Clipsal Iconic Series Push-button Electronic Switches, Timers, and Timeclocks
Installation Instructions
Product Overview
The Clipsal Iconic range offers modular electronic switches, dimmers, timers, and timeclocks with advanced remote load control technology and multi-way switching/dimming capabilities. The range also includes USB charging mechanisms and complementary wall plates and parts packs in various finishes.
Key Features
Push-button Electronic Switch
- Integrally switched push-button (tactile) control
- Suitable for multi-way switching
- ControlLink enabled for remote control
- Bluetooth Low Energy (BLE) support for configuration and control with the Wiser Room App (6 A unit only)
- In-built over-current, over-voltage, short-circuit and thermal fuse protection (2-wire 350 W unit only)
- Over-temperature protection
- LED indicator
- Suitable for a wide range of load types, including dimmable and non-dimmable LEDs
- Multi-gang capacity up to 6 mechanisms per plate (for 2-wire 350 W and 6 A units)
- Easy wiring using on-board integral terminals with unique combination Square Drive / Phillips Drive terminal screws (2-wire 350 W unit only)
- Wide range of plate and button colour variants available
- Complies with Australian and New Zealand electrical safety and EMC Standards.
Push-button Timer
- All features of the Push-button Electronic Switch
- Timer mode with configurable Timer function
- Bluetooth Low Energy (BLE) support for configuration and control with the Wiser Room App (6 A / 10 A units only)
- Can be configured as a fan run-on timer (6 A / 10 A units only)
- Includes a Bell Press mode.
Timeclock
- All features of the Push-button Electronic Switch and Timer
- Up to 16 configurable time schedules
- Support for days of the week (weekdays and weekends) and months of the year
- Sunrise and sunset support with automatic adjustment for geolocation.
Safety Information
DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Only licensed electrical contractors or authorized persons should work on fixed wiring.
- Use the product only as described in this instruction and in accordance with wiring rules and regulations.
- No user-serviceable parts inside.
- Failure to follow these instructions will result in death or serious injury.
DANGER: RISK OF ELECTRIC SHOCK
- Hazardous voltage may be present at wire leads and outputs even when the device is switched off.
- Lock out and tag the input circuit before accessing wiring connections.
- Failure to follow these instructions will result in death or serious injury.
WARNING: RISK OF USE IN SAFETY- AND LIFE-CRITICAL APPLICATIONS
- This product is intended for general lighting and small motor applications (e.g., exhaust fans).
- Schneider Electric does not warrant or endorse this product for use in applications critical to health or life.
- Failure to follow these instructions can result in death or serious injury.
CAUTION: EQUIPMENT DAMAGE HAZARD
- Install the device according to instructions.
- Pay attention to specifications and wiring diagrams.
- Do not use the product for purposes other than specified.
- Failure to follow these instructions can result in minor injuries or equipment damage.
Unit Operation
Push-button Electronic Switch
- Switch: Press the push-button to switch the load On or Off.
- Configuration Mode: If the push-button is pressed for more than 15 seconds, the load switches Off and the unit enters Configuration Mode.
Push-button Timer/Timeclock
- Switch Mode (configurable): Press the push-button to switch the load On or Off.
- Timer Mode (default): Press the push-button to switch the load On and start the timer. The load switches Off when the timer expires. Pressing the push-button while the timer is operating switches the load Off and resets the timer.
- Run-on Timer Mode: Short press the push-button to delay the load's Off state based on the set time. This can be triggered by a light switch via ControlLink or used as a stand-alone timer. A short press during countdown cancels the load and turns the fan Off.
- Bell-press Mode: The load is switched On while the push-button is pressed and switches Off when released.
- Configuration Mode: If the push-button is pressed for more than 15 seconds, the load switches Off and the unit enters Configuration Mode.
Configuration Mode
Setting Configuration Mode
- Press and hold the push-button for at least 15 seconds.
