Neptronic Networkable Wall-Mount Controller

Specification and Installation Instructions

Models

>
Model Temp RH PIR
TSUB00-100
TSUB30-100
TSUB60-100
TSUB00-101
TSUB30-101
TSUB60-101
TSUB00-104
TSUB30-104
TSUB60-104
TSUB00-105
TSUB30-105
TSUB60-105

The TSUB is a universal wall-mount controller with a built-in temperature sensor. The unit is designed for simple and accurate control of a fan coil unit or heating/cooling equipment. Its field configurable algorithms enable versatile implementation of required control sequences.

The controller is available with additional sensors, such as the PIR motion detection and humidity sensor, providing more functionality for the terminal device.

Equipped with an on-board humidity sensor, for accurate humidity control, this comprehensive unit also provides a dehumidification sequence compensated by auto activation of reheat output.

Features

Onboard Sensors

Network Communication

BACnet MS/TP

Modbus

Technical Specifications

Temperature Sensor

>
Description Value
Setpoint Range 10°C to 40°C [50°F to 104°F]
Control Accuracy Temperature: ±0.4°C [0.8°F]
Display Resolution ±0.1°C [0.2°F]

Humidity Sensor (select models)

>
Description Value
Setpoint Range 10% to 90% RH
Control Accuracy ±3.5% RH
Display Resolution 0.1%

PIR Motion Sensor (select models)

>
Description Value
Operating Principle Passive Infrared (PIR)
Detection Angle 100°
Detection Distance 4m [13ft]

Detection Area:

4m [13ft]

100°

Other

>
Description Value
Inputs 2 Universal Inputs (0-10Vdc, 10kΩ sensor, dry contact)
Outputs 5 Binary Outputs (OptoFET, 250mA max)
2 Analog Outputs (0-10Vdc, adjustable, 5mA max)
Power supply 22 to 26 Vac or Vdc 50/60Hz
Power consumption 1 VA max
Proportional band 0.5°C to 5°C [1°F to 9°F] adjustable (heat/cool/reheat independent)
Dead band 0.0°C to 5°C [0.0°F to 9°F] adjustable (heat/cool/reheat independent)
Electrical connection 0.8 mm² [18 AWG] minimum
Operating temperature 0°C to 50°C [32°F to 122°F]
Storage temperature -30°C to 50°C [-22°F to 122°F]
Relative Humidity 5 to 95% noncondensing
Degree of protection of housing IP 30 (EN 60529)
Weight 135 g. [0.30 lb]

Dimensions:

A = 4.88" | 124mm

B = 3.25" | 83mm

C = 1.75" | 44mm

D = 0.96" | 24mm

E = 2.07" | 53mm

F = 2.36" | 60mm

G = 3.28" | 83mm

H = 0.78" | 20mm

PIR Sensor (Optional)

E

A

B

G

F

H→

Wiring

We strongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.

TB1

JP1

Mode Selector Jumper

RUN = Operation Mode

PGM = Programming Mode

Temperature and Humidity sensors

BACnet service port

End of Line

None = No end of line

120Ω = Last node on network

Terminal Description

>
Terminals Analog Option On/Off
Fan analog 1-Speed Fan 2-Speed Fan 3-Speed Fan Fan analog 1-Speed Fan 2-Speed Fan 3-Speed Fan
1 COM Common
2 24V 24V (power supply) 24V (power supply)
3 EXT SRC External power supply External power supply
4 N/A N/A N/A
5 N/A N/A N/A
6 BO3 select any ramp* select any ramp* select any ramp* select any ramp* On/Off Valve (COr) Fan (speed 3) Fan (speed 3) Fan (speed 3)
7 BO4 select any ramp* select any ramp* select any ramp* select any ramp* Fan (speed 2) Fan (speed 2) Fan (speed 2)
8 BO5 select any ramp* Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1)
9 BO6 select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp*
10 BO7 Fan Speed option • Modulating 0-10Vdc for ECM Motors • Steps of 3,6,9V for 3 Speed Heating Ramp 1 (Hr1) Heating Ramp 1 (Hr1) Heating Ramp 1 (Hr1)
11 AO2 Fan Analog Local Reheat (HR1) Fan Analog Local Reheat (HR1)
12 AO3 Changeover with fan (COr)
13 COM Common Common
14 UI1 Universal Input selection: • 0-10 Vdc (External sensor, humidity, CO2) • 10K Ohm (External sensor, changeover) • Dry Contact**
15 UI2
16 A+ BACnet communication port (A+)
17 B- BACnet communication port (B-)

* = select from any of the following ramps:

• Cooling 1 w/ fan • Cooling 2 w/ fan • Heating 1 w/ fan • Heating 2 w/ fan • Heating 2 without fan • Off

• Cool/Heat 1 w/ fan • COR (changeover) w/ fan • Humidify w/ fan • CO2 Alarm • Off

** = select from any of the following:

• Dirty Filter • Window & Door Contacts • Occupancy & NSB Sensor • Changeover Input

Wiring - 2 Pipe Terminal Description Details

>
Terminals Analog On/Off
Fan analog 1-Speed Fan 2-Speed Fan 3-Speed Fan Fan analog 1-Speed Fan 2-Speed Fan 3-Speed Fan
1 COM Common
2 24V 24V (power supply) 24V (power supply)
3 EXT SRC External power supply External power supply
4 N/A N/A N/A
5 N/A N/A N/A
6 BO3 select any ramp* select any ramp* select any ramp* select any ramp* On/Off Valve (COr) Fan (speed 3) Fan (speed 3) Fan (speed 3)
7 BO4 select any ramp* select any ramp* select any ramp* select any ramp* Fan (speed 2) Fan (speed 2) Fan (speed 2)
8 BO5 select any ramp* Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1)
9 BO6 select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp*
10 BO7 Heating Ramp 1 (Hr1) Heating Ramp 1 (Hr1) Heating Ramp 1 (Hr1) Heating Ramp 1 (Hr1) Heating Ramp 1 (Hr1) Heating Ramp 1 (Hr1) Heating Ramp 1 (Hr1) Heating Ramp 1 (Hr1)
11 AO2 Fan Analog Local Reheat (HR1) Fan Analog Local Reheat (HR1)
12 AO3 Changeover with fan (COr) Changeover with fan (COr)
13 COM Common Common
14 UI1 Universal Input selection: • 0-10 Vdc (External sensor, humidity, CO2) • 10K Ohm (External sensor, changeover) • Dry Contact**
15 UI2
16 A+ BACnet communication port (A+)
17 B- BACnet communication port (B-)

* = select from any of the following ramps:

• Cooling 1 w/ fan • Cooling 2 w/ fan • Heating 1 w/ fan • Heating 2 w/ fan • Heating 2 without fan • Off

• Cool/Heat 1 w/ fan • COR (changeover) w/ fan • Humidify w/ fan • CO2 Alarm • Off

** = select from any of the following:

• Dirty Filter • Window & Door Contacts • Occupancy & NSB Sensor • Changeover Input

Wiring - 4 Pipe Terminal Description Details

>
Terminals Cool: Analog Heat: Analog Cool: On/Off Heat: On/Off
1-Speed Fan 2-Speed Fan 3-Speed Fan Fan Analog 1-Speed Fan 2-Speed Fan 3-Speed Fan Fan Analog 1-Speed Fan 2-Speed Fan 3-Speed Fan
1 COM Common
2 24V 24V (power supply) 24V (power supply)
3 EXT SRC External power supply External power supply
4 N/A N/A N/A
5 N/A N/A N/A
6 BO3 select any ramp* select any ramp* select any ramp* select any ramp* On/Off Heating Valve (Hr1) Fan (speed 3) Fan (speed 3) Fan (speed 3) On/Off Cooling Valve (Cr1) Fan (speed 3) Fan (speed 3) Fan (speed 3)
7 BO4 select any ramp* select any ramp* select any ramp* select any ramp* Fan (speed 2) Fan (speed 2) Fan (speed 2) Fan (speed 2) Fan (speed 2) Fan (speed 2) Fan (speed 2)
8 BO5 select any ramp* Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1)
9 BO6 select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp*
10 BO7 Heating Valve (Hr1) Cooling Valve (Cr1) Heating Valve (Hr1) On/Off Cooling Valve (Cr1)
11 AO2 Fan Analog Local Reheat (HR1) Fan Analog Local Reheat (HR1) Fan Analog Local Reheat (HR1)
12 AO3 Changeover with fan (COr) Changeover with fan (COr) Changeover with fan (COr)
13 COM Common Common
14 UI1 Universal Input selection: • 0-10 Vdc (External sensor, humidity, CO2) • 10K Ohm (External sensor, changeover) • Dry Contact**
15 UI2
16 A+ BACnet communication port (A+)
17 B- BACnet communication port (B-)

* = select from any of the following ramps:

• Cooling 1 w/ fan • Cooling 2 w/ fan • Heating 1 w/ fan • Heating 2 w/ fan • Heating 2 without fan • Off

• Cool/Heat 1 w/ fan • COR (changeover) w/ fan • Humidify w/ fan • CO2 Alarm • Off

† = Fan Speed Option:

• Modulating: 0-10Vdc for ECM Motors • Steps of 3,6,9V for 3 Speed

Power Supply for Binary Outputs

Using Internal Power Supply for BOs

TB1

COM (1

24V

24V (2

EXT SRC (3

Jumper

Line

Voltage

Using External Power Supply for BOs

TB1

COM (1

24V

24V (2

EXT SRC (3

To External (Secondary)

