start; Voltage output 3.3-24 VDC, Pmax = 800 mW; Control interface with SELV potential safely disconnected from the mains; Thermal overload protection for electronics/motor; Line undervoltage / phase failure detection.
  • Touch current according to IEC 60990 (measuring circuit Fig. 4, TN system): ≤ 3.5 mA
  • Electrical hookup: Terminal box.
  • Motor protection: Reverse polarity and locked-rotor protection.
  • Protection class: I (with customer connection of protective earth).
  • Conformity with standards: EN 61800-5-1; CE; UKCA.
  • Approval: CSA C22.2 No. 77 + CAN/CSA-E60730-1; EAC; UL 1004-7 + 60730-1.

Use the device in accordance with its degree of protection.

Information on Surface Quality

The surfaces of the products conform to the generally applicable industrial standard. The surface quality may change during the production period. This has no effect on strength, dimensional stability and dimensional accuracy. The color pigments in the paints used perceptibly react to UV light over the course of time. The product is to be protected against UV radiation to prevent the formation of patches and fading. Changes in color are not a reason for complaint and are not covered by the warranty. UV radiation in the frequency range and the intensity of natural solar radiation has no effect on the technical properties of the products.

3.5 Mounting Data

Further mounting data can be taken from the product drawing or Chapter 4.1 Mechanical connection as required.

ParameterValue
Strength class of screws8.8
  • Secure the screws against unintentional loosening (e.g. use self-locking screws).

3.6 Transport and Storage Conditions

ParameterValue
Max. permitted ambient temp. for motor (transport/storage)+80 °C
Min. permitted ambient temp. for motor (transport/storage)-40 °C

3.7 Electromagnetic Compatibility

  • EMC immunity to interference: According to EN 61000-6-2 (industrial environment).
  • EMC interference emission: According to EN 61000-6-3 (household environment), except EN 61000-3-2 for professionally used equipment with a total rated power greater than 1 kW.

If several devices are connected in parallel on the supply side so that the line current of the arrangement is in the range 16 - 75 A, this arrangement conforms to IEC 61000-3-12, provided that the short-circuit power Ssc at the connection point of the customer system to the public power grid is greater than or equal to 250 times the rated output of the arrangement. It is the responsibility of the installation engineer or operator/owner of the device to ensure, if necessary after consultation with the network operator, that this device is only connected to a connection point with an Ssc value greater than or equal to 250 times the rated output of the arrangement.

4. Connection and Startup

4.1 Mechanical Connection

CAUTION: Cutting and crushing hazard when removing fan from packaging.

  • Carefully remove the device from its packaging, by the fan impeller. Strictly avoid shocks.
  • Wear safety shoes and cut-resistant safety gloves.

CAUTION: Heavy load when unpacking device. Risk of physical injury, such as back injuries.

  • Two people should work together to remove the device from its packaging.

NOTE: Damage to the device from vibration. Bearing damage, shorter service life.

  • The fan must not be subjected to force or excessive vibration from sections of the installation.
  • If the fan is connected to air ducts, the connection should be isolated from vibration, e.g. using compensators or similar elements.
  • Ensure stress-free attachment of the fan to the substructure.
  • Check the device for transport damage. Damaged devices are not to be installed.
  • Install the undamaged device in accordance with your application.

CAUTION: Possible damage to the device. If the device slips during installation, serious damage can result.

  • Ensure that the device is securely positioned at its place of installation until all fastening screws have been tightened.
  • The fan must not be strained on fastening.

4.2 Electrical Connection

DANGER: Voltage on the device. Electric shock.

  • Always connect a protective earth first.
  • Check the protective earth.

DANGER: Faulty insulation. Risk of fatal injury from electric shock.

  • Use only cables that meet the specified installation regulations for voltage, current, insulation material, capacity, etc.
  • Route cables so that they cannot be touched by any rotating parts.

