Luxpower ECO Hybrid Inverter User Manual
Where sun shined
Power always on
USER MANUAL
ECO Hybrid Inverter
Information on this Manual
Validity: This manual is valid for the following devices: SNA3000WPV/SNA4000WPV/SNA5000WPV.
Scope: This manual provides the installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations.
Target Group: For qualified persons and end users. Qualified persons and end users must have the following skills:
- Knowledge about this unit operation.
- Training in dealing with security issues associated with installations and electrical safety.
- Training in the installation and commissioning of electrical devices and installations.
- Knowledge of the applicable local standards and directives.
Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- All operation and connection need to be operated by qualified persons.
- Before using the unit, read all instructions and cautionary markings on the unit. Any damage caused by inappropriate operation is not warranted by Luxpower.
- All electrical installation must comply with the local electrical safety standards.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire. Do not open inverter cover or change any components without Luxpower's authorization, otherwise the warranty commitment for the inverter will be invalid.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries and lithium batteries. Other types of batteries may burst, causing personal injury and damage.
- NEVER charge a frozen battery.
- For optimum operation of this unit, please follow required specifications to select appropriate cable size and breaker.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
- GROUNDING INSTRUCTIONS: This unit should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input to short circuit. Do not connect to the mains when DC input is short-circuited.
1. Brief Introduction
1.1 Features of the inverter
The SONAR series is a multifunctional, high-frequency pure sine wave ECO Hybrid inverter solar inverter, featuring:
- Applicable for pure off-grid inverter, backup power, self-consumption, or on-grid situations.
- Integrated with 2 MPPT solar charge controllers, MPPT voltage range 120V~385V.
- Rated power 5KW, power factor 1.
- Able to run with or without a battery in on-grid and off-grid mode.
- With a separated generator input interface, able to control the generator remotely.
- Solar and utility grid can power loads at the same time.
- With integrated advanced parallel function, up to 10 units can be paralleled.
- Support CAN/RS485 for Li-ion battery BMS communication.
- WIFI/GPRS remote monitoring, setting, and firmware update, supporting website, free iOS/Android APP.
System connection overview:
- Solar Panel
- Utility Grid
- Generator
- Battery
- Wifi/4G
- Internet
- Luxpower Server
- Luxpower View
- Home Loads
1.2 Interface of the inverter
LCD display: Shows system information and allows for settings adjustments.
Function buttons: UP, Down, Return, Enter for navigation and selection.
Fault/Warning Status indicator: Red light indicates a fault or warning.
Normal Status indicator: Green light indicates normal operation.
Terminal Connections:
- BAT+/BAT-: Battery positive and negative terminals.
- MPPT485, Li-ion, CAN/RS485: Communication ports for battery management systems.
- NTC: For temperature sensing.
- WIFI: For wireless connectivity.
- PV A+/PV A-, PV B+/PV B-: Solar panel input terminals.
- AC INPUT (L, N, PE): Connection for AC power input.
- AC OUTPUT (L, N, PE): Connection for AC power output.
- GEN (L, N): Generator input connection.
- Dry Port (NO2, COM2, NC2): For dry contact signal control.
- GEN (NO1, COM1, NC1): For generator control.
- Parallel BAT+/BAT-: Terminals for parallel battery connection.
- EPS Output (L, N): Emergency Power Supply output.
- Power on/off switch.
- Circuit breaker connections.
- Parallel communication resistor switch.
- EPS on/off switch.
- Parallel communication ports.
1.3 Packing List
Before installation, please inspect the unit. Ensure that nothing inside the package is damaged. You should have received the following items:
- ECO Hybrid inverter X1
- User Manual X1
- Expansion Screw and Tube X4
- Wi-Fi Module X1
- Cross Head Screw X5 / Nut X2
Storing the Inverter
The inverter must be stored appropriately if not installed immediately. Refer to the figure below.
CAUTION!
- The inverter and its components must be stored in their original packaging.
- The storage temperature should be within -25~60°C and humidity within 0~85%.
- The packing should be upright and maximum stacked layers is 6.
- Do not directly expose the inverter and its packaging to sunshine, raindrops, and keep away from corrosion.
Storage conditions: Temperature < 60°C, Humidity < 85%, Height < 2m.
2. Installation
2.1 Preparation
The system connection is shown in the diagram. Please prepare the breakers and cables in advance before installation.