- The LED indicator will flash once every second, indicating entry into Configuration Mode with Preset 1 selected.
Selecting a Configuration Preset
- Short press the push-button to cycle through Configuration Presets.
- Observe the number of LED indicator flashes (followed by a pause) to determine the selected Preset.
Configuration Presets for Push-button Electronic Switch
Preset | Setting |
---|---|
1 | Indicator settings (ON state: 100 %; OFF state: 10 %) |
2 | Indicator settings (ON state: 100 %; OFF state: 0 %) |
3 | Indicator settings (ON state: 0 %; OFF state: 0%) |
4 | Factory Reset (BLE-capable units only) |
Configuration Presets for Push-button Timer/Timeclock (Switch Mode)
Preset | Setting |
---|---|
1 | Indicator settings (ON state: 100 %; OFF state: 10 %) |
2 | Indicator settings (ON state: 100 %; OFF state: 0 %) |
3 | Indicator settings (ON state: 0 %; OFF state: 0%) |
4 | Return unit to Timer Mode |
5 | Factory Reset (BLE-capable units only) |
Configuration Presets for Push-button Timer/Timeclock (Timer Mode)
Preset | Setting |
---|---|
1 | Place unit in Switch Mode (infinite delay time) |
2 | Run-on timer (output remains On for 5 minutes after push-button is pressed from On state or Active is removed from ControlLink terminal) |
3 | Set timer delay to 30 seconds |
4 | Set timer delay to 1 minute |
5 | Set timer delay to 5 minutes |
6 | Set timer delay to 15 minutes |
7 | Set timer delay to 30 minutes |
8 | Set timer delay to 1 hour |
9 | Set timer delay to 2 hours |
10 | Set timer delay to 4 hours |
11 | Bell Press mode (output remains On while push-button is pressed or Active is applied to the ControlLink terminal) |
12 | Factory Reset (BLE-capable units only) |
Exit Configuration Mode
If the push-button is pressed for more than 15 seconds whilst in Configuration Mode, the currently selected preset is stored and the device exits Configuration Mode. If more than 30 seconds elapse without the push-button being pressed, the device exits Configuration Mode without storing any changes. Configuration settings are stored in nonvolatile memory.
Overload Protection Facilities
The Iconic range incorporates sophisticated protection mechanisms to reduce the risk of damage during abnormal operating conditions.
Over-temperature Protection
All Iconic Push-button Switches, Timers, and Timeclocks have Over-temperature Protection that switches the load Off if the unit is exposed to over-temperature conditions. The protection resets automatically once conditions are corrected.
Thermal Fuse, Over-current and Short Circuit Protection
Iconic 2-wire 350 W Switches and Timers include:
- Thermal Fuse: A non-resettable thermal fuse designed to blow in case of catastrophic failure, acting as a backup for persistent overload conditions. If the fuse blows, the unit is permanently inoperable and must be replaced.
- Over-current and Short Circuit Protection: These capabilities protect the unit under abnormal operating conditions, such as wiring faults or catastrophic load failure. Short circuit protection resets automatically once the condition is removed.
Load Compatibility
Important Notices for Iconic Push-button Electronic Switch, Timer & Timeclock
NOTICE: EQUIPMENT DAMAGE HAZARD (LOAD AND OPERATION)
- Operating units at elevated temperatures or voltages outside specification may cause over-temperature protection to operate.
- Operating 2-wire units with significant overload may cause the thermal fuse to blow, rendering the unit inoperable. Reduce connected load or use a different lamp brand.
- Do not operate the product for prolonged periods in extreme conditions.
- Failure to follow these instructions can result in equipment damage.
NOTICE: RISK OF ABNORMAL OPERATION OR REDUCED PERFORMANCE
- Do not connect mixed load types to 2-wire 350 W units. Use 3-wire 6 A units for mixed loads.
