User Manual for MARATHON models including: 5KCP33KNB267AS AC Induction Motors, 5KCP33KNB267AS, AC Induction Motors, Motors
Marathon Motors 5KCP33KNB267AS :: Motor, Blower, 1PH, 1/10HP, 115/230VAC, 3250/2700RPM :: Rexel USA
Marathon Motors 5KCP37SNC304S :: Motor, 1/2HP, 115/230VAC, 1075RPM, 1/3PH, Stainless Steel :: Gexpro
File Info : application/pdf, 15 Pages, 298.87KB
DocumentDocument!"# $ %& Phone: (715) 675 3311 +++, - ' %$ () * , Form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motor is suitable for use on Pulse Width Modulated (PWM) type VFD power. In addition, the nameplate must be marked with the inverter rating; for example, "2:1 CT", "2 to 1 Constant Torque", etc. <, (% '' $9 5 $9 ; $ % $ $ (; ( 7 ' %.: <,< ' %$ ' ( %. 5 $ 6* ' %$ ' (& F & G $? Electrical connections shall be made by a qualified electrical personnel in accordance with all applicable codes, ordinances and sound practices. Failure to follow these instructions could result in serious personal injury, death and/or property damage. Only qualified personnel who are familiar with the applicable National Code (USA = NEC) and local codes should install or repair electrical motors and their accessories. 5 $ 6* ' %$ ' ' = $ / % & G $? Do not touch electrically live parts. Disconnect, lockout and tag input power supply before installing or servicing motor (includes accessory devices). Use a voltmeter to verify that power is off before contacting conductors. 5 $ 6* ' %$ ' 6$ / ? 6 & G $? Failure to properly ground motors, per the National Electrical Code (NEC) Article 430 and local codes may cause serious injury or death to personnel. For general information on grounding refer to NEC Article 250. (Also see "Ground Connections section 3.4.4"). 5 $ 6* /% % $ ( % ;$ % % $ & G $? Do not use automatic reset protectors if automatically restarting the motor will place personnel or equipment at risk. . Failure to follow this instruction could result in serious personal injury, death and/or property damage 5 $ 6* / ' $ ( % ;$ % % $ & G $? If a tripped manual reset thermal protector is exposed to a temperature less than 7°C (20°F) it may reset and restart the motor automatically. If an application requires a motor with a manual reset thermal protector that will be operated at temperatures less than 7°C (20°F) contact the manufacturer to review the application / motor requirements. Failure to follow this instruction could result in serious personal injury, death and/or property damage <,# & ' ( %. 5 $ 6* ' ( ; $%( & G $? Before starting the motor, remove all unused shaft keys and loose rotating parts to prevent them from flying off. Failure to follow these instructions could result in serious personal injury, death and/or property damage. 5 $ 6* $ % % 6 ; $%( & G $? Keep extremities, hair, jewelry and clothing away from moving parts. Failure to follow these instructions could result in serious personal injury, death and/or property damage. <,! = $ % ' ( %. 5 $ 6* & G $? /( ' % ( (1) The NEC and the local authority having jurisdiction must be consulted concerning the installation and suitability of motors for use in Hazardous Locations. The local authority having jurisdiction must make the final determination of what type of motor is required. The application and operation is beyond the control of the motor manufacturer. (2) Division 1 Hazardous Locations motors can only be modified or reworked by the manufacturer or a facility that is Listed under UL's category "Motors and Generators, Rebuilt for use in Hazardous Locations". Failure to follow these instructions could result in serious personal injury, death and/or property damage. (3) Do not use a Hazardous Locations motor with a Variable Frequency Drive (VFD) unless the motor nameplate specifically states that the #, $ = 6 ? (; % #,< % ' (; % ( #,<,< & F ; F 6 ' (% ? (; % the packaging to make certain no damage has occurred in shipment. If there is visible damage to the packaging, unpack and inspect the motor immediately. Claims for any damage done in shipment must be made by the purchaser against the transportation company. #,<,# %/$ % $ (& % by hand to be certain that it rotates freely. Note: Shaft seals and bearing seals may add drag. #,<,! & F ;' % for conformance with purchase order requirements and compliance with power supply and control equipment requirements. #,# & ?' 6* 5 $ 6* '' 6 7C % & G $? 01 4 4 +- ) 4 0- 10 - unless specifically stated otherwise on the motor). Utilizing the motor lifting provision to lift other components such as pumps and gear boxes could result in serious personal injury, death and/or property damage. 5 $ 6* '' 6 7C % & G $? Before using the lifting provision, check the eyebolts and/or other lifting means to assure they are not bent or damaged and are completely threaded, seated & secured to the motor. Equipment to lift motor must have adequate lifting capacity. While lifting the motor DO NOT stand under or in the vicinity of the motor. Failure to follow these instructions could result in serious personal injury, death and/or property damage. #,#,< ' % 6 6' ' % % ( #,! (% $ 6 * Motors, not put into service immediately, must be stored indoors in a clean, dry location. Avoid locations with large temperature swings that will result in condensation. Motors must be covered to eliminate airborne dust and dirt. If the storage location exhibits high vibration, place isolation pads under motor to minimize damage to motor bearings. #,!,< 7 $ 6 '/7$ % * Bearings are grease packed at the factory; relubrication upon receipt of motor or while in storage is not necessary. If stored more than one year, add grease per lubrication instructions (Table 4 4) before start up. #,!,# (& % $ % % * It is recommended that the motor shaft be rotated 5 to 10 rotations every three months to distribute the grease in the bearings. This will reduce the chance for corrosion to form on the bearing rolling elements and raceways. Note: Shaft seals and bearing seals may add drag. #,!,! ? ; $ &/ ? (% $ 6 ' % (: Treat unpainted flanges, shafts, and fittings with a rust inhibitor. Apply appropriate power to the motor's space heaters (if so equipped) !, (% '' % ? ;$% 5 $ 6* Only qualified personnel who are familiar with the appropriate national code, local codes and sound practices should install or repair electrical motors and their accessories. Installation should conform to the appropriate national code as well as local codes and sound practices. Failure to follow these instructions could result in serious personal injury, death and/or property damage. 