Installation Instructions
Model PIM-1 Peripheral Interface Module

INTRODUCTION
The Model PIM-1 module from Siemens Industry, Inc., is an interface for an MXL/MXLV/MXL-IQ System to remote peripheral devices such as printers, VDTs, and CRTs. It connects an RS232C device or CRT to an MXL/MXLV/MXL-IQ System without the peripheral devices protective ground causing a ground fault. The interface operates at up to 9600 baud without losing any characters.
Mounting the PIM-1 in the MME-3 in the upper right-hand corner provides an isolated RS-232C port for an RS-232C printer when used with an MXL/MXLV System. The PIM-1 bidirectional interface supports a supervised or nonsupervised printer, a CRT, or a VDT. Do not use a nonsupervised printer for an NFPA 72 Proprietary or UL 1076 system. For NFPA 72 Local, any EDP UL listed equipment may be used.
The PIM-1 has one factory installed jumper. See Figure 1 for the location of this jumper. Set it according to the instructions below before installing the PIM-1 on the MME-3.
JUMPER G1
This jumper disconnects the output of the remote printer from PIM-1.
For supervised printers: Leave jumper G1 in place. For non-supervised printers: Cut G1 to stop any input to the PIM-1.

TB1, TERMINAL 1 (Refer to the table on Figure 1)
If the printer output is not regulated by using a printer busy signal, the PIM-1 may overwrite the printer buffer. If the busy signal is not used, the printer data is transmitted without any delay. However, if the printer cannot keep up with the data being sent, material may be lost.
To use the busy signal, select the appropriate PIM-1 printer busy signal from the terminals described in the table in Figure 1.
INSTALLATION
1. Install the PIM-1 in the upper right-hand corner of the MME-3 backbox. Position the PIM-1 so that TB1 is on the left side of the board.
2. Mount the PIM-1 module with the hardware provided.
3. Make the necessary cable connections for the PIM-1 according to the System configurations described below.
For an MXL System without the Voice option: (See Figure 2)
a. With an MKB-2: Use the cable (P/N 555-192242) supplied with the PIM-1 to connect P2 on the PIM-1 to P8 on the MMB-1/-2.
b. Use the cable supplied with the MKB-2 to connect P1 of the PIM-1 to P1 of the ANN-1.
c. With an MKB-1: Use the cable (P/N 555-191323) supplied with the PIM-1 to connect the PIM-1 to the MMB-1/-2 on the MKB-1.

Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-091462-14

Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada

firealarmresources.com

Leave jumper G1 in place if the System printer is supervised. Cut jumper G1 if the System has an unsupervised printer.
TB1 CONNECTIONS CAUTION: This table refers to whether or not the wiring connections are supervised.
The table does not refer to the type of printer used in the System.

NOTES: 1. Terminals TB1-8 and 9 are connected together on the PIM-1. 2. The busy signal from the printer prevents the loss of characters if the printer falls behind. Refer to the
printer manual for the proper pin [usually 11 (TB1-3) or 20 (TB1-9)].
Figure 1 PIM-1 PC Board Connections

For an MXLV System with the Voice option: (See Figure 3)
a. Use the cable (P/N 555-192242) supplied with the PIM to connect P2 on the PIM with P8 on the MMB-1/-2.
b. Use the cable supplied with the MKB-2 to connect P1 on the PIM-1 to P5 on the ACM-1. (P4 on the ACM-1 then connects to P1 on the ANN-1 in this configuration.)

For an MXL-IQ System: (See Figure 4) a. Install the PIM-1 on the back of the MKB-4 panel as shown in Figure 4. Position the PIM-1 so that TB1 is on the left side of the board. b. Mount the PIM-1 module on the raised studs with the hardware provided. c. Using the cable supplied with the PIM-1, connect PIM-1, P1 to ANN-1, P1. d. Using the cable supplied with the MKB-4, connect PIM-1, P2 to SMB-1/-2, P8.

2
firealarmresources.com

Installing the PIM-1 in other Enclosures: The PIM-1 can also be installed in the RCC-1/-1F box or the MSE-2 enclosure. For information on those configurations, refer to the RCC-1/-1F Installation Instructions (P/N 315-095364) or to the MSE-2 Installation Instructions (P/N 315092403), as appropriate.

ELECTRICAL RATINGS
Active 5VDC Module Current Active 24VDC Module Current Standby 24VDC Module Current

50mA 0mA 15mA

COMMUNICATION PARAMETERS
Set the communication parameters for the connected devices so that they agree with those specified by CSG-M. See the CSG-M Manual (P/N 315-090381) for information on setting the parameters. UL requires that the printer be in the same room as the MXL/MXLV Control Panel.

Electrical Ratings for the RS-232C Interface

VMAX: ±12 VDC

IMAX : ±5mA

Maximum Cable Length: 25 feet (2 ohms max per circuit)

Refer to Figure 1 to complete the necessary wiring.

TI82OKSR (RC119/RC319) Supervised Printer Setup The TI82OKSR (RC119/RC319) must have the following codes selected:
14 25-28 Baud rate to agree with CSG-M 38 81

MME-3

To P8 on the MMB-1/-2. Cable P/N 555-192242 (supplied with PIM-1)

Cable supplied with the MKB-2

Back of MKB-2

Figure 2 MXL System Without Voice
3
firealarmresources.com

MME-3

To P8 on the MMB-1/-2. Cable P/N 555-192242 (supplied with PIM-1)

Cable supplied with the MKB-2

Back of MKB-2

Cable supplied with ACM-1

Figure 3 MXLV System With Voice Option

P/N 315-091462-14

Figure 4 MXL-IQ System
firealarmresources.com