Breaker Specifications:
- QF 1: In ≥ 63A
- QF 2: In ≥ 63A
- QF 3: In ≥ 140A
- QF 2 is a Double interlock switch or Dual Power Switch, In ≥ 63A.
2.2 Mounting the Unit
Notice: Consider the following points before selecting where to install:
- Mount on a solid surface.
- Do not mount the inverter on flammable construction materials.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
Steps to mounting the unit:
- Use the wall-mounting bracket as a template to mark the position of the 4 holes, then drill 8 mm holes and ensure the depth of the holes is deeper than 50mm.
- Install the expansion tubes into the holes and tighten them, then use the expansion screws (packaged together with the expansion tubes) to install and fix the wall-mounting bracket on the wall.
- Install the inverter on the wall-mounting bracket and lock the inverter using the security screws.
Dimensions: 519 mm (Height) x 180 mm (Width) x 500 mm (Depth). Clearance: 200 mm on sides, 500 mm above and below.
2.3 Battery Connection
2.3.1 Battery Power Cable Connection
Note: For lead-acid batteries, the recommended charge current is 0.2C (C = battery capacity).
- Please follow the steps below to implement battery connection.
- Assemble battery ring terminals based on recommended battery cable and terminal size.
- Connect all battery packs as the unit requires. It is suggested to connect at least a 200Ah capacity battery for the SNA5000WPV.
- Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and make sure the bolts are tightened with a torque of 2~3 Nm. Make sure the polarity of the battery is correctly connected and ring terminals are tightly screwed to the battery terminals.
2.3.2 Lithium Battery Connection
If choosing a lithium battery for the SNA5000WPV, please ensure the battery BMS is compatible with the Luxpower inverter. Please check the compatible list on the Luxpower website.
- Connect the power cable between the inverter and the battery.
- Connect the CAN or RS485 communication cable between the inverter and the battery. If you do not have the communication cable from the inverter manufacturer or battery manufacturer, please make the cable according to the PIN definition.
- Lithium battery configuration: To communicate with the battery BMS, you should set the battery type to "Li-ion" in Program "03" via the LCD and choose the correct battery brand (for details, please check the LCD setting chapter). Users can also choose the battery type and brand via the monitor system.
Communication Port Pin Definitions:
Pin | RS 485 port | CAN port | Pin | RS 485 port | CAN port |
---|---|---|---|---|---|
1 | RS 485B | 1 | RS 485B | ||
2 | RS 485A | 2 | RS 485A | ||
3 | CANL | 3 | CANL | ||
4 | CANH | 4 | CANH | ||
5 | CANH | 5 | CANH | ||
6/7/8 | CANL | 6/7/8 | CANL |
Battery Pack Connections:
Parallel connections are shown for the inverter and battery pack.
2.4 AC Input/Output Connection
CAUTION!!
There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mix up input and output connectors.
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuit when these inverters are worked in parallel operation.
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open the DC protector or disconnect it first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor first.
- Insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor first.
- Make sure the wires are securely connected.
Wire identification: Ground (yellow-green), L-LINE (brown or black), N-Neutral (blue).
2.5 PV Connection
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check correct polarity of connection cables from PV modules and PV input connectors.
- Connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.
- Make sure the wires are securely connected.
- Finally, after connecting all wiring, please put the bottom cover back by screwing two screws as shown below.
2.6 Generator Connection
CAUTION: Before making Generator connection, be sure to open the DC protector or disconnect it first.
- Remove insulation sleeve 10mm for 2 conductors.
- Insert L and N wires according to polarities indicated on the terminal block and tighten the terminal screws.
2.7 Dry Contact Signal control
The Dry port (NO2, COM2, NC2) can be used to deliver a signal to an external device when the battery voltage reaches a warning level. The GEN port (NO1, COM1, NC1) can be used to wake up the generator, and then the generator can charge the battery.
Unit Status | Condition | Dry port (NO2 & COM2) | GEN port (NO1 & COM1) |
---|---|---|---|
Power Off | Inverter is off and no output is powered. | Open | Open |
Without Grid | Battery voltage < Low DC warning voltage | Close | Close |
Without Grid | Battery voltage > Setting value or battery charging reaches floating stage | Open | Open |
Power On | Battery voltage < Low DC warning voltage | Close | Open |
With Grid | Battery voltage > Setting value or battery charging reaches floating stage | Open | Open |
Notice: NO = Normal open. Dry Port Relay Maximum Specification: 250VAC 5A. Gen Port Relay Maximum Specification: 250VAC 5A.