5 $ 6* ' %$ ' ' = $ / % & G $? Do not touch electrically live parts. Disconnect, Lockout and Tag input power supply before installing or servicing motor (includes accessory devices). Use a voltmeter to verify that power is off before contacting conductors. !,< ' % !,<,< ( ' % 6 ' % * Consideration should be given to environment and ventilation. Motors should be installed in an area that is protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic particles, and vibration. A motor with the proper enclosure for the expected operating condition should be selected. Provide accessible clearance for cleaning, repair, service, and inspections (See section 3.1.3 for construction clearances). The location should be considered for possible future motor removal / handling. The free flow of air around the motor should not be obstructed. !,<,# 7 % % ; $ %/$ ' %(* The ambient temperatures of the air inlet to the motor should not exceed 40°C (104°F) or be less than 30°C ( 22°F) unless the motor nameplate specifically states an ambient temperature outside of these limits. The ambient inside an enclosure built around the motor shall not exceed the nameplate ambient. For ambient temperatures outside of these limits consult the motor manufacturer. /% * (/' % ? 6$ ? % 5 $ 6 Insulation at high temperatures ages at an accelerated rate. Each 10°C increase in temperature reduces the insulation life by one half. 5 $ 6* & G $? /( ' % ( 7 % ' %* Division 1 Hazardous Locations motors shall % be operated below 25°C ( 13°F) ambient. (Low temperatures reduce the component mechanical properties.) !,<,! (%$/ % ( ' % ' %* !,<,!,< ?$ ;;$ ; % $( are intended for use indoors where the atmosphere is relatively clean, dry, and non corrosive. Recommended a minimum clearance of ½ the shaft height between vent openings and the nearest obstruction. !,<,!,# % % ''. ' ( ? % $( are suitable for indoor or outdoor standard service applications. % %0 ) motors must be mounted in the air stream. When the motor nameplate states a minimum airflow the motor must be mounted in an air stream meeting this minimum value. % %0 motors must meet a minimum distance of ½ the shaft height between the fan guard grill openings and the nearest obstruction. !,<,!,! & G $? /( ' % ( % $(* Hazardous Locations motors are intended for installations in accordance with NEC Article 500. For all installations involving Hazardous Locations motors, consult the applicable national codes, local codes, and the authority having jurisdiction. ?) < " > * Use only motors that are UL Listed and CSA Certified or UL Listed and UL Certified for Canada. These motors bear a separate nameplate that includes the UL Listing Mark and CSA Certification Mark or includes the UL Listing Mark and the UL Mark for Canada. This plate also bears the phrase: " Electric motor for Hazardous Locations" and is marked with the Class, Group and Operating Temperature Code. ?) # " 0* Use only motors that are CSA Certified and bear the CSA Certification Mark. These motors include a phrase on the main motor nameplate that indicates the motor is CSA Certified for Class I, Division 2 / Zone 2 locations. ?) # " 0* Use only Class II motors as described above under "Division I Installations". 5 $ 6* H;' ( & G $? A motor should never be placed in an area with a hazardous process or where flammable gases or combustible materials may be present unless it is specifically designed and nameplated for this type of service. Hazardous Locations motors are intended for installations in accordance with NEC Article 500. For all installations involving Hazardous Locations motors, consult the NEC, local codes, and the authority having jurisdiction. Failure to follow these instructions could result in serious personal injury, death and/or property damage. (For other limitations see section 1.3) !,# / % 6 % $* !,#,< $ 6 ? 7 ( % ? * The motor must be securely installed to a rigid foundation or a mounting surface to minimize vibration and maintain alignment between the motor shaft and the load's shaft. The mounting surfaces of the four mounting pads must be flat within 0.01 inches for 210 frame & smaller; 0.015 inches for 250 frame & larger. [IEC 0.25 mm for 130 frame & smaller, 0.38 mm for 160 frame & larger]. This may be accomplished by shims under the motor feet. For special isolation mounting, contact manufacturer for assistance !,#,# $ 6 ? 7 ( & ' ( ' % $ & '( !,#,! = $% ' / % 6* /% * ' (/$ ;$ % % /% * Most Dripproof rigid base (footed) motors do % meet "Dripproof" requirements when mounted vertically. If the motor is located in unprotected environments, the addition of a drip cover may be available. Drip covers not available for cast iron rigid base motors. 5 $ 6* '' 6 7C % & G $? The lifting provision on standard horizontal footed motors is not designed for lifting the motor in a vertical shaft up or shaft down position. (see 2.2.1 lifting angles). Lifting method / provisions for mounting a rigid base (footed) motor vertically is the responsibility of the installer. = $% ' (& % ? 5 * Most standard horizontal motors thru 449 Fr. (excluding brake motors) can be mounted in a vertical shaft down orientation. For vertical brake motors see section 3.3.6.2. = $% ' (& % /;* 5 $ 6* & G $? /( ' % ( = $% ' / %* Hazardous locations motors must % be mounted vertically shaft up without approval by the motor manufacturer. Without proper retaining provisions the rotor may move axially and contact components, creating a spark hazard. 7 $ ' +- ) 0: The following frame sizes / constructions with applied (axial) down loads within the limit stated are acceptable when mounted vertical shaft up. % 1 !<7 $' B (- / (3 F ?+ '! 56 TEFC & ODP Steel Yes 25 lbs 140 TEFC Steel & Cast Iron Yes 25 lbs ODP Steel Yes 25 lbs 180 TEFC ODP All Steel Yes 35 lbs Yes 35 lbs 210 TEFC ODP All Steel Yes 40 lbs Yes 40 lbs TEFC All Yes 40 lbs 250 ODP Steel Cast Iron Yes 40 lbs No2 N/A 320 TTFC models Cast Iron Eng1 N/A All Other 280 320 TEFC ODP Cast Iron & Aluminum Cast Iron Yes 30 lbs No2 N/A TEFC & ODP Steel Build Up Only4 N/A 360 & Up TEFC ODP TEFC & ODP Cast Iron Cast Iron Steel Build Up Only4 N/A No2 N/A Build Up Only4 N/A Notes: 1 For TEFC model numbers beginning with 324TTFC or 326TTFC consult the motor manufacturer to determine if a build up motor is required. 2 The max applied down load is any applied load external to the motor, including such things as sheave weight, fan loads, axial belt force, pump load, etc. If the application is direct drive with no applied radial load, consult the motor manufacturer. 3 "Build up only", refers to motors that are specifically ordered and built for shaft up applications. It does not imply that all build up motors are suitable for shaft up applications. !,! ;;' % (( 7'. % % $* /% * I/ ; % ? 