Power Supply

Wiring - 4 Pipe Terminal Description Details

>
Terminals Cool: Analog Heat: Analog Cool: On/Off Heat: On/Off
1-Speed Fan 2-Speed Fan 3-Speed Fan Fan Analog 1-Speed Fan 2-Speed Fan 3-Speed Fan Fan Analog 1-Speed Fan 2-Speed Fan 3-Speed Fan
1 COM Common
2 24V 24V (power supply) 24V (power supply)
3 EXT SRC External power supply External power supply
4 N/A N/A N/A
5 N/A N/A N/A
6 BO3 select any ramp* select any ramp* select any ramp* select any ramp* On/Off Heating Valve (Hr1) Fan (speed 3) Fan (speed 3) Fan (speed 3) On/Off Cooling Valve (Cr1) Fan (speed 3) Fan (speed 3) Fan (speed 3)
7 BO4 select any ramp* select any ramp* select any ramp* select any ramp* Fan (speed 2) Fan (speed 2) Fan (speed 2) Fan (speed 2) Fan (speed 2) Fan (speed 2) Fan (speed 2)
8 BO5 select any ramp* Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1) Fan (speed 1)
9 BO6 select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp* select any ramp*
10 BO7 Heating Valve (Hr1) Cooling Valve (Cr1) Heating Valve (Hr1) On/Off Cooling Valve (Cr1)
11 AO2 Fan Analog Local Reheat (HR1) Fan Analog Local Reheat (HR1) Fan Analog Local Reheat (HR1)
12 AO3 Changeover with fan (COr) Changeover with fan (COr) Changeover with fan (COr)
13 COM Common Common
14 UI1 Universal Input selection: • 0-10 Vdc (External sensor, humidity, CO2) • 10K Ohm (External sensor, changeover) • Dry Contact**
15 UI2
16 A+ BACnet communication port (A+)
17 B- BACnet communication port (B-)

* = select from any of the following ramps:

• Cooling 1 w/ fan • Cooling 2 w/ fan • Heating 1 w/ fan • Heating 2 w/ fan • Heating 2 without fan • Off

• Cool/Heat 1 w/ fan • COR (changeover) w/ fan • Humidify w/ fan • CO2 Alarm • Off

† = Fan Speed Option:

• Modulating: 0-10Vdc for ECM Motors • Steps of 3,6,9V for 3 Speed

Interface

>
Icon Description Icon Description Icon Description

Network

Communication

Alarm Status

°C: Celsius Scale

°F: Fahrenheit Scale

%RH: Humidity

Heating

User Lock

Energy Saving Mode

(NSB/OCC)

AM PM

Time

Programming Mode

(Technician Setting)

A

Automatic Mode

Fan

Cooling

Humidify/

De-humidify

Mounting Instructions

CAUTION: Remove power to avoid a risk of malfunction.

  1. Remove the captive screw that's holding the base and the front cover of the unit together.
  2. Lift the front cover of the unit to separate it from the base.
  3. Pull all wires through the holes in the base.
  4. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections.
  5. Mount the control module on the base and secure using the screw.

A

B

C

D

E

Do not use the supplied screws to mount the unit to an electric box or an equivalent device. The supplied screws are only suitable for mounting the unit to the wall. Ensure to use the appropriate screws for any other application. Tighten by hand only and ensure not to overtighten the screws.

Programming Mode

The Mode Selector jumper JP1 must be set to the PGM position (Programming Mode). Refer to the Wiring section on page 3. To exit, set the jumper back to the RUN position (Operation Mode). Advance to the next or return to the previous setting in order to save a changed value.

Setting Value

Advance to next setting

Change value

Return to previous setting

Symbols used in this Manual

>
Icon Description Icon Description Icon Description Icon Description
Temperature Heating Cooling Humidity
Fan A02 Analog Output 2 A03 Analog Output 3 12 9 3 6 Time
BO3 Binary Output 3 BO4 Binary Output 4 BO5 Binary Output 5 BO6 Binary Output 6
BO7 Binary Output 7 UI1 Universal Input 1 U12 Universal Input 2 NSB Night Set Back
OCC Occupancy Communication Valve Lock
CO2 Carbon Dioxide

Setpoint and User Control

1. "Intern Temp Sensor Offset"

Range: 0°C to 50°C [32°F to 122°F]

Offset: Max. ± 5°C [± 9°F]

Increment: 0.1°C [0.2°F]

Compare the displayed temperature reading with a known value from a thermometer or other temperature sensing device. To offset or calibrate the sensor, use the arrow buttons to set the desired temperature reading. This is useful for controllers installed in areas where the temperature read is slightly different than the room's actual temperature. For example, a controller placed right under the air diffuser.

2. "Minimum User Setpnt"

Default: 15°C [59°F]

Range: 10°C to 40°C [50°F to 104°F]

Increment: 0.5°C [1.0°F]

In Operation mode, you cannot decrease the setpoint to less than the value set as the minimum user point. The minimum value is restricted by the maximum value set at Step 3, "Maximum User Setpnt". In other words, the value that is set as the minimum cannot be greater than the maximum value.

3. "Maximum User Setpnt"

Default: 30°C [86°F]

Range: 10°C to 40°C [50 to 104°F]

Increment: 0.5°C [1.0°F]

In Operation mode, you cannot increase the setpoint to more than the value set as the maximum user point. The maximum value is restricted by the minimum value set at Step 2, "Minimum User Setpnt". In other words, the value that is set as the maximum cannot be less than the minimum value.

4. "User Setpnt locked"

Default: No (Unlocked)

Range: No (Unlocked), yES (Locked)

If set to No, the user setpoint option is not locked and the user can adjust the desired temperature setpoint. If set to yES, the user setpoint option is locked and the user cannot set the desired temperature setpoint. A lock symbol ? appears to indicate that the setpoint is locked.

5. "User Setpnt"

Default: 22°C [72°F]

Range: 10°C to 40°C [50°F to 104°F]

Increment: 0.5°C [1.0°F]

Set the desired temperature setpoint within the defined range. If the setpoint option was locked at Step 4, "User Setpnt locked", a lock symbol ? is displayed. The setpoint value is restricted by the minimum at Step 2, “Minimum User Setpnt" and maximum at Step 3, "Maximum User Setpnt" values. In other words, the setpoint should be within the minimum and maximum setpoint range.

6. "Temp Control Mode"

Default: Auto (Automatic)

Range: Auto (Automatic), HEAt (Heating Only), COOL (Cooling Only), On (Cooling or Heating), CLHt (Automatic only)

Select the control mode that you want to authorize to the user. To authorize all the available modes, select Auto (Automatic Mode). The cooling and heating symbols are also displayed. The selection made at this step determines the options available via the Control Mode (see page 35).

7. "Enable On Off Control Mode"

Default: YES (Enable)

Range: YES (Enable), No (Disable)

If set to yES, the user can set the unit to "Off" via the Control Mode (see page 35). If set to No, the "Off" selection does not appear in the Control Mode.

8. "Display Info"

Default: t - Hu %RH °C

Range: t - Hu %RH °C (temperature, humidity), StP %RH °C (temperature, humidity setpoint), OFF (no display), t - Hu %RH °C (temperature, humidity, and cooling heating demand), StP %RH °C (temperature, humidity setpoint, and cooling heating demand)

Select the desired information to appear on the display.

Keypad Lock Settings

9. "Keypad Upper Left Locked"

Default: No (Disable)

Range: YES (Enable), No (Disable)

If set to yES, the ⬆ button is locked and cannot be used by the user. If set to No, the ⬆ button is unlocked and can be used by the user.

10. “Keypad Lower Left Locked”

Default: No (Disable)

Range: YES (Enable), No (Disable)

If set to yES, the ⬇ button is locked and cannot be used by the user. If set to No, the ⬇ button is unlocked and can be used by the user.

11. "Keypad Arrows Locked"

Default: No (Disable)

Range: YES (Enable), No (Disable)

If set to yES, the ◀ and ▶ buttons are locked and cannot be used by the user. If set to No, the ◀ and ▶ buttons are unlocked and can be used by the user.

Valve Settings

12. "Valve Size"

Default: 1"

Range: 1/2", 3/4", 1"

Select the desired valve size in inches for the 6-way valve from the available options.

Analog Output 2 (AO2)

13. "AO2 Ramp"

Default: Hr1 (Heating Ramp 1)

Range: Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, 6W, dto, VFdt, VFdP, FAN, OFF, COr

Select the desired signal from the available options.

14. "AO2 Minimum Voltage"

Default: 0.0 Volt

Range: 0.0 to 10.0 Volts

Increment: 0.1 Volt

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13, "AO2 Ramp"). Select the desired minimum voltage ("zero" value) for the AO2 ramp. The minimum value is restricted by the maximum value at Step 15, "AO2 Maximum Voltage". In other words, the minimum value should be less than the maximum value.

15. "AO2 Maximum Voltage"

Default: 10.0 Volts

Range: 0.0 to 10.0 Volts

Increment: 0.1 Volt

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13, "AO2 Ramp"). Select the desired maximum voltage ("span" value) for the AO2 ramp. The maximum value is restricted by the minimum value at Step 14, "AO2 Minimum Voltage". In other words, the maximum value should not be less than the minimum value.