DANGER: Electrical charge (>50 µC) between phase conductor and protective earth connection after switching off supply with multiple devices connected in parallel. Electric shock, risk of injury.

  • Ensure sufficient protection against accidental contact.
  • Before working on the electrical hookup, short the supply and PE connections.

CAUTION: Voltage. The fan is a built-in component and has no disconnecting switch.

  • Only connect the fan to circuits that can be switched off with an all-pole disconnection switch.
  • When working on the fan, secure the system/machine in which the fan is installed so as to prevent it from being switched back on.

NOTE: Device malfunctions possible.

  • Route the device's control lines separately from the supply line.
  • Maintain the greatest possible clearance. Recommendation: clearance > 10 cm (separate cable routing).

NOTE: Water ingress into wires or cables. Water ingress at the customer end of the cable can damage the device.

  • Make sure the end of the cable is connected in a dry environment.
  • Only connect the device to circuits that can be switched off with an all-pole disconnection switch.

4.2.1 Requirements

  • Check whether the information on the nameplate matches the connection data.
  • Before connecting the device, make sure the power supply matches the device voltage.
  • Only use cables designed for the current level indicated on the nameplate. For determining the cross-section, note the sizing criteria according to EN 61800-5-1. The protective earth must have a cross-section equal to or greater than that of the phase conductor.
  • We recommend the use of 105 °C cables. Ensure that the minimum cable cross-section is at least AWG 26 / 0.13 mm².

Protective earth contact resistance according to EN 61800-5-1

Compliance with the resistance specifications according to EN 61800-5-1 for the protective earth connection circuit must be verified in the end application. Depending on the installation situation, it may be necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device. The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole.

4.2.2 Supply Connection and Fuses

Assignment of supply cable cross-sections and their required fuses (line protection only, no equipment protection).

Nominal voltageFuse VDEFuse ULAutomatic circuit breaker VDECable cross-section mm²Cable cross-section *AWG
3/PE AC 380-480 VAC16 A15 AC16A1.516
3/PE AC 380-480 VAC20 A20 AC20A2.514
3/PE AC 380-480 VAC25 A25 AC25A4.012

* AWG = American Wire Gauge

4.2.3 Reactive Currents

Because of the EMC filter integrated for compliance with EMC limits (interference emission and immunity to interference), reactive currents can be measured in the supply line even when the motor is at a standstill and the line voltage is switched on.

  • The values are typically in the range < 500 mA.
  • At the same time, the effective power in this operating state (operational readiness) is typically < 6 W.

4.2.4 Residual Current Circuit Breaker (RCCB)

If the use of a residual current device (RCD) is required in your installation, only AC/DC-sensitive residual current devices (type B or B+) are permissible. As with variable frequency drives, residual current devices cannot provide personal safety while operating the device. When the device power supply is switched on, pulsed charging currents from the capacitors in the integrated EMC filter can lead to the instant tripping of residual current devices. We recommend the use of residual current circuit breakers (RCCB) with a trip threshold of 300 mA and delayed tripping (super-resistant, characteristic K).

4.2.5 Leakage Current

For asymmetrical power systems or if a phase fails, the leakage current can increase to a multiple of the nominal value.

4.2.6 Locked-Rotor Protection

Due to the locked-rotor protection, the starting current (LRA) is equal to or less than the nominal current (FLA).

4.3 Connection in Terminal Box

4.3.1 Preparing Cables for Connection

Only strip the cable as far as necessary, ensuring that the cable gland is sealed and there is no strain on the connections. For tightening torques, see Chapter 3.1 Product drawing.

NOTE: Tightness and strain relief are dependent on the cable used. This must be checked by the user.

Diagram showing recommended stripped lengths inside the terminal box for supply line (1) and control/relay line (2).

