Manual SP series
SP Series User's Manual
SP-700/1000/1500/2000/3000/4000 PURE SINE WAVE INVERTER

Table of Content

1. SAFETY INSTRUCTIONS

1

1-1. General Safety Precautions

1

1-2. Other Safety Notes

2

2. FUNCTIONAL CHARACTERISTICS INTRODUCTION 3

2-1. System

3

2-2. Block Diagram

3

2-3. Electrical Specification

4

2-3-1. SP-700 Specification

4

2-3-2. SP-1000 Specification

6

2-3-3. SP-1500 Specification

8

2-3-4. SP-2000 Specification

10

2-3-5. SP-3000 Specification

12

2-3-6. SP-4000 Specification

14

2-3-7. Voltage & temperature performance

16

2-4. Mechanical Drawings

17

3. INSTALLATION AND MAINTENANCE

18

3-1. AC Output Side (Front Panel) Introduction

18

3-1-1. Main Switch

19

3-1-2. LED Indicator

19

3-1-3. Function Switch Introduction

20

3-1-4. TRC Port (for optional kits TR-40, RJ-45)

21

3-1-5. AC output Interface

22

3-2. DC Input Side (Rear Panel) Introduction

24

3-2-1. Remote Port (RJ-11)

25

3-2-2. Remote Control Green Terminal

25

3-2-3. General instruction before DC Input

26

3-2-4. Chassis Ground

27

3-3. Maintenance

27

4. OPERATION

28

4-1. Connection the DC cable

28

4-2. Connecting the input power

29

4-3. Connecting the loads

29

4-4. Switch ON Inverter

29

4-5. Protection Mechanism

30

5. RS-232 COMMUNICATION AND OPERATION

30

5-1. RS-232 Port

30

5-2. RS-232 Port Operating

31

5-3. Example of RS-232 Port Operating

31

5-3-1. RS-232 command format

31

5-3-2. Command format

31

6. INFORMATION

36

6-1. Warning

36

6-2. Warranty

36

1. Safety Instructions
1-1. General Safety Precautions
Warning! Before using the Inverter, read the safety instructions.
z Do not expose the inverter to rain, snow, spray or dust. To reduce the risk of fire hazard, do not cover or obstruct the ventilation openings and do not install the inverter in a zero-clearance compartment.
z To avoid the risk of fire and electric shock, make sure that the existing wiring is in good electrical condition, and the wire size is not undersized.
z This equipment contains components which can produce arcs or sparks. To prevent fire or explosion do not install in compartment containing batteries or flammable materials or in location which require ignition protected equipment. This includes any space containing gasoline-powered machinery, fuel tanks, or joints, fittings, or other connection between components of the fuel system.
z Depending on the user scenario, the AC output of the inverter may require user installed breaker or fuse. In AC output hardwire application, AC socket will not been provided. The inverter incorporates standard AC short circuit protection.
z An over current protection at the time of installation shall be provided by others for the AC output circuit.
z Additional breakers suitable for 20 A branch circuit protection shall be provided for the GFCI receptacles.
z The following precautions should be taken when working on the inverter: Step 1 Remove watches, rings, or other metal objects Step 2 Use tools with insulated handles Step 3 Wear rubber gloves and boots
1

1-2. Other Safety Notes
z Upon receipt, examine the carton box for damage. If you have found any damage on the carton box please notify the company you purchased this unit from.
z Do not operate near water or in excessive humidity. z Do not open or disassemble the inverter, and warranty may be
voided. z The DC side connections should be firm and tight. z Grounding: Reliable grounding should be maintained. z Do not drop a metal tool on the battery. The resulting spark or
short-circuit on the battery or on the other electrical part may cause an explosion. z Install the inverter in a well-ventilated area. Do not block the front air vents, or the rear air exhausts of the unit. z Wiring: Adequate input power must be supplied to the inverter for proper use; correct wiring sizes must be ensured. z Mount the inverter such that the fan axis is horizontal. z Do not operate the inverter close to combustible gas or open fire. z Do not operate appliances that may feed power back into the inverter. z Temperature: The inverter should be operated in an ambient temperature range of -20 to 40 otherwise the output efficiency may be affected. Air flow to the inverter must not be blocked.
2

2. Functional Characteristics Introduction
2-1. System
The unit is a highly reliable DC-AC inverter system, designed with advanced power electronic and microprocessor technology offering the following features: z Pure sine wave output waveform O/P voltage 1xx THD < 5 %,
2xx THD < 3 % z Optional bypass relay (TR-40) function z Intelligent software for power management z Loading and temperature controlled cooling fan z CR-8/CR-16 remote management and control z RS-232 communication z Dry contact terminal z Advanced Protection Features
¾ Input over/under voltage protection ¾ Internal over temperature protection ¾ Input reverse polarity protection (Fuse) ¾ Output overload protection ¾ Output short circuit protection
2-2. Block Diagram
3

2-3. Electrical Specification

2-3-1. SP-700 Specification

Electrical
Input Characteristics
Output Characteristics
Signal and Control Protection

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode
Continuous Output Power
Maximum output Power (1Min)
Surge Power (1Sec) Frequency
Output Voltage
Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Environment

Operating Temp.
Storage Temp. Storage Temp. &
Humidity

Safety Standards

Safety & EMC

EMC standards

E-mark

Dimension(WxHxD)

Weight

Cooling

AC Transfer Function Accessories

SP-700-112
12VDC
16.5 ± 0.3VDC

Model No. SP-700-124
24VDC
33 ± 0.5VDC

SP-700-148
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5VDC 1.5A @12VDC
<0.1A @12VDC

21 ± 0.5VDC
21~33VDC 0.8A @24VDC <0.06A @24VDC
700 VA (± 3%)

42 ± 1.0VDC
42~66VDC 0.5A @48VDC <0.05A @48VDC

> 700 VA~810 VA (100%~115%)

< 1230 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

100 / 110 / 115 / 120 VAC (± 5%)

(Dip Switch Selectable)

91%

93%

93%

1 Sec Shutdown

Pure Sine Wave (THD < 5%@ Normal Load)N

CR-8 / CR-16 (optional)
Red / Orange / Green LED By a relay
6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O -30 ~70
10 ~95% RH

Certified UL 458 (UL only for GFCI receptacles)

----

Certified FCC class B

----

200mm X 83mm X 330mm

2.6 KG

Temperature & Load Controlled cooling Fan

TR-40 (optional)

Note

Table 1. SP-700 for Output 100/110/115/120 VAC Specification.