16. "AO2 Off Voltage"

Default: MIN (Minimum voltage)

Range: MIN (Minimum voltage), OFF (0 Volt)

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13, "AO2 Ramp"). Set the analog output voltage when the controller is turned off. When set to MIN, the output will remain at the minimum voltage level defined by (Step 14, "AO2 Minimum Voltage"). When set to OFF, the output will remain at OV.

17. "AO2 Dirrev"

Default: dir (Direct)

Range: dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13, "AO2 Ramp"). Set the direction of the analog signal to either Direct (e.g. 0 to 10Vdc), or Reverse (e.g. 10 to 0Vdc).

18. "AO2 Signal Type"

Default: ANLg (Analog Output)

Range: ANLg (Analog Output), OnOF (On/Off), PuLs (Pulsing)

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13, "AO2 Ramp"). Set the signal type for AO2 to either Analog Output, On/Off or Pulsing.

Analog Output 3 (AO3)

19. "AO3 Ramp"

Default: Cr1 (Cooling Ramp 1)

Range: Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, 6W, dto, OFF, COr

Select the desired signal from the available options. The AO2 input signal has priority over AO3.

If you select OFF, Steps 0 to 24 will not be available.

If you select CH1, Step 25, "Minimum Cool 1 Heat 1 Percent" will be available.

If you select FAN, Step 26, "Fan Spd Signal" will not be available.

20. "AO3 Minimum Voltage"

Default: 0.0 Volt

Range: 0.0 to 10.0 Volts

Increment: 0.1 Volt

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19, "AO3 Ramp"). Select the desired minimum voltage ("zero" value) for the AO3 ramp. The minimum value is restricted by the maximum value at Step 21, "AO3 Maximum Voltage". In other words, the minimum value should be less than the maximum value.

21. "AO3 Maximum Voltage"

Default: 10.0 Volts

Range: 0.0 to 10.0 Volts

Increment: 0.1 Volt

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19, "AO3 Ramp"). Select the desired maximum voltage ("span" value) for the AO3 ramp. The maximum value is restricted by the minimum value at Step 20, "AO3 Minimum Voltage". In other words, the maximum value should not be less than the minimum value.

22. "AO3 Off Voltage"

Default: MIN (Minimum voltage)

Range: MIN (Minimum voltage), OFF (0 Volt)

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19, "AO3 Ramp"). Set the analog output voltage when the controller is turned off. When set to MIN, the output will remain at the minimum voltage level defined by Step 20, "AO3 Minimum Voltage". When set to OFF, the output will remain at OV.

23. "AO3 Dirrev"

Default: dir (Direct)

Range: dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19, "AO3 Ramp"). Set the direction of the analog signal to either Direct (e.g. 0 to 10Vdc), or Reverse (e.g. 10 to 0Vdc).

24. "AO3 Signal Type

Default: ANLg (Analog Output)

Range: ANLg (Analog Output), OnOF (On/Off), PuLs (Pulsing)

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19, "AO3 Ramp"). Set the signal type for AO3 to either Analog Ouptut, On/Off or Pulsing.

25. "Minimum Cool 1 Heat 1 Percent"

Default: 0%

Range: 0 to 100%

Increment: 5%

This option appears if you have selected CH1 at Step 13, "AO2 Ramp" or at Step 19, "AO3 Ramp”. Set the percentage at which the controller sets the CH1 output during heating, provided another output has also been set to heating.

Fan Settings

26. "Fan Spd Signal"

Default: 3

Range: 1, 2, 3

This option does not appear if you have selected FAN at Step 13, "AO2 Ramp". Select the desired number of fan speed contacts. The fan symbol ? is also displayed.

27. "Fan Speed Option"

Default: Std (Standard)

Range: AdV (Advanced), Std (Standard)

Select between the Standard (Neptronic) and Advanced (OE1) fan speed specifications. The fan symbol ? is also displayed.

28. "Enable Fan Ctrl Mode"

Default: No (Disable)

Range: YES (Enable), No (Disable)

This option appears only if you have selected Adv at Step 27, "Fan Speed Option". Select to enable or disable the fan control mode option. If you select No, the Fan Speed Selection Mode option is not available in Control Mode. The fan symbol ? is also displayed.

29. "Hide Fan Display Info"

Default: No (Disable)

Range: YES (Enable), No (Disable)

Select to enable or disable the fan display information. If you select Yes, the Fan demand (fan icon) does not appear on the display and the Fan Speed Selection Mode is disabled. The fan symbol ? is also displayed.

30. "Fan Auto Mode"

Default: YES (Enable)

Range: YES (Enable), No (Disable)

If set to yES, the user can set the fan speed to "Automatic" via the Fan Speed Selection Mode (see page 36). If set to No, the "Automatic" speed does not appear in the Fan Speed Selection Mode. The fan symbol ? is also displayed.

If you select yES, Step 31 "Fan Auto Timeout Seconds" will be available.

If you select No, Step 31 "Fan Auto Timeout Seconds" will not be available.

31. "Fan Auto Timeout Seconds"

Default: 120 seconds

Range: 0 to 255 seconds

Increment: 1 second

This option appears only if you have selected yES at Step 30, "Fan Auto Mode". Select the desired value for the automatic shutoff delay when there is no demand. The fan symbol ? is also displayed.

32. "Damping Factor Time In Seconds"

Default: 0 second

Range: 0 to 255 seconds

Increment: 1 second

Select the desired damping factor value for the fan. The fan symbol ? is also displayed.

Binary Output 3 (BO3)

33. "BO3 Ramp"

Default: Hr1 (Heating Ramp 1)

Range: Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr

Select the desired ramp from the available options.

If you select OFF, Steps 34 to 39 will not be available.

34. "BO3 Signal Type"

Default: OnOF (On/Off)

Range: tPm (Pulsing), OnOF (On/Off), FLot (Floating)

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, "BO3 Ramp"). Select the signal type for BO3 to either Pulsing, On/Off or Floating.

35. "BO3 Float Timer Seconds"

Default: 100 seconds

Range: 15 to 250 seconds

Increment: 5 seconds

This option only appears if the signal type for BO3 is set to FLot (Step 34, "BO3 Signal Type"). Set the time required for the valve actuator to complete a stroke.

36. "BO3 Close Percent"

Default: 20% of the demand

Range: 15 to 80%

Increment: 1%

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, "BO3 Ramp") and if the signal type for BO3 is set to either tPm or FLot (Step 34, "BO3 Signal Type"). Select the percentage at which you want BO3 to close (at % of demand of the ramp selected at Step 33, "BO3 Ramp").

37. "BO3 Open Percent"

Default: 0% of the demand

Range: 0 to (BO3 Close)-4%

Increment: 1%

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, "BO3 Ramp") and if the signal type for BO3 is set to either tPm or FLot (Step 34, "BO3 Signal Type"). Select the percentage at which you want BO3 to open (at % of demand of the ramp selected at Step 33, "BO3 Ramp").

38. "BO3 Dirrev"

Default: dir (Direct)

Range: dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, "BO3 Ramp") and if the signal type for BO3 is set to either tPm or FLot (Step 34, "BO3 Signal Type"). Set the direction of the binary signal to either Direct or Reverse.

39. "BO3 Contact Delay Minutes"

Default: 0 minute

Range: 0 to 15 minutes

Increment: 1 minute

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, "BO3 Ramp") and if the signal type for BO3 is set to either tPm or FLot (Step 34, "BO3 Signal Type"). Select the closing delay for BO3 output.

Binary Output 4 (BO4)

The Binary Output 4 settings appear only if you have selected either fan speed 1 or 2 at Step 26, "Fan Spd Signal" or VFdP, VFdt or FAN at Step 13, "AO2 Ramp".

40. "BO4 Ramp"

Default: OFF

Range: Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr

Select the desired ramp from the available options. Same as BO3 options.

If you select OFF, Steps 41 to 45 will not be available.

41. "BO4 Signal Type"

Default: OnOF (On/Off)

Range: tPm (Pulsing), OnOF (On/Off)

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40,"BO4 Ramp"). Select the signal type BO4 to either Pulsing or On/Off.

42. "BO4 Close Percent"

Default: 20% of the demand

Range: 15 to 80%

Increment: 1%

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40,"BO4 Ramp") and if the signal type for BO4 is set to tPm (Step 41, "BO4 Signal Type"). Select the percentage at which you want BO4 to close (at % of demand of the ramp selected at Step 40,"BO4 Ramp").

43. "BO4 Open Percent"

Default: 0% of the demand

Range: 0 to (BO4 Close)-4%

Increment: 1%

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40,"BO4 Ramp") and if the signal type for BO4 is set to tPm (Step 41, "BO4 Signal Type"). Select the percentage at which you want BO4 to open (at % of demand of the ramp selected at Step 40,"BO4 Ramp").

44. "BO4 Dirrev"

Default: dir (Direct)

Range: dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40,"BO4 Ramp") and if the signal type for BO4 is set to tPm (Step 41, "BO4 Signal Type"). Set the direction of the binary signal to either Direct or Reverse.

45. "BO4 Contact Delay Minutes"

Default: 0 minute

Range: 0 to 15 minutes

Increment: 1 minute

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40, "BO4 Ramp") and if the signal type for BO4 is set to tPm (Step 41, "BO4 Signal Type"). Select the closing delay for BO4 output.