- The 2-wire 350 W Push-button Electronic Switch has a 10 W minimum load. For loads sensitive to low leakage currents, fit a 31LCDA Load Correction Device.
- Use 3-wire 6 A or 10 A units for small motor loads (e.g., exhaust fans).
- For 2-wire electronic switches and timers, use only iron-core transformers recommended by the manufacturer.
- Failure to follow these instructions can result in abnormal equipment operation or reduced performance.
Load Compatibility Table
Push-button Electronic Switch
Load Symbol | Compatible Loads | 2-wire Switch | 6 A Switch |
---|---|---|---|
? | LED Lighting | 350 W (Dimmable) 250 W (Non-Dim.) |
6 A |
☀️ | Incandescent Lighting MV Halogen / Dichroic Lamps | 350 W | 6 A |
?? | Low voltage halogen / dichroic lighting with electronic transformers | 350 W | 6 A |
?? | Low voltage halogen / dichroic lighting with iron-core transformers | 350 W | 6 A |
〰️? | Linear Fluorescent Lamps | 250 W | 6 A |
〰️? | Compact Fluorescent Lamps | 250 W | 6 A |
〰️⚡ | Inductive Loads | Not Compatible | 6 A @ 0.8 Power Factor |
⚡ | Contactors | Not Compatible | 6 A |
〰️ | Purely Resistive Loads | 350 W | 6 A |
Push-button Timer
Load Symbol | Compatible Loads | 2-wire Timer | 6 A Timer | 10 A Timer |
---|---|---|---|---|
? | LED Lighting | 350 W (Dimmable) 250 W (Non-Dim.) |
6 A | 10 A |
☀️ | Incandescent Lighting MV Halogen / Dichroic Lamps | 350 W | 6 A | 10 A |
?? | Low voltage halogen / dichroic lighting with electronic transformers | 350 W | 6 A | 10 A |
?? | Low voltage halogen / dichroic lighting with iron-core transformers | 350 W | 6 A | 10 A |
〰️? | Linear Fluorescent Lamps | 250 W | 6 A | 10 A |
〰️? | Compact Fluorescent Lamps | 250 W | 6 A | 10 A |
〰️⚡ | Inductive Loads | Not Compatible | 6 A @ 0.8 Power Factor | 10 A @ 0.8 Power Factor |
⚡ | Contactors | Not Compatible | 6 A | 10 A |
〰️ | Purely Resistive Loads | 350 W | 6 A | 15 A |
Timeclock
Load Symbol | Compatible Loads | 6 A Timeclock | 10 A Timeclock |
---|---|---|---|
? | LED Lighting | 6 A | 10 A |
☀️ | Incandescent Lighting MV Halogen / Dichroic Lamps | 6 A | 10 A |
?? | Low voltage halogen / dichroic lighting with electronic transformers | 6 A | 10 A |
?? | Low voltage halogen / dichroic lighting with iron-core transformers | 6 A | 10 A |
〰️? | Linear Fluorescent Lamps | 6 A | 10 A |
〰️? | Compact Fluorescent Lamps | 6 A | 10 A |
〰️⚡ | Inductive Loads | 6 A @ 0.8 Power Factor | 10 A @ 0.8 Power Factor |
⚡ | Contactors | 6 A | 10 A |
〰️ | Purely Resistive Loads | 6 A | 15 A |
Incompatible Loads
Push-button Electronic Switch
The 2-wire 350 W Push-button Electronic Switch is not compatible with motor loads. Use the Push-button Electronic 6 A Switch for small motor loads. Iconic Push-button Electronic Switches do not have dimming capability; use a Dimmer from the Iconic range for dimming applications.
Push-button Timer
The 2-wire 350 W Push-button Timer is not compatible with motor loads. Use the Push-button Electronic 6 A Timer or 10 A Timer for small motor loads. Iconic Push-button Timers do not have dimming capability; use a Dimmer from the Iconic range for dimming applications.
