Ruud Air to Water Heat Pump
Where Energy Efficiency is Essential, Air to Water Heat Pump offers up to 150°F outlet water temp in a Super-efficient, Super-compact Package
Key Features
Highly Efficient
Delivers hot water with a system Coefficient of Performance (COP) exceeding 4.0 at 80°F ambient and 60% relative humidity. Heat pumps can also be used as a preheat to other fuel types. Contributes to the overall increase in building efficiency and can qualify for LEED points. HPHD135 models are ENERGY STAR® certified.
Installation Flexibility
Available models and options to meet the diverse needs of every building, the heat pump takes gas lines and flue venting out of the equation. It can be installed indoors or outdoors with a choice between vertical and horizontal discharge models. Optional kits are available to connect ductwork for ducting cool discharge air, as well as stacking kits to stack horizontal discharge models, saving valuable floor space.
Suits Most Mild Climates
The heat pump will efficiently perform in ambient temperatures down to 40°F. For colder days, it includes an auxiliary boost mode and auto defrost. In addition, it features an epoxy coated evaporator coil which provides extra protection in coastal and non-coastal environments.
Product Overview
Models: Ruud Air to Water Heat Pump
Voltage/Phase: 208 or 240 Volt / 1 PH or 480 Volt /3 PH
Installation: Flexible Indoor or Outdoor Use
Heat Exchanger: Double Wall Heat Exchanger
Warranty: 1-Year Limited Warranty
Visual Description: The product is shown in both horizontal and vertical configurations, illustrating their compact design and external components.
Performance Data
Performance Graphs
HPHD-60 Heating COP Graph: This graph illustrates the relationship between Ambient Temperature (F) on the x-axis and COP and Capacity (BTU/h) on the y-axis. It shows increasing COP and Capacity as ambient temperature rises.
HPHD-135 Heating COP Graph: Similar to the HPHD-60 graph, this shows COP and Capacity (BTU/hr) versus Ambient Temperature (F), indicating performance trends.
System Diagram
The diagram illustrates the water flow and connections for the Air to Water Heat Pump system. It shows the direction of flow for cold water supply, primary flow, primary return, hot water flow, and hot water return. Key components include the A2W Heat Pump, Primary Pump, Storage Tanks, and connections to the building's hot water supply and return. It also indicates the location of a Building Hot Water Temp Sensor and a Tank Thermostat Sensor, along with the Electrical Supply and Heat Pump LAN Connection.
Technical Specifications
HPHD-60 Series (Horizontal & Vertical)
ELECTRICAL INPUT | HPHD-60HNU-201 (Horizontal) | HPHD-60VNU-201 (Vertical) | |
---|---|---|---|
Voltage/Phase | 208/240 Volt/ 1 Phase / 60 Hz | 208/240 Volt/ 1 Phase / 60 Hz | |
Full Load / Locked Rotor (Amps Per Phase) | 29.5 FLA / 176 LRA | 29.5 FLA / 176 LRA | |