M Voltage range Please refer to Figure 1

N Normal load Condition Vin =12.5V/25V/50V, Vo=100/110/115/120 VAC 80% Full load (PF=1.0)

O Operating temperature Please refer to Figure 2

4

Electrical
Input Characteristics
Output Characteristics

Specification Item
Voltage Input Over-Voltage
Protection M Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode
Continuous Output Power
Maximum output Power (1Min)
Surge Power (1Sec) Frequency
Output Voltage

Signal and Control Protection

Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Environment

Operating Temp. Storage Temp. Storage Temp. &
Humidity
Safety Standards

Safety & EMC

EMC standards

E-mark
Dimension(WxHxD) Weight Cooling
AC Transfer Function Accessories

SP-700-212
12VDC
16.5 ± 0.3VDC

Model No. SP-700-224
24VDC
33 ± 0.5VDC

SP-700-248
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5VDC 1.5A @12VDC
<0.1A @12VDC

21 ± 0.5VDC
21~33VDC 0.8A @24VDC <0.06A @24VDC
700 VA (± 3%)

42 ± 1.0VDC
42~66VDC 0.5A @48VDC <0.05A @48VDC

> 700 VA~810 VA (100%~115%)

< 1230 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

200 / 220 / 230 / 240 VAC (± 3%)

(Dip Switch Selectable)

91%

93%

94%

1 Sec Shutdown Pure Sine Wave (THD < 3%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O -30 ~70

10 ~95% RH

Certified EN 60950-1 Certified EN 55022 class B; EN 55024; EN 61000-3-2, -3-3
EN 61000-4-2, 3, 4, 5, 6, 8, 11 Certified CISPR 25; ISO 7637-2
200mm X 83mm X 330mm 2.6 KG
Temperature & Load Controlled cooling Fan TR-40 (optional)

Note

Table 2. SP-700 for Output 200/220/230/240 VAC Specification.

M Voltage range Please refer to Figure 1

N Normal load Condition Vin =12.5V/25V/50V, Vo=200/220/230/240 VAC 80% Full load (PF=1.0)

O Operating temperature Please refer to Figure 2

5

2-3-2. SP-1000 Specification

Electrical
Input Characteristics
Output Characteristics
Signal and Control Protection

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode Continuous Output
Power Maximum output
Power (1Min) Surge Power (1Sec)
Frequency
Output Voltage
Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Environment

Operating Temp.
Storage Temp. Storage Temp. &
Humidity

Safety Standards

Safety & EMC

EMC standards

E-mark

Dimension(WxHxD)

Weight

Cooling

AC Transfer Function Accessories

SP-1000-112
12VDC
16.5 ± 0.3VDC

Model No. SP-1000-124
24VDC
33 ± 0.5VDC

SP-1000-148
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5 VDC 1.5A @12VDC
<0.1A @12VDC

21 ± 0.5VDC
21~33 VDC 0.8A @24VDC <0.06A @24VDC
1000 VA (± 3%)

42 ± 1.0VDC
42~66 VDC 0.5A @48VDC <0.05A @48VDC

> 1000 VA~1150 VA (100%~115%)

< 1750 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

100 / 110 / 115 / 120 VAC (± 5%)

(Dip Switch Selectable)

92%

93%

93%

1 Sec Shutdown Pure Sine Wave (THD < 5%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O -30 ~70

10 ~95% RH

Certified UL 458 (UL only for GFCI receptacles)

----

Certified FCC class B

----

200mm X 83mm X 372mm

3.26 KG

Temperature & Load Controlled cooling Fan

TR-40 (optional)

Table 3. SP-1000 for Output 100/110/115/120 VAC Specification.
Note
M Voltage range Please refer to Figure 1 N Normal load Condition Vin =12.5V/25V/50V, Vo=100/110/115/120 VAC 80% Full load (PF=1.0) O Operating temperature Please refer to Figure 2

6

Electrical
Input Characteristics
Output Characteristics

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode
Continuous Output Power
Maximum output Power (1Min)
Surge Power (1Sec) Frequency
Output Voltage

Signal and Control Protection

Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Environment

Operating Temp. Storage Temp. Storage Temp. &
Humidity
Safety Standards

Safety & EMC

EMC standards

E-mark
Dimension(WxHxD) Weight Cooling
AC Transfer Function Accessories

SP-1000-212
12VDC
16.5 ± 0.3VDC

Model No. SP-1000-224
24VDC
33 ± 0.5VDC

SP-1000-248
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5 VDC 1.5A @12VDC
< 0.1A @12VDC

21 ± 0.5VDC
21~33 VDC 0.8A @24VDC <0.05A @24VDC
1000 VA (± 3%)

42 ± 1.0VDC
42~66 VDC 0.4A @48VDC <0.05A @48VDC

> 1000 VA~1150 VA (100%~115%)

< 1750 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

200 / 220 / 230 / 240 VAC (± 3%)

(Dip Switch Selectable)

92%

94%

94%

1 Sec Shutdown Pure Sine Wave (THD < 3%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O -30 ~70

10 ~95% RH

Certified EN 60950-1 Certified EN 55022 class B; EN 55024; EN 61000-3-2, -3-3
EN 61000-4-2, 3, 4, 5, 6, 8, 11 Certified CISPR 25; ISO 7637-2
200mm X 83mm X 372mm 3.26 KG
Temperature & Load Controlled cooling Fan TR-40 (optional)

Table 4. SP-1000 for Output 200/220/230/240 VAC Specification.
Note
M Voltage range Please refer to Figure 1 N Normal load Condition Vin =12.5V/25V/50V, Vo=200/220/230/240 VAC 80% Full load (PF=1.0) O Operating temperature Please refer to Figure 2

7

2-3-3. SP-1500 Specification

Electrical
Input Characteristics
Output Characteristics
Signal and Control Protection

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode Continuous Output
Power Maximum output
Power (1Min) Surge Power (1Sec)
Frequency
Output Voltage
Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Environment

Operating Temp.
Storage Temp. Storage Temp. &
Humidity

Safety Standards

Safety & EMC

EMC standards

E-mark

Dimension(WxHxD)

