Unit Dimensions
The unit is a split system cooling unit. Diagrams illustrate the external dimensions labeled A through F, and the hanging bracket placement.
Diagram Description:
- The main unit is shown from the front, side, and top.
- Dimensions A, B, C represent the body dimensions.
- Dimensions D, E, F represent the installation dimensions.
- Hanging brackets are shown for mounting.
Model | Body dimension (mm) | Installation dimension (mm) | ||||
---|---|---|---|---|---|---|
A | B | C | D | E | F | |
CC-FPA012-1S | 1050 | 675 | 235 | 933 | 440 | 188 |
CC-FPA016-1S | 1050 | 675 | 235 | 933 | 440 | 188 |
CC-FPA020-1S | 1050 | 675 | 235 | 933 | 440 | 188 |
CC-FPA024-1S | 1300 | 675 | 235 | 1185 | 440 | 188 |
CC-FPA028-1S | 1300 | 675 | 235 | 1185 | 440 | 188 |
CC-FPA030-1S | 1670 | 675 | 235 | 1553 | 440 | 188 |
CC-FPA036-1S | 1670 | 675 | 235 | 1553 | 440 | 188 |
CC-FPA048-1S | 1670 | 675 | 235 | 1553 | 440 | 188 |
CC-FPA060-1S | 1670 | 675 | 235 | 1553 | 440 | 188 |
Specifications: CC-FPA060-1S
Comfortstar Model | CC-FPA060-1S | |
---|---|---|
Power supply | 220-240V/1N/50Hz | |
Capacity | Cooling | 16 kW |
Heating | 17 kW | |
Power Input | 0.1 kW | |
Fan motor | Model | 2*DR-310-75LD-8 |
Type | DC | |
Brand | LIFENG | |
Capacitor | - | |
Speed (Rated) | 1180/1030/850 r/min | |
Indoor coil | Number of rows | 4 |
Fin type | Hydrophilic aluminum | |
Tube diameter and type | Ø7, Innergroove tube | |
Air flow (max.) | 1900 m³/h | |
Sound pressure level | 45~54 dB(A) | |
Body | Dimension (W×H×D) | 1670×675×235 mm |
Packing (W×H×D) | 1750×765×325 mm | |
Net/Gross weight | 43.5/49.5 kg | |
Refrigerant type | R410A | |
Throttle type | EXV | |
Design pressure | 4.5/1.6 MPa | |
Liquid pipe / Gas pipe | Ø9.53/Ø15.9 mm | |
Connecting wire | Power wire | 2.5*2+2.5(L≤20m) mm² |
Signal wire | 4*2+2.5(20m | |
Drainage water pipe (Outer diameter) | 0.75*2 shield DN25 mm | |
Controller | Standard | Remote controller |
Optional | Wired controller | |
Operation temp | 16~32 °C |
Company Information & Certifications
Address: 12201 NW 107th Avenue, Miami, FL 33178
Toll Free: 1.866.524.9898
Office: 305.500.9898
Fax: 305.500.9896
Website: http://www.comfortstarusa.com
Certifications:
- AHRI CERTIFIED®: Unitary Small AC, AHRI Standard 210/240. Certification applies only when the complete system is listed with AHRI. Visit ahridirectory.org for verification of individual certified products.
- cULus LISTED
Comfortstar reserves the right to change design and specs without notice. Comfortstar has a policy of updating data continuously. We are committed to using environmentally conscious print practices.
Document Version: CC-FPA060-1S, 14th April 2023 (Supersedes CC-FPA060-1S Apr.2023)