2.8 Parallel function
SNA series inverters support up to 10 units to compose single-phase parallel systems or three-phase parallel systems. For parallel system setup:
Step 1: Cable connection: The system connection is as below. Cannot share PV input at any time!
Step 2: Please put the CAN communication PIN to ON status for the first and the end inverter.
Step 3: Setup the monitor for the system, add all datalogs in one station. Users can login to the visit interface of the monitor system, Configuration -> Station -> Plant Management -> Add Datalog to add the datalogs.
Step 4: Enable shared battery for the system if the system shares one battery bank, otherwise disable the shared battery function.
Step 5: Set the system as a parallel group in the monitor system.
For more detailed guidance for paralleling systems, please visit https://www.luxpowertek.com/download/ and download the guidance.
2.9 Power and EPS ON/OFF
1. Power Switch: Controls power supply for the unit.
2. EPS Output Switch: Used to control the AC output.
After connection, please turn on both switches. Users can turn off the EPS output switch to turn off the power supply in an emergency case.
3. Working modes
3.1 ECO Hybrid inverter modes introduction:
Bypass Mode | AC Charge | PV Charge Bypass | BAT Grid off | PV+BAT Grid off | PV Charge | PV Charge+Grid off |
---|---|---|---|---|---|---|
AC is used to take the load. | 1. AC charges the battery from AC Input or GEN Input. 2. When the battery is power off, the AC can wake up the battery automatically. |
PV charge the battery while the AC power the load. | Battery is used to take the load. | PV+Battery power the load together. | 1. When the EPS key is off, the inverter charges the battery only. 2. When the battery is power off, the PV can wake up the battery automatically. |
PV charges the battery and powers the load. |
PV+AC charge | PV Grid off | PV+BAT Grid off | PV Gridon | PV+BAT Gridon |
---|---|---|---|---|
PV+AC charge the battery. AC is from AC Input or GEN Input. | NOTE: The output power depends on the PV energy input. If the PV energy is unstable, it will influence the output power. When setting without battery, the PV can power the load. | PV charge battery and power the load. | PV power the load, the rest power from PV can feed into Grid. | PV+Battery power the load, and the AC can power the load if PV+Battery power is not enough. |
3.2 Working Modes related setting description
Situation | Setting 1 | Setting 2 | Setting 3 | Working modes and Description |
---|---|---|---|---|
AC abnormal | NA | NA | NA | Off-grid inverter mode. If P_Solar >= P_load, solar is used to take load and charge battery. If P_Solar < P_load, solar and battery take the load together, system will discharge until battery lower than the Cut Off Voltage/SOC. |
AC normal | In the AC first time | NA | NA | Hybrid Mode 1 (charge first). Solar power will be used to charge the battery first. AC will take the load. 2. If solar power is higher than the power needed to charge the battery, the extra power will be used to take the load together with the grid. 3. If there is still more energy after charging the battery and taking the load, it will feed energy into the grid if the export to grid function is enabled. |
AC normal | PV&AC Take Load Jointly Enable | Enable AC charge and in the AC charge time | AC charge according to battery voltage or SOC | Hybrid Mode 1 (charge first) + AC charge battery if solar power is not enough to charge battery. Hybrid Mode 1 (charge first) + AC charge battery if solar power is not enough to charge battery and the battery voltage/SOC is lower than AC start charge voltage/SOC, the AC will stop charging when the battery voltage/SOC is higher than AC end charge battery voltage/SOC. |
AC normal | 1. Not in the AC first time and 2. Disable AC charge or not in the AC charge time |
NA | NA | Hybrid Mode 2 (load first). Solar power will be used to take load first. 1. If solar power is lower than load, battery will discharge together to take load until battery lower than EOD voltage/SOC. 2. Disable AC charge or not in the AC charge time. 2. If solar power is higher than load, the extra power will be used to charge the battery. If there is still more energy, it will feed into the grid if export is enabled. |
AC normal | In the AC first time | NA | AC will take the load and Solar is used to charge battery. | Bypass Mode + AC charge battery. Solar is used to charge battery. |
AC normal | PV&AC Take Load Jointly Disable | Enable AC charge and in the AC charge time | AC charge according to Time | Bypass Mode + AC charge battery. Solar is used to charge battery. AC will take load and also charge battery during AC charge time if solar power is not enough. |
AC normal | 1. Not in the AC first time and 2. Disable AC charge or not in the AC charge time |
AC charge according to SOC/Battery voltage | AC will take load and also charge battery when battery SOC/Voltage is lower than start SOC/Voltage, and the AC will stop charging when the battery voltage/SOC is higher than AC end charge battery voltage/SOC. | Off-grid inverter mode. If P_Solar >= P_load, solar is used to take load and charge battery. If P_Solar < P_load, solar and battery take the load together, system will discharge until battery lower than EOD Voltage/SOC. |
4. LCD Display and settings
4.1 LED Display
LED Indicator | Solid On | Flashing | Messages |
---|---|---|---|
1 Green | Normal | fast: Warning slow: Firmware update |
Working normal |
2 Red | Fault condition occurs in the inverter | Normal / Fault |
Buttons: Return, UP, Down, Enter.
