Over-Paneling an MPPT Solar Charge Controller

Warning: Most MPPT controllers allow over-paneling. However, there are a small number of them that do not. Be sure to check the specifics for your controller.

Warning: This paper is about MPPT controllers. PWM controllers are very different and none of what is in this paper applies to PWM controllers.

Background: What is Power Point Tracking?

For any given set of light and temperature conditions, a solar panel will have a different current-voltage curve. The point a panel is operating on that curve is known as the 'Power Point'. To get the most possible power out of a panel, the current should be adjusted to the point where the Voltage times Current produces the highest value (Power = Current x Voltage). This is known as the Maximum Power Point (MPP).

An MPPT controller will occasionally raise and lower the current going through the panel to find the MPP. Since the MPP changes as the conditions change during the day, each time it scans it might find a slightly different MPP to use. By doing the scan on a regular basis, the controller can track the MPP. Thus, the name Maximum Power Point Tracking (MPPT).

When the system cannot take the full power from the panels, the controller will move to a less efficient power point. The limit of this is when the battery is full, no power is needed, and the controller stops all input current. This means the voltage will go to Voc and power production will be zero. (0A x Voc = 0W)

NOTE: Not all MPPT controllers are alike. Each MPPT controller can have a different algorithm for how it does the scan and how often it does the scan. These differences can make a difference in how well the controller will harvest the power from the solar panels.

Diagram Description: A graph showing two curves: an I-V curve (blue) and a P-V curve (red). The I-V curve shows current decreasing as voltage increases. The P-V curve shows power increasing to a maximum (Pmax) at a specific voltage (Vmp) and then decreasing. Key points labeled are Isc (short circuit current), Imp (maximum power point current), Vmp (maximum power point voltage), and Voc (open circuit voltage).

What is Over-paneling on an MPPT controller?

Short Answer: Installing more panel wattage on an MPPT Solar charge controller than the controller is rated for.

Long Answer: Most MPPT controllers have two specifications: the Max Input Voltage they can handle and the Max Output Current they will generate. This means that 1) you cannot exceed the specified voltage on the input without damage, and 2) the controller will produce no more than the specified max output current. The output current is used to determine how much power it can pass to the battery (e.g., a 30A output to a 24V LIFEPO4 battery will produce a nominal 27.2V x 30A = 816W). However, with many MPPT controllers, the PV array wattage can be significantly higher than the wattage the controller will pass to the battery. The controller will just not use the power it cannot handle.

Why would I want to over-panel? Aren't I wasting power?

There are many conditions when production is lower than desired. A few examples are:

Panels often (usually) do not produce at 100% of their rating. It is not unusual to see panels perform at a power level that is 20%-25% less than the STC (Standard Test Condition) ratings.

At these times, a panel array that is sufficient for sunny summer days may become insufficient. By over-paneling, the array can produce more power in sub-optimal situations without using a larger, expensive charge controller.

In the past, panel costs were high, and systems were designed to milk every possible watt-hour out of the precious panels. However, the price of panels is now so low that it is now a viable option to over-panel even though some production may be wasted.

How does Over-Paneling work?

An MPPT controller has no direct control over its input voltage, but it can limit the current at the input. When the controller detects that it has reached its max output current, it will start throttling the input current. When the current through the panels goes down, the voltage from the panels will go up and the panel starts operating at a point that is less than optimal. Consequently, the total production of power goes down. Therefore, by controlling the input current, the MPPT controller can limit the power production and power throughput to a level it can handle.

Also note that when limiting the power from the panels, the controller is doing the opposite of Maximum Power Point Tracking (MPPT). It is purposely changing the current to move the Power Point to a less productive setting for the panels. This is also called clipping.

The power production for a cloudy day followed by a sunny day might look something like the image below.

