Owner's Manual for DELTA models including: Amplon RT Gen3 Series UPS 1-3 kVA Single Phase, Amplon RT Gen3 Series, UPS 1-3 kVA Single Phase, kVA Single Phase, Single Phase

ZARINA.LIAO 廖巧婷

Amplon RT Gen3 Series UPS

Mar 31, 2025 — User manual. More Product Information. USB cable (1.5 m). AC input cable with Schuko plug (1.5 m). External battery cable (1.5 m). Ear kit and tower stand.

PDF preview unavailable. Download the PDF instead.

Leaflet UPS RT-Gen3-1-3 kVA LB en-gb EKAGCE-06-ZL
Amplon RT Gen3 Series UPS
Single-phase, 1-3 kVA, 230 Vac
Extended Runtime Model
Safeguard your edge with a smart and economical power solution
Delta's Amplon RT series UPS is a robust online double-conversion UPS offering strong power protection with a convertible rack and tower configuration in 2U size. With its clean output power in pure sine wave, RT Gen3 can handle a wide range of utility problems, from blackout to harmonic distortion. Rest assured that your device is always fortified and safeguarded with RT Gen3!
High Availability
· True online double-conversion topology and zero transfer time to battery mode · Operates at up to 50 adapting to various environments · Excellent overload capacity allows the overload condition to continue within the timeframe
Green with Low TCO
· Output power factor 0.9 provides more capacity to load · Up to 90% online mode efficiency and 95% ECO mode efficiency contributes to significant energy cost savings · Capable of working in harsh electrical environments with a wide input voltage range to minimize battery usage
Easy Management
· Convertible rack and tower configuration with rotatable LCD screen · LCD display and intuitive interface offer effortless monitoring and configuration · Excellent local communications through rotatable LCD display · Intelligent management software connectivity via RS-232, mini slot or USB port for remote monitoring and setting

IT

Telecom

Industrial Transportation

Financial Government

SME

Retail

Rear Panel

LCD

Form Factor

Runtime Table

1 kVA
UPS+1EBC UPS+2EBC UPS+3EBC UPS+4EBC

90 W 87.4 201.9 318.3 435.3

180 W 38.2 96.7 158.5 221.2

270 W 22.3 59.2 100.2 142.5

360 W 15.4 40.6 70.5 102.0

450 W 12.0 29.9 52.9 77.6

540 W 10.0 23.2 41.4 61.5

630 W 8.8 18.8 33.5 50.2

720 W 7.7 15.8 27.8 41.8

810 W 6.6 13.7 23.6 35.5

900 W 5.3 12.2 20.4 30.7

2 kVA
UPS+1EBC UPS+2EBC UPS+3EBC UPS+4EBC

180 W 90.8 209.3 329.7 450.7

360 W 39.8 100.6 164.6 229.6

540 W 23.3 61.7 104.3 148.1

720 W 16.0 42.3 73.5 106.2

900 W 12.4 31.2 55.2 80.9

1080 W 10.4 24.3 43.2 64.1

1260 W 9.1 19.7 35.0 52.3

1440 W 8.0 16.5 29.0 43.7

1620 W 6.9 14.3 24.6 37.1

1800 W 5.7 12.7 21.3 32.0

3 kVA
UPS+1EBC UPS+2EBC UPS+3EBC UPS+4EBC

270 W 58.8 142.8 229.5 317.1

540 W 24.9 65.9 111.3 158.0

810 W 15.1 39.2 68.6 99.7

1080 W 11.2 26.6 47.3 70.0

1350 W 9.2 19.7 34.9 52.4

(1) Up to 4 EBCs can be paralleled. (2) Runtime table is estimated based on operation at 25 °C with batteries fully charged.

