System description
The image displays a cross-section of Uponor Ecoflex pipes. It shows a corrugated outer jacket (labeled 'A') made of PE-HD with a ring stiffness SN4 (4 kN/m²) according to EN ISO 9969. Inside this jacket is an insulation layer (labeled 'B') made of closed-cell, cross-linked polyethylene foam with a thermal conductivity of approximately 0.041 W/mK. A Vacuum Insulation Panel (VIP) (labeled 'C') with a thermal conductivity of approximately 0.004 W/mK is also present. The core of the pipe contains medium pipes (labeled 'D') made of cross-linked polyethylene (PE-Xa) based on EN 15875, designed for heating and cooling applications, often with an EVOH layer. In twin versions, a colored centering profile (labeled 'E') is used to separate the pipes. A 'NEW' badge is overlaid on the image.
The Uponor Ecoflex VIP Thermo and VIP Aqua (VIP = Vacuum Insulation Panel) are part of Uponor's Ecoflex range of flexible, pre-insulated piping. The flexibility of the material, the convenient connecting methods and the well-attested service life contribute to projects being completed quickly, economically and reliably. Features like the corrugated jacket and the layer of cross-linked PE foam together with the VIP insulation material provide an optimal solution for energy efficient distribution networks. The system has a great variety of applications from an extensive supply network to a single connection for one building. Hot water, warm tap water or cooling water are transported as reliably as many other liquid media in industrial settings.
Uponor Ecoflex VIP Thermo and VIP Aqua are designed and manufactured in accordance with the requirements of EN 15632-1 and -3.
Uponor Ecoflex VIP Thermo Single/Twin, PN6 (SDR 11)
Uponor Ecoflex VIP Thermo pipes, produced based on European Standard EN 15632 and EN 17414, are for heating and cooling applications. Single pipes are for projects with large flow requirements. VIP Thermo Twin offers supply and return pipes in one jacket. The pipes have extremely good insulation performance and flexibility.
- Transport of heating and cooling water for buried installations.
- Operating temperature up to 80 °C based on EN 15632.
- Maximum load temperature / pressure: 95 °C / 6 bar.
- Static verification for heavy traffic load of 60 tons.
Diagrams show cross-sections of single and twin pipes with labels indicating outer diameter (do), inner diameter (do1, do2), and wall thickness (s1, s2). For twin pipes, dimensions for both inner pipes are shown.
Uponor Ecoflex VIP Thermo Single, PN6 (SDR 11)
Status | Type | Medium pipe do1 x s1 [mm] | Jacket pipe do [mm] | Bending radius [m] | Weight empty [kg/m] | Volume Medium pipe [l/m] | Coil length [m] | U-Value [W/mK] |
---|---|---|---|---|---|---|---|---|
40/140 | 40 x 3,7 | 140 | 0,35 | 1,67 | 0,83 | 200 | 0,098 | |
50/140 | 50 x 4,6 | 140 | 0,40 | 1,93 | 1,31 | 200 | 0,115 | |
63/140 | 63 x 5,8 | 140 | 0,50 | 2,35 | 2,07 | 200 | 0,138 | |
75/140 | 75 x 6,8 | 140 | 0,60 | 2,73 | 2,96 | 200 | 0,163 | |
NEW | 90/175 | 90 x 8,2 | 175 | 0,70 | 4,11 | 4,25 | 150 | 0,146 |
NEW | 110/175 | 110 x 10,0 | 175 | 0,90 | 5,20 | 6,36 | 150 | 0,179 |
125/200 | 125 x 11,4 | 200 | 1,30 | 6,65 | 8,20 | 120 | 0,215 | |
NEW | 140/200 | 140 x 12,7 | 200 | 1,70 | 8,52 | 10,31 | 95 | 0,253 |
Maximum load temperature / pressure: 95 °C / 6 bar
Operating temperature: 80 °C based on EN 15632
Uponor Ecoflex VIP Thermo Twin, PN6 (SDR 11)
Status | Type | Medium pipe, do1 x s1 [mm] | Medium pipe, do2 x s2 [mm] | Jacket pipe do [mm] | Bending radius [m] | Weight [kg/m] | Volume medium pipe [l/m] | Coil length [m] | U-Value [W/mK] |
---|---|---|---|---|---|---|---|---|---|
2x 25/140 | 25 x 2,3 | 25 x 2,3 | 140 | 0,40 | 1,70 | 2x 0,33 | 200 | 0,122 | |
2x 32/140 | 32 x 2,9 | 32 x 2,9 | 140 | 0,50 | 1,91 | 2x 0,54 | 200 | 0,145 | |
NEW | 2x 40/140 | 40 x 3,7 | 40 x 3,7 | 140 | 0,80 | 2,28 | 2x 0,83 | 200 | 0,152 |
NEW | 2x 50/175 | 50 x 4,6 | 50 x 4,6 | 175 | 0,90 | 3,53 | 2x 1,31 | 200 | 0,150 |
NEW | 2x 63/200 | 63 x 5,8 | 63 x 5,8 | 200 | 1,20 | 4,99 | 2x 2,07 | 100 | 0,169 |
NEW | 2x 75/250 | 75 x 6,8 | 75 x 6,8 | 250 | 1,40 | 6,74 | 2x 2,96 | 100 | 0,212 |
Maximum load temperature / pressure: 95 °C / 6 bar
Operating temperature: 80 °C based on EN 15632
Uponor Ecoflex VIP Aqua Single/Twin, PN10 (SDR 7,4)
Uponor Ecoflex VIP Aqua pipes are a reliable choice for hygienic and energy-efficient distribution of warm tap water in buried installations. VIP Aqua pipes come in two versions: single pipe for large flow capacity or when one supply line is sufficient; twin pipe with supply and circulating pipe in the same jacket. The pipes have extremely good insulation performance and flexibility. Available in long coils or in requested length.