6 * Do not connect or couple motor to load until correct rotational direction is established. !,!,< 6 $ '* ;$ ; $ ' 6 % of the motor and driven equipment minimizes vibration levels, maximizes bearing life, and extends the overall life of the machinery. Consult the drive or equipment manufacturer for more information. /% * 7 $ 6 '/$ During assembly do NOT force components onto the shaft. Striking or hammering the component may result in bearing damage. !,!,# ? $ % /;' 6* Use flexible couplings if possible. For applications that apply radial, axial or moment loading on the motor shaft see section 3.3.3. /% * 7 $ 6 '/$ Unless approved by the motor manufacturer do % direct couple a vertical shaft up or roller bearing motor. Direct coupling a vertical shaft up motor or a motor with a roller bearing may result in bearing damage. !,!,! ? $ % % ?* Radial loading for direct connected equipment (gears, fans etc.) must be approved by the motor manufacturer unless within the maximum overhung load limits (Table 3 2). Combined loading (axial, radial and/or moments) must be approved by motor manufacturer. For belted loads see section 3.3.4. % 1 !# B $ B ' 4- ' 1 J $ $; - (- 1 ! < <# K 143T 106 166 193 210 145T 109 170 199 218 182T 187 230 261 287 184T 193 237 273 301 213T 319 317 470 510 215T 327 320 480 533 254T 500 631 729 793 256T 510 631 736 820 284T 866 990 1100 286T 871 1005 1107 324T 950 1100 1215 326T 950 1113 1230 364T 1078 1365 1515 365T 1078 1380 1540 404T 1388 1590 1762 405T 1400 1610 1780 444T 1580 1795 2005 445T 1520 1795 1985 447T 1455 1765 1985 449T 1640 1885 2130 Values based on 26,280 hrs B 10 Life For "End of Shaft" Load multiply value by 0.88 To convert from lbf to N multiply value by 4.4482. !,!,@ 7 '% ?* The goal of any belted system is to efficiently transmit the required torque while minimizing the loads on the bearings and shafts of the motor and driven equipment. This can be accomplished by following four basic guidelines: 1. Use the largest practical sheave diameter. 2. Use the fewest number of belts possible. 3. Keep sheaves as close as possible to support bearings. 4. Tension the belts to the lowest tension that will still transmit the required torque without slipping. It is normal for V belts to squeal initially when line starting a motor !,!,@,< (- ) ? 6 * In general, smaller sheaves produce greater shaft stress and shaft deflection due to increased belt tension. See Table 3 3 for recommended minimum sheave diameters. Using larger sheaves increases the contact with belts which reduces the number of belts required. It also increases the belt speed, resulting in higher system efficiencies. When selecting sheaves, do not exceed the manufacturer's recommended maximum belt speed, typically 6,500 feet per minute for cast iron sheaves. Determine belt speed by the following formula: 4< 7 '% (; ? 9 L !,!,@,# 17 In general, use the fewest number of belts that will transmit the required torque without slipping. See Table 3 3 for recommended maximum number of belts. Each belt adds to the tension in the system, which increases load on the shafts and bearings. Belts are most efficient when operated at or near their rated horsepower. If the sheaves have more grooves than the number of belts required, use the grooves closest to the motor. !,!,@,! (- ) ' Install sheaves as close to the housing as possible to increase the bearing life of the motor and driven equipment 4# !,!,@,@ 7 % /% * : Belt tensioning by feel is % acceptable. Tensioning by "feel" can be very misleading, and can damage motor and equipment. It is normal for V belts to squeal initially when line starting a motor. In general, belt tensions should be kept as loose as possible while still transmitting the required torque without slipping. Belt tensions must be measured with a belt tension gage. These inexpensive gages may be obtained through belt manufacturers, or distributors. Proper belt tension is determined by measuring the force required to deflect the center of the belt a given distance. The proper deflection (in inches) is determined by dividing the belt span in inches by 64. Calculate the proper deflection and then see Table 3 3 for the required "Deflected Force" to achieve that deflection. After tensioning the belt, rotate the sheaves for several rotations or operate the system for a few minutes to seat belts into the grooves, then re tension the belts. New belts will stretch during use, and should be retensioned after the first eight hours of use. % 1 !! $ (- ) ? 7 %0 1 7 ? Min Sheave Dia (in) & <# Belt Type Max # of Belts Avg. Deflected Force (lbs) Min Sheave Dia (in) < Belt Type Max # of Belts Avg. Deflected Force (lbs) Min Sheave Dia (in) ! Belt Type Max # of Belts Avg. Deflected Force (lbs) 0 75 22 3VX 1 1 2.4 3VX 1 1.5 2.4 3VX 2 2 2.4 3VX 3 3 3.0 3VX 2 5 3.0 3VX 3 7.5 3.8 3VX 4 10 4.4 3VX 4 15 4.4 3VX 5 20 5.2 3VX 6 25 6.0 3VX 7 30 68 3VX 7 40 6.8 5VX 4 50 8.2 5VX 4 60 8.2 5VX 5 75 10.0 5VX 5 100 10.0 5VX 6 125 12.0 5V 7 150 13.2 5V 7 200 15.0 5V 8 250 15.0 8V 6 300 16.0 8V 7 350 16.5 8V 7 400 17.5 8V 8 450 18 8V 8 500 18.5 8V 9 600 700 800 34 22 3VX 1 22 4.0 2.2 3VX 1 3.1 3.1 2.4 3VX 2 2.1 2.8 2.4 3VX 2 2.9 3.3 2.4 3VX 3 2.9 4.0 3.0 3VX 3 3.7 4.7 3.0 3VX 4 4.1 5.4 3.8 3VX 4 4.3 5.4 4.4 3VX 4 5.4 6.0 4.4 3VX 6 4.8 5.6 4.4 3VX 7 5.2 59 52 3VX 7 53 11.6 6.0 3VX 7 6.0 14.6 6.8 3VX 8 5.9 14.1 7.4 5VX 4 13.3 14.5 8.6 5VX 4 14.3 16.0 8.6 5VX 6 13 14.1 10.5 5V 6 13.1 15.4 10.5 5V 7 13.4 16.0 13.2 5V 8 13.1 27.6 14.0 5V 9 13.8 27.1 14.0 5V9 = 11 / A 23.4 30.3 14.5 5V/ = 12 / A 26.0 29.1 15.0 5V/ = 13 / 25.7 31.6 16.0 5V/ = 14 / K 25.2 30.7 16.5 5V/ = 15 / K 26.9 17.5 8V 11 26.3 19.0 8V 12 27.3 20.0 8V 13 28.2 22 3VX 1 13 2.2 3VX 1 1.6 2.2 3VX 1 2.5 2.4 3VX 1 2.7 2.4 3VX 2 2.3 2.4 3VX 3 2.5 3.0 3VX 2 4.2 3.0 3VX 3 3.8 3.8 3VX 3 4.4 4.4 3VX 3 5.0 4.4 3VX 4 4.7 +- 7 4 ! 6 - # &; * 1. Horsepower is the nameplate motor horsepower, and RPM is the motor (driver) speed. 2. Minimum sheave diameters are from NEMA standards where applicable. 3. )1 ) - , 4. Selections are based on a 1.4 service factor, 5 to 1 speed ratio and various Power Transmission Manufacturers' catalogs. 5. These selections are for Narrow V belt sections only. Consult manufacturer for details on conventional V belt sections (A, B, C, D and E), or other belt types. 6. "Average Deflected Force is per section 3.3.4.4 of this document and is the force required to deflect the center of a belt 1/64 of the belt span distance. Tolerance on this force is ±1 lbf for forces 10 lbs, and ±2 lbs for forces >10 lbs as measured utilizing a belt tension gage. 7. When more than one belt is required the belts must be a matched set (matched for length). 