4.2 LCD Display
No. | Description | Remarks |
---|---|---|
1 | Generally Information Display Area | Display the currently time/date by default (year/month/day/hour/minute). Switching automatically. When press Up or Down buttons, this area will display the firmware version information, serial number, etc. Display the setting selection information when entering settings. |
2 | On-grid solar inverter output power and energy data | This area shows the data of PV voltage, power and the setting of PV input connection information. |
3 | Battery information and data | This area shows the battery type, battery brand (lithium battery), the lead-acid battery setting of CV voltage, Floating charging voltage, Cut off voltage, Discharge end voltage. It also displays the voltage, SOC and power in turns of period of 1 second. |
4 | System working status / setting code | There are three types of working status: normal, warning, and fault. In the right side of this area, there is code display. It will display different types of code - the system working mode code, warning code, fault code, and setting code. |
5 | UPS/EPS output information and data | When UPS function is enabled, this area will display UPS voltage, frequency, power, etc. in turns of periods of 1s. |
6 | Programming & the percentage of AC output power | When firmware updating is in process, it will display relevant information. When in grid off, this area will display the percentage of the maximum AC output power. |
7 | Loads consumption | Display the power consumption by the loads in on-grid model. |
8 | Grid information and Generator information | Display the grid (GRIDA) information of voltage, frequency, input or output power. The Generator (GRIDB) information of voltage, frequency, input power, switch period of 1s. |
9 | Working mode settings area | When making settings on the SNA5000 inverter through the LCD, this area will display the AC Charge, Force Discharge, Charge First options, UPS/EPS output information, etc. It will not display this information unless in the setting process. |
4.3 Inverter Status Display
Various status displays are shown, including Normal status, Warning status, Fault status, and Flash status (download percent).
When display 'GRIDA', it means the Grid information is about AC utility. The percent display on the right down corner means the load percentage.
When display 'GRIDB', it means the AC information is about Genset input.
4.4 LCD Settings
There are four buttons on the LCD: Return, UP, Down, Enter.
Step 1: After touching the Enter button for about 2 seconds, the unit will enter setting mode. The setting icon and index will be flashing.
Step 2: Touch UP or Down button to select the setting index from 1 to 19.
Step 3: Touch Enter button to set this item.
Step 4: Touch UP or Down button to change the settings.
Step 5: Touch Enter to confirm the setting or Return to the setting list.