Control and relay cables
Parametermin.max.
Rigid cable cross-section0.2 mm²1.5 mm²
Flexible cable cross-section0.2 mm²1.5 mm²
AWG/kcmil cable cross-section2416
Wire-end ferrules with insulating collar, in accordance with DIN 46228-4 for flexible cable0.14 mm²0.75 mm²
Wire-end ferrules without insulating collar, in accordance with DIN 46228-1 for flexible cable0.25 mm²1.5 mm²

NOTE: Crimping and pressing forms of the wire-end ferrules. For flexible control and relay cables, from a cable cross-section of 1.0 mm², a trapezoid crimp is required to ensure correct installation on the connector.

Diagram showing trapezoid crimp dimensions (max. 2.2 mm and max. 1.2 mm).

4.3.2 Terminal Connection Data

Supply line
Parametermin.max.
Rigid cable cross-section0.2 mm²4 mm²
Flexible cable cross-section0.2 mm²4 mm²
AWG/kcmil cable cross-section2412
Wire-end ferrules with insulating collar, in accordance with DIN 46228-4 for flexible cable0.25 mm²4 mm²
Wire-end ferrules without insulating collar, in accordance with DIN 46228-1 for flexible cable0.25 mm²4 mm²

NOTE: The cable and cable cross-section must be selected taking into account the max. starting current of the drive and the type of cable routing (see Chapter 4.2.2 Supply connection and fuses).

4.3.3 Connect Cables to Terminals

WARNING: Live terminals and connections even with device switched off. Electric shock.

  • Wait five minutes after disconnecting the voltage at all poles before opening the device.
  • Open the terminal box.
  • Remove the cap from the cable gland.
  • Only remove caps where cables are fed in.

Diagram showing installation of connectors in the terminal box. Ensure connectors engage properly.

  • Depending on the cable diameter, the seals included in the terminal box must be inserted into the cable gland if necessary.
  • Route the cable(s) (not included in the scope of delivery) into the terminal box.
  • Ensure separate routing of the supply cable(s) and the cables for status contact and control interface. Depending on the requirements for the end device, the physical separation of these cables in the terminal box may be mandatory. Use the partitions inside the terminal box as an aid to routing for this purpose.
  • First connect the protective earth "PE". Tightening torque 3.5 ±0.4 Nm.
  • Connect the cables to the corresponding terminals. Use a screwdriver to do so. When connecting, make sure the wires do not splay out. Insert the strands until they meet with resistance.

Diagram showing connection of cables at terminals. Ensure no tensile stress and proper strain relief.

  • There must not be any tensile stress between the terminal and the cable gland. The cable must be provided with strain relief.
  • The cable glands must be tight.
  • Fit the terminal box cover, making sure that the sealing surfaces are clean.
  • Screw in the four screws (for tightening torque, see Chapter 3.1 Product drawing).

4.3.4 Cable Routing

Water must be prevented from reaching the cable gland along the cable.

NOTE: Damage caused by moisture penetration. Moisture can penetrate into the terminal box if water is constantly present at the cable glands.

  • To prevent the constant accumulation of water at the cable glands, the cable should be routed in a U-shaped loop wherever possible.
  • If this is not possible, a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example.

When routing the cable, make sure that the cable glands are located at the bottom. The cables must always be routed downward.

4.4 Factory Settings

Factory settings made for the device by ebm-papst.

ParameterMode parameter set 1Mode parameter set 2
ModePWM controlPWM control
Fan/device address0101
Max. PWM/%100100
Min. PWM/%55
Save set value to EEPROMYesYes
Set value requirementAnalog (linear)Analog (linear)
Direction of action parameter set 1Positive (heating)
Direction of action parameter set 2Positive (heating)

4.5 Connection Diagram

Diagram illustrating the electrical connections for the device, showing terminal assignments for power supply, communication interfaces (MODBUS), and control signals. Includes input and output characteristic curves.