8. If possible, the lower side of the belt should be the driving side to increase the length of wrap on the sheave). 9. For belted loads do not exceed 125% of 60 Hz operating RPM. _________________________________________________________________________________________________________________________ !,!, = ? = 1 : 0? ) ;$% * 5 $ 6* = ? + - $ %- ; UL Recognition, UL Listing, or CSA certification does not apply to motors that are equipped with a manual or automatic reset thermal protector when the motor is operated on VFD power. 5 $ 6* ; + * Power factor correction capacitors should never be installed between the drive and the motor. /% * = ? 9 (* It is the responsibility of the startup personnel during set up of the VFD / motor system to properly tune the drive to the motor for the specific application per the VFD user manual. The correct voltage boost and volts per hertz settings are application dependent and unique to each motor design. Failure to connect over temperature devices (when provided) will void the warranty. !,!, ,< ) 1 0* Belted loads: Do not exceed 125% of 60 Hz operating RPM. % 1 !@ B ( ( $; ? ' 9M N (3 #; @ ; 56 180 [80 110] 7200 5400 210 250 [130 160] 5400 4200 280 [180] 5400 3600 320 [200] 4500 3600 360 [225] 4500 2700 400 440 [250 280] 3600 2700 >440 [>280] 3600 1800 = Fan cooled motors (Totally Enclosed & Hazardous Locations Motors) are limited to a maximum safe continuous speed of 4000 RPM - 4- - 00 !,!, ,# 1 ' 4 - * For optimum insulation life, limit VFD to motor cable lengths of general purpose motors to Table 3 5 values. Definite purpose VFD motors may accommodate longer cable lengths. For additional information contact motor manufacturer. % 1 ! B 1 ' 4- 6 ; These values are based on 3 kHz carrier frequency. Add suitable VFD output side filters when exceeding the listed values. (3 #! = @ = A = !# 600 ft. 125 ft. 40 ft. ! << 1000 ft. 225 ft. 60 ft. # 180 m. 40 m. 12 m. ## # , 300 m. 70 m. 18 m. !,!, ,! = ? 6 4* Equipment grounding conductors may be run in the same conduit as the AC motor power leads. This wire must be used as the equipment ground for the motor and not as the fourth current carrying wire of a "WYE" motor circuit. The grounded metal conduit carrying the output power conductors can provide EMI shielding, but the conduit does not provide an adequate ground for the motor; a separate grounding conductor must be used. Grounding the motor neutral (WYE) of a VFD powered motor may result in a VFD ground fault trip. Improper grounding of an inverter fed motor may result in frame voltages in excess of 500 Volts. Refer to Grounding section 3.4.4 !,!, ,@ = ? " ( 4 ;- * /% * ( 6' ;& ( % $ '/$ * Single Phase motors are % suitable for use on VFD power. Connecting a Single Phase Motor to a VFD voids the warranty. !,!, , ( 0 = 4 0' * VFD's will couple stray (common mode) voltage to motor mounted RTDs, thermistors, thermostats and space heaters. The leads of these elements must be properly insulated and control input circuits must be designed to withstand this common mode voltage. !,!, (( $ ( 9 ;$ = ( (* !,!, ,< 6 * Carefully read and understand the accessory manufacturer's instructions, supplied with motor. Contact the manufacturer for additional information. !,!, ,# 7 8 : /% * = ; 78 Motors with brakes that are designed for vertical applications are equipped with springs to support the brake pressure plate. Mounting a horizontal brake motor vertically shaft up or down may require a pressure plate spring modification. Failure to modify the brake for the vertical application may result in premature brake failure. If in question, consult brake literature or brake manufacturer. 78 ( 5 4* Do NOT connect the brake solenoid to the output of a VFD. The brake solenoids must be wired to 50/60 Hz line power !,!, ,! ( & * Motors provided with space heaters have two leads that are brought into the conduit box or into an auxiliary box. These leads are marked "H1", "H2" ("H3", "H4" if a second space heater is supplied). See the space heater nameplate on motor for heater rating. 5 $ 6* ? = ( # H;' ( & G $? The space heater temperature rating when used in Class I, Division 2 motors shall % exceed 80% of the auto ignition temperature of the hazardous gas or vapor. See the space heater nameplate on motor for heater Temperature Code and heater rating. Failure to follow this instruction could result in serious personal injury, death and/or property damage !,!, ,@ %- ; * 6 * When thermal protection is provided, one of the following will be stamped on the nameplate: <, O%& $ ''. ;$ % % ?" This motor has built in thermal protection. Thermal protectors open the motor circuit electrically when the motor overheats or is overloaded. The protector cannot be reset until the motor cools. If the protector is automatic, it will reset itself. If the protector is manual, disconnect motor from power supply. After protector cools (five minutes or more) press the reset button and reapply power to the motor. In some cases a motor is marked "Auto" and the connection diagram on the motor will identify T'Stat leads see "2 " below. (See warnings on Manual and Automatic reset protectors section 1.1) #, O5 %& = $& % ;$ % % = ? = ": This motor is provided with an overheat protective device that does not directly open the motor circuit. Motors nameplated with this phrase have either thermostats, thermisters or RTD's. The leads to these devices are routed into the motor conduit box or into an auxiliary box. The lead markings are defined on the nameplate (normally "P1", "P2") . The circuit controlled by the overheat protection device must be limited to a maximum of 600 volts and 360 volt amps. See connection decal provided inside the terminal box cover. Failure to connect these over temperature devices (when provided) will void the warranty. 5 $ 6* H;' ( & G $? For Hazardous Locations motors provided with thermostats UL and the NEC require connection of thermostat leads into the control portion of a manual reset start circuit. Failure to follow this instruction could result in serious personal injury, death and/or property damage $ % ? $%? * When winding and/or bearing RTDs are provided the RTD lead markings are defined on the nameplate. (Normally "R1", "R2", "R3" etc.) !,!, , $%? >% ( 4 * Tables 3 6 & 3 7 are suggested initial RTD alarm and trip settings. For motors found to operate significantly below these values the settings may be reduced accordingly. %1 ! @ B ' 5 4 $%? " % 1 7% $ % Up to 1.0 SF 130 140 >1.0 to 1.15 SF 140 150 ' % $ < % 155 165 160 165 % 1 ! A 7 4 $%? " % ' @ B1 1 % Up to 40 95 100 > 40 110 115 Bearings that are Heat Stabilized to 130 135 150 !,!,A 6/ $?