Weight

Cooling

AC Transfer Function Accessories

SP-1500-112
12VDC
16.5 ± 0.3VDC

Model No. SP-1500-124
24VDC
33 ± 0.5VDC

SP-1500-148
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5 VDC 1.8A @12VDC
<0.1A @12VDC

21 ± 0.5VDC
21~33 VDC 1.0A @24VDC <0.05A @24VDC
1500 VA (± 3%)

42 ± 1.0VDC
42~66 VDC 0.5A @48VDC <0.05A @48VDC

> 1500 VA~1730VA (100%~115%)

<2650 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

100 / 110 / 115 / 120 VAC (± 5%)

(Dip Switch Selectable)

91%

92%

93%

1 Sec Shutdown Pure Sine Wave (THD < 5%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O -30 ~70

10 ~95% RH

Certified UL 458 (UL only for GFCI receptacles)

----

Certified FCC class B

----

248mm X 83mm X 421mm

4.14 KG

Temperature & Load Controlled cooling Fan

TR-40 (optional)

Table 5. SP-1500 for Output 100/110/115/120 VAC Specification.
Note
M Voltage range Please refer to Figure 1 N Normal load Condition Vin =12.5V/25V/50V, Vo=100/110/115/120VAC 80% Full load (PF=1.0) O Operating temperature Please refer to Figure 2

8

Electrical
Input Characteristics
Output Characteristics

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode
Continuous Output Power
Maximum output Power (1Min)
Surge Power (1Sec) Frequency
Output Voltage

Signal and Control Protection

Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Environment

Operating Temp. Storage Temp. Storage Temp. &
Humidity
Safety Standards

Safety & EMC

EMC standards

E-mark
Dimension(WxHxD) Weight Cooling
AC Transfer Function Accessories

SP-1500-212
12VDC
16.5 ± 0.3VDC

Model No. SP-1500-224
24VDC
33 ± 0.5VDC

SP-1500-248
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5 VDC 1.8A @12VDC
<0.1A @12VDC

21 ± 0.5VDC
21~33 VDC 1.0A @24VDC <0.05A @24VDC
1500 VA (± 3%)

42 ± 1.0VDC
42~66 VDC 0.5A @48VDC <0.05A @48VDC

> 1500 VA~1730VA (100%~115%)

<2650 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

200 / 220 / 230 / 240 VAC (± 3%)

(Dip Switch Selectable)

93%

94%

94%

1 Sec Shutdown Pure Sine Wave (THD < 3%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O -30 ~70

10 ~95% RH

Certified EN 60950-1 Certified EN 55022 class B; EN 55024; EN 61000-3-2, -3-3
EN 61000-4-2, 3, 4, 5, 6, 8, 11 Certified CISPR 25; ISO 7637-2
248mm X 83mm X 421mm 4.14 KG
Temperature & Load Controlled cooling Fan TR-40 (optional)

Table 6. SP-1500 for Output 200/220/230/240 VAC Specification.
Note
M Voltage range Please refer to Figure 1 N Normal load Condition Vin =12.5V/25V/50V, Vo=200/220/230/240 VAC 80% Full load (PF=1.0) O Operating temperature Please refer to Figure 2

9

2-3-4. SP-2000 Specification

Electrical
Input Characteristics
Output Characteristics
Signal and Control Protection

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode
Continuous Output Power
Maximum output Power (1Min)
Surge Power (1Sec) Frequency
Output Voltage
Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Environment

Operating Temp.
Storage Temp. Storage Temp. &
Humidity

Safety Standards

Safety & EMC

EMC standards

E-mark

Dimension(WxHxD)

Weight

Cooling

AC Transfer Function Accessories

SP-2000-112
12VDC
16.5 ± 0.3VDC

Model No. SP-2000-124
24VDC
33 ± 0.5VDC

SP-2000-148
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5 VDC 1.8A @12VDC
<0.1A @12VDC

21 ± 0.5VDC
21~33 VDC 1.0A @24VDC <0.05A @24VDC
2000 VA (± 3%)

42 ± 1.0VDC
42~66 VDC 0.5A @48VDC <0.05A @48VDC

> 2000 VA~2300 VA (100%~115%)

< 3500 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

100 / 110 / 115 / 120 VAC (± 5%)

(Dip Switch Selectable)

92%

93%

94%

1 Sec Shutdown Pure Sine Wave (THD < 5%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O
-30 ~70

10 ~95% RH

Certified UL 458 (UL only for GFCI receptacles)

----

Certified FCC class A

----

248mm X 83mm X 443mm

5.24 KG

Temperature & Load Controlled cooling Fan

TR-40 (optional)

Table 7. SP-2000 for Output 100/110/115/120 VAC Specification.
Note
M Voltage range Please refer to Figure 1 N Normal load Condition Vin =12.5V/25V/50V, Vo=100/110/115/120 VAC 80% Full load (PF=1.0) O Operating temperature Please refer to Figure 2 P Warning This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.

10

Electrical
Input Characteristics
Output Characteristics
Signal and Control Protection

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode
Continuous Output Power
Maximum output Power (1Min)
Surge Power (1Sec) Frequency
Output Voltage
Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Environment

Operating Temp. Storage Temp. Storage Temp. &
Humidity
Safety Standards

Safety & EMC

EMC standards

E-mark
Dimension(WxHxD) Weight Cooling
AC Transfer Function Accessories

SP-2000-212
12VDC
16.5 ± 0.3VDC

Model No. SP-2000-224
24VDC
33 ± 0.5VDC

SP-2000-248
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5 VDC 1.8A @12VDC
<0.1A @12VDC

21 ± 0.5VDC
21~33 VDC 1.0A @24VDC <0.05A @24VDC
2000 VA (± 3%)

42 ± 1.0VDC
42~66 VDC 0.5A @48VDC <0.05A @48VDC

> 2000 VA~2300 VA (100%~115%)

< 3500 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

200 / 220 / 230 / 240 VAC (± 3%)

(Dip Switch Selectable)

94%

94%

95%

1 Sec Shutdown Pure Sine Wave (THD < 3%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O -30 ~70

10 ~95% RH

Certified EN 60950-1 Certified EN 55022 class A; EN 55024; EN 61000-3-2, -3-3
EN 61000-4-2, 3, 4, 5, 6, 8, 11 Certified CISPR 25; ISO 7637-2
248mm X 83mm X 443mm 5.24 KG
Temperature & Load Controlled cooling Fan TR-40 (optional)

Table 8. SP-2000 for Output 200/220/230/240 VAC Specification.
Note
M Voltage range Please refer to Figure 1 N Normal load Condition Vin =12.5V/25V/50V, Vo=200/220/230/240 VAC 80% Full load (PF=1.0) O Operating temperature Please refer to Figure 2 P Warning This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.