Timeclock
Iconic Timeclocks do not have dimming capability; use a Dimmer from the Iconic range for dimming applications.
Installation Requirements
DANGER: HAZARD OF ELECTRIC SHOCK
- The Locking Bar on Iconic plates must be set to the Closed position to ensure the mechanism cannot be removed during normal operation. Failure to follow these instructions will result in death or serious injury.
DANGER: RISK OF ELECTRIC SHOCK
- Hazardous voltage and electrical current may be present at the wire leads and outputs even when the device is switched off.
- Lock out and tag the input circuit before accessing the wiring connections. Failure to follow these instructions will result in death or serious injury.
9.1 Fitting the Mechanism to the Plate
Follow these steps:
- On the plate, move the locking bar Ⓐ to the Open position. (Note: On multi-gang plates, the locking bar covers all cutouts Ⓑ.)
- Push the head of the mechanism into the plate cutout Ⓒ until it clicks into place.
- Once the mechanism is installed, move the locking bar to the Closed position Ⓓ.
9.2 Preparing and Fitting the Flush Box (when required)
For 10 A mechanisms fitted to certain flush boxes (New Zealand installations), the flush box may need modification to accommodate the mechanism body. If the flush box has a back section, this section may need to be removed to allow the plate and mechanism to be fixed flush to the wall.
9.3 Fitting the Plate
- 2-wire 350 W and 3-wire 6 A Units: Allow a minimum 35 mm depth in the wall box/cavity for mechanisms and wiring.
- 3-wire 10 A Units: Allow a minimum 70 mm depth in the wall box/cavity for mechanisms and wiring.
9.4 Fascia Installation and Removal
Installation:
- Place the upper section of the fascia against the upper section of the plate (A).
- Apply pressure to the bottom section of the fascia (B) so it snaps into the plate.
Removal:
- Insert the flat tip of a plastic tool into one of the slots at the center of the long edges of the fascia (C).
- Gently prise the fascia edge away from the plate until the clips release the fascia (D).
Wiring Diagrams
DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Only licensed electrical contractors or authorized persons should work on fixed wiring.
- Use the product only as described in this instruction and in accordance with wiring rules and regulations.
- No user-serviceable parts inside.
- Failure to follow these instructions will result in death or serious injury.
DANGER: RISK OF ELECTRIC SHOCK
- Hazardous voltage may be present at wire leads and outputs even when the device is switched off.
- Lock out and tag the input circuit before accessing wiring connections. Failure to follow these instructions will result in death or serious injury.
WARNING: RISK OF USE IN SAFETY– AND LIFE-CRITICAL APPLICATIONS
- This product is intended for general lighting and small motor applications (e.g., exhaust fans).
- Schneider Electric does not warrant or endorse this product for use in applications critical to health or life.
- Failure to follow these instructions can result in death or serious injury.
NOTICE: RISK OF EQUIPMENT DAMAGE OR MALFUNCTION (WIRING CONNECTIONS)
- Do not connect multiple Primary Units in parallel; connect Remote Units to the Primary Unit via ControlLink for Multi-Way control.
- Do not connect a Remote Unit to the load.
- Always wire Remote Units to the same circuit and phase as the Primary Unit.
- Test operation during installation and correct any wiring errors immediately.
- Keep cable insulation away from enclosure sides to avoid damage or degradation.
- Failure to follow these instructions can result in equipment damage or malfunction.
10.1 Connection Limitations
ControlLink-enabled devices can connect to a single Primary Unit for remote switching. Maximum total cable length is 30 meters.
10.2 Overview
Terminals:
- A: Active
- B: Load
- C: ControlLink Terminal
- D: Neutral (6 A / 10 A units only)
About the ControlLink Terminal: Connect a standard 1.5 mm² cable between ControlLink terminals of a Push-button Electronic Switch/Timer/Timeclock and other ControlLink-enabled Iconic units for multi-way switching.