Binary Output 5 (BO5)

The Binary Output 5 settings appear only if you have selected either fan speed 1 at Step 26, "Fan Spd Signal" or VFdP, VFdt or FAN at Step 13, "AO2 Ramp".

46. "BO5 Ramp"

Default: OFF

Range: Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr

Select the desired ramp from the available options. Same as BO3 options.

If you select OFF, Steps 47 to 51 will not be available.

47. "BO5 Signal Type"

Default: OnOF (On/Off)

Range: tPm (Pulsing), OnOF (On/Off)

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, "BO5 Ramp"). Select the signal type for BO5 to either Pulsing or On/Off.

48. "BO5 Close Percent"

Default: 20% of the demand

Range: 15 to 80%

Increment: 1%

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, "BO5 Ramp") and if the signal type for BO5 is set to tPm (Step 47, "BO5 Signal Type"). Select the percentage at which you want BO5 to close (at % of demand of the ramp selected at Step 46, "BO5 Ramp").

49. "BO5 Open Percent"

Default: 0% of the demand

Range: 0 to (BO5 Close)-4%

Increment: 1%

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, "BO5 Ramp") and if the signal type for BO5 is set to tPm (Step 47, "BO5 Signal Type"). Select the percentage at which you want BO5 to open (at % of demand of the ramp selected at Step 46, "BO5 Ramp").

50. "BO5 Dirrev"

Default: dir (Direct)

Range: dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, "BO5 Ramp") and if the signal type for BO5 is set to tPm (Step 47, "BO5 Signal Type"). Set the direction of the binary signal to either Direct or Reverse.

51. "BO5 Contact Delay Minutes"

Default: 0 minute

Range: 0 to 15 minutes

Increment: 1 minute

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, "BO5 Ramp") and if the signal type for BO5 is set to tPm (Step 47, "BO5 Signal Type"). Select the closing delay for BO5 output.

Binary Output 6 (BO6)

The Binary Output 6 settings appear only if you have selected either FAN, VFdt or VFdP at Step 13, "AO2 Ramp".

52. "BO6 Ramp"

Default: OFF

Range: Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, 6w, dto, VFdt, VFdP, OFF, COr

Select the desired ramp from the available options. Same as BO3 options. The VFdt and VFdP options are available only if you have selected them at Step 13, "AO2 Ramp".

If you select OFF, Steps 53 to 57 will not be available.

53. "BO6 Signal Type"

Default: OnOF (On/Off)

Range: tPm (Pulsing), OnOF (On/Off)

This option does not appear if the signal ramp for BO6 is set to OFF (Step 52, "BO6 Ramp"). Select the signal type for BO6 to either Pulsing or On/Off.

54. "BO6 Close Percent"

Default: 20% of the demand

Range: 15 to 80%

Increment: 1%

This option does not appear if the signal ramp for BO6 is set to OFF ((Step 52, "BO6 Ramp") and if the signal type for BO6 is set to tPm (Step 53, "BO6 Signal Type"). Select the percentage at which you want BO6 to close (at % of demand of the ramp selected at (Step 52, "BO6 Ramp").

55. "BO6 Open Percent"

Default: 0% of the demand

Range: 0 to (BO6 Close)-4%

Increment: 1%

This option does not appear if the signal ramp for BO6 is set to OFF ((Step 52, "BO6 Ramp") and if the signal type for BO6 is set to tPm (Step 53, "BO6 Signal Type"). Select the percentage at which you want BO6 to open (at % of demand of the ramp selected at (Step 52, "BO6 Ramp").

56. "BO6 Dirrev"

Default: dir (Direct)

Range: dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO6 is set to OFF ((Step 52, "BO6 Ramp") and if the signal type for BO6 is set to tPm (Step 53, "BO6 Signal Type"). Set the direction of the binary signal to either Direct or Reverse.

57. "BO6 Contact Delay Minutes"

Default: 0 minute

Range: 0 to 15 minutes

Increment: 1 minute

This option does not appear if the signal ramp for BO6 is set to OFF ((Step 52, "BO6 Ramp") and if the signal type for BO6 is set to tPm (Step 53, “BO6 Signal Type"). Select the closing delay for BO6 output.

Binary Output 7 (BO7)

The Binary Output 7 settings do not appear if the BO3 signal type is set to FLot at Step 34, "BO3 Signal Type".

58. "BO7 Ramp"

Default: Cr1

Range: Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr

Select the desired ramp from the available options. Same as BO3 options.

If you select OFF, Steps 59 to 63 will not be available.

59. "BO7 Signal Type"

Default: OnOF (On/Off)

Range: tPm (Pulsing), OnOF (On/Off)

This option does not appear if the signal ramp for BO7 is set to OFF (Step 58, "BO7 Ramp"). Select the signal type for BO7 to either Pulsing or On/Off.

60. "BO7 Close Percent"

Default: 20% of the demand

Range: 15 to 80%

Increment: 1%

This option does not appear if the signal ramp for BO7 is set to OFF (Step 58, "BO7 Ramp") and if the signal type for BO7 is set to tPm (Step 59, "BO7 Signal Type"). Select the percentage at which you want BO7 to close (at % of demand of the ramp selected at Step 58, “BO7 Ramp").

61. "BO7 Open Percent"

Default: 0% of the demand

Range: 0 to (BO6 Close)-4%

Increment: 1%

This option does not appear if the signal ramp for BO6 is set to OFF (Step 58, "BO7 Ramp") and if the signal type for BO7 is set to tPm (Step 59, "BO7 Signal Type"). Select the percentage at which you want BO7 to open (at % of demand of the ramp selected at Step 58, "BO7 Ramp").

62. "BO7 Dirrev"

Default: dir (Direct)

Range: dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO7 is set to OFF (Step 58, "BO7 Ramp") and if the signal type for BO7 is set to tPm (Step 59, “BO7 Signal Type"). Set the direction of the binary signal to either Direct or Reverse.

63. "BO7 Contact Delay Minutes"

Default: 0 minute

Range: 0 to 15 minutes

Increment: 1 minute

This option does not appear if the signal ramp for BO7 is set to OFF (Step 58, "BO7 Ramp") and if the signal type for BO7 is set to tPm (Step 59, "BO7 Signal Type"). Select the closing delay for BO7 output.

Proportional and Deadband Settings

64. "CH Over Prop Band"

Default: 2.0°C [4°F]

Range: 0.5°C to 5.0°C [1°F to 9°F]

Increment: 0.5°C [1°F]

Select the desired proportional band value of the changeover ramp. The cooling ❄️ and heating ? symbols are also displayed.

65. "CH Over Dead Band"

Default: 0.3°C [0.6°F]

Range: 0.0°C to 5.0°C [0°F to 9°F]

Increment: 0.1°C [0.2°F]

Select the desired dead band value of the changeover ramp. The cooling ❄️ and heating ? symbols are also displayed.

66. "Heat 1 Prop Band"

Default: 2.0°C [4°F]

Range: 0.5°C to 5.0°C [1°F to 9°F]

Increment: 0.5°C [1°F]

Select the desired proportional band value of the heating ramp 1. The heating symbol ? is also displayed.

67. "Heat 1 Dead Band"

Default: 0.3°C [0.6°F]

Range: 0.0°C to 5.0°C [0°F to 9°F]

Increment: 0.1°C [0.2°F]

Select the desired dead band value of the heating ramp 1. The heating symbol ? is also displayed.

68. "Heat 2 Prop Band"

Default: 2.0°C [4°F]

Range: 0.5°C to 5.0°C [1°F to 9°F]

Increment: 0.5°C [1°F]

Select the desired proportional band value of the heating ramp 2. The heating symbol ? is also displayed.

69. "Heat 2 Dead Band"

Default: 0.3°C [0.6°F]

Range: 0.0°C to 5.0°C [0°F to 9°F]

Increment: 0.1°C [0.2°F]

Select the desired dead band value of the heating ramp 2. The heating symbol ? is also displayed.

70. "Cool 1 Prop Band"

Default: 2.0°C [4°F]

Range: 0.5°C to 5.0°C [1°F to 9°F]

Increment: 0.5°C [1°F]

Select the desired proportional band value of the cooling ramp 1. The cooling symbol ❄️ is also displayed.

71. "Cool 1 Dead Band"

Default: 0.3°C [0.6°F]

Range: 0°C to 5.0°C [0°F to 9°F]

Increment: 0.1°C [0.2°F]

Select the desired dead band value of the cooling ramp 1. The cooling symbol ❄️ is also displayed.

72. "Cool 2 Prop Band"

Default: 2.0°C [4°F]

Range: 0.5°C to 5.0°C [1°F to 9°F]

Increment: 0.5°C [1°F]

Select the desired proportional band value of the cooling ramp 2. The cooling symbol ❄️ is also displayed.

73. "Cool 2 Dead Band"

Default: 0.3°C [0.6°F]

Range: 0.0°C to 5.0°C [0°F to 9°F]

Increment: 0.1°C [0.2°F]

Select the desired dead band value of the cooling ramp 2. The cooling symbol ❄️ is also displayed.

74. "Cooling Cycle Minutes"

Default: 0 minutes

Range: 0 to 15 minutes

Increment: 1 minute

To protect the compressor, set the delay in minutes before activating or reactivating the cooling output. The cooling symbol ❄️ is also displayed.