Index | Description | Setting Option |
---|---|---|
1 | Date & time | Setting Year/Month/day: 2018:08:08 Setting hour/minute/second: 10:09:08 |
2 | PV input mode | Default: S (Same string input for 2 MPPTs) Alternative: P (two independent Strings input) |
3 | Battery | Run with No Battery: Step 1: Choose battery type first, when no flashing, select Enter to choose Run with No battery. For Lead Acid: Step 1: Choose battery type first, when Lead-Acid flashing, select Enter to choose Lead-acid battery. Step 2: Then choose battery capacity. For Lithium battery: Step 1: Choose battery type first, when Li-ion flashing, select Enter to choose Li-ion battery. Step 2: Choose battery brand. 0 -> Standard Battery 2 -> Pylon Battery 6 -> Luxpower protocol Battery 8 -> Dyness Battery |
4 | UPS Output voltage and frequency | AC Output voltage: 220Vac/230Vac/240Vac (Default)/240Vac AC Output frequency: 50Hz (Default)/60Hz |
5 | Buzzer enable | Buzzer enable (Default) Enable / Disable |
6 | Maximum charge current | Total charge current setting. Setting range: 10A~140A Default: 110A |
7 | CV voltage setting (Only in Lead-acid battery type) | Setting range: 50.0-59.0Vdc Default: 56.4V |
8 | Floating charging voltage setting (Only in Lead-acid battery type) | Setting range: 50.0-56.0Vdc Default: 54.0V |
9 | Maximum discharge current | Total discharge current setting. Setting range: 10A~140A Default: 110A |
10 | TEOd: Discharge control type: VOLT/SOC | Setting Range: VOLT/SOC Default: VOLT |
11 | CutOFF: Cut off Voltage or SOC, depend on TEOd | Setting range: VOLT: 40.0-OnGrid EOD Volt Default: 42V SOC: 0-OnGrid EOD SOC Default: 15% |
12 | Eod: Discharge end voltage or SOC with grid, depend on TEOd | Setting range: VOLT: Cut off Volt-56V Default: 42V SOC: Cut off SOC -90 Default: 15% |
13 | Acin: AC voltage range setting | Acin: APL (Default) AC Output voltage range: 170Vac~280Vac |
14 | AC charge setting | AC Charge function: Disable (Default) Enable Setting AC Charge current: 30A (Default) Range:0%~100% Setting AC Charge to battery SOC: Default:100% Setting AC Charge time of 1 start: Range:00:00~23:59 Default:00:00~00:00 Setting AC Charge time of 1 end: Range:00:00~23:59 Default:00:00~00:00 |
15 | Utility source (AC Input) to take Load time setting | Setting time of 1 start: Range:00:00~23:59 Default:00:00~00:00 Setting time of 1 end: Range:00:00~23:59 Default:00:00~00:00 |
16 | Hybrid enable/disable | Hybrid Disable (default) Disable / Enable |
17 | Maximum Feed-In percent | Feed-In Disable (default) Disable / Enable Setting Range: 0-100% (default) FEED:100% |
18 | Battery Wakeup enable/disable (Not for No Battery type) | Enable wakeup battery YES / NO |
19 | Max Generator Input Power | Setting Range: 0-7369W 7369W (default) |
20 | Green Function enable/disable | Green Function Disable (default) Disable / Enable |
21 | Parallel setting | ECO Mode Disable (default) Disable / Enable Parallel phase setting: P1 (Rphase)/ P2(Sphase) /P3(Tphase) P1 (default) Parallel type setting: NoPL (not Parallel)/1PH (Single phase)/3PH (Three phase) NoPL (default) |
22 | Error/Alarm Record | Alarm Record -> Record Index -> Record Msg: (Year:Month:Day; Hour: Min:Sec; Alarm code) ALA REC Error Record -> Record Index -> Record Msg: (Year: Month: Day; Hour: Min:Sec; Error code) Err REC |
23 | CT Offset | Setting Range: -200~200W 20W (default) |
24 | Fan speed setting | Fan1 Speed Percent Setting Range: 20-100% 70% (default) Fan1 Speed New Slope Setting Range: Disable (default) Enable Fan2 Speed Percent Setting Range: 20-100% 70% (default) Fan1 Speed New Slope Setting Range: Disable (default) Enable |
25 | Generator charge setting | Generator charge setting -> charge control type Setting Range: 1.VOL (default) 2.SOC -> control type -> control value Setting Range: VOL: 1.Start Voltage:38.4-52V; 2.End Voltage:48-59V; SOC: 1.Start Soc:1-90%; 2.End Soc: 20-100%; |
5. Monitor System for ECO Hybrid inverter
Users can use a Wi-Fi dongle / WLAN dongle / 4G dongle (available from March 2021 for some countries) to monitor the energy storage system. The monitor website is: server.luxpowertek.com
The APP is also available in the Google Play and Apple APP store (Scan QR code to download the APP).
Please download the introduction of guidance by website: https://www.luxpowertek.com/download/
Document Reference:
- 1. Wifi Quick Guidance: Quick guidance for setting the password for the Wi-Fi module. The paper is also available in the Wi-Fi box.
- 2. Monitor system setup for Distributors and Monitor system setup for end-users: Monitor system registration, Wi-Fi password setting, and Wi-Fi local monitor and setting.
- 3. Lux_Monitor_UI_Introduction: Introduction of monitor interface.
- 4. WebsiteSetting Guidance: Introduction of website settings for off-grid inverter.