(* 5 $ 6* $ % % 6 ; $%( & G $? When devices are assembled to the motor shaft, be sure to install protective devices such as belt guards, chain guards, and shaft covers. These devices must protect against accidental contact with extremities, hair, and clothing. Consider the application and provide guarding to protect personnel. Remove all unused shaft keys and loose rotating parts to prevent them from flying off and causing bodily injury. Failure to follow this warning could result in serious personal injury, death and/or property damage. !,@ ' %$ ' % (* 5 $ 6* ' %$ ' & G $?( Before proceeding read Section 1 1 on Electrical Safety. Failure to follow the instructions in Section 1 1 could result in serious personal injury, death and/or property damage !,@,< ; 5 $ (/;;'. 9 7$ & $ / % 5 $ 6* ; 5 $ (/;;'. ; % 7 ' %. & G $? Check power supply to make certain that voltage, frequency and current carrying capacity are in accordance with the motor nameplate. Failure to match motor nameplate values could result in serious personal injury, death and/or property damage 5 $ 6* 7$ & $ / % (/;;'. & G $? Motor and control wiring, fusing, overload protection, disconnects, accessories and grounding must always conform to the applicable electrical codes as well as local codes and sound practices. !,@,<,< 7 - ( 0 to a motor should include a disconnect switch, short circuit current fuse or breaker protection, motor starter (controller) and correctly sized thermal elements or overload relay protection. !,@,<,# 78 ) $0 Short Circuit Current Fuses or Breakers are for the protection of the branch circuit. Starter or motor controller overload relays are for the protection of the motor. Each of these should be properly sized and installed per the applicable electrical codes as well as local codes and practices. 5 $ 6* ;$ % % = ? = ? ( 7' ? & G $? DO NOT bypass or disable protective devices. Protection removal could result in serious personal injury, death and/or property damage !,@,<,! ; + ( 0 ' Motors are designed to operate within the following limits at the motor terminals: 1 AC power is within +/ 10 % of rated voltage with rated frequency applied. (Verify with nameplate ratings) $ 2 AC power is within +/ 5% of rated frequency with rated voltage $ 3 A combined variation in voltage and frequency of +/ 10% (sum of absolute values) of rated values, provided the frequency variation does not exceed +/ 5% of rated frequency. 4 For 3 phase motors the line to line full load voltage must be balanced within 1%. 5 If the motor is rated 208 230V, the voltage deviations must be calculated from 230V. /% * $ ; Operation outside of these limits will degrade motor performance and increase operating temperature. !,@,# % $ ' 7 H* !,@,#,< 4* For ease of connections, motors are typically provided with large terminal boxes. Most motors have conduit access in 90 degree increments, the terminal box conduit opening is typically provided via knockouts, holes with covers, or the terminal box is rotate able. Fabricated conduit boxes may have a removable plate for the installer to provide correctly sized hole(s). !,@,#,# & 3 ' * 5 $ 6* H;' ( & G $?( < % 7B +- : If a pipe nipple mounted terminal box is removed or rotated it must be reassembled with a minimum of five full threads of engagement. # $ ) : Do not set a terminal box component on its machined surfaces. Prior to component reassembly wipe clean all machined surfaces. ! - ( 6 &3 ' % 7 B * The gap between mating surfaces with the machined terminal box MUST BE LESS THAN 0.002 inches. This gap must be checked with a feeler gage along the entire perimeter. If there is visible damage to the mating surfaces, or if the gap between these surfaces exceeds 0.002 inches, DO NOT complete the installation and contact the motor manufacturer. Failure to follow these instructions could result in serious personal injury, death and/or property damage !,@,! ' ? %( Electrical connections to be made per nameplate connection diagram or separate connection plate. In making connections follow the applicable electrical code as well as local codes and practices. 5 $ 6* ' %$ ' % & G $? Failure to correctly connect the motor leads and grounding conductor can result in injury or death. Motor lead connections can short and cause damage or injury if not well secured and insulated. !,@,!,< 5 ( 3 ( 4 ;- $ : The minimum wire size for Single Phase, 115 & 230 Volt Circuits must meet table 3 8 for a given distance between motor and either Fuse or Meter Box. %1 ! 5 << > #! = ? 6 4 ( 3 ( 4 ;7B <, #, !, , &; << #! << #! << #! << #! <9@ 14 14 10 12 8 10 6 8 <9! 12 14 10 12 6 10 4 8 <9# 10 12 8 10 6 8 4 6 !9@ 10 12 6 10 4 8 2 6 < 8 10 6 8 4 6 4 < <9# 4 10 0 8 6 4 # 8 6 4 2 ! 8 6 4 2 6 4 2 0 !,@,!,# B ( 4 ;- * Where an extension cord(s) is utilized to provide power to the motor the extension cord(s) must be...(1) the proper gauge size per table 3 8, (2) in good working condition (3) properly grounded. !,@,@ 6$ / ? % (* 5 $ 6* ' %$ ' 6$ / ? 6 & G $? For general information on grounding (USA) refer to NEC Article 250. Improper grounding of an inverter fed motor may result in frame voltages in excess of 500 Volts. In making the ground connection, the installer must make certain that a good electrical connection is obtained between motor and grounding lead. Failure to properly ground motors, per the applicable national code (such as NEC Article 430) and local codes may cause serious injury or death to personnel. ; 0O P6 * A grounding conductor must be connected to the grounding terminal provided in the terminal housing. This grounding terminal is either a ground screw, ground lug, or a tapped hole to be used with a separately provided ground screw. The internal grounding feature is accessible inside the terminal housing and must be used as the primary grounding connection. ( 0O B P6 * Some motors are provided with a supplemental grounding terminal located on the external surface of the motor frame or feet. This external terminal is for supplemental bonding connections where local codes permit or require such connection !,@, (% $% /;* 5 $ 6* ' %$ ' (& F & G $?* Be certain that all connections are secure and the conduit box cover is fastened in place before electrical power is connected. Failure to follow these instructions could result in serious personal injury, death, and/or property damage. 