75. "Heating Intgral Time In Seconds"

Default: 0 seconds

Range: 0 to 250 seconds

Increment: 5 seconds

Set the desired value for heating integration factor compensation. The heating symbol ? is also displayed.

76. "Cooling Intgral Time In Seconds"

Default: 0 seconds

Range: 0 to 250 seconds

Increment: 5 seconds

Set the desired value for cooling integration factor compensation. The cooling symbol ❄️ is also displayed.

77. "Cl Ht Switch Timer Minutes"

Default: 0 minutes

Range: 0 to 120 minutes

Increment: 1 minute

Time required in minutes before a changeover can take place. The cooling ❄️ and heating ? symbols are also displayed.

Universal Input 1 (UI1)

78. "UI1 Signal Type"

Default: OFF

Range: OFF, t10.0, SENs, noCL, noHt, OAS, 110V, CO2, OCC, nSb, oVrd, win, door, dFt, FLS, oVht, SEL, FrFb, HU, P10V, t012, dt1t, dt1u, dt0t, dtou

Select the input signal type for UI1 (Universal Input 1).

If you select one of the following options: OFF, t10.0, SENs, noCL, noHt, OAS, 110V, CO2, HU, P10V, or t012, Steps 80 and 81 will not be available.

79. "UI1 Minimum Voltage"

Default: 2.0

Range: 0.0, 2.0

This option appears only if you have selected either P10V or t10V at Step 78, "UI1 Signal Type". Select the minimum voltage for UI1.

80. "UI1 Contact"

Default: NO (Normally Open)

Range: NO (Normally Open), NC (Normally Close)

This option appears only if you have selected any one of the options: OCC, nSb, oVrd, win, door, dFt, FLS, oVht, SEL at Step 78, "UI1 Signal Type". Select the desired contact option.

81. "UI1 Delay Seconds"

Default: 120 seconds

Range: 0 to 3600 seconds

Increment: 10 seconds

This option appears if you have selected any one of the options: oVrd, win, door, dFt, FLS, oVht, SEL at Step 78, "UI1 Signal Type". Set the delay in seconds before the state of input for UI1 is changed.

Universal Input 2 (UI2)

82. "UI2 Signal Type"

Default: OFF

Range: OFF, t10.0, SENs, noCL, noHt, OAS, t10V, CO2, OCC, nSb, oVrd, win, door, dFt, FLS, oVht, SEL, HU, P10V, t012

Select the input signal type for UI2 (Universal Input 2). Same options as Step 78, "UI1 Signal Type". The Ul1 input signal has priority over UI2. If you select the same input signal type as UI1, UI2 will not be functional.

If you select one of the following options: OFF, noCL, noHt, OAS or HU, Steps 83 to 95 will not be available.

If you select t10.0, Steps 83 to 87 will not be available.

If you select t10V, Steps 84 and 85 will not be available.

If you select SENs, Steps 83 to 88 will not be available.

If you select CO2, Steps 83 to 92 and 96 to 106 will not be available.

If you select P10V or t10V, Step 83, "UI2 Minimum Voltage" will be available.

If you select P10V, Step 96, "Pressur Maximum Range" will be available.

83. "UI2 Minimum Voltage"

Default: 2.0

Range: 0.0, 2.0

This option appears only if you have selected either P10V or t10V at Step 82, "UI2 Signal Type". Select the minimum voltage for UI2.

84. "UI2 Contact"

Default: NO (Normally Open)

Range: NO (Normally Open), NC (Normally Close)

This option appears only if you have selected any one of the options: OCC, nSb, oVrd, win, door, dFt, FLS, oVht, SEL at Step 82, "UI2 Signal Type". Select the desired contact option.

85. "UI2 Delay Seconds"

Default: 120 seconds

Range: 0 to 3600 seconds

Increment: 10 seconds

This option appears if you have selected any one of the options: oVrd, win, door, dFt, FLS, oVht, SEL at Step 82, "UI2 Signal Type". Set the delay in seconds before the state of input for UI2 is changed.

Temperature Settings

86. "Extern Temp Minimum"

Default: 0°C [32°F]

Range: -40.0°C to 0°C [-40°F to 32°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected any of the temperature sensors such as t10.0, t10v, or t012 at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type".

Set the minimum external temperature value. The minimum value is restricted by the maximum value set at Step 87, "Extern Temp Maximum". In other words, the value that is set as the minimum cannot be greater than the maximum value.

87. "Extern Temp Maximum"

Default: 50°C [122°F]

Range: 50°C to 100°C [122°F to 212°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected any of the temperature sensors such as t10.0, t10v, or t012 at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type".

Set the maximum external temperature value. The maximum value is restricted by the minimum value set at Step 86, "Extern Temp Minimum". In other words, the value that is set as the maximum cannot be less than the minimum value.

88. "Extern Temp Sensor Offset"

Range: -40.0°C to 100°C (-40°F to 212°F]

Offset: Max. ± 5°C [± 9°F]

Increment: 0.1°C [0.2°F]

This option appears only if you have selected any of the temperature sensors such as t10.0, t10v, or t012 at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type".

The display shows the temperature read by the external temperature sensor. Adjust the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, the unit displays the sensor's limit.

89. "Extern Temp 2 Minimum"

Default: 0°C [32°F]

Range: -40.0°C to 0°C [-40°F to 32°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected one of the t10.0, t10v, or t012 temperature sensors at Step 78, "UI1 Signal Type" and Step 82, "UI2 Signal Type".

For example, select t10.0 at Step 78, "UI1 Signal Type" and Step 82, "UI2 Signal Type".

Set the minimum external temperature value of sensor 2. The minimum value is restricted by the maximum value set at Step 90, "Extern Temp 2 Maximum". In other words, the value that is set as the minimum cannot be greater than the maximum value.

90. "Extern Temp 2 Maximum"

Default: 50°C [122°F]

Range: 50°C to 100°C [122°F to 212°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected one of the t10.0, t10v, or t012 temperature sensors at Step 78, "UI1 Signal Type" and Step 82, "UI2 Signal Type".

For example, select t10.0 at Step 78, "UI1 Signal Type" and Step 82, "UI2 Signal Type".

Set the maximum external temperature value of sensor 2. The maximum value is restricted by the minimum value set at Step 89, "Extern Temp 2 Minimum". In other words, the value that is set as the maximum cannot be less than the minimum value.

91. "Extern Temp Sensor 2 Offset"

Range: -40.0°C to 100°C (-40°F to 212°F]

Offset: Max. ± 5°C [± 9°F]

Increment: 0.1°C [0.2°F]

This option appears only if you have selected one of the t10.0, t10v, or t012 temperature sensors at Step 78, "UI1 Signal Type" and Step 82, "UI2 Signal Type". For example, select t10.0 at Step 78, "UI1 Signal Type" and Step 82, "UI2 Signal Type".

The display shows the temperature read by the external temperature sensor 2. Adjust the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, the unit displays the sensor's limit.

92. "CH Over Setpnt"

Default: 24.0°C [75°F]

Range: 10.0°C to 40.0°C [50°F to 104°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected SENs at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Set the desired changeover temperature setpoint. Note that the heating mode activates when the temperature read by the external sensor is above the changeover setpoint and cooling mode activates when the temperature read by the external sensor is below the changeover setpoint.

CO2 Sensor Settings

The CO2 Sensor Settings appear only for the following conditions: if you have selected CO2 at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type".

93. "CO2 Maximum Range"

Default: 2000 PPM

Range: 100 to 5000 PPM

Increment: 50 PPM

Select the maximum range value for carbon dioxide (CO2).

94. "CO2 Setpnt"

Default: 800 PPM

Range: 100 to 2000 PPM

Increment: 10 PPM

Indicates the maximum limit of the CO2 concentration beyond which an alarm is activated. The setpoint value is restricted by the maximum range at Step 93, "CO2 Maximum Range".

95. "Display CO2”

Default: No (Disable)

Range: No (Disable), YES (Enable)

Select whether to enable or disable the display of the CO2 value.

VFD Pressure Settings

The VFD Pressure Settings appear only if you have selected VFdP at Step 13, "AO2 Ramp" and P10V at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type".

96. "Pressur Maximum Range"

Default: 2000 Pa

Range: 200 to 200.0 Pa

Increment: 50 Pa

This option appears if you have selected P10V at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Select the maximum range for pressure. If the value is higher than 10,000, the value will be divided by 100 and shows a decimal point. For example, 10,000 will be displayed as 100.0 and 10050 will be displayed as 100.5.

97. "VFD Pressur Setpnt"

Default: 500 Pa

Range: 100 to pressure maximum range (value set at Step 96)

Increment: 1 Pa

Select the setpoint value for VFD pressure. If the value is higher than 10,000, the value will be divided by 100 and shows a decimal point. The increment is displayed as 0.1. The fan symbol ? is also displayed.

98. "VFD Pressur Dead Band"

Default: 50 Pa

Range: 0 to 100 Pa

Increment: 1 Pa

Select the desired dead band value for VFD pressure. The fan symbol ? is also displayed.

99. "VFD Pressur Prop Band"

Default: 200 Pa

Range: 100 to 500 Pa

Increment: 1 Pa

Select the desired proportional band value for VFD pressure. The fan symbol ? is also displayed.