10.3 Terminal Blocks for 3-Wire 6 A Units
Use the supplied terminal blocks to connect the mechanism to the circuit. Wrap terminal blocks with insulating tape after wiring.
10.4 Cabling Diagrams: 2-Wire 350 W Units
Diagrams illustrate 1x and 2x Push-button Electronic Switch or Timer (2-wire) configurations with optional ControlLink Push-buttons for two-way and three-way applications.
10.5 Cabling Diagrams: 6 A Units
Diagrams illustrate 1x and 2x Push-button Electronic Switch/Timer/Timeclock (6 A) configurations with optional ControlLink Push-buttons for two-way and three-way applications.
10.6 Cabling Diagrams: 10 A Units
Diagrams illustrate 1x and 2x Push-button Electronic Timer/Timeclock (10 A) configurations with optional ControlLink Push-buttons for two-way and three-way applications.
10.7 Using the Iconic Smart Remote Mechanism
The Iconic Smart Remote Mechanism (41EPBCLM-VW / PDL356PBSSL-VW) is a 3-wire optional ControlLink Push-button. It is compatible with Iconic Push-button Switches, Timers, and Timeclocks and includes a configurable LED indicator. The mechanism requires a Neutral connection.
10.8 Wiring Diagrams: Run-on Timer Application
Diagram shows triggering a fan run-on timer from a separate BLE light switch.
10.9 Multi-Gang Derating
For multi-ganged applications, derate the maximum load rating of each unit according to the table below. Only Primary Units need derating; Multi-Way Remote Units on the same plate can be ignored.
Primary Mechanisms per Plate | Max. Load per Primary Mechanism | ||
---|---|---|---|
(2-Wire Units) | (6 A Units) | (10 A Units) | |
1 | 350 W | 6 A | 10 A |
2 | 250 W | 4.5 A | 7.5 A |
3 | 220 W | 4 A | 6.5 A |
4 | 175 W | 3 A | N/A |
5 | 120 W | 2 A | N/A |
6 | 100 W | 1.5 A | N/A |
Wiser Room App
11.1 About the Wiser Room App
Operate BLE-enabled Iconic devices using the Wiser Room app on a tablet or smartphone. Change modes and set values by downloading and installing the app, and pairing your Iconic devices.
11.2 Download and Install the Wiser Room App
System Requirements:
- Android™: Version 4.4 or higher
- Apple®: iOS 9.1 or higher
- Bluetooth interface: Bluetooth Smart Ready V4.1 or higher
Download the Wiser Room app from the relevant store (QR codes provided for Android, Apple (AUS), and Apple (PDL NZ)). Install the app on your smart device.
11.3 Pair Iconic Device with the App
NOTICE: For pairing, ensure your smart device is within Bluetooth range (max. 10 m). You can connect up to 8 smart devices per Iconic device.
Establish a Bluetooth connection and add devices:
- Activate Bluetooth on your smart device and open the app.
- Tap 'Edit' in the top right corner of the 'My devices' screen.
- Follow the app instructions: Tap 'Add new device'.
- Press the button on your Iconic device 4x. (For Android, the Bluetooth address will be shown for identification.)
- Follow the wizard to set the mode for the Iconic device. NOTICE: If changing the mode after original setup, perform a physical factory reset first (see "Configuration Mode" on page 14).
- Choose a device name and room name.
- Choose an icon for the device.
- Tap 'Done' to add the device to your dashboard.
The app is now paired. Each new Bluetooth connection is established automatically when accessing the Iconic device in the app.
11.4 Restore Point and Password
Create a restore point to save settings. A password is required for creation (Password: 1 2 3 4). This password cannot be changed. Refer to the Wiser Room app Help for more information.
Electrical Specifications
12.1 Electrical Specification Notes
- Specifications are typical @ 240 V AC, 25 °C.
- Suitable for indoor use only.
- No user-serviceable parts inside.