- Transport of warm tap water for buried installations.
- Operating temperature: 70 °C based on EN ISO 15875
- Maximum load temperature / pressure: 95 °C / 10 bar.
- Static verification for heavy traffic load of 60 tons.
Diagrams show cross-sections of single and twin pipes with labels indicating outer diameter (do), inner diameter (do1, do2), and wall thickness (s1, s2). For twin pipes, dimensions for both inner pipes are shown.
Uponor Ecoflex VIP Aqua Single, PN10 (SDR 7,4)
Status | Type | Medium pipe do1 x s1 [mm] | Jacket pipe do [mm] | Bending radius [m] | Weight empty [kg/m] | Volume Medium pipe [l/m] | Coil length [m] | U-Value [W/mK] |
---|---|---|---|---|---|---|---|---|
40/140 | 40 x 5,5 | 140 | 0,40 | 1,84 | 0,66 | 200 | 0,098 | |
50/140 | 50 x 6,9 | 140 | 0,45 | 2,19 | 1,03 | 200 | 0,115 | |
63/140 | 63 x 8,6 | 140 | 0,55 | 2,76 | 1,65 | 200 | 0,137 | |
75/140 | 75 x 10,3 | 140 | 0,70 | 3,33 | 2,32 | 100 | 0,161 | |
NEW | 90/175 | 90 x 12,3 | 175 | 0,80 | 4,99 | 3,36 | 150 | 0,146 |
NEW | 110/175 | 110 x 15,1 | 175 | 1,00 | 6,45 | 5,00 | 150 | 0,179 |
Maximum load temperature / pressure: 95 °C / 10 bar
Operating temperature: 70 °C based on DIN EN 15875
Uponor Ecoflex VIP Aqua Twin PN10 (SDR 7,4)
Type | Medium pipe do1 x s1 [mm] | Medium pipe do2 x s2 [mm] | Jacket pipe do [mm] | Bending radius [m] | Weight empty [kg/m] | Volume Medium pipe [l/m] | Coil length [m] | U-Value [W/mK] |
---|---|---|---|---|---|---|---|---|
25-20/140 | 25 x 3,5 | 20 x 2,8 | 140 | 0,45 | 1,74 | 0,25+0,16 | 200 | 0,118 |
32-20/140 | 32 x 4,4 | 20 x 2,8 | 140 | 0,55 | 1,88 | 0,42+0,16 | 200 | 0,125 |
40-25/140 | 40 x 5,5 | 25 x 3,5 | 140 | 0,70 | 2,18 | 0,66+0,25 | 200 | 0,148 |
50-32/175 | 50 x 6,9 | 32 x 4,4 | 175 | 0,80 | 3,36 | 1,03+0,42 | 200 | 0,158 |
63-40/175 | 63 x 8,6 | 40 x 5,5 | 200 | 0,90 | 4,83 | 1,65 + 0,66 | 100 | 0,171 |
Maximum load temperature / pressure: 95 °C / 10 bar
Operating temperature: 70 °C based on DIN EN 15875
Heat loss tables
The heat loss figures in the following tables have been calculated using CFD (Computational Fluid Dynamics) simulation with the conditions and parameters given in EN 15632-1 and EN 13941-1.
For single pipes the tables show the heat loss of one pipe. To get the total heat loss combine the flow and the return heat losses.
For the Uponor Ecoflex Twin pipes the tables show the heat loss of the complete pipe (flow and return).
Calculation conditions
Pipe installation, Single pipes: 2-Pipe
Pipe distance, Single pipes (A): 0,1 m
Pipe installation, Twin and Quattro pipes: 1-Pipe
Depth of cover (H): 0,8 m
Heat conductivity, soil (λsoil): 1,0 W/mK
Heat conductivity, VIP (λVIP): 0,0042 W/mK
Heat conductivity, PE-x foam (λfoam): 0,0410 W/mK
Heat conductivity, PE-x pipe: 0,4000 W/mK
Heat conductivity, PE jacket pipe: 0,4000 W/mK
Heat loss calculation symbols
- q = Heat loss [W/m]
- U = Heat loss coefficient [W/mK]
- Δθ = Temperature difference between average operating temperature and ground [K]
- θav = Average operating temperature [°C]
- θf = Flow pipe temperature [°C]
- θr = Return pipe temperature [°C]
- θg = Ground temperature [°C]
Heat loss calculation
q = U · Δθ [W/m], where
Δθ = θav - θg [K]
θav = ½ · (θf + θr) [°C]
For Uponor Ecoflex Quattro pipes θav is calculated as average of all four service pipes for heating and warm tap water.