Local Monitor:
- Solar Yielding: 0.0 kWh
- Today Yielding: 300.8 kWh
- Total Yielding: 9532004127
- Feed-in Energy: 0.0 kWh
- Today Export: 77.1 kWh
- Total Export: 0.0 kWh
- Battery Discharging: 0.0 kWh
- Today Discharging: 50.1 kWh
- Total Discharging: 0.0 kWh
- Consumption: 0.0 kWh
- Today Usage: 255.3 kWh
- Total Usage: 0.0 kWh
- PV Power: 0 W
- Battery Level (SOC): 0%
- EPS: Backup Power (EPS): 0 W
- Notice: PV Power, EPS
6. Specifications
Table 1 Line Mode Specifications
INVERTER MODEL | SNA5000WPV/SNA4000WPV/SNA3000WPV |
---|---|
Input Voltage Waveform | Sinusoidal (utility or generator) |
Nominal Input Voltage | 230Vac |
Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) |
Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) |
High Loss Voltage | 280Vac±7V |
High Loss Return Voltage | 270Vac±7V |
Max AC Input Voltage | 280Vac |
Nominal Input Frequency | 50Hz/60Hz (Auto detection) |
Output Short Circuit Protection | Software protect when GridOff discharge |
Transfer Time | <20ms @ Single; <30ms @ Parallel |
Output power derating: When AC input voltage drops to 170V, the output power will be derated. | Output Power Rated Power 20% Power |
Charge power derating: When AC input voltage drops to 170V depending on models, the charge power will be derated. | Output Power Rated Power 50% Power |
Input Voltage: 90V - 170V - 280V | |
Output Power: 0 W | |
Battery Power: 0 W | |
Battery Level(SOC): 0 W | |
PV Power: 0 W | |
EPS: Backup Power(EPS): 0 W |
Table 2 Inverter Mode Specifications
5KVA/5KW | 4KVA/4KW | 3KVA/3KW | |
---|---|---|---|
Rated Output Power | 5KVA/5KW | 4KVA/4KW | 3KVA/3KW |
Output Voltage Waveform | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave |
Output Voltage Regulation | 208Vac/220Vac/230Vac/240Vac±5% | 208Vac/220Vac/230Vac/240Vac±5% | 208Vac/220Vac/230Vac/240Vac±5% |
Output Frequency | 50Hz/60Hz | 50Hz/60Hz | 50Hz/60Hz |
Peak Efficiency | 93% | 93% | 93% |
Overload Protection | 5s@≥150% load; 10s@110%~150% load | 5s@≥150% load; 10s@110%~150% load | 5s@≥150% load; 10s@110%~150% load |
Surge Capacity | 2* rated power within 5 seconds | 2* rated power within 5 seconds | 2* rated power within 5 seconds |
Table 3 Charge Mode Specifications
Utility Charging Mode | ||
---|---|---|
Lead_Acid Battery Charging Algorithm | 3-Step | |
Max. AC Charging Current | 60Amp(@VI/P=230Vac) | |
Bulk Charging Voltage | Flooded Battery: 58.4Vdc AGM / Gel Battery: 56.4Vdc Li-ion Battery: 54Vdc |
|
Floating Charging Voltage | Flooded Battery: 56.4Vdc AGM / Gel Battery: 54Vdc |
Battery Voltage Range:
- 46.4V-60V(Li) / 38.4V-60V(Lead_Acid)
- High DC Cut-off Voltage: 59VDC(Li) / 60VDC(Lead_Acid)
- High DC Recovery Voltage: 57.4VDC(Li) / 58VDC(Lead_Acid)
- Low DC Warning Voltage: 44.0Vdc (Settable) (load < 20%)
- Warning Voltage @load < 20% -1.2V (load < 20%)
- Warning Voltage @load < 20% -3.6V (load ≥ 50%)
- Low DC Warning Return Voltage: Low DC Warning Voltage@Different load +2V
- Low DC Cut-off Voltage: 42.0Vdc(Settable)
- Low DC Cut-off Return Voltage: Cut-off Voltage @load < 20% -1.2V
- Low DC Warning SOC: 20% SOC (Settable)
- Low DC Warning Return SOC: Low DC Warning SOC +10%
- Low DC Cut-off SOC: 15% SOC (Grid on) (settable)
- Low DC Cut-off Return SOC: Low DC Cut-off SOC +10%
- Charge Cut-off Voltage: 58.4Vdc
- No Load Power Consumption: <60W
MPPT Solar Charging Mode:
- Max. PV Array Power: 3200W*2
- Start-up Voltage: 100Vdc±10Vdc
- PV Array MPPT Voltage Range: 120Vdc~385Vdc
- Max. PV Array Open Circuit Voltage: 480Vdc
- Max. PV Charging Current: 110A
- Max. Charging Current (AC Charger Plus Solar Charger): 110A
Table 4 General Specifications
INVERTER MODEL | SNA5000WPV/SNA4000WPV/SNA3000WPV |
---|---|
Safety Certification | CE |
Operating Temperature Range | 0°C to 50°C |
Storage temperature | -15°C~60°C |
Humidity | 5% to 95% Relative Humidity (Non-condensing) |
Altitude | <2000m |
Dimension(D*W*H) | 505*330*135mm |
Net Weight | 14.5Kg |