12.2 Electrical Specifications
Parameter | 2-wire 350 W Units | 3-wire 6 A Units | 3-wire 10 A Units |
---|---|---|---|
Nominal Operating Voltage | 220–240 V AC | ||
Nominal Operating Frequency | 50 Hz | ||
Maximum Load Rating | 350 W | 6 A | 10 A |
Switching Technique | Semiconductor | Relay | Relay |
Wiring Configuration: | |||
Incandescent Loads | 350 W | 6 A | 10 A |
MV Halogen Loads | 350 W | 6 A | 10 A |
Electronic LV Lighting Transformers | 350 W | 6 A | 10 A |
Iron Core LV Lighting Transformers (EI and Toroidal Types) | 350 W | 6 A | 10 A |
Linear Fluorescent Ballasts | 250 W | 6 A | 10 A |
Compact Fluorescent Loads | 250 W | 6 A | 10 A |
LED Lighting Drivers | 350 W (Dimmable) 250 W (Non-Dim.) |
6 A | 10 A |
Inductive Loads (e.g. Small Motors such as Ceiling Exhaust Fans) | Not Compatible | 6 A @ 0.8 Power Factor | 10 A @ 0.8 Power Factor |
Purely Resistive Loads | 350 W | 6 A | 15 A |
Voltage / Frequency Stability | YES | NO | NO |
Over-current / Thermal Fuse Protection | YES | YES | YES |
Over-temperature Protection | YES | YES | YES |
Short Circuit Protection | YES | NO | NO |
BLE-enabled | NO | YES | YES |
LED Indicator | YES | YES | YES |
Multi-Way Control | YES | YES | YES |
Parameter | 2-wire 350 W Units | 3-wire 6 A Units | 3-wire 10 A Units |
---|---|---|---|
Multi-Gang Plate Capacity | Max. 6 Primary Mechanisms per Plate, Combinations Allowed, Derating to be applied (refer to section 'Multi-Gang Derating') | Max. 3 Primary Mechanisms per Plate, Combinations Allowed, Derating to be applied (refer to section 'Multi-Gang Derating') | |
Available Plate / Control Styles | Iconic Style, Standard and Architrave Options, Colour Packs for Push-button Caps and Plates: Vivid White (VW), Warm Grey (WY), Cool Grey (CY), Anthracite (AN) | ||
Mounting Centres | 84 mm Australian Pattern Plate | ||
Safety Compliances | AS/NZS 60669.2.1 | ||
EMC Emission Compliance | AS/NZS 60669.2.1 |
Troubleshooting
13.1 Switches and Timers (2-Wire Units)
Problem: The LED load is glowing in the Off state and/or occasionally flickering when on.
Recommended Resolution: Iconic 2-wire Electronic Switches and Timers are designed to work with Clipsal LED loads. If other LED loads are used and the problem occurs, try installing a Clipsal 31LCDA load correction device across the load for improved performance.
13.2 Troubleshooting Notes
- Iconic Push-button Electronic Switches, Timers, and Timeclocks are not suitable for dimming applications; select a Dimmer from the Iconic range for this purpose.
- Ensure to use Iconic 3-wire products on non-dimmable or non-lighting loads (such as small motors).
- Contact Customer Care for further guidance if issues persist.
Warranty
Schneider Electric (Australia) Pty Ltd warrants this product to be free from defects in materials and workmanship for two years from the date of installation. This warranty is in addition to other rights and remedies available by law.
Australia
Australian Consumer Law guarantees apply, including entitlement to replacement or refund for major failures and compensation for other loss or damage. Goods must be of acceptable quality and failures must not be major.
New Zealand
This guarantee is in addition to rights under applicable law. The Consumer Guarantee Act 1993 (NZ) does not apply if the product is purchased for business purposes. The warranty is subject to the product being installed, wired, tested, operated, and used according to instructions and specifications. Alterations or modifications without permission void the warranty. Schneider Electric may repair, replace, or refund defective products. Costs for retrieval, removal, reinstallation, or transport are not covered.
