Phoenix Phase Converters

GP40NL

Installation Guide and Support Manual

Precision Balanced

Electrical Specifications Sheet

General Specifications

HP40
KW29.8
KVA43.37
HZ50/60
ENCLTEFC/NEMA 4
FRAME326T
IDLER WEIGHT539.1
PANEL WEIGHT51

Single Phase Electrical Specs

VOLTAGE INPUT208-250V
MOTOR LOAD BREAKER Minimum Size80
MOTOR LOAD BREAKER Maximum Size200
SERVICE KVA Minimum Size50
SERVICE AMPS Minimum Size200
COPPER WIRE Minimum Size1/0

Construction, Dimensions, Weight

ELECTRICAL PANEL ENCLOSURE TYPENEMA 4
ENCLOSURE CERTIFICATIONSUL 508A (CSA C22.2 No. 14-13.), TUV, CE.
COLORLight Gray
HEIGHT20
WIDTH12
DEPT10
MOUNTINGWALL MOUNT

Three Phase Electrical Specs

VOLTAGE OUTPUT208-230 Volts Delta
MAX OUTPUT INDUCTIVE LOAD AMPS104
MAX OUTPUT RESISTIVE LOAD AMPS56
VOLTAGE BALANCING+/-2%
WIRE SIZE MIN Idler/Generator3
LARGEST SPINDLE MOTOR START20
LARGEST COMPRESSOR LOAD START16
TOTAL COMBINED HORSEPOWER RUN40

Optional Features

  • 208, 460 Volt Output (includes transformer)
  • AutoStart and AutoOff with load detection
  • PL Model (includes Start and Stop with Built-in Mag Starter)
  • GPX Model (includes WFI Cloud Controls, Timers, Energy Monitor)
  • Wireless Remote ON/OFF

PHOENIX PHASE CONVERTERS 800-417-6568

Read First - Before Installation

Important Safety and Installation Notes

  • Most important step to know.
  • NEVER start the phase converter with a load, this includes transformers.
  • Verify incoming service KVA size with your electric company; it should be larger than the idler motor's HP.
  • DO NOT use WIRE NUTS for any connection; use bolt-down lugs.
  • Ensure all connections, including factory connections to the power block, are secure. Recheck connections after a few weeks of use.
  • If the idler does NOT reach FULL SPEED upon powering up, shut down the phase converter immediately. If unsure, contact Phoenix Phase Converters or a qualified electrician. Failure to shut down may damage the idler motor, voiding the warranty.
  • Must be installed by a licensed industrial electrician. These guidelines do not supersede local and state laws.

Power Requirements

Breaker and Wire Sizing

  • Use a motor load type breaker, not a quick-blow or trip breaker.
  • For single-machine operation with inductive loads (motors), double the machine's amp size for the breaker. Example: 20 amps load requires a 40 amp breaker.
  • For multiple machines, double the amp size of the largest machine and add the amp requirements of other machines running simultaneously. Example: 20 AMP Lathe, 9 amp saw, 6 amp milling machine. Calculation: (20 * 2) + 9 + 6 = 45 amps. Use the next standard size breaker, which would be a 50 Amp two-pole breaker.
  • Refer to the chart for minimum and maximum allowed wire and breaker sizes. For rural areas, increase the minimum breaker size by 20%.

Wire and Breaker Sizes Table

SINGLE PHASE1/0 under 50 feet
IDLER MOTOR3 AWG COPPER
BREAKER/FUSE60 MIN/200MAX

Mounting the Phase Converter Panel

Installation Procedure

Mount the enclosure first to a non-vibrating surface. Two mounting options are provided. Install the back plate with the four provided nuts. Mounting the phase converter panel near the breaker panel is recommended. Keep the single-phase line wire as short as possible. Increase wire size for every 50 feet of run.

Illustration showing additional mounting brackets and hardware included inside the enclosure.
Illustration of an IP65 waterproof and weatherproof enclosure suitable for indoor or outdoor use.
Illustration showing a person installing the phase converter panel, connecting wires.

Connecting the Idler Motor Wires

This is an illustration of wire connections. DO NOT USE WIRE NUTS; USE BOLT DOWN LUGS.

For Motors with 9 Leads

Illustration showing wire connections for an idler motor with 9 leads. L1, L2, L3 connections are shown.