11

2-3-5. SP-3000 Specification

Electrical
Input Characteristics
Output Characteristics
Signal and Control Protection

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode
Continuous Output Power
Maximum output Power (1Min)
Surge Power (1Sec) Frequency
Output Voltage
Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Operating Temp.

Environment

Storage Temp. Storage Temp. &

Humidity

Safety Standards

Safety & EMC

EMC standards

E-mark

Dimension(WxHxD)

Weight

Cooling

AC Transfer Function Accessories

SP-3000-112
12VDC
16.5 ± 0.3VDC

Model No. SP-3000-124
24VDC
33 ± 0.5VDC

SP-3000-148
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5 VDC 3.8A @12VDC
<0.4A @12VDC

21 ± 0.5VDC
21~33 VDC 2.0A @24VDC <0.2A @24VDC
3000 VA (± 3%)

42 ± 1.0VDC
42~66 VDC 1.0A @48VDC <0.1A @48VDC

> 3000 VA~3450 VA (100%~115%)

< 6000 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

100 / 110 / 115 / 120 VAC (± 5%)

(Dip Switch Selectable)

90%

91%

92%

1 Sec Shutdown Pure Sine Wave (THD < 5%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O
-30 ~70

10 ~95% RH

Certified UL 458

----

Certified FCC class A

----

255mm X 158mm X 442mm

8.2 KG

Temperature & Load Controlled cooling Fan

TR-40 (optional)

Note

Table 9. SP-3000 for Output 100/110/115/120 VAC Specification.

M Voltage range Please refer to Figure 3

N Normal load Condition Vin =12.5V/25V/50V, Vo=100/110/115/120 VAC 80% Full load (PF=1.0)

O Operating temperature Please refer to Figure 4

P Warning This is a class A product. In a domestic environment this product may cause radio

interference in which case the user may be required to take adequate measures.

12

Electrical
Input Characteristics
Output Characteristics
Signal and Control Protection

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage
Protection Voltage Range No Load Current Power Saving Mode
Continuous Output Power
Maximum output Power (1Min)
Surge Power (1Sec) Frequency
Output Voltage
Efficiency max. Short-Circuit Protection
Output Waveform
Remote Controller Panel Unit
LED Indicator Dry Contact Terminal
Remote Control Terminal
Input Protection AC Output Protection
Others

Environment

Operating Temp. Storage Temp. Storage Temp. &
Humidity
Safety Standards

Safety & EMC

EMC standards

E-mark
Dimension(WxHxD) Weight Cooling
AC Transfer Function Accessories

SP-3000-212
12VDC
16.5 ± 0.3VDC

Model No. SP-3000-224
24VDC
33 ± 0.5VDC

SP-3000-248
48VDC
66 ± 1.0VDC

10.5 ± 0.3VDC
10.5~16.5 VDC 3.8A @12VDC
<0.4A @12VDC

21 ± 0.5VDC
21~33 VDC 2.0A @24VDC <0.2A @24VDC
3000 VA (± 3%)

42 ± 1.0VDC
42~66 VDC 1.0A @48VDC <0.1A @48VDC

> 3000 VA~3450 VA (100%~115%)

< 6000 VA

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

200 / 220 / 230 / 240 VAC (± 3%)

(Dip Switch Selectable)

90%

93%

94%

1 Sec Shutdown Pure Sine Wave (THD < 3%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse) Short-Circuit, Overload
Over / Under Temperature Protection (by Heat sink Temperature +80 /-20 )
-20 ~40 O -30 ~70

10 ~95% RH

Certified EN 60950-1 Certified EN 55022 class A; EN 55024; EN 61000-3-2, -3-3
EN 61000-4-2, 3, 4, 5, 6, 8, 11 Certified CISPR 25; ISO 7637-2
255mm X 158mm X 442mm 8.2 KG
Temperature & Load Controlled cooling Fan TR-40 (optional)

Table 10. SP-3000 for Output 200/220/230/240 VAC Specification.
Note
M Voltage range Please refer to Figure 3 N Normal load Condition Vin =12.5V/25V/50V, Vo=200/220/230/240 VAC 80% Full load (PF=1.0) O Operating temperature Please refer to Figure 4 P Warning This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.

13

2-3-6. SP-4000 Specification

Electrical
Input Characteristics
Output Characteristics
Signal and Control

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage Protection
Voltage Range No Load Current Power Saving Mode Continuous Output Power Maximum output Power (1Min) Surge Power (1Sec)
Frequency
Output Voltage
Efficiency max. Short-Circuit Protection
Output Waveform Remote Controller Panel Unit
LED Indicator Dry Contact Terminal Remote Control Terminal

Protection

Input Protection AC Output Protection
Others

Operating Temp.

Environment

Storage Temp.

Storage Temp. & Humidity

Safety Standards

Safety & EMC

EMC standards

E-mark

Dimension(WxHxD)

Weight

Cooling

AC Transfer Function Accessories

Model No.

SP-4000-124

SP-4000-148

24VDC

48VDC

33 ± 0.5VDC

66 ± 1.0VDC

21 ± 0.5VDC

42 ± 1.0VDC

21~33 VDC

42~66 VDC

2.0A @24VDC

1.0A @48VDC

<0.2A @24VDC

<0.1A @48VDC

4000 VA (± 3%)

> 4000 VA~4600 VA (100%~115%)

< 8000 VA 50 / 60 Hz ± 0.5% (Dip Switch Selectable)

100 / 110 / 115 / 120 VAC (± 5%) (Dip Switch Selectable)

91%

91%

1 Sec Shutdown Pure Sine Wave (THD < 5%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED

By a relay 6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse)

Short-Circuit, Overload

Over / Under Temperature Protection
(by Heat sink Temperature +80 /-20 ) -20 ~40 O

-30 ~70

10 ~95% RH

Certified UL 458

----

Certified FCC class A

----

255mm X 158mm X 462mm

10 KG

Temperature & Load Controlled cooling Fan

TR-40 (optional)

Table 11. SP-4000 for Output 100/110/115/120 VAC Specification.
Note
M Voltage range Please refer to Figure 3 N Normal load Condition Vin =12.5V/25V/50V, Vo=100/110/115/120 VAC 80% Full load
(PF=1.0) O Operating temperature Please refer to Figure 4
P Warning This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.