Diagram Description: Two graphs side-by-side, illustrating power production over a day. The left graph shows a cloudy day, and the right graph shows a sunny day. Each graph compares 'Cloudy Day With Over-Paneling (Good Production)' and 'No Over-paneling (Poor Production)' on the left, and 'Sunny day With Over-paneling (Great Production)' and 'No Over-paneling (Good Production)' on the right. The graphs show power output over time from morning to evening. Key elements include 'Array Power Limit', 'Controller Power Limit', 'Added Production', 'Unrealized Capacity', and labels indicating when the controller is performing Maximum Power Point Tracking or power limiting ('clipping').

A Practical Example of Over-Paneling

A recent poster on the forum had the configuration shown but needed more production on winter and/or cloudy days.

Sunpower 435-watt panel Panel Specs

Electrical Data SPR-E20-435-COM
Nominal Power (Pnom) 435 W
Power Tolerance +5/-3%
Avg. Panel Efficiency 20.3%
Rated Voltage (Vmpp) 72.9 V
Rated Current (Impp) 5.97 A
Open-Circuit Voltage (Voc) 85.6 V
Short-Circuit Current (Isc) 6.43 A

SmartSolar 150/35 Controller Specs

Spec Value
Input Voltage Max 150V
Max Output Current 35A
Power (14Vx35A) 490W
Isc Limit 40A

The person had three additional panels and wanted to use them for cloudy days but was concerned about burning out the controller from too much input wattage. (2 Panels would be 870W, but the controller will only output 490W)

Since the panel Voc is 85.6V, two panels in series would exceed the input voltage limit of the controller (2x85.6V=171.2V). However, the Voc of 2 panels in parallel would stay at 85.6V. Therefore, two panels in parallel can be used and not damage the controller.

Diagram Description: A schematic showing two 435W Sunpower panels connected in parallel to a Victron SmartSolar 150/35 charge controller, which is then connected to a 12V system.

In this configuration, the panels have the capability of producing up to 870W, but the controller would adjust the input current in order to limit power and keep the output current to 35A (490 W).

In fact, all four of the panels could be hooked up in parallel for a possible 1740W, but the controller will limit it to 490W. However, that much excess would be well past the point of diminishing returns.

The hidden Over-paneling limit: Max Array Isc

Some controllers do not specify a direct over-paneling limit, but they do specify a Max Array Isc. This in turn will often limit the amount of over-paneling the controller will support.

In general, the lower the Voc is for an array, the higher the Isc will be for the same wattage. Consequently, the limit on the Array Isc is most likely to be a limiting factor when the Voc of the PV Array is at the lower end of the operating PV voltage for the controller. Conversely, the closer to the max PV input the PV array operates, the higher wattage the array can typically be without violating the Isc spec of the controller. Consequently, it is usually possible to over-panel an MPPT controller that has an Isc limit by designing the array to produce a Voc that is higher in the controller's safe operating range. There are examples of these calculations on the Victron Specific section of this document.

Over-paneling vs larger or additional controller.

It must be acknowledged that when over-paneling, there is unrealized capacity (wasted capacity) of the PV array. This begs the question: Why not use a larger controller or a second controller to harvest the full capability of the array.

The primary reason not to have a larger or additional controller is cost. Controllers can be pricy, and panels are relatively cheap so just adding panels may be the most cost-effective solution. However, there are good reasons to add a controller even if the system does not need the unrealized capacity:

Redundancy: In an off-grid situation it is very beneficial to have multiple controllers in the system. If one controller goes out, the other can still provide the critical power needed.

Controller Stress: When over-paneled, the controller will be spending more time operating at its max capacity. A quality controller from a reputable manufacturer should be able to handle this.... But it is always best to avoid running equipment at its max capacity.

Notes, Warnings and Limitations.

Related Resources

A note about 12v Panels and 24V Panels.

When working with an MPPT controller, the concept of 12V panels or 24V panels can be completely ignored. All that is important is the total Voc of the array.

