User Manual for SmartGen models including: DOUT16B-2, DOUT16B-2 Digital Output Module, Digital Output Module, Output Module, Module

USER MANUAL

User Manual V1.1

SmartGen DOUT16B-2 16 channels digital output module,RS485. Digital Output Modules.Technical Parameters: Working Voltage DC8.0V~ DC35.0V continuous power supply Power Consumption


File Info : application/pdf, 13 Pages, 841.56KB

PDF preview unavailable. Download the PDF instead.

DOUT16B2 en-User-Manual
DOUT16B-2 DIGITAL OUTPUT MODULE
USER MANUAL
SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.

Chinese trademark

English trademark
SmartGen -- make your generator smart
SmartGen Technology Co., Ltd. No.28 Jinsuo Road Zhengzhou P. R. China Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas) Fax: +86-371-67992952 Web: http://www.smartgen.com.cn
http://www.smartgen.cn Email: sales@smartgen.cn

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder. Applications for the copyright holder's written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies.

SmartGen Technology reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date

Version

Note

2020-10-16

1.0

Original Release

2020-12-15

1.1

Replaced the panel drawing.

DOUT16B-2 Digital Output Module User Manual

Page 2 of 13

CONTENTS
1 OVERVIEW .....................................................................................................................................4
2 TECHNICAL PARAMETERS ..........................................................................................................4
3 MODULE ADDRESS ......................................................................................................................5
4 TERMINAL DIAGRAM ....................................................................................................................6
5 COMMUNICATION CONFIGURATION AND MODBUS COMMUNICATION PROTOCOL...........8
5.1. RS485 COMMUNICATION PORT........................................................................................8 5.2. INFORMATION FRAME FORMAT EXAMPLE .....................................................................8
5.2.1. FUNCTION CODE 01H .............................................................................................. 8 5.2.2. FUNCTION CODE 03H .............................................................................................. 9 5.2.3. FUNCTION CODE 05H ............................................................................................ 10 5.2.4. FUNCTION CODE 06H .............................................................................................11 5.3. CORRESPONDING ADDRESS TO FUNCTION CODE ....................................................12
6 INSTALLATION .............................................................................................................................13

DOUT16B-2 Digital Output Module User Manual

Page 3 of 13

1 OVERVIEW

DOUT16B-2 Digital Output Module is an expansion module which has 16 auxiliary digital output channels. Expansion module status is transmitted to DOUT16B-2 by main control board via RS485.

2 TECHNICAL PARAMETERS

Items Working Voltage Power Consumption
Aux. relay output port 1-16
Case Dimension Installation Way Working Conditions Storage Conditions Weight

Table 2 Technical Parameters Contents
DC8.0V~ DC35.0V continuous power supply <6W 10A relay for output port 1~4, 7~14. 16A relay for output port 5~6, 15~16. 161.6mm x 89.7mm x 60.7mm 35mm guide-rail installation or screw installation Temperature: (-25~+70) Humidity: (20~93)%RH Temperature: (-30~+80) 0.4kg

DOUT16B-2 Digital Output Module User Manual

Page 4 of 13

3 Module Address
This is a 4-bit in-line DIP switch with 16 coding status, namely 16 module addresses (from 100 to 115). When it is turned to ON, the status is 1. The module address formula is Module Address=1A+2B+4C+8D+100. For example, when ABCD is 0000, the module address is 100. When ABCD is 1000, the module address is 101. When ABCD is 0100, the module address is 102. Similarly, when ABCD is 1111, the module address is 115. The corresponding module addresses

of DIP switch

A

B

0

0

1

0

0

1

1

1

0

0

1

0

0

1

1

1

0

0

1

0

0

1

1

1

0

0

1

0

0

1

1

1

are as follows.

Table 3 Module Addresses

C

D

Module Addresses

0

0

100

0

0

101

0

0

102

0

0

103

1

0

104

1

0

105

1

0

106

1

0

107

0

1

108

0

1

109

0

1

110

0

1

111

1

1

112

1

1

113

1

1

114

1

1

115

DOUT16B-2 Digital Output Module User Manual

Page 5 of 13

4 TERMINAL DIAGRAM

No.
1.
2.
3. 4.
5.
6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19.

Fig.1 DOUT16B-2 Panel Diagram

Table 4 Description of Rear Panel Terminal Connection

Name

Description

Cable Size

Remarks

B-

DC power supply 1.5mm2

DC power supply negative

negative input

input.