5 $ 6* ' ( > $ % % 6 ; $%( & G $? Before proceeding read Section 1 2 on Mechanical Safety. Failure to follow the instructions in Section 1 2 could result in serious personal injury, death and/or property damage 5 $ 6* H (( = (/$ % ; $ %/$ & G $? Motors with the temperature code stated on the nameplate are designed to operate within this limit. Improper application or operation can cause the maximum surface temperature to be exceeded. A motor operated in a Hazardous Location that exceeds this surface temperature limit increases the potential of igniting hazardous materials. (1) Motor load exceeds service factor value, (2) Ambient temperature above nameplate value, (3) Voltages outside of limits (3.4.1.3), (4) Loss of proper ventilation, (5) VFD operation exceeding motor nameplate rating, (6) Altitude above 3300 feet / 1000 meters, (7) Severe duty cycles, (8) Repeated starts, (9) Motor stall, (10) Motor reversing, and (10) Single phase operation. Failure to follow these instructions could result in serious personal injury, death and/or property damage. /% * & % (/$ Normal motor surface temperatures may exceed 90 ° C (194° F). Touching the motor frame may cause discomfort or injury. Surface temperatures should only be measured with suitable instruments and not estimated by hand touch. !,@, ,< ( / '; <, - 8 * Before startup carefully read and fully understand these instructions including all warnings, cautions and safety notice statements. #, 4 -- -* Check winding insulation integrity with a Megger. If winding resistance to ground is less than 1.5 Meg ohms consult the local authorized service shop before energizing the motor. !, - 8 *- Check tightness of all bolts and nuts. Manually rotate the motor shaft to ensure motor shaft rotates freely. Note: Shaft & bearing seals will add drag. Inspect all electrical connections for proper terminations, clearance, mechanical tightness and electrical continuity. Be sure to verify connections are made per the nameplate connection diagram or separate connection plate. Replace all panels and covers that were removed during installation before energizing the motor. @, 43 * - 8$ If practical check motor rotation before coupling to the load. Unlock the electrical system. Momentarily provide power to motor to verify direction of rotation. If opposite rotation is required, lock out power before reconnecting motor. If motor has a rotational arrow only operate the motor in the rotation identified. Reapply power to ensure proper operation. ,$ ' 5 >= 4 * Recommend To establish a baseline value check and record the no load amps, watts, and voltage. !,@, ,# ( / " ' ; <, - 8 * Before startup carefully read and fully understand these instructions including all warnings, cautions safety notice statements. #, 4 * Check that the connected equipment is properly aligned and not binding. Check that all guards and protective devices are properly installed. !, 43 * When all personnel are clear of the machine, apply power and verify that the load is not transmitting excessive vibration back to the motor though the shaft or the foundation. Verify that motor amps are within nameplate rating. For repeated starts see 3.4.5.3. The equipment can now be fully loaded and operated within specified limits as stated on the nameplate. !,@, ,! C 44 4 9 $ ( Do not start more than twice in succession under full load. Repeated starts and/or jogs of induction motors can cause overheating and immediate failure. Contact the motor manufacturer if it is necessary to repeatedly start or jog the motor. @, % * 5 $ 6* & 3 ' $ & G $?* Division 1 Hazardous Locations motors can only be modified or repaired by the manufacturer or a facility that is Listed under UL's category "Motors and Generators, Rebuilt for use in Hazardous Locations". Failure to follow these instructions could result in serious personal injury, death and/or property damage. 5 $ 6* ' %$ ' (& F & G $? Electrical connections are to be made by qualified electrical personnel in accordance with all applicable codes, ordinances and sound practices. Failure to follow these instructions could result in serious personal injury, death and/or property damage. Only qualified personnel who are familiar with the applicable national codes, local codes and sound practices should install or repair electric motors and their accessories. 5 $ 6* ' %$ ' ' = $ / % & G $? Do not touch electrically live parts. Disconnect, lockout and tag input power supply before installing or servicing motor (includes accessory devices). @,< 6 $ ' (; % Inspect the motor approximately every 500 hours of operation or every three months, whichever occurs first. Keep the motor clean and the ventilation and fin openings clear. The following steps should be performed at each inspection: @,<,< = % ' % * Check that the ventilation openings and/or exterior of the motor is free of dirt, oil, grease, water, etc, which can accumulate and block motor ventilation. If the motor is not properly ventilated, overheating can occur and cause early motor failure. @,<,# (/' % : Use a "Megger" periodically to ensure that the integrity of the winding insulation has been maintained. Record the Megger readings. If winding resistance to ground is less than 1.5 Meg ohms consult the local authorized service shop before re energizing the motor. @,<,! ' %$ ' % (* Check all electrical connectors to be sure that they are tight. @,# '/7$ % > 7 $ 6(* The lubricating ability of grease (over time) depends primarily on the type of grease, the size of the bearing, the speed at which the bearing operates and the severity of the operating conditions. Longer bearing life can be obtained if the listed recommendations are followed: NOTE: If lubrication instructions are provided on the motor nameplate, the nameplate instructions will supersede these instructions. Motors marked "Permanently Lubricated" do not require additional service. /% * 7 $ 6 9 % $ ? 6 5 $ 6 Lubricant should be added at a steady moderate pressure. If added under heavy pressure bearing shield(s) may collapse. Over greasing bearings greatly increases bearing friction and can cause premature bearing and/or motor failure. @,#,< 6$ ( %.; -+ * 1% 1 + ! Q ##Q Q <Q ) * Recommended grease for standard service conditions is Mobil Polyrex ® EM. Equivalent and compatible greases include: Texaco Polystar RB, Rykon Premium #2, Pennzoil Pen 2 Lube, Chevron SRI & Mobil SHC 100. 1% 1 + ! Q ##Q ): Special low temperature grease is recommended, such as Aeroshell 7 or Beacon 325 for ball bearings and Mobil SHC 100 for roller bearings. 