Owner's Manual for Honeywell models including: VA301C Analytics Network Controller, VA301C, VA301C Analytics Controller, Analytics Network Controller, Analytics Controller

Click here to download

Honeywell VA301C toxic gases, combustible gases, and oxygen hazard monitor - Fire Alarm Resources - Free fire alarm PDF manuals, documents, installation instructions, and technical specifications


File Info : application/pdf, 2 Pages, 1.05MB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676769816
VA301C
Offering unique zoning capabilities which permit the averaging and comparison of multiple sensor readings firealarmresources.com

The VA301C continuously monitors and controls toxic gases, combustible gases, and oxygen hazards. Designed for installation and operational simplicity, the VA301C reduces the cost of installation and ownership.
Using an addressable RS-485 Modbus communication protocol, the 301C uses daisy chain wiring requiring only 2 pairs of wires to connect up to 96 transmitters on the 3 input channels. This simplifies installation, in turn lowering costs. The 301C's zoning and averaging abilities significantly reduce operational and maintenance costs.

User Friendly
· Zero maintenance · Automatic quick self-test and warm-up · Continuous alphanumeric display
Inexpensive and Reliable
· Low installation costs · Allows for up to 126 zoning groups which can save
energy and extend fan and relay life
· Manages up to 768 events with programmable latching alarms
Flexible Operation
· Modbus compatible; with BACnet/IP available · Interchangeable transmitters able to detect different
gases
· Expands to handle up to 96 transmitters or relay modules and up to 50 301W wireless sensors
· Programmable time delays · Integrated time clock enables scheduling of system
operations
Safety Measures
· Full array of visual indicators and integrated 65dBA alarm levels
· Fully programmable relays (can be set as fail-safe or not)
Beneficial Options
· Available in a heavy duty industrial housing · Datalogging option

Zoning/Averaging Capabilities Reduce Operational Costs The 301C controller offers unique zoning capabilities which permit the averaging and comparison of multiple sensor readings. Zoning can reduce operational costs by ensuring that localized brief fluctuations registered at a single transmitter do not activate relays. For example, a car idling in a parking structure may locally increase a reading at a nearby transmitter. Rather than activating a fan as a result of the temporary localized fluctuation, zoning can be used to limit relay activation until the average reading for a zone exceeds a set-point. This can reduce run time of fans, yielding savings in both energy usage and wear and tear. The 301C has the capacity to manage input from three Modbus channels for up to 96 transmitters and up to 50 wireless transmitters which can be associated with up to 126 zones. Transmitters can belong to an unlimited number of zones, providing maximum operational and control flexibility.

General Specifications

Use

Modbus controller for centralized gas detection monitoring with real-time gas reading, selective alarm activation and low

cost of installation.

Size

28 x 20.3 x 7 cm (11.02 x 7.99 x 2.76 in.)

Weight

1.1 kg (2.4 lb.)

Power Requirement

17-27 Vac, 24-38 Vdc, 500 mA

Network Capacity

Three Modbus channels for up to 96 transmitters, one wireless channel for up to 50 301W wireless transmitters and an optional BACnet/IP output

Communication Line Lengths

Up to 609 m (2000 ft.) per channel T-Tap: 20 m (65 ft.), maximum per T-Tap 40 m (130 ft.), maximum for all T-Tap combined

Relay Output Rating

5 A, 30 Vdc or 250 Vac (resistive load)

Alarm Levels

3 fully programmable alarm levels

Time Delays

0, 30 sec., 45 sec., 1-99 minutes before and after alarm

Outputs

4 DPDT relays (alarms and/or fault); 65dBA buzzer

Display

Large 122 x 32 dot matrix display

Operating Humidity Range

0-95% RH, non-condensing

Operating Temperature Range

-20 to 50°C (-4 to 122°F)

Ratings and Certifications

Certified to

CAN/CSA C22.2 No 61010-1

Conforms to

116662
ANSI/UL 61010-1 IEC 61010-1 Including Amendments A1:1992 + A2:1995 and National Deviations (Canada, US)

Please Note: While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract. © 2007 Honeywell Analytics
H_301C_DS01015_V3 10/09 © 2009 Honeywell Analytics
firealarmresources.com

HWA6075