14

Electrical
Input Characteristics

Specification Item
Voltage Input Over-Voltage
ProtectionM Input Under-Voltage Protection
Voltage Range No Load Current Power Saving Mode Continuous Output Power Maximum output Power (1Min)
Surge Power (1Sec)

Model No.

SP-4000-224

SP-4000-248

24VDC

48VDC

33 ± 0.5VDC

66 ± 1.0VDC

21 ± 0.5VDC

42 ± 1.0VDC

21~33 VDC

42~66 VDC

2.0A @24VDC

1.0A @48VDC

<0.2A @24VDC

<0.1A @48VDC

4000 VA (± 3%)

> 4000 VA~4600 VA (100%~115%)

< 8000 VA

Output Characteristics
Signal and Control Protection
Environment

Frequency
Output Voltage
Efficiency max. Short-Circuit Protection
Output Waveform Remote Controller Panel Unit
LED Indicator Dry Contact Terminal Remote Control Terminal
Input Protection
AC Output Protection
Others
Operating Temp. Storage Temp. Storage Temp. & Humidity Safety Standards

Safety & EMC

EMC standards

E-mark
Dimension(WxHxD) Weight Cooling
AC Transfer Function Accessories

50 / 60 Hz ± 0.5% (Dip Switch Selectable)

200 / 220 / 230 / 240 VAC (± 3%) (Dip Switch Selectable)

90%

91%

1 Sec Shutdown Pure Sine Wave (THD < 3%@ Normal Load)N

CR-8 / CR-16 (optional)

Red / Orange / Green LED

By a relay

6-port Green terminal (for inverter ON / OFF)

Over / Under Voltage, Reverse Polarity (Internal Fuse)

Short-Circuit, Overload

Over / Under Temperature Protection
(by Heat sink Temperature +80 /-20 ) -20 ~40 O

-30 ~70

10 ~95% RH

Certified EN 60950-1

Certified EN 55022 class A; EN 55024; EN 61000-3-2, -3-3;
EN 61000-4-2, 3, 4, 5, 6, 8, 11

Certified CISPR 25; ISO 7637-2

255mm X 158mm X 462mm

10 KG

Temperature & Load Controlled cooling Fan

TR-40 (optional)

Table 12. SP-4000 for Output 100/110/115/120 VAC Specification.
Note
M Voltage range Please refer to Figure 3 N Normal load Condition Vin =25V/50V, Vo=200/220/230/240 VAC 80% Full load (PF=1.0) O Operating temperature Please refer to Figure 4 P Warning This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.

15

Power (W) Power (W)

2-3-7. Voltage & temperature performance

175%
115% 100%

1 Sec

1 Min Continue

1 Sec

0% 10.5V 21V 42V

16V

16.5V

32V

33V

64V

66V

Voltage (V) SP-700~2000 Power / Voltage Curve

Figure 1. SP-700~2000 Output power vs. input voltage

175%

1 Sec

115% 100%
40%

1 Min
Continue Output Power

0%

-20oC

0oC

40oC

60oC

Temperature (oC) SP700-2000
Power / Temperature Curve
Figure 2. SP-700~2000 Output power vs. temperature

200%
115% 100%

1 Sec

1 Min Continue

1 Sec

0% 10.5V 21V 42V

16V

16.5V

32V

33V

64V

66V

Voltage (V) SP-3000/4000 Power / Voltage Curve

Figure 3. SP-3000/4000 Output power vs. input voltage

200%

1 Sec

115% 100%
40%

1 Min
Continue Output Power

0%

-20oC

0oC

40oC

60oC

Temperature (oC) SP3000-4000
Power / Temperature Curve
Figure 4. SP-3000/4000 Output power vs. temperature

Power (W) Power (W)

16

2-4. Mechanical Drawings
AC Output Side

AC Output Side

B B
E E

C A

C A

DC Input Side
D SP-700/1000
Figure 5. SP series drawing (Top View)

DC Input Side
D
SP-1500/2000/3000/4000

F F

Figure 6. SP series drawing (AC output/Front View)

Model SP-700 SP-1000 SP-1500 SP-2000 SP-3000 SP-4000

A (mm) 330 372 421 443 442 462

B (mm) 80 69 92 103 103 113

C (mm) 132 196 196 196 196 196

D (mm) 200 200 248 248 255 255

Table 13. SP Series Dimension

E (mm) 7.0 7.0 7.0 7.0 7.0 7.0

F (mm) 83 83 83 83 158 158

17

3. Installation and Maintenance
3-1. AC Output Side (Front Panel) Introduction
A

B E
C

D

F

Figure 7. SP-700/1000 AC output panel view
A

B E
C

D

F

Figure 8. SP-1500/2000 AC output panel view
A

B

C

E

D F

Model A B C D E F

Figure 9. SP-3000/4000 AC output panel view

SP-700 SP-1000 SP-1500 Saving power adjustment Function switch Function LED TRC port (RJ-45) Main switch AC output socket

SP-2000

SP-3000 SP-4000 AC output terminal

Table 14. SP Series AC output side introduction

18

3-1-1. Main Switch
The 3-stage switch remote mode.

is for turning on, turning off and

3-1-2. LED Indicator

3-1-2-1. Input voltage level: to display Input Voltages

LED status

DC 12V

DC 24V

DC 48V

Red Orange

< 11.0V 11.0 ~ 11.5V

< 22.0V 22.0 ~ 23.0V

< 44.0V 44.0~46.0V

Green Orange Red

11.5 ~ 15.0V 15.0 ~ 15.5V
>15.5V

23.0 ~ 30.0V 30.0 ~ 31.0V
>31.0V

46.0~60.0V 60.0~62.0V
>62.0V

Table 15. Input Voltage Level LED Indicator

3-1-2-2. Output Load Level to display AC Loads (PF=1)