In the past, panels were either hooked directly to the batteries or a PWM controller was used. In these cases, it was important to match the panel voltage to the battery voltage. With so-called 12V panels (actual Voc is ~18V), you could put it on a 12V battery and know the voltage was about right for charging. A 24V panel could be put on a 24 volt battery and the voltage would be about right.

MPPT controllers will transform the input voltage and current to what is needed for battery voltage and current. Consequently, input voltage is almost completely isolated from the output voltage. The only aspect of the battery voltage that impacts the controller input voltage is that the input voltage needs to be some amount higher than the battery voltage for the controller to start up and run. (This is usually ~5V higher than battery voltage to start and 1V-3V higher than battery voltage to run.... Check the specs of your controller for specifics)

MPPT Controller Specifics

Check the manual for your controller for any max array size for over-paneling or other limits. (Click on link to jump to pages with more controller specific information)

The following controllers support over-paneling to varying degrees:

According to the manufacturers, the following controllers do not support Over-Paneling:

Note: Additional vendor specific pages will be added as time and motivation permits and information becomes available.

Victron BlueSolar and SmartSolar controllers (1 of 2)

As with all other MPPT controllers, the primary not-to-exceed spec for the Victron MPPT controllers is the input voltage. However, they also list a "Max Isc" spec. Victron has clearly stated in their manuals that if the PV is hooked up in reverse polarity and the Isc is over the limit, it can damage the controller. It turns out that there are other instances that are not documented in the manual, where exceeding the Isc might be damaging to the controller. Consequently, the system designer should never exceed the Isc Specification on a Victron MPPT Controller.

It is still possible to over-panel a Victron MPPT controller, but the Isc specification will limit the amount of over-paneling and in some panel configurations, the Isc limit will prevent over-paneling. (See the following page for an example of using Isc in calculating how to over-panel a Victron MPPT controller)

Note: It is unusual but possible to go over the Victron Isc spec with configurations that are not over-paneled. Consequently, it is important to check the array Isc even when not over-paneling the controller. Furthermore, the Victron online MPPT calculator does not appear to check the Isc of a configuration so this must be checked manually even if the calculator indicates the configuration is good.

Victron BlueSolar and SmartSolar controllers (2 of 2)

This example will use the SmartSolar 150/35 MPPT controller and Renogy 100 Watt 12 Volt Monocrystalline Solar Panels.

SmartSolar 150/35 MPPT spec Renogy 100W 12V Solar Panel Spec
Input Voltage Max 150V Voc 22.3V
Max Output Current 35A Isc 5.86A
Power on 12V system 490W Power 100W
Isc Limit 40A

How would we over panel to 800W (8 Panels) on a 12V system?

× 8 panels in parallel would provide an array voltage of 22.3V, leaving ample room for cold weather. However, the array Isc would be 5.86V x 8 = 46.88V which is over the 40A Isc limit of the controller.

× With 8 panels in series the Voc would be 22.3V x 8 = 178.4V.... Exceeding the input voltage limit of the controller.

With two parallel strings of 4 panels in series, the Array Voc is 4 x 89.2V. This is within the controller spec and leaves ample room for cold weather voltage rise. The array Isc will be 2 x 5.86 = 11.72a, well under the 40A limit of the controller. This configuration will work and is over-paneled by ~63%.

Notice that even 4 strings of 5 panels (2000W total) would not exceed any of the SmartSolar 150/35 controller specifications. (2000W on a 490W controller would be way past the point of diminishing returns, but it would work)

Midnight Solar Classic

The Midnite Solar Classic manual does not directly address over-paneling, but their phone tech support assures me that the Classic will simply current limit the output if the array can produce more power than the Classic can pump into the batteries. As with all controllers the Voc is a critical specification that must not be exceeded.

The Midnight online calculator (shown to the right) will indicate an additional controller is needed if the over-paneling is over 20%. The calculator assumes that over-paneling by 20% will make up for the difference between the rated STC power and actual, real-world production. Above that it recommends an additional controller in order to capture the extra power. However, the recommendation does not imply a damaging condition when using a single controller.