1% 1 ) Q < Q ): Dow Corning DC44 or equivalent, a special high temperature grease is required. Note that Dow Corning DC44 grease does not mix with other grease types. For RTD settings see Table 3 7. @,#,# 7 $ 6 ; $ % 6 % ; $ %/$ * /% * & % (/$ The external surface temperature of the end shield (bracket) bearing hub may reach 100° C (212° F) during normal operation. Touching this surface may cause discomfort or injury. Surface temperatures should only be measured with suitable instruments and not estimated by hand touch. _________________________________________________________________________________________________________________________ @,#,! '/7$ % % $= '(* +- 4 4) :, @,# ' 1 ) L M% 1 @< - N B M ) % 1 @#N B M % 1 @!N %1 ( ? @< ' 1 9M N )& (3 RA# %- ) 1 ) 4( " $; ( % 1 !,@ R@ R@ R! 4 , B R< 4( R<# 56 180 [80 110] 2500 Hrs. 4000 Hrs 5000 Hrs 6000 Hrs. 17000 Hrs. 20000 Hrs. 210 250 [130 160] 2500 Hrs 4000 Hrs 5000 Hrs. 12000 Hrs. 16000 Hrs. 280 [180] 2000 Hrs 3000 Hrs 4000 Hrs. 10000 Hrs. 14000 Hrs. 320 [200] 2000 Hrs 3000 Hrs. 9000 Hrs. 12000 Hrs. 360 [225] 1500 Hrs 2000 Hrs. 8000 Hrs. 10000 Hrs. 400 440 [250 280] >440 [>280] 1500 Hrs. 1000 Hrs. 4000 Hrs. 3000 Hrs. 7000 Hrs. 5000 Hrs. ( ) * If motor remains idle for more than six months, Lubricate at the beginning of the season, then follow lubrication interval. B B 4 % 1 !@+ - D ) % 1 @# ( ) / - 4- ) () 0 () : Maximum Ambient Temperature and Contamination are independent factors B 1 % - Standard Severe Extreme Less than 40° C (104° F) Clean, Slight Corrosion, indoors, less than 16 hrs per day 1.0 Above 40° C (104° F) to 50° Moderate dirt or Corrosion or outdoors or more than 16 hrs C per day 0.5 Greater than 50° C or Class H Insulation Severe dirt or Abrasive dust or Corrosion 0.2 ________________________________________________________________________________________________________________________ % 1 @! Angular Contact or Roller Bearing 0.5 Vertical Motor 0.5 All others 1.0 %1 @@$ 1 (3 = ,, 3 48 56 80 0.25 0.14 4.0 143 145 90 0.25 0.14 4.0 182 184 110 0.50 0.28 8.0 213 215 130 0.75 0.42 12.5 254 256 160 1.00 0.55 16.0 284 286 180 1.50 0.83 25.0 324 326 200 2.00 1.11 33.0 364 365 225 3.00 1.66 50.0 404 405 250 3.80 2.11 62.0 444 449 280 4.10 2.27 67.0 >449 >280 4.50 2.50 74.0 For regreasing while operating multiply volume by 125%. ________________________________________________________________________________________________________________________ @,#,@ '/7$ % ;$ ?/$ * + -$ 4 4; ) /% * 7 $ 6 ? 6 5 $ 6 Added grease must be compatible with the original equipment's grease. If a grease other than those stated in 4.2.1 is to be utilized contact the motor manufacturer. Nameplate information supersedes section 4.2.1 (GREASE TYPE). New grease must be free of dirt. Failure to follow these instructions and procedure below may result in bearing and/or motor damage. For an extremely dirty environment, contact the motor manufacturer for additional information. '/7$ % ;$ ?/$ * <, Clean the grease inlet plug or zerk fittings prior to regreasing. #, (If present) Remove grease drain plug and clear outlet hole blockage. /% * 6$ ( ?$ ;'/66 ?* Old grease may completely block the drain opening and must be mechanically removed prior to regreasing. Forcing a blocked drain open by increased greasing pressure may collapse bearing shields and / or force excess grease through the bearings and into the motor. !, Add grease per Table 4 4 @, Re install grease inlet and drain plugs (if removed). 5 $ 6* H;' ( & G $? ? % energize a Hazardous Locations motor without all grease fittings properly installed. @,#, H ;' * '/7$ % Assume NEMA 286T (IEC 180), 1750 RPM Vertical motor driving an exhaust fan in an ambient temperature of 43° C and the atmosphere is moderately corrosive. <, Table 4 1 list 10,000 hours for standard conditions. #, Table 4 2 classifies severity of service as "Severe" with a multiplier of 0.5. !, Table 4 3 lists a multiplier value of 0.5 for "Vertical" @, (Eq. 4.2) Interval = 10,000 hrs x 0.5 x 0.5 = 2500 hrs 3 Table 4 4 shows that 1.5 in of grease is to be added. ! $1 ) 0# - ) + - <, 4 , @,! %$ /7' (& % 6 5 $ 6* $ ? (%$/ % (* Before trouble shooting a motor, carefully read and fully understand the warnings, cautions safety notice statements in this manual. 5 $ 6* & 3 ' $* Motors nameplated for use in Division 1 Hazardous Locations can only be disassembled, modified or repaired by the plant of manufacturer or a facility that is Listed under UL's category "Motors and Generators, Rebuilt for use in Hazardous Locations". Failure to follow these instructions could result in serious personal injury, death and/or property damage /% * ? ( (( 7'. ;;$ = ' $ I/ $ ?* Motor disassembly must be performed by a party approved by the motor manufacturer. To disassemble the motor without approval voids the warranty. @,!,< 6 $ ' %$ /7' (& % 6 5 $ 6( <, ? ( % ; 5 $ % %& %$ 7 $ ; $ $ 6 ( $= $ % , #, ? - 4 1 )4 , !, + 0 8 - - 4 +0 )4 , @, 7 : 04 1 4: , , -1 - , @,!,# %1 - 4 * '8 0 * 9 ) %1 @ ) * * , Supply voltage is too low or is severely unbalanced (one (1) Check power supply fuses (2) Match motor lead wiring to nameplate connection phase is low or missing). diagram and supply voltage (3) Ensure that steady state supply voltage at motor terminals is within limits (see section 3.4.1.3). Correct as needed (4) Obtain correct 7, Motor leads are miswired at conduit box. motor to match actual supply voltage. , Driven load exceeds motor capacity ?, Load is jammed. , Fan guard is bent and making contact with fan (1) Verify that motor & load turn freely (2) Disconnect motor from load & ensure motor turns freely. Note: Roller bearings make noise when motor is uncoupled and shaft is rotated (3) Verify that motor starts when disconnected from load (4) Remove excessive / binding load if present. Replace fan guard & fan (if blades are damaged) , VFD with power factor capacitors installed Remove power factor correction capacitors if equipped 6, VFD with motor neutral lead grounded &, VFD programmed incorrectly Ensure that motor neutral lead is ungrounded (1) Repeat checks listed above (2) Verify that VFD current limit and starting boost are set correctly (5) Double check motor and feedback parameter settings and VFD permissives (6) Repeat autotune (for vector drives) procedure (7) Consult VFD supplier. -1 4- ++ * (1) Replace fuse or reset circuit breaker. Allow motor to cool down before resetting , Supply voltage unbalanced has drooped or has become severely manual protector on motor. 5 4 See section reset protector warnings (2) Verify that rated and 1.1 for automatic balanced supply and manual voltage has been restored before restarting motor. Measure voltage during restart. Ensure that steady state supply voltage at motor terminals is within limits (see section 3.4.1.3). 