1620 W 7.6 15.6 27.1 40.9

1890 W 5.8 13.1 22.0 33.1

2160 W 3.3 11.5 18.4 27.5

2430 W 2.5 10.3 15.8 23.3

2700 W 2.0 9.4 14.0 20.2
Unit: min

Technical Specifications

Model Topology Power Rating
INPUT Nominal Voltage Voltage Range Frequency Range Power Factor
OUTPUT Nominal Voltage Voltage Regulation Frequency Total Harmonic Distortion (THDv) Power Factor Connection Overload Capability Current Crest Ratio
EFFICIENCY Online Mode ECO Mode
BATTERY Battery Type Nominal Voltage Parallel Configuration Charge Current
COMMUNICATION INTERFACE Display Port
PHYSICAL Dimensions (W x D x H) Net Weight Packing Dimensions (W x D x H) Packing Weight
ENVIRONMENT Operating Temperature Humidity Audible Noise Altitude Storage Temperature Ingress Protection
CONFORMANCE Safety EMC Sustainability
(1) De-rating to 70% load

RT-1K Online double-conversion 1 kVA 0.9 kW

RT-2K
2 kVA 1.8 kW

RT-3K
3 kVA 2.7 kW

208(1)/220/230/240 Vac, 1P2W+PE 180-280 Vac (100% load); 120-300 Vac (50-100% load) 40-70 Hz  0.99 (100% load)

208(1)/220/230/240 Vac, 1P2W+PE

±1%

50/60 ± 3 Hz

< 3% (linear load)

0.9

IEC C13 x4

IEC C13 x4 + IEC C19 x1

< 105-110%: 10 mins; 110-130%: 30 secs; 130-150%: 3 secs

3:1

88% 93%

94%

90% 95%

VRLA, External battery cabinet (Optional)

36 Vdc

72 Vdc

Up to 4 EBCs

1/ 2/ 4/ 6 A (configurable)

LCD display with LED indicators USB, RS-232, mini slot (option for mini SNMP, mini MODBUS and mini relay I/O card)

438 x 310 x 86 mm 5.7 kg 600 x 500 x 240 mm 9.4 kg

438 x 410 x 86 mm 8.4 kg 565 x 700 x 240 mm 12.8 kg

438 x 460 x 86 mm 8.9 kg 545 x 760 x 240 mm 13.3 kg

0 to 50 °C (40 to 50 °C de-rating to 70% load) 10-90% (non-condensing)  50 dBA 0-3000 m (derating 1%/100 m from 2000-3000 m) -20 to 50 °C IP20

CE, UKCA, KC IEC 62040-2 RoHS, REACH

All specifications are subject to change without prior notice.

Management Solution
UPSentry  Supports RS-232 & USB communication  Schedules shutdown, restart and battery test  Event tracking ShutdownAgent  Provides a graceful unattended shutdown of multiple loads in a
network SNMP IPv6 (optional)  Remote UPS management from any workstation through
internet or intranet  UPS and system function configuration from any client (password protected)  Event logs and data tracking

What's in the Box
Standard Accessories
RT Gen3 UPS USB cable (1.5 m) External battery cable (1.5 m) UPSentry software

User manual AC input cable with Schuko plug (1.5 m) Ear kit and tower stand ShutdownAgent software

More Product Information

Optional Accessories

External Battery Cabinet
RT-1K External Battery Cabinet
(Part number: BBA032B9009035)
RT-2/3K External Battery Cabinet
(Part number: BBA062B6009135)

Net Dimensions (W x D x H) 438 x 410 x 86 mm
438 x 410 x 86 mm

Net Weight 13.8 kg
21.9 kg

Packing Dimensions (W x D x H) Packing Weight

600 x 500 x 240 mm

15.8 kg

600 x 500 x 240 mm

23.9 kg

UPS Management Accessories
Mini SNMP IPv6
(Part number: SCMS100035)
Mini Relay I/O Card
(Part number: 3915101864-S)
Mini MODBUS Card
(Part number: 3915101865-S)

Manages UPS and system functions securely and adjusts parameters through SNMP management stations or internet browsers using HTTP forms.
Offers 6 relay output contacts to monitor status and 2 input contacts for simple shutdown and battery testing in UPS management.
Supports MODBUS communication with a PC via RS-485 and RS-232 interfaces, allowing for flexible and simultaneous use.

Installation
Rail Kit
(Part number: 3915100011)

Mount UPS and External Battery Cabinet within a 19'' rack.