100. "VFD Pressur Intgral Seconds"

Default: 0 seconds

Range: 0 to 250 seconds

Increment: 5 seconds

Set the desired value for VFD pressure integral seconds. The fan symbol ? is also displayed.

VFD Temperature Settings

The VFD Temperature Settings appear only if you have selected VFdt at Step 13, "AO2 Ramp".

101. "VFD Temp Setpnt sOURCE"

Default: VFd (VFD Temp Setpoint)

Range: VFd (VFD Temp Setpoint), CtrL (User Temp Setpoint)

Select the desired setpoint source for the VFD temperature control. The fan symbol ? is also displayed.

102. "VFD Temp Setpnt"

Default: 22.0°C [72°F]

Range: 10.0°C to 40.0°C [50°F to 104°F]

Increment: 0.5°C [1°F]

Select the desired VFD temperature setpoint. The fan symbol ? is also displayed.

103. "VFD Temp Dead Band"

Default: 0.3°C [0.6°F]

Range: 0.0°C to 5.0°C [0°F to 9°F]

Increment: 0.1°C [0.2°F]

Select the desired VFD temperature dead band value. The fan symbol ? is also displayed.

104. "VFD Temp Prop Band"

Default: 2.0°C [3.6°F]

Range: 0.5°C to 5.0°C [1°F to 9°F]

Increment: 0.1°C [0.2°F]

Select the desired VFD temperature proportional band value. The fan symbol ? is also displayed.

105. "VFD Temp Intgral Seconds"

Default: 0 seconds

Range: 0 to 250 seconds

Increment: 5 seconds

Set the desired value for VFD temperature integral seconds. The fan symbol ? is also displayed.

106. "VFD Temp Control Source"

Default: itS (internal)

Range: itS (internal), EtS (External), EtS2 (External2)

Select the source for VFD temperature control.

Temperature Control Source Settings

107. "Temp Control Source"

Default: itS (internal)

Range: itS (internal), EtS (External), nEt (Network)

Select the source for temperature control.

If you select its or Ets, Step 108, "Network Timeout Minutes" will not be available.

If you select nEt, Step 108, "Network Timeout Minutes" will be available.

108. "Network Timeout Minutes"

Default: 5 minutes

Range: 0 to 60 minutes

Increment: 1 minute

This option appears only if you have selected nEt at Step 107, "Temp Control Source". Select the duration in minutes after which the controller will go to OFF mode if it does not receive the temperature value via BMS.

Window and Door Settings

109. "Window Open Mode"

Default: StP (Setpoint/override enabled)

Range: StP (Setpoint/override enabled), OFF

This option appears only if you have selected win at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". The alarm symbol ? is also displayed.

110. "Window Fan Mode"

Default: AUto (Automatic)

Range: AUto (Automatic), LO (Low), mEd (Medium), HI (High)

This option appears only if you have selected win at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Select the fan speed mode when the window is open. The fan symbol ? and alarm A symbols are also displayed.

111. "Door Open Mode"

Default: StP (Setpoint/override enabled)

Range: StP (Setpoint/override enabled), OFF

This option appears only if you have selected door at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type".

112. "Door Fan Mode"

Default: AUto (Automatic)

Range: AUto (Automatic), LO (Low), mEd (Medium), HI (High)

This option appears only if you have selected door at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Select the fan speed when the door is open. The fan symbol ? and alarm A symbols are also displayed.

Night Set Back (NSB)

113. “NSB Overide Delay Minutes"

Default: 120 minutes

Range: 0 to 180 minutes

Increment: 15 minutes

This option appears only if you have selected nSb at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". When in Night Set Back (NSB) Mode, the user can override Night Set Back (NSB) (see page 36) for the duration of this delay. To disable night set back override, set the delay to 0. The moon symbol ? is displayed to indicate Night Set Back (NSB) Mode.

114. "NSB Fan Mode"

Default: AUto (Automatic)

Range: AUto (Automatic), LO (Low), mEd (Medium), HI (High)

This option appears only if you have selected nSb at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Select the fan speed mode for night set back. The fan symbol ? is also displayed.

115. "Nsb Mode"

Default: StP (Setpoint/override enabled)

Range: StP (Setpoint/override enabled), OFF

This option appears only if you have selected nSb at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type".

116. "NSB Heating Setpnt"

Default: 16°C [61°F]

Range: 10°C to 40°C [50°F to 104°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected nSb at Step 78, "UI1 Signal Type"or Step 82, "UI2 Signal Type". Set the heating setpoint that will be used when the system is in Night Set Back (NSB) Mode (see page 36). The heating setpoint value is restricted by the cooling setpoint value at Step 117, "NSB Cooling Setpnt". The moon symbol ? and heating symbols ? are also displayed.

117. "NSB Cooling Setpnt"

Default: 28°C [82°F]

Range: 10°C to 40°C [50°F to 104°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected nSb at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Set the cooling setpoint that will be used when the system is in Night Set Back (NSB) Mode (see page 36). The cooling setpoint value is restricted by the heating setpoint value at Step 116, "NSB Heating Setpnt". The moon symbol ? and cooling symbols ❄️ are also displayed.

Occupancy (OCC)

118. "ОСС Minimum Time In Minutes"

Default: 30 minutes

Range: 0 to 720 minutes

Increment: 1 minute

This option appears only if you have selected OCC at Step 78, "Ul1 Signal Type" or Step 82, "UI2 Signal Type". Set the minimum time in minutes the controller must remain in the occupied state before it can be enabled to enter or re-enter the No Occupancy Mode (see page 36). The moon symbol ? is also displayed.

119. "No OCC Override Delay Minutes"

Default: 120 minutes

Range: 0 to 180 minutes

Increment: 15 minutes

This option appears only if you have selected OCC at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". When in no occupancy mode, the user can override the No Occupancy Mode (see page 36) up to the duration of this delay by pressing the ? button. To disable the no occupancy override, set the delay to 0. The moon symbol ? is displayed to indicate the No Occupancy Mode.

120. "No OCC Fan Mode"

Default: AUto (Automatic)

Range: AUto (Automatic), LO (Low), mEd (Medium), HI (High)

This option appears only if you have selected OCC at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Select the fan speed mode for no occupancy mode. The fan symbol ? is also displayed.

121. "No OCC Mode"

Default: StP (Setpoint/override enabled)

Range: StP (Setpoint/override enabled), OFF

This option appears only if you have selected OCC at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". The moon symbol ? is also displayed.

If you select OFF, Steps 122 and 123 will not be available.

122. "No OCC Heating Setpnt"

Default: 16°C [61°F]

Range: 10°C to 40°C [50°F to 104°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected OCC at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Set the heating setpoint that will be used when the system is in Night Set Back (NSB) Mode/No Occupancy Mode/Window Open Mode/Door Open Mode. The heating setpoint value is restricted by the cooling setpoint value at Step 123, "No OCC Cooling Setpnt". The moon symbol ? and heating symbols ? are also displayed.

123. "No OCC Cooling Setpnt"

Default: 28°C [82°F]

Range: 10°C to 40°C [50°F to 104°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected OCC at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Set the cooling setpoint that will be used when the system is in Night Set Back (NSB) Mode/No Occupancy Mode/Window Open Mode/Door Open mode. The cooling setpoint value is restricted by the heating setpoint value at Step 122, "No OCC Heating Setpnt". The moon symbol ? and cooling symbols ❄️ are also displayed.

Humidity Settings

The Humidity Settings appear only for the following conditions: if you have selected HU at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type" or for the models with the built-in humidity sensor, unless otherwise specified.

124. "Extern Humidty Sensor Offset"

Offset: ± 5%

Range: 10% RH to 90% RH

Increment: 0.1% RH

This option appears only if you have selected HU at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". The display shows the relative humidity percentage read by the external humidity sensor. Adjust the offset by comparing it with a known value humidistat. If the sensor is not connected or short circuited, unit displays the sensor's limits. The humidify symbol ? is also displayed.

125. “Intern Humidty Sensor Offset"

Offset: ± 5%

Range: 10% RH to 90% RH

Increment: 0.1% RH

This option appears only for the models with the humidity sensor. Compare the displayed humidity percentage reading with a known value from a humidistat. This is useful for the humidistats installed in areas where the humidity reading is slightly different than the room's actual humidity. For example, a humidistat placed right under the air diffuser. The humidify symbol ? is also displayed.

126. "Humidty Control Mode"

Default: OFF

Range: OFF, Auto (Automatic humidify and dehumidify), dEHU (dehumidify only), Hu (humidify only)

If you select OFF, Steps 129 to 138 will not be available.

If you select Hu or deHU, Step 129, "Humidty User Setpnt Minimum" will be available.

127. "Display Humidity"

Default: No

Range: No, Yes

This option appears only if you have selected OFF at Step 126, "Humidty Control Mode". Select whether to display humidity value or not. If set to No, the controller will not show the humidity value and if set to Yes, it will display the humidity value.

128. "Humidity Control Source"

Default: irh

Range: Erh, irh

This option appears only for models with the built-in humidity sensor, while also having selected HU at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Select the source for humidity control.