No.Conn.DesignationFunction/assignment
CON1L1, L2, L3Power supply, phase, see nameplate for voltage range
PEProtective earth
CON2RSARS485 interface for MODBUS, RSA; SELV
RSBRS485 interface for MODBUS, RSB; SELV
GNDReference ground for control interface, SELV
CON2IO1Function parameterizable (see "Optional interface functions" table). Factory setting: Digital input - high active, function: Disable input, SELV. - inactive: Pin open or applied voltage < 1.5 VDC. - active: applied voltage 3.5-50 VDC. Reset function: Triggering of error reset on change of state from "enabled" to "disabled".
CON2IO2Function parameterizable (see "Optional interface functions" table). Factory setting: Analog input 0-10 V / PWM, Ri=100 kΩ, function: Set value. Characteristic curve parameterizable (see input characteristic curve P1-IN), SELV.
CON2IO3Function parameterizable (see "Optional interface functions" table). Factory setting: Analog output 0-10 V, max. 5 mA, function: Fan modulation level. Characteristic curve parameterizable (see output characteristic curve P3-OUT), SELV.
CON2VoutVoltage output 3.3-24 VDC ±5%, Pmax=800 mW, voltage parameterizable. Factory setting: 10 VDC. Short-circuit-proof, supply for external devices, SELV. Alternatively: 15-50 VDC input for parameterization via MODBUS without line voltage.
CON2COMStatus relay, floating status contact, common connection, contact rating 250 VAC / 2 A (AC1) / min. 10 mA, reinforced insulation on supply side and on control interface side.
CON2NCStatus relay, floating status contact, break for failure.
LEDgreen: status = good, ready for operation; orange: status = warning; red: status = failure.
P1-INInput characteristic curve.
P3-OUTOutput characteristic curve.

4.6 Configuration Options

For further information and additional functions see EC Control Software, Fan-Set-App, or MODBUS Parameter Specification V6.3.

ParameterINPUTOUTPUTMODBUSIO ModeElectrical SpecificationConfiguration
CON2
D130 [0]signal: fan modulation level %(selected directly via IO mode)
D130 [1]signal: actual speed(selected directly via IO mode)
D130 [2]signal: system modulation level %
D130 [5]signal: remote control output 0-10V
D00C [1]pulse input for auto-addressing
D130 [4]pulse output for auto-addressing
D147 [...]switch: parameter set: #1 / #2
D101 [...]switch: control function: heating (pos.) / cooling (neg.)
D104 [...]switch: direction of rotation: cw / ccw
D148 [...]switch: set value source
D16C [...]switch: fan enable / disable
D16A [...]configurable IO functions: normal / inverse
source: set value
source: sensor value
IO1D158 [0]Din1 (active high): digital inputactive: applied voltage 3,5-50VDC, SELV; not active: pin open or applied voltage < 1,5VDC
D158 [2]Ain1 0-10V/PWM: analog inputRi = 100K, characteristic curve parameterizable, fPWM = 1k..10KHz, SELV
D158 [5]Tacho out (open collector output)Umax = 50VDC, Imax = 20mA, SELV
D158 [6]Diagnostics out (open collector output)Umax = 50VDC, Imax = 20mA, SELV
IO2D159 [0]Din2 (active high): digital inputactive: applied voltage 3,5-50VDC, SELV; not active: pin open or applied voltage < 1,5VDC
D159 [2]Ain2 0-10V/PWM: analog inputRi = 100K, characteristic curve parameterizable, fPWM = 1k..10KHz, SELV
D159 [3]Ain2 4-20mA: analog inputRi = 125R, characteristic curve parameterizable, SELV
IO3D15A [0]Din3 (active high): digital inputactive: applied voltage 3,5-50VDC, SELV; not active: pin open or applied voltage < 1,5VDC
D15A [1]Din3 (active low): digital inputactive: applied voltage < 1,5VDC, SELV; not active: pin open or applied voltage 3,5-50VDC
D15A [7]PWMin3: digital input, idle level highPWM = 40Hz-10kHz, characteristics parameterizable; active: pin open or applied voltage 3,5-50VDC; not active: applied voltage < 1,5VDC, SELV
D15A [8]PWMin3: digital input, idle level low40Hz-10kHz, characteristics parameterizable; active: applied voltage 3,5-50VDC; not active: pin open or applied voltage < 1,5VDC, SELV
D15A [4]Aout3 0-10V: analog outputfunction parameterizable, max. 5mA, max output frequency 300Hz, SELV
D15A [5]Tacho out (pulses), analog output0-10V max. 5mA, max output frequency 300Hz, SELV
D15A [6]Diagnostics out (pulses)0-10V max. 5mA, max output frequency 300Hz, SELV
RSARS485 bus connection, MODBUS RTU, specification V6.3, SELV
RSB
Voutvoltage outputvoltage parameterizable 3,3...24VDC ±5%, Pmax=800mW, short-circuit-proof, supply for external devices, SELV
alternatively: Input auxillary power supply for 15...50VDCparameterization via RS485/MODBUS RTU without line voltage