For Motors with 12 Leads

Illustration showing wire connections for an idler motor with 12 leads. L1, L2, L3 connections are shown.

NL and NH Models Wiring Diagram

Must be installed by an industrial licensed electrician.

Schematic diagram illustrating the connection of a single-phase circuit breaker panel, a phase converter panel, and an idler/generator motor for NL and NH models. It indicates that a disconnect should be used if the run is over 50 feet. It also specifies 230V connection for NL and PL Models (low voltage) and 460V connection for NH and PH Models (high voltage).

Idler Motor Dimensions

Dimensional drawings of the idler motor, showing front, side, and top views with various measurements indicated. Includes a terminal box detail. The nameplate area is also shown. Weight: 40 HP = 539.1 lbs.

GP40NL Dimensions

Dimensional drawings of the GP40NL unit, showing front, side, and top views with measurements. Includes a view of the internal components mounted on a plate.

40 HP Rotary Phase Converter Components

Component List

Item NumberDescriptionQuantityPriceSKU#
1Relay147.00GP90-66
32 Pole Contactor128.00GP2P30A
4OPTIONAL 3 Pole Contactor 60 amp - 230V152.84C360C
59 Bank Start and Run Capacitor Holder Only with Base1239.00CB409HO
63 Phase Power Block145.00RS2540
7630 MFD 220V Start Capacitor324.14PTMJ630
*100 MFD 370V Run Capacitor126.00TRC100
*Complete Capacitor Bank Assembly - Prewired1390.00CP309
*Complete Back Plate Assembly - Prewird PL Model (with Start and Stop Button)11574.50CBA25PL
*Complete Panel with NEMA 4 Enclosure Prewird PL Model (with Start and Stop Button)11748.50GP24PLPO
*Idler Motor11764.00
*Complete Unit Phase Converter Panel (PL Model) and Idler/Generator Motor13497.00GP25PL
Illustrations of the idler motor with dimensions and weight, similar to those on page 8.
Models: GP40NL, GP40NL 40 HP Rotary Phase Converter, 40 HP Rotary Phase Converter, Rotary Phase Converter, Phase Converter, Converter

File Info : application/pdf, 10 Pages, 6.16MB

PDF preview unavailable. Download the PDF instead.

GP40NL ?v=1706948581

References

GPL Ghostscript 10.00.0 Keynote

Related Documents

Preview Phoenix GP25NL Phase Converter Installation and Support Manual
Comprehensive installation guide and support manual for the Phoenix GP25NL Rotary Phase Converter, detailing specifications, power requirements, mounting, wiring, and components.
Preview GP30NL 30 HP Rotary Phase Converter Installation and Operation Guide
Comprehensive guide for installing and operating the GP30NL 30 HP Rotary Phase Converter from Phoenix Phase Converters, including critical pre-installation notes, power requirements, wiring instructions, and component details.
Preview GP60PL Rotary Phase Converter Installation and Operation Guide
Comprehensive guide for installing and operating the Phoenix Phase Converters GP60PL 60 HP Rotary Phase Converter, including wiring, breaker sizing, and component details.
Preview GP50PL 50 HP Rotary Phase Converter Installation and Operation Manual
Comprehensive guide for the Phoenix Phase Converters GP50PL 50 HP Rotary Phase Converter, covering installation, power requirements, wiring, dimensions, and component details for single-phase to three-phase power conversion.
Preview GP50PL 50 HP Rotary Phase Converter: Installation and Specifications
Comprehensive guide to the GP50PL 50 HP Rotary Phase Converter by Phoenix Phase Converters, covering installation, power requirements, wiring, and component details for converting single-phase to three-phase power.
Preview GP10NL Rotary Phase Converter Installation and Operation Guide
Comprehensive guide for installing and operating the GP10NL Rotary Phase Converter, including power requirements, wiring instructions, and component details from Phoenix Phase Converters.
Preview Phoenix GP10PL Rotary Phase Converter Installation Guide and Support Manual
Comprehensive installation guide and support manual for the Phoenix GP10PL Rotary Phase Converter, detailing electrical specifications, power requirements, mounting, wiring, and component information.
Preview GP40NL Rotary Phase Converter Installation Guide and Specifications
Comprehensive guide for installing and operating the Phoenix Phase Converters GP40NL 40 HP Rotary Phase Converter, covering power requirements, wiring, and component details.