Installation Guide for VERIS models including: H608 Split Core Current Switch, H608, Split Core Current Switch, Core Current Switch, Current Switch

H608 Installation

Current Switch Adj 0.5-175A

H608 - Veris Industries

Mar 17, 2023 — Z201757-0J. Page 1 of 4. ©2019 Veris Industries USA 800.354.8556 or 1.503.598.4564 / support@veris.com. 0619. Alta Labs, Enercept, Enspector, Hawkeye, ...

Installation Guide Current Monitoring Product Overview Split-Core Current Switch, Adjustable Trip Point Specifications


File Info : application/pdf, 4 Pages, 900.10KB

PDF preview unavailable. Download the PDF instead.

h608 i0k2 installation guide
Installation Guide

Current Monitoring

TM

TM
H608

Split-Core Current Switch, Adjustable Trip Point

Product Overview

DANGER

The H608 is a current-sensitive switching device that monitors current (amperage) in the conductor passing through it. A change in amperage in the monitored conductor that crosses the switch (setpoint) threshold plus the hysteresis value causes the resistance of the FET status output to change state, similar to the action of a mechanical switch. In this model, the setpoint is adjustable through the action of a 20-turn potentiometer (see the Calibration section). The status output is suitable for connection to building controllers or other appropriate data acquisition equipment operating at up to 30 volts. The H608 requires no external power supply to generate its output.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
· Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. · This equipment must only be installed and serviced by qualified electrical personnel. · Read, understand and follow the instructions before installing this product. · Turn off all power supplying equipment before working on or inside the equipment. · Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION · Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

NOTICE
· This product is not intended for life or safety applications. · Do not install this product in hazardous or classified locations. · The installer is responsible for conformance to all applicable codes. · Mount this product inside a suitable fire and electrical enclosure.

Specifications
Sensor Power Induced from the monitored conductor Amperage Range 0.5 to 175 A continuous Status Output Ratings N.O. 1.0 A @ 30 Vac/dc, not polarity sensitive
Insulation Class 600 Vac RMS (UL); 300 Vac (CE) Setpoint Adjustable, 0.5 A or less
Frequency Range 50/60 Hz Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10-90% RH non-condensing Hysteresis 10% typical
Off State Resistance Open switch represents >1 M On State Resistance Closed switch represents < 200 m Terminal Block Max. Wire Size 24 to 14 AWG (0.2 to 2.1 mm2) Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m) Mounting Location Not suitable for wet locations. For indoor use only.

COMPLIANCE INFORMATION

Agency Approvals UL508 open device listing, CE: EN61010-1 Installation Category Cat. III, pollution degree 2

For applications requiring double or reinforced insulation, please contact the factory. The product design provides basic insulation only. Do not use the LED indicators as evidence of applied voltage.

Z201757-0J

Page 1 of 4

©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies' trademarks are hereby acknowledged to belong to their respective owners.

0619

H608 Installation Guide
Dimensions
Installation

TM

2.1" (54 mm)

Removable Mounting Bracket

0.6" (16 mm)

1.2" 0.7" (31 mm) (18 mm)

0.5" (13 mm)

2.5" (64 mm)

0.4" x 0.2" (10 mm x 5 mm)
Slot (2x)

2.1" (54 mm)
2.9" (74 mm)
3.5" (89 mm)

1.0" (26 mm)

Disconnect and lock out power to the enclosure containing the conductor to be

monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow the monitored conductor to pass through the center window when it is installed and that will keep the product at least ½" (13 mm) from any uninsulated conductors. Determine cable

CONTACTOR

Insulated Conductor ONLY DDC CONTROLLER

routing for the controller connection, allowing the wiring to reach

the mounting location.
DI
2. Drill holes to mount the bracket to the chosen surface using the

included screws.

3. Wire the output connections from the sensor to the controller (solidstate contact).

4. Snap the sensor over the conductor and clip the assembly to the

Fan

mounting bracket. Important: If there is a paper inhibitor

sheet between the contacts, remove before use.

5. Secure the enclosure and reconnect power. Motor
6. Calibrate the sensor with the load running normally.

Z201757-0J

Page 2 of 4

©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies' trademarks are hereby acknowledged to belong to their respective owners.

0619

H608 Installation Guide
Notes

TM
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) current transformer (CT) as shown. This technique can be combined with wrapping (see below) to add range for a low current load on a high current source.
240 A >175 A (sensor max.)

300A:5A H68xx-5A CT
4 A
For load currents less than sensor minimum rating:

DANGER: 5A CTs can present hazardous voltages. Install CTs in accordance with manufacturer's instructions. Terminate the CT secondary before applying current.

Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases the current measured by the transducer. Program the controller to account for the extra turns (e.g., if four turns pass through the sensor (as shown) divide the normal reading by 4).

< 0.5 A (Sensor Min.)

0.35A

4x

CAUTION
RISK OF EQUIPMENT DAMAGE · Derate the product's maximum current for the number of turns
through the sensing window using the following formula. Rated Max. Amps ÷ Number of Turns = Max. monitored Amps e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor · Failure to follow these instructions can result in overheating and permanent equipment damage.

Z201757-0J

Page 3 of 4

©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies' trademarks are hereby acknowledged to belong to their respective owners.

0619

H608 Installation Guide TM

Calibration

Before beginning calibration, establish normal load conditions. Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)

Status
1. Turn setpoint screw clockwise CLOSED
until Status Open LED turns
on. Status OPEN

Setpoint

Status
2. Slowly turn the screw counter CLOSED
clockwise until the Status
Closed LED turns on. Status OPEN

Setpoint

3. Turn the screw an additional ¼ turn counter clockwise for operational margin.

¼
Setpoint

B. To monitor over-current (mechanical problems, seized impeller)

Status

1. Turn setpoint screw counter

CLOSED

clockwise until Status Closed

LED turns on. Status OPEN

Setpoint

Status
2. Slowly turn the setpoint screw CLOSED
clockwise until the Status
Open LED just turns on. Status OPEN

Setpoint

3. Turn the setpoint screw an additional ¼ turn clockwise for operational margin.

¼
Setpoint

Troubleshooting

Problem No Reading at Controller
Setpoint screw has no stops Both LEDs are lit

Solution
· Check sensor calibration (see above) · Check for control voltage at sensor (<30V, <1A) · Check for amperage in monitored conductor (> 0.5A) · Assure that sensor core mating surfaces are clean and that the core clamp is completely closed
The setpoint screw has a slip-clutch at both ends of its travel to avoid damage. Twenty turns CCW will reset the sensor to be most sensitive. Repeat calibration above.
Setpoint screw is too far clockwise. See solution above.

Z201757-0J

Page 4 of 4

©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris `V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies' trademarks are hereby acknowledged to belong to their respective owners.

0619