Diagram Description: A screenshot of the Midnite Solar Classic calculator results. It shows PV Array details like Rated PV Array Power (2880 Watts), Anticipated Array Power @ 104F (2755 Watts), Rated PV Array Current (29.55 Amps), and Battery Charging Current @ 28.8 V (100 Amps). It also lists controller specifications like Max Operating Voltage (150V for the Classic 150), Max Non-operating VOC (174V for the Classic 150), Maximum Number Of Modules In Series (3 for the Classic 150), and Max Allowable Output Current Per Classic (91A for the Classic 150). A design check section shows 'OK' for Max VOC, but 'EXCESSIVE' for Array Power (Wattage) when considering a 2880W array with a 150V controller. It indicates 1.2 Classics are required for this configuration. A note states that the minimum initial PV input voltage should be at least 30% higher than the highest expected battery voltage.

EPever Tracer & DuoRacer controllers

The image to the left is from the EPever Tracer manual. As can be seen, the Tracer has a simple limit of a 50% over-paneling.

The EPever DuoRacer controller has the same 50% over-paneling limit and a corresponding chart in it's manual.

Diagram Description: A table listing EPever Tracer models (Tracer1206AN, Tracer2206AN, Tracer1210AN, Tracer2210AN, Tracer3210AN, Tracer4210AN) with their Rated charge current, Rated charge power, Max. PV power, and Max. PV open circuit voltage. The table specifies that for the Tracer series, the maximum PV array power should not be higher than 1.5 times the rated charging power of the controller. It also warns that exceeding the PV array's maximum open-circuit voltage can damage the controller.

Sol-Ark 8K and 12K

The image to the left is from the SolArk 12K manual. This implies the SolArk is limited to 8.3% over-paneling.

The SolArk 8K has a similar spec sheet and indicates a max over-panel of 37.5%.

The low limits on the 12K and 8K are surprising for a known brand like Sol-Arc, but their Tech support has confirmed the limitation.

Solar Input Power 12000W
Max Allowed PV Power 6500W + 6500W = 13000W
Max PV Power Delivered to Battery & AC Outputs 12000W
Max DC Voltage (Voc) 500V @ 18A, 450V @ 20A
MPPT Voltage Range 150-425V
Starting Voltage 125V
Number of MPPT 2
Max Solar Strings Per MPPT 2
Max DC Current per MPPT (Self Limiting) 20A
Max AC Coupled Input (Micro/String Inverters) 9600W

Sol-Ark 5K

No over-paneling supported

The image to the left is from the SolArk 5K manual. The 3250W per controller is a hard limit.

This is surprising for a known brand like Sol-Arc, but their Tech support has confirmed the limitation.

Sol-Ark-5K-48-ST Specifications Solar Output Power 6500W
Max allowed PV Power 3250W+3250W = 6,500W
Max PV power delivered to Battery & AC outputs 6500W
Max DC voltage 500V
MPPT voltage range 150-425V
Starting voltage 125V
Number of MPPT 2
Max Solar Strings per MPPT 2
Max DC current per MPPT (self limiting) 10A/10A

Schneider Electric Conext MPPT 100 (or MPPT 80)

The image to the left is from the Schneider Electric Conext manual.

Electrical Specifications MPPT 80 600 MPPT 100 600
Max PV array open circuit voltage 600 V 600 V
MPPT voltage range 195 to 510 VDC 195 to 510 VDC
PV array operating voltage 195 to 550 V 195 to 550 V
Max. array short circuit current at STC 28 A 35 A
Max. input operating current 23 A 29 A
Max. output power 4800 W (nominal 48 V systems) 6000 W (nominal 48 V systems)
Nominal battery voltage 24 and 48 VDC 24 and 48 VDC
Battery voltage operating range 16 to 67 VDC 16 to 67 VDC
Max. output charge current 80 A 100 A
Charger regulation method Three-stage (bulk, absorption, float) plus manual equalization Two-stage (bulk, absorption) plus manual equalization
Supported battery types Flooded, GEL, AGM, Lithium-ion, Custom Flooded, GEL, AGM, Lithium-ion, Custom