B+

DC power supply 1.5mm2

DC power supply positive

positive input

input.

120

RS485

Twisted shielded line is used.

RS485B (-)

communication port

If the terminal needs to match

0.5 mm2 120 resistance, terminal 3

RS485A (+)

and 4 need to be short

circuited.

Volt free relay N/O

Aux. output port 1

1.5 mm2

output

Capacity 250VAC/10A.

Volt free relay N/O

Aux. output port 2

1.5mm2

output

Capacity 250VAC/10A.

Volt free relay N/O

Aux. output port 3

1.5mm2

output

Volt free relay N/O

Aux. output port 4

1.5mm2

output

Capacity 250VAC/10A.

N/C

Aux. output port 5 N/O

2.5mm2 Capacity 250VAC/16A.

Common

N/C

Aux. output port 6 N/O

2.5mm2 Capacity 250VAC/16A.

Common

DOUT16B-2 Digital Output Module User Manual

Page 6 of 13

No. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41.
POWER
Module Address

Name

Description

Cable Size

Volt free relay N/O

Aux. output port 7

1.5mm2

output

Volt free relay N/O

Aux. output port 8

1.5mm2

output

Volt free relay N/O

Aux. output port 9

1.5mm2

output

Volt free relay N/O

Aux. output port 10

1.5mm2

output

Volt free relay N/O

Aux. output port 11

1.5mm2

output

Volt free relay N/O

Aux. output port 12

1.5mm2

output

Volt free relay N/O

Aux. output port 13

1.5mm2

output

Volt free relay N/O

Aux. output port 14

1.5mm2

output

Common

Aux. output port 15 N/O

2.5mm2

N/C

Common

Aux. output port 16 N/O

2.5mm2

N/C

Power indicator

Module address

Remarks Capacity 250VAC/10A. Capacity 250VAC/10A. Capacity 250VAC/10A. Capacity 250VAC/10A. Capacity 250VAC/10A. Capacity 250VAC/10A. Capacity 250VAC/10A. Capacity 250VAC/10A.
Capacity 250VAC/16A.
Capacity 250VAC/16A. Light when power supply is normal, distinguish when abnormal. Select module address by DIP switch.

DOUT16B-2 Digital Output Module User Manual

Page 7 of 13

5 COMMUNICATION CONFIGURATION AND MODBUS COMMUNICATION PROTOCOL

5.1. RS485 COMMUNICATION PORT

DOUT16B-2 is an expansion output module with RS485 communication port, which follows

Modbus-RTU communication protocol.

Communication Parameters

Module Address 100(range 100-115)

Baud Rate

9600bps

Data Bit

8-bit

Parity Bit

None

Stop Bit

2-bit

5.2. INFORMATION FRAME FORMAT EXAMPLE

5.2.1. FUNCTION CODE 01H

Slave address is 64H (decimal 100), read 10H (decimal 16 ) status of starting address 64H (decimal 100).
Table 5 Function Code 01H Master Request Example

Request

Bytes

Example (Hex)

Slave address

1

64 Send to slave 100

Function code

1

01 Read status

Starting address

2

00 Starting address is 100

64

Count number

2

00 Read 16 status

10

CRC code

75 CRC code which calculated by master 2
EC

Table 6 Function Code 01H Slave Response Example

Response

Bytes

Example (Hex)

Slave address

1

64 Respond slave address 100

Function code

1

01 Read status

Read count

1

02 16 status (total 2 bytes)

Data 1

1

01 The content of address 07-00

Data 2

1

00 The content of address 0F-08

CRC code

2

F4 CRC code which calculated by slave.

64

The value of status 07-00 is indicated as 01H in Hex, and 00000001 in binary. Status 07 is the

high-order byte, 00 is the low-order byte. The state of status 07-00 is

OFF-OFF-OFF-OFF-OFF-OFF-OFF-ON.