LED status SP-700 SP-1000 SP-1500 SP-2000 SP-3000 SP-4000

Green 0 ~ 700 VA 0 ~ 1000 VA 0 ~ 1500 VA 0 ~ 2000 VA 0 ~ 3000 VA 0 ~ 4000 VA

Orange 700 ~ 805 VA 1000 ~ 1150 VA 1500 ~ 1725 VA 2000 ~ 2300 VA 3000 ~ 3450 VA 4000 ~ 4600 VA

Red > 805 VA > 1150 VA > 1725 VA > 2300 VA > 3450 VA > 4600 VA

Table 16. Output Load Level LED Indicator

3-1-2-3. Inverter Status to display Fault condition

LED status Green Red
Red Blink Red Fast Blink

Status
Normal Over Current Protection / Over Load Protection (AC output short-circuit and over load) Under Voltage Protection (Input DC voltage under spec) Over Voltage Protection (Input DC voltage over spec)

Recovery point
12.5V @ DC12V system 25V @ DC24V system 50V @ DC48V system 14.5V @ DC12V system 29V @ DC24V system 58V @ DC48V system

19

LED status Orange
Orange Fast Blink
Orange Slow Blink

Status
Device startup process abnormal Under Temperature Protection (Heat sink temp. under -20 ) Over Temperature Protection (Heat sink temp. over 80 )

Recovery point -- >0
< 60 (heat sink temperature)

Table 17. Inverter LED Status Indicator
3-1-3. Function Switch Introduction

Figure 10. DIP switch ON/OFF position
3-1-3-1. Function Switch Definition

Dip Switch S1 S2 S3 S4

Function Voltage select Voltage select Frequency Select Power saving ON/OFF

Table 18. Function Switch Definition

3-1-3-2. Output voltage selection (S1&S2)

Output voltage

S1

S2

100V/200V

OFF

OFF

110V/220V

ON

OFF

115V/230V

OFF

ON

120V/240V

ON

ON

Table 19. Function Switch definition: output voltage selection

Note! 100V series can be selected between 100/110/115/120VAC, and 200V series can be selected between 200/220/230/240VAC.

20

3-1-3-3. Output Frequency Selection (S3)

Frequency

S3

50Hz

OFF

60Hz

ON

Table 20. Function Switch definition: Output Frequency selection

3-1-3-4. Power Saving Selection (S4)

Saving function

S4

Power Saving OFF

OFF

Power Saving ON

ON

Table 21. Function Switch definition: Power Saving selection

3-1-3-5. Power Saving Load Adjustment User can use variable resistor (VR) to set the input and wake up power saving threshold according to the load condition, and the setting range shows below:

SP-700 SP-1000 SP-1500 SP-2000 SP-3000 SP-4000

Input Saving Power (Min)
<20 VA <20 VA <20 VA <20 VA <40 VA <40 VA

Saving Wake up Power (Min)
>40 VA >40 VA >40 VA >40 VA >60 VA >60 VA

SP-700 SP-1000 SP-1500 SP-2000 SP-3000 SP-4000

Table 22. Power saving setting range (Min)

Input Saving Power (Max)
<110 VA <110 VA

Saving Wake up Power (Max)
>160 VA >160 VA

<110 VA <110 VA

>160 VA >160 VA

<240 VA <240 VA

>280 VA >280 VA

Table 23. Power saving setting range (Max)
3-1-4. TRC Port (for optional kits TR-40, RJ-45)

Pin Number 1 2 3

Signal Description

Reserved --

PH-L

Zero-Crossing Signal

PH-N

Zero-Crossing Signal

21

Pin Number 4 5 6 7
8

Signal Description D

Bypass

Transfer Relay Driver Signal

12V

Internal power for TR40 controller

5V

Internal power for TR40 controller

GND

The same polarity as the battery negative side

Reserved --

Table 24. SP Series TRC Port : RJ-45.
TR-40

SP Series

TRC

Inverter Input

Output

Breaker
AC Input

Load

TRC

AC Output

Figure 11. Wiring between SP series and TR-40

Note! The detail information please refer to TR-40 user

manual

3-1-5. AC output Interface

3-1-5-1. SP-700/1000/1500/2000 AC output interface

Socket Type

Applicable Model

North America (GFCI)

NEMA 5-15R

SP-700/1000-112/124/148

North America (GFCI)

NEMA 5-15R

SP-1500/2000-112/124/148

22

Socket Type F

Applicable Model

SP-700/1000/1500/2000/3000-

Australia / New Zealand

Continental European

UK

212/224/248

Universal

SP-700/1000/1500/2000-112/124/148 SP-700/1000/1500/2000/3000-
212/224/248

Hard Wire

SP-3000-112/124/148/212/224/248 SP-4000-124/148/224/248

France Connector

SP-700/1000/1500/2000/3000212/224/248

Table 25. SP Series AC Socket vs. Model

3-1-5-2. SP-3000/4000 AC output interface

Terminal F Line (L)
AC terminal Neutral (N)
FG (Ground)

Wire color Black
White
Green / Yellow or Bare copper

Wire length / gauge Within 6 feet / AWG# 200-240VAC: AWG10 100-120VAC: AWG8 26~32 feet / AWG#
10 ~ 8

Table 26. SP-3000/4000 Series AC output wiring

3-1-5-3. GFCI connector
Recommend GFCI connector HUBBELL INC WIRING DEVICE DIV, Type GF20 and GFRST20. Rated 125V, 20A COOPER WIRING DEVICES, Type VGF20 and SGF20. Rated 125V, 20A LEVITON MFG CO INC, Type 7899-W and GFNT2. Rated 125V, 20A PASS & SEYMOUR INC, Type 2097. Rated 125V, 20A

23

3-2. DC Input Side (Rear Panel) Introduction
1 2
4 3
Figure 12. SP-700/1000
1

4

23

4

Figure 13. SP-1500/2000

1 2

3

Model    

4

4

Figure 14. SP-3000/4000

SP-700 SP-1000 SP-1500 Remote port (RJ-11) Remote control green terminal Chassis ground DC input connector

SP-2000

SP-3000

Table 27. SP Series DC input side introduction

SP-4000

24

3-2-1. Remote Port (RJ-11) The SP Series Inverter can be compatible with CR-8, and CR-16 remote control via RS-232 Communication. Before using the remote control, make sure the main switch on inverter must be at " REMOTE" position.