Example heat loss table reading
Flow temperature: θf = 80 °C
Return temperature: θr = 60 °C
Ground temperature: θg = 10 °C
θav = ½ · (80 °C + 60 °C) = 70 °C
Δθ = θav - θg = 70 °C - 10 °C = 60 K
2 pipe installation - example Uponor Ecoflex VIP Thermo Single 63/140
Heat loss for one pipe: q = 8,3 W/m (from the table)
Heat loss for flow and return: q = 2 x 8,3 W/m = 16,6 W/m
Twin pipe installation - example Uponor Ecoflex VIP Thermo Twin 63/200
Heat loss for flow and return: q = 10,14 W/m (from the table)
Ecoflex VIP Thermo Single PN 6
Type | Heat loss q [W/m] for corresponding temperature difference Δθ [K] | 30 | 40 | 50 | 60 | 70 | 80 |
---|---|---|---|---|---|---|---|
40/140 | 3,0 | 3,9 | 4,9 | 5,9 | 6,9 | 7,9 | |
50/140 | 3,5 | 4,6 | 5,8 | 6,9 | 8,1 | 9,2 | |
63/140 | 4,1 | 5,5 | 6,9 | 8,3 | 9,7 | 11,1 | |
75/140 | 4,9 | 6,5 | 8,1 | 9,8 | 11,4 | 13,0 | |
90/175 | 4,4 | 5,8 | 7,3 | 8,8 | 10,2 | 11,7 | |
110/175 | 5,4 | 7,1 | 8,9 | 10,7 | 12,5 | 14,3 | |
125/200 | 6,4 | 8,6 | 10,7 | 12,9 | 15,0 | 17,2 | |
140/200 | 7,6 | 10,1 | 12,7 | 15,2 | 17,7 | 20,3 |
Ecoflex VIP Thermo Twin PN 6
Type | Heat loss q [W/m] for corresponding temperature difference Δθ [K] | 30 | 40 | 50 | 60 | 70 | 80 |
---|---|---|---|---|---|---|---|
2x 25/140 | 3,7 | 4,9 | 6,1 | 7,3 | 8,5 | 9,8 | |
2x 32/140 | 4,4 | 5,8 | 7,3 | 8,7 | 10,2 | 11,6 | |
2x 40/175 | 4,6 | 6,1 | 7,6 | 9,1 | 10,7 | 12,2 | |
2x 50/175 | 4,5 | 6,0 | 7,5 | 9,0 | 10,5 | 12,0 | |
2x 63/200 | 5,1 | 6,8 | 8,4 | 10,1 | 11,8 | 13,5 | |
2x 75/250 | 6,3 | 8,5 | 10,6 | 12,7 | 14,8 | 16,9 |
Ecoflex VIP Aqua Single PN 10
Type | Heat loss q [W/m] for corresponding temperature difference Δθ [K] | 30 | 40 | 50 | 60 | 70 | 80 |
---|---|---|---|---|---|---|---|
40/140 | 2,9 | 3,9 | 4,9 | 5,9 | 6,9 | 7,8 | |
50/140 | 3,4 | 4,6 | 5,7 | 6,9 | 8,0 | 9,2 | |
63/140 | 4,1 | 5,5 | 6,9 | 8,2 | 9,6 | 11,0 | |
75/140 | 4,8 | 6,5 | 8,1 | 9,7 | 11,3 | 12,9 | |
90/175 | 4,3 | 5,8 | 7,3 | 8,7 | 10,2 | 11,6 | |
110/175 | 5,4 | 7,2 | 8,9 | 10,7 | 12,5 | 14,3 |
Ecoflex VIP Aqua Twin PN 10
Type | Heat loss q [W/m] for corresponding temperature difference Δθ [K] | 30 | 40 | 50 | 60 | 70 | 80 |
---|---|---|---|---|---|---|---|
25-20/140 | 3,5 | 4,7 | 5,9 | 7,1 | 8,3 | 9,5 | |
32-20/140 | 3,7 | 5,0 | 6,2 | 7,5 | 8,7 | 10,0 | |
40-25/140 | 4,4 | 5,9 | 7,4 | 8,9 | 10,3 | 11,8 | |
50-32/175 | 4,7 | 6,3 | 7,9 | 9,5 | 11,0 | 12,6 | |
63-40/200 | 5,1 | 6,8 | 8,5 | 10,3 | 12,0 | 13,7 |