Min. Circuit Amperage | 40 Amps | 40 Amps | |
Refrigerant | R134a | R134a | |
Heating Capacity, BTU/hr | Up to 84,752 | Up to 84,752 | |
Power Input, kW | 5.2 | 5.2 | |
COP | Up to 6.13 | Up to 6.13 | |
Noise Level, dBa @ 10ft | 54 | 54 | |
Rated Load Amps @ 54°F SST / 113°F SCT | 22.6 | 22.6 |
TECHNICAL DATA | ||||
---|---|---|---|---|
Type | Compressor | Fan | Compressor | Fan |
Number Per Unit | Scroll | Axial | Scroll | Axial |
FLA (Full Load Amps, each) | 1 | 2 | 1 | 2 |
Voltage / Phase | 27.3 | 1.06 | 27.3 | 1.06 |
Pole/RPM | 208/240v / 1 P | 208/240v / 1 P | 208/240v / 1 P | 208/240v / 1 P |
Air Flow, CFM | 2/3500 | 6/1060 | 2/3500 | 6/1060 |
Max. Static Pressure for Ducting | N/A | 1695 (Per Fan) | N/A | 1695 (Per Fan) |
HEAT EXCHANGER (Water Side) | |
---|---|
Type of Water Tube | Double Wall - 316L Stainless Steel |
Design | Vented Brazed Plate |
Flow Rate Excl. By Pass, gpm | 17.4 |
Max. Outlet Water Temp, °F | 150 |
Design Pressure Drop, PSI | 4.8 |
Max. Operating Pressure, PSI | 145 |
GENERAL INFORMATION | |
---|---|
Water Connections | 1-1/4" Copper |
Drain | 3/4" Aluminium |
Defrost | Hot Gas Injection |
Cabinet Construction | 18 Gauge Stucco Aluminium |
Approx. Shipping Weight, lbs | 500 |
Size L x W x H | 49.2" x 27.2" x 38.7" (Horizontal) / 49.2" x 26.2" x 39.8" (Vertical) |
HPHD-135 Series (Horizontal & Vertical)
ELECTRICAL INPUT | HPHD-135HNU-483 (Horizontal) | HPHD-135VNU-483 (Vertical) | |
---|---|---|---|
Voltage/Phase | 480 Volts / 3 Phase / 60 Hz | 480 Volts / 3 Phase / 60 Hz | |
Full Load / Locked Rotor (Amps Per Phase) | 26.9 FLA / 150 LRA | 26.9 FLA / 150 LRA | |
Min. Circuit Amperage | 35 Amps | 35 Amps | |
Refrigerant | R134a | R134a | |
Heating Capacity, BTU/hr | Up to 196,508 | Up to 196,508 | |
Power Input, kW | 12.3 | 12.3 | |
COP | Up to 5.60 | Up to 5.60 | |
Noise Level, dBa @ 10ft | 62 | 62 | |
Rated Load Amps @ 54°F SST / 113°F SCT | 21.9 | 21.9 |
TECHNICAL DATA | ||||
---|---|---|---|---|
Type | Compressor | Fan | Compressor | Fan |
Number Per Unit | Scroll | Axial | Scroll | Axial |
FLA (Full Load Amps, each) | 1 | 2 | 1 | 2 |
Voltage / Phase | 23.7 | 1.6 | 23.7 | 1.6 |
Pole/RPM | 480 / 3 | 480 / 3 | 480 / 3 | 480 / 3 |
Air Flow, CFM | 2/3500 | 6/1065 | 2/3500 | 6/1065 |
Max. Static Pressure for Ducting | N/A | 6144 (Per Fan) | N/A | 6144 (Per Fan) |
HEAT EXCHANGER (Water Side) | |
---|---|
Type of Water Tube | Double Wall - 316L Stainless Steel |
Design | Vented Brazed Plate |
Flow Rate Excl. By Pass, gpm | 34.9 |
Max. Outlet Water Temp, °F | 150 |
Design Pressure Drop, PSI | 5.8 |
Max. Operating Pressure, PSI | 145 |
GENERAL INFORMATION | |
---|---|
Water Connections | 2" Copper |
Drain | 3/4" Aluminium |
Defrost | Hot Gas Injection |
Cabinet Construction | 18 Gauge Stucco Aluminium |
Approx. Shipping Weight, lbs | 800 |
Size L x W x H | 73.1" x 36.6" x 48.0" (Horizontal) / 73.1" x 31.8" x 53.8" (Vertical) |
Performance Tables