Pin Number 1
2
3 4 5 6

Signal Description 

Reserved

--

GND

The same polarity as the battery negative side

RXD

RS-232 RXD

TXD

RS-232 TXD

RMT

Remote controller panel (positive)

VCC

Internal power for remote controller

Table 28. SP Series Remote Port : RJ-11

3-2-2. Remote Control Green Terminal Remote control green terminal  may be connected to a Form C relay for "FAULT" indication. When "FAULT" occurs, the relay switches.

Item 1 2 3

Figure 15. Remote control terminal

Description

Item Description

Dry contact (Normal Open)

4

Enable+ (ENB)

Common

5

Enable- ( )

Dry contact (Normal Closed)

6

Ground

Table 29. Dry contact terminal definition
Note! Pin-6 is the same polarity with battery negative electrode.

25

Note! Fault conditions include Input under / over voltage, output short circuit / over load, over / under temperature. Caution! Please follow the following steps for the installation
z Before installing the inverter, make sure the main switch is at "OFF" position.
z Before using the remote function, make sure the main switch pressed toward "REMOTE"
z Use 20 ~ 24 #AWG wire to connect the remote control terminals
Figure 16. Wiring for control
3-2-3. General instruction before DC Input  3-2-3-1 Before installation: The DC cables should be as short as possible (less than 6 feet / 1.8 meters ideally) The size of the cable should be thick enough to limit the voltage drop to less than 2% when carrying the maximum input current to prevent frequent low-input voltage warnings, and shutdown. The following sizes of cables and fuses are recommended distance (<6 ft.) between the batteries and the inverter.
26

Model SP-700-112 / 212 SP-700-124 / 224 SP-700-148 / 248 SP-1000-112 / 212 SP-1000-124 / 224 SP-1000-148 / 248 SP-1500-112 / 212 SP-1500-124 / 224 SP-1500-148 / 248 SP-2000-112 / 212 SP-2000-124 / 224 SP-2000-148 / 248 SP-3000-112 / 212 SP-3000-124 / 224 SP-3000-148 / 248 SP-4000-124 / 224 SP-4000-148 / 248

Wire AWG #6 #10 #16 #4 #8 #14 #1 #6 #10 #1/0 #4 #8 #4/0 #1 #6 #1/0 #4

Inline fuse 150A 80 A 50 A 225A 125A 80A 350A 175A 90A 500A 225A 150A 700A 350A 175A 500A 275A

Table 30. SP Series Wiring Cable diameter and Inline Fuse
Note! Batteries are capable of providing very large currents in case of short circuit. The fuse should be as close to the positive battery terminal as possible. Use Bussmann ANN series fuses (will also require Fuse Block 4164) or equivalent.

3-2-4. Chassis Ground  Must be connected to earth ground prior to making any other connections to the equipment.

3-3. Maintenance
Make sure that the fan vents are not blocked.
Use a vacuum cleaner to remove any dust from the fan area When cleaning the case or front panel, use a soft, dry cloth, only. If the case or front panel is very dirty, use a neutral, non-abrasive detergent. Do not use alcohol or ammonia based solutions.
Regular service, and relocation of the inverter, should be performed by a qualified service technician. Avoid spilling liquid on the inverter.

27

4. Operation
4-1. Connection the DC cable
Connect DC input terminals to 12V / 24V /48V battery or other DC power source [ + ] is positive, [ - ] is negative. Reverse polarity connection can blow the internal fuse and may damage the inverter permanently.
Figure 17. DC cable connection
Warning! Make sure that all the DC connections are tight (torque to 9 ­ 10 ft-lbs, 11.7 ­ 13 Nm). Loose connections could result in overheating and can be a potential hazard. Warning! The recommended inline fuse should be installed as close to the battery positive terminal as possible failure to use a fuse on the "+" cable running between the inverter and battery may cause damage to the cable / inverter and will void warranty. Also, only use high quality copper wire and keep the cable length short which is a maximum of 3 - 6 feet.
28

Figure 18. Battery cabling
4-2. Connecting the input power
Before making the DC input side connections , the main switch must be at "OFF".
4-3. Connecting the loads
Calculate the total power consumption of the output load. Make sure that the total power consumption does not exceed the rated power. If the total power consumption over the rated power of the inverter, remove the non-critical: loads until the total power consumption is below the rated power.
4-4. Switch ON Inverter
Set the power switch to the "ON" position . The inverter will carry out self-diagnosis and, the LED's will also appear various colors. Set the power switch to the "OFF" position . The inverter stops and all the lights that are on will go off.
29

4-5. Protection Mechanism

Model
12V 24V 48V

Over Voltage (DC)

Under Voltage

Shutdown Restart

Alarm

16.5V ± 0.3V 14.5V± 0.3V 10.5V ± 0.3V

33V ± 0.5V

29V ± 0.5V

21V± 0.5V

66 ± 1V

58V ± 1V

42V± 1V

Under Voltage

Shutdown

Restart

10.5V ± 0.3V 12.5V± 0.3V

21V ± 0.5V

25V ± 0.5V

42V ± 1V

50 ± 1V

Model
12V 24V 48V

Table 31. Protection Mechanism

Over temperature protection

Shutdown

Restart

80

60

Table 32. Over Temperature Protection Mechanism

5. RS-232 Communication and Operation
5-1. RS-232 Port
RS-232 Port : Serial port monitoring and control through computer

Figure 19. RS-232 cable

SP Series

PIN Number Description

1

Not used

2

GND

3

RXD

4

TXD

5

Remo Control

6

VCC

Computer

PIN Number

Description

Not used

1

RXD

2

TXD

3

Not used

4

GND

5

Not used

6

Not used

7

Not used

8

Not used

9

Table 33. RS-232 interface definition

30

5-2. RS-232 Port Operating
The following steps show the connection among inverter and computer. Step 1 Connect the RS-232 port to the SP series unit on the front
panel

Step 2 Run the computer communication program

Step 3

Set the transmission protocol Byte structure: START-BIP ­ 8 BIT DATA-STOP BIT Baud rate: 4800

Step 4 Select the COM port and start the operation

5-3. Example of RS-232 Port Operating
5-3-1. RS-232 command format This unit uses high-level language commands starts with CR (0DH) and LF(0AH) as the end of the command, The system would interpret and execute the command only after these two characters are received. After the unit executes the command, it would send a response string to the computer The response string is as follows: => CR LF: Command executed successfully ?> CR LF: Command error, not accepted ! > CR LF: Command correct but execution error (e.g. parameters out of range)
5-3-2. Command format The following table shows the useful command to operate SP series.