129. "Humidty User Setpnt Minimum"

Default: 30% RH

Range: 10% RH to 90% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode". In Operation Mode, you cannot decrease the setpoint to less than the value set as the minimum humidity setpoint. The minimum value is restricted by the maximum value set at Step 130, "Humidty User Setpnt Maximum". In other words, the value that is set as the minimum cannot be greater than the maximum value.

130. "Humidty User Setpnt Maximum"

Default: 65% RH

Range: 10% RH to 90% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode". In Operation mode, you cannot increase the setpoint to more than the value set as the maximum humidity setpoint. The maximum value is restricted by the minimum value set at Step 129, "Humidty User Setpnt Minimum". In other words, the value that is set as the maximum cannot be less than the minimum value.

131. "Humidity User Setpnt Locked"

Default: No (Unlocked)

Range: No (Unlocked), Yes (Locked)

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode". If set to No, the user setpoint option is not locked and the user can adjust the desired humidity setpoint. If set to Yes, the user setpoint option is locked and the user cannot set the desired humidity setpoint. A lock symbol ? appears to indicate that the setpoint is locked.

132. "Humidty User Setpnt"

Default: 40% RH

Range: 10% RH to 90% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode". Set the desired humidity setpoint. If the setpoint option was locked at Step 131, "Humidity User Setpnt Locked", a lock ? symbol is displayed. The setpoint value is restricted by the minimum at Step 129, "Humidty User Setpnt Minimum" and maximum at Step 130, "Humidty User Setpnt Maximum" values.

133. "NSB Humidif Setpnt"

Default: 30% RH

Range: 10% RH to 65% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode", and also nSb at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Adjust the humidify setpoint during Night Set Back (NSB) Mode. The humidify setpoint is restricted by the dehumidify value at Step 134, "NSB Dehumi- Setpnt". The moon symbol ? and humidify symbols ? are also displayed.

134. "NSB Dehumi- Setpnt"

Default: 45% RH

Range: 10% RH to 65% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode", and also nSb at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Adjust the dehumidify setpoint during Night Set Back (NSB) Mode. The dehumidify setpoint is restricted by the humidify setpoint at Step 133, "NSB Humidif Setpnt". The moon symbol ? and dehumidify symbols ? are also displayed.

135. "No OCC Humidif Setpnt"

Default: 30% RH

Range: 10% RH to 65% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode", and also OCC at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Adjust the humidify setpoint during No Occupancy Mode. The humidify setpoint is restricted by the dehumidify value at Step 136, "No OCC Dehumi - Setpnt". The moon symbol ? and humidify symbols ? are also displayed.

136. "No OCC Dehumi - Setpnt"

Default: 45% RH

Range: 10% RH to 65% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode", and also OCC at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Adjust the dehumidify setpoint during No Occupancy Mode. The dehumidify setpoint is restricted by the humidify setpoint at Step 135, "No OCC Humidif Setpnt". The moon symbol ? and dehumidify symbols ? are also displayed.

137. "Humidty Prop Ramp"

Default: 5% RH

Range: 3% RH to 10% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode". Set the desired proportional ramp value for the humidity control. This value applies to both humidification and dehumidification.

138. "Humidty Dead Band"

Default: 1% RH

Range: 0% RH to 5% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 126, "Humidty Control Mode". Set the desired dead band value for the humidity control. This value applies to both humidification and dehumidification.

Anti Freeze

139. "Enable Anti Freeze Protect"

Default: No (Disable)

Range: No (Disable), Yes (Enable)

If this option is enabled, heating starts automatically when the temperature drops to 4°C [39°F], even if the controller is in Cooling or OFF mode. Once the temperature reaches 5°C [41°F], the heating stops.

Delta Temperature

140. "Enable Delta Temp Mode"

Default: OFF

Range: On, OFF

Select whether to enable or disable the AT control based on the inlet and outlet temperature of the water inside the fan coil unit.

141. "Delta Temp Setpnt"

Default: 5°C [41°F]

Range: -12°C to 12°C [10.4°F to 53.6°F]

Increment: 0.01°C [0.018°F]

This option appears only if you have selected On at Step 140, "Enable Delta Temp Mode". Set the desired value of the setpoint for the AT temperature control mode.

Backlight and Contrast Adjustment

142. "User Back Light Adjust” or “User Contrast Adjust"

Default: 50

Range: 0 to 100

Increment: 5

Select the backlight or contrast level in the user mode (controller is in operation). Use the ▲ and ▼ buttons to increase or decrease the backlight or contrast level.

143. “Occ Back Light Adjust” or “Occ Contrast Adjust"

Default: 50

Range: 0 to 100

Increment: 5

Select the backlight or contrast level in the occupied mode (controller is idle and occupancy state is active). Use the ▲ and ▼ buttons to increase or decrease the backlight or contrast level.

144. “No Occ Back Light Adjust” or “No Occ Contrast Adjust"

Default: 50

Range: 0 to 100

Increment: 5

Select the backlight or contrast level in the not occupied mode (controller is idle and occupancy state is inactive). Use the ▲ and ▼ buttons to increase or decrease the backlight or contrast level.

Network Settings

145. "Select Network Proto"

Default: bAC (BACnet)

Range: bAC (BACnet), mod (Modbus)

Select the desired network protocol.

BACnet

146. "BACnet Auto Bauds Rate"

Default: Yes (Enabled)

Range: Yes (Enabled), No (Disabled)

Enable or disable Auto Baud Rate Detection. When enabled, the controller automatically configures its baud rate by detecting the network speed upon connection to the network.

147. "BACnet Bauds Rate"

Default: No default (information display only)

Range: 9.6k, 19.2k, 38.4k, 76.8k

If you enabled Auto Baud Rate Detection at Step 146, "BACnet Auto Bauds Rate" the controller displays the automatically detected baud rate.

148. "MSTP MAC Address"

Default: 0

Range: 0 to 254

Increment: 1

Select the desired MSTP MAC Address. Each device on the network must have a unique MAC address.

149. "MSTP Max Master"

Default: 127

Range: 1 to 127

Increment: 1

Select the desired MSTP MAX address for the master device.

150. "Copy Config"

Default: No (Disable)

Range: No (Disable), Yes (Enable)

Select Yes to copy the configuration of the existing device to other devices of the same type on the network. If you select No, go to Step 154, "Adjust Device Instance 0153000".

151. "Select Begin Address"

Default: 0

Range: 0 to 254

Increment: 1

Select the first address you want to copy to. For example, if you select MAC address 1 as the "begin address" and 54 as the "end address", all the devices from 1 to 54 will receive the configuration of the current device.

152. "Select End Address"

Default: "begin address"

Range: "begin address" + 63

Increment: 1

Select the last address you want to copy to. You cannot copy more than 64 addresses at once.

153. "Copy Config"

Range: "Copy Config" followed by one of these results:

Displays "Succeed" if the addresses have been copied successfully. Otherwise, an error message appears with the associated MAC address. You can scroll through the addresses and see the error message associated with each address. See below for a complete list of error messages.

"copy config succeed"

Copy config was successful.

"copy config progerr"

Copy config failed because the target device is in Program Mode.

"copy config typeerr"

Copy config failed because the target device is not the same as the source device. For example, copying an EVC configuration to an EFC device.

"copy config modlerr"

Copy config failed because the model number of the source device and the target device is not the same. For example, copying a TSUB configuration to an EFCB.

"copy config mem err"

Copy config failed because the software/application version of the source device and the target device is not the same.

"copy config Slave"

The target device has a slave address and it cannot respond to the master. Manually verify that the configuration was copied correctly or avoid using a slave address (128 - 254).

"copy config commerr"

Copy config failed because the target device did not respond after 3 attempts. Either the address does not exist or there is a problem with the wiring or with noise.

154. "Adjust Device Instance 0153000"

Default: No

Range: No, Yes

To change the device instance, select Yes and continue to the next step. If you select No, the device instance will be modified automatically according to the MAC address (the menu starts over at Step 1, "Intern Temp Sensor Offset").

155. "0153000"

Default: "current value"

Range: 0 to 4194302

Increment: 1

Use the arrow keys to change the value and press the ▶ button to move to the next digit or press ◀ to move to the previous digit. Ensure that you provide a unique device instance.

Modbus

156. "Modbus Auto Bauds Rate"

Default: Yes (Automatic)

Range: No (Manual), Yes (Automatic)

Enable or disable Modbus Auto Baud Rate Detection. When enabled, the controller automatically configures its baud rate by detecting the network speed upon connection to the network.

157. "Modbus Bauds Rate"

Default: No default (information display only)

Range: 9.6k, 19.2k, 38.4k, 57.6k

If you enabled Modbus Auto Baud Rate Detection at Step 156, "Modbus Auto Bauds Rate", the controller displays the automatically detected baud rate.

158. "Modbus Comport Config"

Default: NP2s (no parity, 2 stop bits)

Range: EP1s (even parity, 1 stop bit), OP1s (odd parity, 1 stop bit), NP2s (no parity, 2 stop bits)

Select the desired parity and number of stop bits for the modbus communication.

159. "Modbus Address"

Default: 1

Range: 1 to 247

Increment: 1

Select the desired Modbus address. Each device on the network must have a unique Modbus address.

Scheduling Mode Settings

This menu is accessible through normal operation mode. The Mode Selector Jumper (JP1) must be set to the RUN position (Operation Mode).