7, Motor is overloaded , Motor bearings are seized ?, Load Is jammed. , VFD will not restart motor after tripping , Capacitor failure on single phase motor (if equipped) 8 4 * (1) Verify that motor & load turn freely. Repair binding components as needed (2) Reduce driven load to match motor capacity or increase motor size to match load requirements. (1) Check fault codes on VFD and follow VFD troubleshooting procedures (2) Verify that VFD input voltage is balanced and within limits (3) Remove excessive mechanical load if present. 5 4* ; (- 8 & 3 : Contact service shop to check capacitor. , Motor leads are not connected correctly Match motor lead wiring to nameplate diagram. 7, Supply voltage unbalanced. has drooped or become severely (1) Ensure that steady state supply voltage at motor terminals is within limits (see section 3.4.1.3). Correct as needed (2) Obtain correct motor to match actual supply voltage. , Load exceeds motor capability Determine correct motor size and contact motor representative to obtain replacement motor. ?, Faulty start capacitor (Single Phase) Motor may be too small for load. Record acceleration time. Start capacitors may fail if acceleration time exceeds 3 seconds. , Mechanical Failure -+ 4 , Incorrect wiring connection at motor )- ) (1) Check to make sure motor & load turn freely (2) Disconnect motor from load & ensure motor turns freely * [Single Phase] Reconnect motor according to wiring schematic provided. Some motors are non reversible [Three Phase] Interchange any two power supply (phase) leads. Note: 0 , Driven Load is excessive 7, Ambient temperature too high , Motor cooling fins and/or vent openings blocked ?, Insufficient Air Flow (1) If motor current exceeds nameplate value, ensure that driven load has not increased. Correct as needed. (2) If new motor is a replacement, verify that the rating is the same as the old motor. If previous motor was a special design, a general purpose motor may not have the correct performance. Most motors are designed to operate in an ambient up to 40 C. (See section 4.2.2 Hot Surface Caution) Remove foreign materials clear vent openings, fan guard air inlets and frame fins (TEFC motors) TEAO (Totally Enclosed Air Over) motors: Measure airflow next to motor surface and obtain minimum requirements from motor manufacturer. , Motor is started too frequently , Supply voltage too low, too high, or unbalanced =1 , Motor misaligned to load. 7, Load out of balance (Direct drive application) , Uneven tension on multiple belts See section 3.4.5.3 (1) Ensure that steady state supply voltage at motor terminals is within limits (see section 3.4.1.3) Correct as needed (2) Reconnect motor per input voltage (3) Obtain correct motor to match power supply. Realign load (1) Ensure that load is dynamically balanced: (2) Remove motor from load and inspect motor by itself. Verify that motor shaft is not bent. Rule of thumb is 0.002" runout for shafts extension lengths up to 3.00". Add 0.0005" per every additional inch of shaft length beyond 3.00". Mixing new with used belts. Replace multiple belt applications with a complete set of matched belts. (1) De energize motor and record vibration as load coasts from 100% speed to 0 RPM. If vibration drops immediately, vibration source is electrical. If levels do not ?, Driven load operating at resonant point / natural drop immediately, source is mechanical (2) Redesign system to operate below the frequency. resonant point (3) On VFD driven loads, program skip frequencies to bypass resonant points (4) Increase carrier frequency to obtain <3% THD current (5) On variable torque loads reduce volts/hertz below base speed. , VFD torque pulsations , Motor miswired at terminal box 6, Uneven, weak or loose mounting support. &, Motor bearings defective , Motor out of balance (1) Adjust VFD to obtain <3% THD current @ rated motor current (2) Adjust VFD stability for smooth operation. Vector drives may be unstable at light load. Match motor lead wiring to nameplate connection diagram. Shim, strengthen or tighten where required. Test motor by itself. If bearings are bad, you will hear noise or feel roughness. Roller bearings are normally noisy when operated without load. If sleeve bearing, add oil per nameplate instructions. For motors with regreasing provisions, add grease per relubricating instructions (see section 4.2.3). If noise persists contact warranty service. Disconnect from load. Set motor on rubber pads on solid floor. Secure a ½ height key in shaft keyway and energize from balanced power supply @ rated voltage. Record vibration levels and compare with appropriate standards. If excessive vibration persists contact motor manufacturer. 74 0, , Load to motor may be excessive or unbalanced 7, Bearings contaminated. , Incorrect grease or bearings for ambient extremes. ?, VFD bearing damage (1) If belt drive check system per section 3.3.4. (2) Other than belting, check loading on motor shaft. An unbalanced load will also cause the bearings to fail. (3) Check runouts of mating components, such as a C face and pump flange. Motor enclosure not suitable for environment. Replace with correct enclosure construction See section 4.2.1 Ground brush, common mode filter, or insulated bearings must be added. Contact motor manufacturer. 8 11 4 4 4: 4 , , Contact between rotating and stationary components Belt squeal during across the line starting is normal: (1) Verify that supply voltage is within limits (see section 3.4.1.3). (2) Ensure that motor lead wiring matches nameplate connection diagram: (3) Isolate motor from load. (4) To locate point of contact turn motor shaft by hand. (5) If point of contact is not located contact motor service shop. ( 0, , The motor acceleration time is too long 7, Motor is being started too frequently , Motor voltage low ?, Defective start switch inside motor $ , Motor may be too small for load. Record acceleration time. Start capacitors may fail if acceleration time exceeds 3 seconds. Excessive starting will damage motor capacitors. Contact motor manufacturer if motor is started more than 20 times/hour or if acceleration time exceeds 3 seconds. Verify that voltage at the motor terminals is within limits (see section 3.4.1.3). Motor internal switch failure overheats start capacitor. Contact service shop or motor manufacturer. , High ambient temperature Verify that the ambient does not exceed motor's nameplate value 7, Input voltage exceeds limit Verify that voltage to the motor terminals is within limits (see section 3.4.1.3). , Power surge to motor (caused high transient voltage). by lightning strike or other If a common problem, install surge protector.