4.7 Equivalent Circuit Diagrams

Schematic diagrams illustrating the electrical behavior of various input and output interfaces, including digital inputs (Din1, Din2, Din3), analog inputs (Ain1, Ain2), analog outputs (Aout), tachometer outputs, and RS485 connections.

4.8 Checking Connections

  • Ensure isolation from supply (all phases).
  • Make sure a restart is impossible.
  • Check the cables for proper fit.
  • Screw the terminal box cover back on again. Terminal box tightening torque, see Chapter 3.1 Product drawing.
  • Route the cables in the terminal box so that the terminal box cover closes without resistance.
  • Use all screw plugs. Insert the screws by hand to avoid damage to the threads.
  • Make sure the terminal box is completely closed and sealed and that all screws and cable glands have been properly tightened.

4.9 Switching on the Device

The device may only be switched on if it has been installed properly and in accordance with its intended use, including the required safety mechanisms and professional electrical hookup. This also applies for devices which have already been equipped with plugs and terminals or similar connectors by the customer.

WARNING: Hot motor housing. Risk of fire.

  • Ensure that no combustible or flammable materials are located close to the fan.
  • Before switching on, check the device for visible external damage and make sure the protective devices are functional.
  • Check the fan's air flow paths for foreign matter and remove any foreign matter found.
  • Apply the nominal supply voltage.
  • Start the device by changing the input signal.

NOTE: Damage to the device from vibration. Bearing damage, shorter service life.

  • Low-vibration operation of the fan must be ensured over the entire speed control range.
  • Severe vibration can arise for instance from inexpert handling, transportation damage and resultant imbalance or be caused by component or structural resonance.
  • Speed ranges with excessively high vibration levels and possibly resonant frequencies must be determined in the course of fan commissioning.
  • Either run through the resonant range as quickly as possible with speed control or find another remedy.
  • Operation with excessively high vibration levels can lead to premature failure.
  • The maximum permissible vibration severity must not exceed 3.5 mm/s and should be checked at intervals of 6 months. It is to be determined at the motor mount at the motor support plate at least in axial direction and transversely to this. Measurement of the vibration in all three axes is recommended and should be performed over the entire speed range in order to obtain a complete picture of the vibrations occurring in the application, see Chapter 6. Maintenance, malfunctions, possible causes and remedies.

4.10 Switching off the Device

Switching off the device during operation:

  • Switch off the device via the control input.
  • Do not switch the motor (e.g. in cyclic operation) on and off via power supply.

Switching off the device for maintenance:

  • Switch off the device via the control input.
  • Do not switch the motor (e.g. in cyclic operation) on and off via power supply.
  • Disconnect the device from the power supply.
  • When disconnecting, be sure to disconnect the ground connection last.

5. Integrated Protective Features

The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table.