Function
Turn ON / OFF SP series
Query the SP series output frequency Query the SP series output voltage

Command and description Format : Power <value> <value> can be one of the following. "0" : Power OFF "1" : Power ON
Format: FRQ?
Format: VINV?

31

Function Query the SP series output current
Query the SP series status

Command and description

Format: IINV?

Format: ERR? (SP-700~2000)

Bit

Description

BIT0

0: No OLPL Protection 1: OLPL Protection

BIT1

0:No Sof Fail Protection 1:SofFail Protection

BIT2

0:No Poff Protection 1:Poff Protection

BIT3

0:No UVP Protection 1:UVP Protection

BIT4

0:No OVP Protection 1:OVP Protection

BIT5

0:No OLPM Protection 1: OLPM Protection

BIT6

0:No OLPH Protection 1: OLPH Protection

BIT7

0:No OTP Protection 1: OTP Protection

BIT8

0:No UTP Protection 1: UTP Protection

BIT9

0:No OOCP Protection 1: OOCP Protection

* Status definition refer to Table 35. Status definition

Format: ERR? (SP-3000~4000)

Bit BIT0

Description
0: No ID Fail 1: ID Fail

BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7

0:No Sof Fail Protection 1:SofFail Protection
0:No PLL Fail 1:PLL Fail 0:No Poff Protection 1:Poff Protection 0:No Short Protection 1:Short Protection 0:No OOCP Protection 1: OOCP Protection 0:NoOVP Protection 1:OVP Protection 0:No UVP Protection 1:UVP Protection

32

Function

Command and description

BIT8

0:No OTP Protection 1: OTP Protection

BIT9

0:No UTP Protection 1: UTP Protection

BIT10

0:No OLPH Protection 1: OLPH Protection

BIT11

0:No OLPL Protection 1: OLPL Protection

* Status definition refer to Table 36. Status definition

Query the SP series DC input voltage of the battery Query the SP series output power Reset default

Format: VBAT?
Format: PINV? Format:*RST

Select the Setup Menus with the help of Function Codes

Format : FUNC <Function Code>

Function code

Setting Menu

0

OVP setting

1

OVP Recovery

2

UVP Setting

3

UVP Recovery

5

RS-232 Baud-rate

6

Retry Time

Query the functions No Query the setting value of the function Set or adjust the value of the function

Format: FUNC? Format: SETT?
Format: SETT <value>

Table 34. RS-232 interface command

SP-700 ~ SP-2000 Status Definition

Description OLPL Protection Sof Fail Protection Poff Protection UVP Protection OVP Protection OLPM Protection OLPH Protection OTP Protection UTP Protection OOCP Protection

Definition OLPL: Over Load Protection Low (101~115%) Sof Fail: Soft Start Fail Poff: Power off UVP: Under Voltage Protection OVP: Over Voltage Protection OLPM: Over Load Protection Middle (116~200%) OLPH: Over Load Protection High (>200%) OTP: Over Temperature Protection UTP: Under Temperature Protection OOCP: Output Over Current Protection

Table 35. SP-700 ~ SP-2000 Status Definition

33

SP-3000 ~ SP-4000 Status Definition

Description ID Sof Fail Protection PLL Poff Protection
OOCP Protection
OVP Protection UVP Protection OTP Protection UTP Protection OLPH Protection OLPL Protection

Definition ID: ID Connection Error Sof Fail: Soft Start Fail PLL: Phase lock loop Poff: Power off OOCP: Output Over Current Protection (Over Load > 200%) OVP: Over Voltage Protection UVP: Under Voltage Protection OTP: Over Temperature Protection UTP: Under Temperature Protection OLPH: Over Load Protection High (116~200%) OLPL: Over Load Protection Low (101~115%)

Table 36. SP-3000 ~ SP-4000 Status Definition

The following data shows the function code detail setting value.

Note: Below setting value will go back to default value by switching on / off the inverter.

5-3-2-1. FUNC 0 : OVP setting

SETT <value> 15.0 ~ 16.5 30.0 ~ 33.0 60.0 ~ 66.0

Default 16.5V <16.5> 33.0V <33.0> 66.0V <66.0>

Model SP series-112 / 212 SP series-124 / 224 SP series-148 / 248

Table 37. OVP setting

5-3-2-2. FUNC 1 : OVP Recovery

SETT <value> 13.5 ~ 14.5 27.0 ~ 29.0 54.0 ~ 58.0

Default 14.5V <14.5> 29.0V <29.0> 58.0V <58.0>

Model SP series-112 / 212 SP series-124 / 224 SP series-148 / 248

Table 38. OVP recovery

5-3-2-3. FUNC 2 : UVP setting

SETT <value> 10.5 ~ 11.5 21.0 ~ 23.0 42.0 ~ 46.0

Default 10.5V <10.5> 21.0V <21.0> 42.0V <42.0>

Model SP series-112 / 212 SP series-124 / 224 SP series-148 / 248

Table 39. UVP setting

34

5-3-2-4. FUNC 3 : UVP Recovery

SETT <value> 12.5 ~ 13.5 25.0 ~ 27.0 50.0 ~ 54.0

Default 12.5V <12.5> 25.0V <25.0> 50.0V <50.0>

Table 40. UVP recovery

5-3-2-5. FUNC 5 : RS-232 Baud rate

SETT <value> 0 1 2 3

Default 2

Table 41. RS-232 baud rate
5-3-2-6. FUNC 6 : Retry time
SETT <value> 0 1 2 3

Table 42. retry time

Model SP series-112 / 212 SP series-124 / 224 SP series-148 / 248
Model 1200 2400 4800 9600
Default
3

35

6. Information
6-1. Warning
Warning! Do not open or disassemble the Inverter. Attempting to do so may cause risk of electrical shock or fire.
6-2. Warranty
We guarantee this product against defects in materials and workmanship for a period of 24 months from the date of purchase. In case you need to repair or replace any defective power inverters, please contact COTEK local distributor. This warranty will be considered void if the unit has been misused, altered, or accidentally damaged. COTEK is not liable for anything that occurs as a result of the user's fault.