HPHD-60 Performance
WATER OUT °F | AMBIENT TEMPERATURE | UNITS | |||||||
---|---|---|---|---|---|---|---|---|---|
40°F | 50°F | 60°F | 70°F | 80°F | 90°F | 100°F | 110°F | ||
100°F | 44,057 | 49,866 | 57,130 | 62,806 | 67,307 | 78,937 | 81,845 | 84,752 | BTU/hr |
3.01 | 3.42 | 3.85 | 4.26 | 4.65 | 5.14 | 5.64 | 6.13 | COP | |
110°F | 41,267 | 47,617 | 55,059 | 61,310 | 66,667 | 77,383 | 80,062 | 82,741 | BTU/hr |
2.98 | 3.32 | 3.67 | 4.01 | 4.33 | 4.74 | 5.15 | 5.56 | COP | |
120°F | 38,477 | 45,369 | 52,988 | 59,813 | 65,031 | 76,194 | 78,985 | 81,776 | BTU/hr |
2.96 | 3.22 | 3.50 | 3.77 | 3.76 | 4.23 | 4.70 | 5.17 | COP | |
130°F | 35,687 | 43,120 | 50,917 | 58,316 | 64,917 | 73,934 | 76,188 | 78,442 | BTU/hr |
2.93 | 3.13 | 3.33 | 3.52 | 3.57 | 3.82 | 4.08 | 4.33 | COP | |
140°F | 32,897 | 40,872 | 48,846 | 56,820 | 64,784 | 72,768 | 74,762 | 76,755 | BTU/hr |
2.90 | 3.03 | 3.15 | 3.28 | 3.40 | 3.52 | 3.65 | 3.77 | COP | |
150°F | N/A | 38,623 | 46,775 | 55,323 | 64,737 | 71,599 | 73,314 | 75,030 | BTU/hr |
N/A | 2.93 | 2.98 | 3.03 | 3.28 | 3.30 | 3.32 | 3.34 | COP |
HPHD-135 Performance
WATER OUT °F | AMBIENT TEMPERATURE | UNITS | |||||||
---|---|---|---|---|---|---|---|---|---|
40°F | 50°F | 60°F | 70°F | 80°F | 90°F | 100°F | 110°F | ||
100°F | 98,398 | 110,187 | 121,986 | 133,329 | 143,606 | 175,748 | 186,128 | 196,508 | BTU/hr |
3.34 | 3.54 | 3.74 | 3.97 | 4.27 | 5.09 | 5.34 | 5.60 | COP | |
110°F | 96,532 | 107,240 | 117,948 | 129,300 | 142,153 | 174,023 | 184,612 | 195,201 | BTU/hr |
2.76 | 3.03 | 3.30 | 3.59 | 3.92 | 4.58 | 4.86 | 5.13 | COP | |
120°F | 96,184 | 106,935 | 117,687 | 128,787 | 140,701 | 161,898 | 176,735 | 191,571 | BTU/hr |
2.77 | 2.92 | 3.06 | 3.26 | 3.57 | 4.08 | 4.37 | 4.66 | COP | |
130°F | 94,907 | 105,488 | 116,069 | 126,896 | 138,298 | 157,661 | 173,249 | 188,837 | BTU/hr |
2.50 | 2.64 | 2.78 | 2.95 | 3.23 | 3.63 | 3.96 | 4.28 | COP | |
140°F | 93,631 | 104,040 | 114,450 | 125,004 | 135,894 | 153,458 | 169,781 | 186,103 | BTU/hr |
2.24 | 2.36 | 2.49 | 2.65 | 2.89 | 3.18 | 3.54 | 3.90 | COP | |
150°F | N/A | 102,172 | 109,994 | 118,472 | 128,482 | 141,953 | 163,580 | 185,208 | BTU/hr |
N/A | 1.82 | 1.96 | 2.12 | 2.31 | 2.54 | 3.12 | 3.70 | COP |
Installation Clearances
HPHD-60 Clearances
Sides | 60K BTU | Direction | Description | Minimum Clearance Required | |
---|---|---|---|---|---|
Horizontal | Vertical | ||||
Evap Coil Side | 20" | A | Evaporator Coil | 20" | 20" |
Back (Vert. Discharge) | Nil | B | Water Connections | 20" | 20" |
Back (Horiz. Discharge) | 47" | C | Horizontal - Fan Discharge | 47" | Nil |
Display Side | 34" | D | Compressor Access | 34" | 34" |
Water Conn. Side | 20" | E | Top - Fan Discharge | 20" | 47" |
Top (Vert. Discharge) | 47" | ||||
Top (Horiz. Discharge) | Clearance above unit required for service personnel to stand |
Note: When units are placed side by side, allow at least 40" between evaporator coils.