FaultSafety feature description/function
Rotor position detection errorAn automatic restart follows. After the blockage is removed, the motor restarts automatically.
Blocked rotor
Line undervoltage (line voltage outside of permitted nominal voltage range)If the line voltage returns to permitted values, the motor restarts automatically.
Phase failureA phase of the supply voltage fails for at least 5 s. When all phases are correctly supplied again, the motor automatically restarts after 10-40 s.

6. Maintenance, Malfunctions, Possible Causes and Remedies

Do not perform any repairs on your device. Send the device to ebm-papst for repair or replacement.

WARNING: Live terminals and connections even with device switched off. Electric shock.

  • Wait five minutes after disconnecting the voltage at all poles before opening the device.

CAUTION: If control voltage or a stored speed set value is applied, the motor will restart automatically, e.g. after a power failure. Risk of injury.

  • Keep out of the device's danger zone.
  • When working on the device, switch off the line voltage and ensure that it cannot be switched back on.
  • Wait until the device comes to a stop.
  • After working on the device, remove any tools or other objects from the device.

NOTE: If the device is not operated for a lengthy period in installed condition in a dry environment, it is to be started up and operated at full speed for one hour at least every four months. If the device is not operated for a lengthy period in installed condition in a damp environment (e.g. outdoors), it is to be started up and operated at full speed for at least three hours once a month to move the bearings and allow any condensate that may have ingressed to evaporate.

Malfunctions and Remedies

Malfunction/faultPossible causePossible remedy
Impeller not running smoothlyImbalance in rotating partsClean the device; replace it if imbalance persists after cleaning. Make sure no weight clips are removed during cleaning.
Motor not turningMechanical blockageSwitch off, isolate from supply and remove mechanical blockage.
Line voltage faultyCheck line voltage, restore power supply. Attention! The error message resets automatically. Device restarts automatically without warning.
Faulty connectionIsolate from supply, correct connection; see connection diagram.
Broken motor windingReplace device.
Inadequate coolingImprove cooling. Allow the device to cool down.
ConditionPossible causePossible remedy
Ambient temperature too highReduce the ambient temperature. Allow the device to cool down.
Impermissible operating point (e.g. back pressure too high)Correct the operating point. Allow the device to cool down.

In the event of further malfunctions, contact ebm-papst.

6.1 Warning/Status Codes

The LED on the electronics housing shows the motor status with various colors and flash codes. The flash codes have a frequency of 2 Hz. Each flash code is followed by a pause lasting 3 seconds. The following colors are used: Green: no warning or fault. Orange: There is a warning. No user intervention is required for warnings. Red: There is at least one error. See the following table. If there are multiple simultaneous errors, their associated flash codes are displayed in succession. If there are simultaneous warnings and errors, only the errors are displayed.

6.1.1 Warning Codes

Number of pulsesMotor status - LED orangeMessage at status relay
1Current limitation in action
2Line impedance too high (DC-link voltage unstable)
3Power limiter in action
4Output stage temperature high
5Motor temperature high
6Temperature inside electronics high
7DC-link voltage low
8Braking mode: set in case of external drive in opposite direction at high speed for lengthy periodYes
9Calibration of rotor position sensor in progressYes
10Actual speed is lower than run monitoring speed limitYes
11Open circuit at analog input or PWM input for the set valueYes
13DC-link voltage high
15Line voltage high
16Shake-loose function activated

6.1.2 Status Codes

Number of pulsesMotor status - LED redPossible causePossible remedy
1Phase failure or line undervoltageMissing phase, Poor power supply qualityCheck line voltage.
3Output stage overheatingElectronics housing contaminatedProvide better cooling. Manual reset required.
4Communication error between master controller and slave controllerExternal supply applied via Vout for setting parameters. Internal errorSwitch off line voltage - wait - switch back on.
6Motor overheatingAmbient temperature too high, Impermissible operating point (e.g. back pressure too high)Reduce ambient temperature. Allow the device to cool down. Correct the operating point. Allow the device to cool down.
7Hall sensor errorInternal errorSwitch off line voltage - wait - switch back on.
8Motor blockedMechanical blockageSwitch off, isolate from supply - check freedom of movement of rotor.
9Speed limit exceeded
11Rotor position sensor calibration errorRotor position sensor calibration necessary. Notify ebm-papst.
13DC-link undervoltageLine voltage not OKCheck the line voltage applied.