7. Trouble Shooting & Error List
The failures are mainly divided into 5 categories, for each category, the behavior is different:
Code | Description | Trouble shooting | Code | Description | Trouble shooting |
---|---|---|---|---|---|
E000 | Internal communication fault1 | Restart inverter, if the error still exists, contact us (DSP&M3) | W000 | Communication failure with battery | Check if you have chosen the right battery brand and communication cable is right, if the warning still exists, contact us. |
E002 | Bat On Mos Fail | Restart inverter, if the error still exists, contact us (DSP&M3) | W001 | Battery temperature high | Check battery temperature sensor is right connected and the battery temperature is not too high. |
E003 | CT Fail | Restart inverter, if the error still exist, contact us (DSP&M3) | W002 | Battery temperature low | Check battery temperature sensor is right connected and the battery temperature is not too low. |
E008 | CAN communication error in Parallel System | Check CAN cable connection is connected to the right COM port. | W004 | Battery failure | Inverter get battery fault info from battery BMS, restart battery, if the warning still exist, contact us or battery manufacturer. |
E009 | No master in parallel system | Check parallel setting for master/Slave part, there should be one master in the system. | W008 | Software mismatch | Please contact Luxpower for firmware update. |
E010 | Multi master in parallel system | Check parallel setting for master/Slave part, there should be one master in the system. | W009 | Fan Stuck | Check if the fan is OK. |
E011 | AC inconsistent in parallel system | Check if AC Connection is same for all inverters in parallel system. | W012 | Bat On Mos | Restart inverter, if the error still exists, contact us. |
E012 | UPS output short circuit | Check if the load is short circuit, try to turn off the load and restart inverter. | W013 | Over temperature | The temperature is a little bit high inside inverter. |
E013 | UPS reserve current | Restart inverter, if the error still exists, contact us. | W018 | AC Frequency out of range | Check AC frequency is in range. |
E015 | Phase Error in three phase parallel system | Check if the AC connection is right for three phase system, there should be one at least one inverter in each phase. | W025 | Battery voltage high | Check if battery voltage is in normal range. |
E016 | Relay fault | Restart inverter, if the error still exists, contact us. | W026 | Battery voltage low | Check if battery voltage is in normal range, need to charge the battery if battery voltage is low. |
E017 | Internal communication fault2 | Restart inverter, if the error still exists, contact us (DSP&M8) | W027 | Battery open | Check if there is output from the battery and battery connection with inverter is OK. |
E018 | Internal communication fault3 | Restart inverter, if the error still exists, contact us (DSP&M3) | W028 | EPS Over load | Check if EPS load is too high. |
E019 | Bus voltage high | Check if PV input voltage is higher than 480V. | W029 | EPS voltage high | Check if EPS voltage is high. |
E020 | EPS connection fault | Check if EPS and AC connection is in wrong terminal. | W031 | EPS DCV high | Restart inverter, if the error still exists, contact us. |
E021 | PV voltage high | Check PV input connection and if PV input voltage is higher than 480V. | |||
E022 | Over current internal | Restart inverter, if the error still exists, contact us. | |||
E024 | PV short | Check PV connection. | |||
E025 | Temperature over range | The internal temperature of inverter is too high, turn off the inverter for 10 minutes, restart the inverter, if the error still exists, contact us. | |||
E026 | Internal Fault | Restart inverter, if the error still exists, contact us (Bus sample) | |||
E031 | Internal communication fault4 | Restart inverter, if the error still exists, contact us (DSP&M8) |