HPHD-135 Clearances
Sides | 135K BTU | Direction | Description | Minimum Clearance Required | |
---|---|---|---|---|---|
Horizontal | Vertical | ||||
Evap Coil Side | 40" | A | Evaporator Coil | 40" | 40" |
Back (Vert. Discharge) | Nil | B | Water Connections | 24" | 24" |
Back (Horiz. Discharge) | 78" | C | Horizontal - Fan Discharge | 78" | Nil |
Display Side | 34" | D | Compressor Access | 34" | 34" |
Water Conn. Side | 24" | E | Top - Fan Discharge | 20" | 79" |
Top (Vert. Discharge) | 79" | ||||
Top (Horiz. Discharge) | Clearance above unit required for service personnel to stand |
Note: When units are placed side by side, allow at least 40" between evaporator coils.
Dimensional Drawings
HPHD-60 Horizontal: Shows top, side, and end views with key dimensions for water connections, fan access, electrical access, and overall unit size (approx. 49.2" L x 27.2" W x 38.7" H).
HPHD-60 Vertical: Shows top, side, and end views with key dimensions for water connections, fan access, electrical access, and overall unit size (approx. 49.2" L x 26.2" W x 39.8" H).
HPHD-135 Horizontal: Shows top, side, and end views with key dimensions for water connections, fan access, electrical access, and overall unit size (approx. 73.1" L x 36.6" W x 48.0" H).
HPHD-135 Vertical: Shows top, side, and end views with key dimensions for water connections, fan access, electrical access, and overall unit size (approx. 73.1" L x 31.8" W x 53.8" H).
Sizing and Accessories
Pipe Sizing for HPHD-60 Models
Number of Heat Pumps in Parallel | 1 | 2 | 3 | 4 |
---|---|---|---|---|
Primary Pump | AP22760A CM 3-2 | |||
Branch Size | 1.5" | 1.5" | 2" | 2.5" |
Header Size | 1.5" | 2" | 2.5" | 3" |
Pipe Sizing for HPHD-135 Models
Number of Heat Pumps in Parallel | 1 | 2 | 3 | 4 |
---|---|---|---|---|
Primary Pump | AP22760B CM 10-1 | |||
Branch Size | 2" | 2" | 3" | 4" |
Header Size | 2" | 3" | 4" | 4" |
Note: Header pipe sizing is based on a total length of 130 ft. of primary flow and return piping and 20 bends, and heat pumps @ 3.9 ft./sec velocity. One pump per Heat Pump.
Accessories for HPHD-60 Models
Pump | BMS Card* | LAN Cable |
---|---|---|
AP22760A CM 3-2 | 17412 BACNET MS/TP 17447 PCOWEB SE Ethernet 17414 PCOS004850 Serial |
19616 |
Accessories for HPHD-135 Models
Pump | BMS Card* | LAN Cable |
---|---|---|
AP22760B CM 10-1 | 17412 BACNET MS/TP 17447 PCOWEB SE Ethernet 17414 PCOS004850 Serial |
17615 |
*Additional BMS Cards available, contact Ruud application engineering.
Available Kits
Part Number | Description |
---|---|
45259 | HPHD-60 Vertical Discharge Ducting Kit |
45260 | HPHD-135 Vertical Discharge Ducting Kit |
45261 | HPHD-60 Horizontal Discharge Ducting Kit |
45262 | HPHD-135 Horizontal Discharge Ducting Kit |
45263 | HPHD-60 Horizontal Stacking Kit |
45264 | HPHD-135 Horizontal Stacking Kit |
Visual Description of Kits: The document displays visual representations of six different kits: Part 45259 (Vertical Ducting Kit for HPHD-60), Part 45260 (Vertical Ducting Kit for HPHD-135), Part 45261 (Horizontal Ducting Kit for HPHD-60), Part 45262 (Horizontal Ducting Kit for HPHD-135), Part 45263 (Horizontal Stacking Kit for HPHD-60), and Part 45264 (Horizontal Stacking Kit for HPHD-135). These appear to be frame-like structures for managing air discharge or stacking units.