6.2 Vibration Testing

Checking of fan for mechanical vibration based on ISO 14694. Recommendation: Every 6 months. Max. vibration severity is 3.5 mm/s, measured at the motor fastening diameter on the motor support plate in the direction of the motor axis of rotation and perpendicular to this.

Illustration showing the placement of sensors for vibration measurement on the fan motor. The arrangement of the sensors depends on the device concerned and the installation situation.

6.3 Cleaning

To ensure a long service life, check the fans regularly for proper operation and soiling. The frequency of checking is to be adapted accordingly depending on the degree of soiling.

DANGER: Risk of injury from rotating fan.

  • Only clean when not in motion. Do not disconnect the fan from the power supply, just switch it off via the control input. This will prevent start-up of the fan.

Dirt deposits on the motor housing can cause overheating of the motor. Soiling of the impeller can cause vibration that will shorten the service life of the fan. Severe vibration can destroy the fan.

  • In such cases, switch off the fan immediately and clean it.
  • The preferred method of cleaning is dry cleaning, e.g. using compressed air.
  • Do not use aggressive cleaning agents!

NOTE: Damage to the device during cleaning. Malfunction possible.

  • Do not clean the device using a high-pressure cleaner. Do not use acid, alkali or solvent-based cleaning agents.
  • Do not use any pointed or sharp-edged objects for cleaning.
  • Completely remove any cleaning agents used.
  • If severe corrosion is visible on load-bearing or rotating parts, switch off the device immediately and replace it.
  • Repair of load-bearing or rotating parts is not permitted!
  • Operate the fan for 2 hours at maximum speed so that any water that has ingressed can evaporate.
  • If cleaning does not eliminate vibrations, the fan may need to be rebalanced. To have it rebalanced, contact ebm-papst.
  • The fan is equipped with maintenance-free ball bearings. The lifetime lubrication of the ball bearings is designed for a service life of 40,000 hours.
  • If bearing replacement is necessary after that period, contact ebm-papst.
  • Adapt the maintenance intervals to the actual level of dust exposure.

6.4 Safety Inspection

NOTE: High-voltage test. The integrated EMC filter has Y capacitors. The tripping current is exceeded when AC testing voltage is applied.

  • Test the device with DC voltage when you perform the legally required high-voltage test. The voltage to be used corresponds to the peak value of the AC voltage required by the standard.
What to checkHow to checkHow oftenWhat action?
Contact protection cover for intactness or damageVisual inspectionAt least every 6 monthsRepair or replacement of device
Device for damage to blades and housingVisual inspectionAt least every 6 monthsReplacement of device
Fastening the cablesVisual inspectionAt least every 6 monthsFasten
Insulation of cables for damageVisual inspectionAt least every 6 monthsReplace cables
Impeller for wear/deposits/ corrosion and damageVisual inspectionAt least every 6 monthsClean impeller or replace device
Tightness of cable glandVisual inspectionAt least every 6 monthsRetighten, replace if damaged
Condensation drainage holes for clogging, where necessaryVisual inspectionAt least every 6 monthsOpen holes
Abnormal bearing noiseAcousticAt least every 6 monthsReplace device
Vibration testVibration tester, start-up or deceleration measurementRecommended every 6 monthsClean impeller or replace device

6.5 Disposal

For ebm-papst, environmental protection and resource preservation are top priority corporate goals. ebm-papst operates an environmental management system which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards. Right from the development stage, ecological design, technical safety and health protection are fixed criteria. The following section contains recommendations for ecological disposal of the product and its components.