  1. Press and hold the ▶ button for 5 seconds. The “Enter Password” screen appears.
  2. Enter the password (367) within 1 minute. Use the ▲ and ▼ arrow keys to increase or decrease the value and the ◀ and ▶ buttons to toggle between the digits. If you enter the wrong password, the controller displays "Eror" and returns to Operation Mode.

Use the same menu operations as described in Programming Mode on page 6.

The controller will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 minutes. The changed values will be saved automatically.

Scroll menu items

Schedul Main Menu

HrS (Time)

dAtE (Date)

Opt (Options)

SCHd (Schedule)

rst (Reset Schedule)

quit (Exit Menu)

Time

1. “Set Time Display Format"

Default: 12

Range: 12 hours, 24 hours

Select the desired time format.

2. "Set Hours"

Range: 00 to 23 hours

Increment: 1 hour

Select the time in hours.

3. "Set Minutes"

Range: 0 to 59 minutes

Increment: 1 minute

Select the time in minutes.

Date

4. "Enter Year"

Default: 2020

Range: 2009 to 2099

Increment: 1 year

Select the year.

5. "Enter Month"

Range: 01 to 12

Increment: 1 month

Select the month.

6. "Set Day"

Range: 01 to 31 days

Increment: 1 day

Select the day.

Options

7. "Used Time Schedul"

Default: No

Range: Yes, No

Select whether to schedule events or not. If set to No, then you will proceed to the quit option. If set to Yes, then you will proceed to Step 8, "Schedul Default Value".

8. "Schedul Default Value"

Default: LOC (Locally)

Range: OFF, OCC (Occupancy), nOCC (Non-Occupancy), LOC (Locally)

Select the default occupancy mode for the schedule.

Schedule

9. "Select Day of Week"

Default: mo

Range: mo (Monday), tu (Tuesday), wE (Wednesday), th (Thursday), Fr (Friday), SA (Saturday), Su (Sunday)

Select the day of the week.

10. "E1 00:00"

Range: E1 to E6,

00 to 23 hours,

00,15, 30, 45 minutes,

Increment: 1

OFF, OCC (Occupancy), nOCC (Non-Occupancy), --- (Null), LOC (Locally)

Set the parameters to schedule an event. Select the event number, followed by the time (hours and minutes) and occupancy mode. If --- (Null) is selected, then the controller will remain turned off and the event will be unused. To exit the Event menu, press the ▶ button.

Reset Schedule

11. "Reset Schedul"

Default: no

Range: YES, nO

Select whether to reset and delete the scheduled events or not.

Network Setup Menu

This menu is accessible through normal operation mode. The Mode Selector Jumper (JP1) must be set to the RUN position (Operation Mode).

  1. Press the ▲ and ▼ keys for 5 seconds. The “Enter Password" screen appears.
  2. Enter the password (637) within 1 minute. Use the ▲ and ▼ arrow keys to increase or decrease the value and the ◀ and ▶ buttons to toggle between the digits. If you enter the wrong password, the controller displays "Eror" and returns to Operation Mode.

Use the same menu operations as described in Programming Mode on page 6.

The controller will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 minutes. The changed values will be saved automatically.

1. "Select Network Proto" to "Modbus Address"

Range: Steps 145 to 159

Page: Page 29 to 31

These network setup steps are exactly the same as those in the Programming Mode. Please refer to Steps 145 to 159, starting on page 29. When complete, continue to the following step.

Sensor Offset Menu

This menu is accessible through normal operation mode. The Mode Selector Jumper (JP1) must be set to the RUN position (Operation Mode).

  1. Press the ▲ and ▼ keys for 5 seconds. The “Enter Password" screen appears.
  2. Enter the password (372) within 1 minute. Use the ▲ and ▼ arrow keys to increase or decrease the value and the ◀ and ▶ buttons to toggle between the digits. If you enter the wrong password, the controller displays "Eror" and returns to Operation Mode.

Use the same menu operations as described in Programming Mode on page 6.

The controller will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 minutes. The changed values will be saved automatically.

1. "Intern Temp Sensor Offset"

Range: 0°C to 50°C [32°F to 122°F]

Offset: Max. ± 5°C [± 9°F]

Increment: 0.1°C [0.2°F]

Compare the displayed temperature reading with a known value from a thermometer or other temperature sensing device. To offset or calibrate the sensor, use the arrow buttons to set the desired temperature reading. This is useful for controllers installed in areas where the temperature read is slightly different than the room's actual temperature. For example, a controller placed right under the air diffuser.

2. "Extern Temp Sensor Offset"

Range: -40.0°C to 100°C (-40°F to 212°F]

Offset: Max. ± 5°C [± 9°F]

Increment: 0.1°C [0.2°F]

This option appears only if you have selected t10.0 or t10V at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". The display shows the temperature read by the external temperature sensor. Adjust the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, the unit displays the sensor's limit.

3. "Extern Humidty Sensor Offset"

Offset: ± 5%

Range: 10% RH to 90% RH

Increment: 0.1% RH

This option appears if the controller is set to use an external humidity sensor. The display shows the relative humidity percentage read by the external humidity sensor. Adjust the offset by comparing it with a known value humidistat. If the sensor is not connected or short circuited, unit displays the sensor's limits. The humidify symbol ? is also displayed.

4. "VFD Pressur Setpnt"

Default: 500 Pa

Range: 100 to pressure maximum range

Increment: 1 Pa

This option appears only if you have selected VFdP at Step 13 "AO2 Ramp", and P10V at Step 78, "UI1 Signal Type" or Step 82, "UI2 Signal Type". Select the setpoint value for VFD pressure. The fan symbol ? is also displayed.

5. "VFD Temp Setpnt"

Default: 22.0°C [72°F]

Range: 10.0°C to 40.0°C [50°F to 104°F]

Increment: 0.5°C [1°F]

This option appears only if you have selected VFdt at Step 13 "AO2 Ramp". Select the setpoint value for VFD pressure. The fan symbol ? is also displayed.

Reset to Factory Default Settings

! This will erase all actual configurations and replace them with the factory default settings.

  1. The Mode Selector jumper (JP1) of the digital room sensor must be set to the “RUN” position (Operation Mode). Refer to the Wiring section on page 3.
  2. During the power up sequence of the controller and digital room sensor, press and hold both the ▲ and ▼ buttons.
  3. The "Enter Password" screen appears. Enter 372 within 1 minute by using the arrow keys to increase or decrease the value and the ◀ and ▶ buttons to toggle between the digits.
  4. Use the arrow buttons to select YES and then press ▶.
Models: TSUB00-100, TSUB30-100, TSUB60-100, TSUB00-101, TSUB30-101, TSUB60-101, TSUB00-104, TSUB30-104, TSUB60-104, TSUB00-105, TSUB30-105, TSUB60-105, TSUB Series Networkable Wall Mount Controller, TSUB Series, Networkable Wall Mount Controller, Wall Mount Controller, Controller

File Info : application/pdf, 40 Pages, 2.19MB

PDF preview unavailable. Download the PDF instead.

TSUB-250723 (V1.12)

References

Microsoft Word for Microsoft 365

Related Documents

Preview Neptronic TUUB Series Networkable Universal Wall-Mount Controller: Specifications and Installation
Comprehensive guide to Neptronic's TUUB Series Networkable Universal Wall-Mount Controllers, detailing specifications, installation, wiring, programming, and operational features for advanced HVAC system control.
Preview Neptronic TSUB Series BACnet Communication Module User Guide
Comprehensive user guide for the Neptronic TSUB Series BACnet Communication Module, detailing configuration, BACnet properties, object types, and parameter descriptions for HVAC control systems.
Preview Neptronic TSUB Series Modbus Communication Module User Guide
User guide for the Neptronic TSUB Series Universal Wall-Mount Controller, detailing its Modbus communication features, function codes, exception responses, serial line configuration, and a comprehensive holding registers table.
Preview Neptronic Networkable VAV Controller: Specification and Installation Instructions
This document details the specifications, features, and installation procedures for the Neptronic Networkable VAV Controller (EVCB Series) and its associated TRL and TDU Series Digital Room Sensors. It covers controller models, sensor types, network communication protocols (BACnet, Modbus), and operational capabilities for HVAC applications.
Preview Neptronic TUCB Series BACnet Controller User Guide
Comprehensive user guide for the Neptronic TUCB Series Universal Wall-Mount Controller with BACnet communication module, covering configuration, properties, and object information for building automation systems.
Preview Neptronic TUUB Series Universal Wall-Mount Controller Modbus Communication Module User Guide
This user guide details the Modbus communication protocol and register map for the Neptronic TUUB Series Universal Wall-Mount Controller. It covers essential Modbus requirements including data model, function codes, and serial line configuration (RS485 RTU). The document provides a comprehensive list of Modbus holding registers, specifying each register's index, description, data type, acceptable range, and writability, facilitating integration with building automation systems.
Preview Neptronic Networkable VAV Controller: Specifications, Installation & Operation Guide
Detailed specifications, installation instructions, wiring diagrams, and operational menu guides for Neptronic's EVCB Series Networkable VAV Controllers and compatible TRL/TDU thermostats.
Preview Neptronic TUUB Series BACnet Communication Module User Guide
Comprehensive user guide for the Neptronic TUUB Series Universal Wall-Mount Controller, detailing BACnet communication module setup, configuration, object properties, and technical specifications for building automation systems.