It appears the limiting factor for over-paneling these controllers is the 'Max. array short circuit current at STC'. The over-paneling can be quite high without exceeding the controller specification, but the system designer will find that to keep the array Isc below the limit, the Array Voc will typically be in the higher part of the allowable range. (This is typical for controllers with an Isc limit in the specifications)

Growatt SPF 3000 TL

The image below is from the Growatt SPF300TL data sheet. Growatt tech support says the Max PV Array Power is a hard limit, so these controllers can not be over-paneled.

Datasheet SPF 3000TL HVM-24 SPF 3000TL HVM-48 SPF 5000TL HVM/HVM-P
SOLAR CHARGER
Maximum PV Array Power 1500W 1800W 4500W
MPPT Range @ Operating Voltage 30VDC~80VDC 60VDC~115VDC 60VDC~115VDC
Maximum PV Array Open Circuit Voltage 102VDC 145VDC 145VDC
Maximum Solar Charge Current 50A 30A 80A
Maximum Efficiency 98% 98% 98%
Models: MPPT Solar Charge Controller, MPPT, Solar Charge Controller, Charge Controller, Controller

File Info : application/pdf, 17 Pages, 924.38KB

PDF preview unavailable. Download the PDF instead.

Over-paneling

References

Microsoft PowerPoint for Microsoft 365

Related Documents

Preview Victron Energy BlueSolar MPPT 150/35 & 150/45 Solar Charger Manual
Comprehensive user manual for Victron Energy BlueSolar MPPT 150/35 and 150/45 solar charge controllers, covering installation, features, operation, troubleshooting, and technical specifications.
Preview Victron Energy SmartSolar MPPT Charge Controllers Manual
User manual for Victron Energy SmartSolar MPPT charge controllers (models 75/10, 75/15, 100/15, 100/20, 100/20-48V). Covers features like Bluetooth Smart, VE.Direct, MPPT tracking, load output, battery management, installation, safety, and troubleshooting.
Preview Victron Energy BlueSolar MPPT 150/35 Charge Controller Datasheet
Technical specifications and features of the Victron Energy BlueSolar MPPT 150/35 charge controller, including MPPT technology, flexible charging, and electronic protections.
Preview Victron Energy BlueSolar MPPT Charge Controllers 75/10, 75/15, 100/15, 100/20-48V Technical Specifications
Detailed technical specifications and features of Victron Energy BlueSolar MPPT solar charge controllers, including models 75/10, 75/15, 100/15, and 100/20-48V. Covers MPPT technology, charge output, BatteryLife management, and performance data.
Preview Victron Energy SmartSolar MPPT Solar Charger Manual
Comprehensive manual for Victron Energy SmartSolar MPPT solar chargers (models 150/60, 150/70, 250/60, 250/70). Covers installation, operation, configuration, monitoring, and troubleshooting for efficient solar energy management.
Preview Victron Energy BlueSolar MPPT 100/30 & 100/50 Solar Charge Controller Manual
Comprehensive manual for Victron Energy BlueSolar MPPT solar charge controllers, models 100/30 and 100/50. Learn about installation, features, operation, troubleshooting, and technical specifications for efficient solar energy management.
Preview Victron Energy SmartSolar MPPT Solar Charger Manual
Comprehensive manual for Victron Energy SmartSolar MPPT solar charge controllers (150/60, 150/70, 250/60, 250/70). Covers safety, installation, configuration, operation, monitoring, and troubleshooting for efficient solar energy management.
Preview Victron Energy BlueSolar PWM-DUO 12/24V 20A Charge Controller Specifications
Detailed specifications, features, and system overview for the Victron Energy BlueSolar PWM-DUO 12/24V 20A solar charge controller, designed for dual battery bank management in solar power systems.