6.5.1 Country-specific Legal Requirements

NOTE: Country-specific legal requirements. Always observe the applicable country-specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle. The corresponding disposal standards are also to be heeded.

6.5.2 Disassembly

Disassembly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge. The product is to be disassembled into suitable components for disposal employing standard procedures for motors.

WARNING: Heavy parts of the product may drop off. Some of the product components are heavy. These components could drop off during disassembly. This can result in fatal or serious injury and material damage.

  • Secure components before unfastening to stop them falling.

6.5.3 Component Disposal

The products are mostly made of steel, copper, aluminum and plastic. Metallic materials are generally considered to be fully recyclable. Separate the components for recycling into the following categories:

  • Steel and iron
  • Aluminum
  • Non-ferrous metal, e.g. motor windings
  • Plastics, particularly with brominated flame retardants, in accordance with marking
  • Insulating materials
  • Cables and wires
  • Electronic scrap, e.g. circuit boards

Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm-papst Mulfingen GmbH & Co. KG.

  • Ferrite magnets can be disposed of in the same way as normal iron and steel.

Electrical insulating materials on the product, in cables and wires are made of similar materials and are therefore to be treated in the same manner. The materials concerned are as follows:

  • Miscellaneous insulators used in the terminal box
  • Power cables
  • Cables for internal wiring
  • Electrolytic capacitors

Dispose of electronic components employing the proper procedures for electronic scrap.

  • Please contact ebm-papst for any other questions on disposal.
Models: R3G500-RA28-03 Axial Fan, R3G500-RA28-03, Axial Fan, Fan

File Info : application/pdf, 17 Pages, 1.69MB

PDF preview unavailable. Download the PDF instead.

R3G500-RA28-03 ?v=1737342755

References

PDFium PDFium

Related Documents

Preview ebm-papst K3G560-PB31-03 Operating Instructions
Comprehensive operating instructions for the ebm-papst K3G560-PB31-03 axial fan, covering safety regulations, technical data, connection, startup, maintenance, and troubleshooting.
Preview ebm-papst A2D250-AD26-05 Axial Fan Operating Instructions
Comprehensive operating instructions for the ebm-papst A2D250-AD26-05 axial fan, covering safety regulations, intended use, technical data, connection, startup, maintenance, and disposal.
Preview ebm-papst R2E225-RA92-20 Operating Instructions
Operating instructions for the ebm-papst R2E225-RA92-20 fan, detailing safety regulations, intended use, technical data, connection procedures, and maintenance guidelines.
Preview ebm-papst A2E200-AF02-01 Operating Instructions
Comprehensive operating instructions for the ebm-papst A2E200-AF02-01 fan, covering safety regulations, intended use, technical data, connection, startup, maintenance, and troubleshooting.
Preview ebm-papst R2E175-AC79-22 Operating Instructions and Technical Manual
Comprehensive operating instructions and technical manual for the ebm-papst R2E175-AC79-22 AC centrifugal fan. Covers safety, installation, connection, operation, maintenance, and disposal.
Preview ebm-papst Centrifugal Fan D2E097-BE01-65 Operating Instructions
Comprehensive operating instructions for the ebm-papst D2E097-BE01-65 centrifugal fan, covering safety regulations, intended use, technical data, connection, startup, maintenance, and disposal.
Preview ebm-papst W2S130-AB03-15 Operating Instructions
Comprehensive operating instructions for the ebm-papst W2S130-AB03-15 fan, covering safety regulations, proper use, technical data, connection, startup, maintenance, and troubleshooting.
Preview ebm-papst AxiACi120-00206 Operating Manual
Comprehensive operating manual for the ebm-papst AxiACi120-00206 fan, detailing safety regulations, intended use, technical specifications, connection and commissioning procedures, troubleshooting, and compliance information.