DOUT16B-2 Digital Output Module User Manual

Page 8 of 13

5.2.2. FUNCTION CODE 03H

Slave address is 64H (decimal 100), starting address is 1 data of 64H (decimal 100)(2 bytes per data).
Table 7 Example Data Address

Address

Data(Hex)

64H

1

Table 8 Function Code 03H Master Request Example

Request

Bytes

Example (Hex)

Slave address

1

64 Send to the slave 64H

Function code

1

03 Read point register

Starting address

2

00 Starting address is 64H

64

Count Number

2

00 Read 1 data (total 2 bytes)

01

CRC code

CC CRC code which calculated by master. 2
20

Table 9 Function Code 03H Slave Response Example

Response

Bytes

Example (Hex)

Slave address

1

64 Respond to the slave 64H

Function code

1

03 Read point register

Read count

1

02 1 data (total 2 bytes)

Data 1 CRC code

2

00 The content of address 0064H

01

2

35 CRC code which calculated by slave.

8C

DOUT16B-2 Digital Output Module User Manual

Page 9 of 13

5.2.3. FUNCTION CODE 05H

Slave address is 64H (decimal 100), starting address is one status of 64H (decimal 100). Set 64H unit as 1.
Table 10 Example Status Data Address

Address

Data(Hex)

64H

1

Illustration: Hex value FF00 forced status is 1. 0000H is forced as 0. Other values are illegal and

do not affect the status.

Table 11 Function Code 05H Master Request Example

Request

Bytes

Example (Hex)

Slave address

1

64 Send to the slave 64H

Function code

1

05 Forced status

Starting address

2

00 Starting address is 0064H

64

Data

2

FF Set status as 1

00

CRC code

C4 CRC code which calculated by master. 2
10

Table 12 Function Code 05H Slave Response Example

Response

Bytes

Example (Hex)

Slave address

1

64 Send to the slave 64H

Function code

1

05 Forced status

Starting address

2

00 Starting address is 0064H

64

Data

2

FF Set status as 1

00

CRC code

C4 CRC code which calculated by master. 2
10

DOUT16B-2 Digital Output Module User Manual

Page 10 of 13

5.2.4. FUNCTION CODE 06H

Slave address is 64H (decimal 100), set one point content of starting address 64H (decimal 100) as 0001H.
Table 13 Function Code 06H Master Request Example

Request

Bytes

Example (Hex)

Slave address

1

64 Send to the slave 64H

Function code

1

06 Write single register

Starting address

2

00 Starting address is 0064H

64

Data

2

00 Set 1 point data (total 2 bytes)

01

CRC code

00 CRC code which calculated by master. 2
20

Table 14 Function Code 06H Slave Response Example

Response

Bytes

Example (Hex)

Slave address

1

64 Send to the slave 64H

Function code

1

06 Write single register

Starting address

2

00 Starting address is 0064H

64

Data

2

00 Set 1 point data (total 2 bytes)

01

CRC code

00 CRC code which calculated by master. 2
20

DOUT16B-2 Digital Output Module User Manual

Page 11 of 13

5.3. CORRESPONDING ADDRESS TO FUNCTION CODE

Address 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115
Address 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115
Address 100

Table 15 Function Code 01H

Item

Description

Output Port 1 Status Output Port 2 Status Output Port 3 Status Output Port 4 Status Output Port 5 Status Output Port 6 Status Output Port 7 Status Output Port 8 Status Output Port 9 Status Output Port 10 Status Output Port 11 Status Output Port 12 Status Output Port 13 Status Output Port 14 Status Output Port 15 Status Output Port 16 Status

1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active 1 for active

Table 16 Function Code 05H

Item

Description

Output Port 1 Status

1 for active

Output Port 2 Status

1 for active

Output Port 3 Status

1 for active

Output Port 4 Status

1 for active

Output Port 5 Status

1 for active

Output Port 6 Status

1 for active

Output Port 7 Status

1 for active

Output Port 8 Status

1 for active

Output Port 9 Status

1 for active

Output Port 10 Status

1 for active

Output Port 11 Status

1 for active

Output Port 12 Status

1 for active

Output Port 13 Status

1 for active

Output Port 14 Status

1 for active

Output Port 15 Status

1 for active

Output Port 16 Status

1 for active

Table 17 Function Code 03H, 06H

Item

Description

Output Port 1-16 Status

Unsigned

2Byte

Bytes

DOUT16B-2 Digital Output Module User Manual

Page 12 of 13

6 INSTALLATION

Unit: mm

Fig.2 Case Dimensions _________________________________

DOUT16B-2 Digital Output Module User Manual

Page 13 of 13



References

Microsoft Word 2016 Microsoft Word 2016