How to make a claim: Provide Schneider Electric with particulars of the defect within 28 days of occurrence. Contact your local Schneider Electric, PDL, or Clipsal supplier with purchase details, load description, connections, and failure circumstances. Returned products must be securely packed and labelled.
Contact Information
Australia
Schneider Electric (Australia) Pty Ltd
33 Port Wakefield Road
Gepps Cross SA 5094
Customer Care Australia: 13 73 28
e: customercare.au@schneider-electric.com
www.schneider-electric.com.au
New Zealand
Schneider Electric (NZ) Ltd
38 Business Parade South, Highbrook,
East Tamaki, Manukau 2013
P.O. Box 259370 Botany, Manukau 2163
Telephone +64 9-829 0490
After hours service hotline: 0800 735 4357 (New Zealand only)
Customer Care: 0800 652 999
e: sales@nz.schneider-electric.com
www.pdl.co.nz/iconic
Schneider Electric reserves the right to change specifications, modify designs, and discontinue items. While every effort is made to ensure accuracy, no warranty is given regarding descriptions, specifications, or other information, and the company is not liable for errors.
© Schneider Electric 2018
This material is copyright under Australian, New Zealand, and international laws. Reproduction without prior written permission is prohibited.
NVE78401-03 January 2019
File Info : application/pdf, 35 Pages, 3.41MB
DocumentDocumentReferences
Adobe PDF Library 15.0Related Documents
![]() |
Clipsal Iconic Series Pushbutton Universal Dimmer Installation Guide Comprehensive installation instructions for the Clipsal Iconic Series Pushbutton Universal Dimmer (2-Wire, ControlLink), model numbers 41E300PBUD2SM-VW and PDL354PBDMUN-VW. Covers features, operation, wiring, load compatibility, troubleshooting, and warranty. |
![]() |
Clipsal Iconic Connected AC Fan Speed Controller (Zigbee/BLE) - Installation and Technical Data Comprehensive guide to the Clipsal Iconic Connected AC Fan Speed Controller, covering installation, safety warnings, product features, technical specifications, and customer support for Zigbee and BLE models. |
![]() |
Iconic Connected Dimmer BLE User Guide User guide for the Clipsal Iconic Connected Dimmer BLE, detailing features, installation, pairing, configuration, and troubleshooting for smart lighting control. |
![]() |
Clipsal 31/2031VETR3 3 Wire Electronic Time Delay Switch Installation Instructions Detailed installation guide for the Clipsal 31/2031VETR3, a 3-wire electronic time delay switch with remote control and override off facilities. It offers adjustable timing from 10 seconds to 15 hours for lighting control and energy savings, with configurable contact and indicator functions. |
![]() |
Clipsal 31/2031VETR Two Wire Electronic Time Delay Switch Installation Instructions Detailed installation instructions for the Clipsal 31/2031VETR Two Wire Electronic Time Delay Switch, covering operation, setting the timer, wiring, and specifications. Learn how to install and configure this energy-saving lighting control solution. |
![]() |
Clipsal TC32V and TC15 Series Timer Range Installation Instructions Installation instructions for the Clipsal TC32V and TC15 Series 'Timer' Range, covering wiring, mounting, and setting/adjusting the clocks for 1-hour, 24-hour, and 7-day timers. |
![]() |
Wiser Water Leakage Sensor User Guide A comprehensive user guide for the Wiser Water Leakage Sensor, detailing its features, installation, operation, and troubleshooting. Learn how to pair, configure, and automate the device for effective water leak detection. |
![]() |
Clipsal 1025-LB Double Switch Power Point - Technical Data Detailed product data sheet for the Clipsal 1025-LB Double Switch Power Point, part of the Solis T Series. Features include living brass finish, horizontal mounting, 230V-240V operation, and 10A rating. |