Emerson EXD-SH1/2 Controller with ModBus Communication for Electrical Control Valves

Operating Instructions

General Information

The EXD-SH1/2 controllers are stand-alone superheat and/or temperature controllers. The EXD-SH1 is intended for the operation of one bipolar electrical control valve, whereas the EXD-SH2 is designed for the operation of two independent bipolar electrical control valves. A table of available application possibilities is listed below:

Controller Circuit 1: Main function Circuit 2: Main function
EXD-SH1 Superheat or temperature control -
EXD-SH2 Superheat or temperature control Superheat Control

Notes: It is possible to use only circuit 1 from EXD-SH2. In this case, circuit 2 must be disabled (C2 parameter) and the sensors and valve for the second circuit are not needed. ModBus communication is described in a Technical Bulletin and is not covered by this document.

Technical Data

Warning: EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not comply with ATEX requirements. Installation only in non-explosive environment. For flammable refrigerants, only use valves and accessories approved for it!

Dimensions (mm)

A visual representation of the dimensions is provided, showing a rectangular unit with specific measurements for length, width, and height. The main body is approximately 70mm in length, 35mm in width, and 117.5mm in height. There are also specific cutouts and mounting points indicated.

Safety Instructions

Electrical Connection and Wiring

Operating condition Digital input status
Compressor starts/run External contact to be closed (Start)
Compressor stops External contact to be open (Stop)

Note: Connecting any EXD-SH1/2 inputs to the supply voltage will permanently damage the EXD-SH1/2.

Temperature Setting in Normal Sense (Controller function as temperature controller)

A graph illustrates the relationship between valve opening percentage and temperature. As temperature increases, valve opening decreases. The graph shows setpoints for 1tAL, 1tbd, 1tst, and 1tAH.

Temperature Setting in Reverse Sense (Controller function as temperature controller)

A graph illustrates the relationship between valve opening percentage and temperature. As temperature increases, valve opening increases. The graph shows setpoints for 1tAL, 1tbd, 1tst, and 1tAH.

Disposal

Electrical and electronic waste must NOT be disposed of with other commercial waste. Instead, it is the user's responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment (WEEE directive 2012/19/EU). For further information, contact your local environmental recycling center.

Wiring Options

Diagrams show various wiring configurations including:

Warning: Use a Class II category transformer for 24VAC power supply. Do not ground the 24VAC lines. It is recommended to use individual transformers for EXD-SH1/2 controllers and for third-party controllers to avoid possible interference or grounding problems in the power supply. If EXD-PM is connected, it is mandatory to have individual transformers for EXD-SH... and EXD-PM.

Parameter List

The document details a comprehensive list of parameters, including their codes, descriptions, available settings (Min, Max, Factory Setting), and specific functions related to control modes, refrigerant types, sensor types, valve types, alarms, and MOP (Maximum Operating Pressure) settings. This list is organized by circuit (Circuit 1 and Circuit 2) and includes detailed tables for parameter values and MOP default values for various refrigerants.

Display/Keypad Unit (LEDs and Button Functions)

The EXD-SH1/2 features a display with LEDs and buttons for operation and parameter setting. The display shows values for circuit 1 and circuit 2, indicating status like 'ON' (alarm) or 'OFF' (no alarm). Buttons include MENU, SET, and directional arrows (▲/▼) for navigation and parameter adjustment. Specific LED indicators show valve status (opening/closing) and regulation status.

Display Description

The upper display typically shows measured values like Superheat (K/F) or controlled temperature (°C/F), while the lower display shows Valve Opening (%) or Suction Pressure (bar/psig). The display can be switched between circuits for the EXD-SH2 using the 1/2 button.

Instant Value Display Mode

This mode allows real-time checking of measured/calculated values such as Superheat (SH), Valve Opening (OPEn), Suction Temperature (tASP), Suction Pressure (PEUA), and Saturation Temperature (tEuA).

Parameter Configuration Mode

Parameter configuration is protected by a numerical password (default '12'). Access involves pressing MENU and SET simultaneously for over 5 seconds. Users can navigate through parameters, adjust values, and save settings. Exiting without saving can be done by pressing SET and MENU or by a timeout.

Special Manual Functions (Reset, Clear)

These functions allow for factory resets (-Fdt) or clearing alarms (ALrr) by following a specific button sequence.

Manual Valve Operation (Service/Maintenance)

Valves can be operated manually by pressing SET for over 5 seconds. This allows for specific adjustments during service or maintenance. Parameters 1Ho and 2Ho control manual operation for circuits 1 and 2 respectively.

Error/Alarm Handling

The document provides a table detailing various error and alarm codes (e.g., 1E0/2E0 for pressure sensor error, AFE 1/2 for freeze protection, LSH 1/2 for low superheat, LOP 1/2 for low pressure, ACEr for Modbus timeout, PFA for power failure). For each alarm, it specifies the related parameter, alarm relay action, valve action, troubleshooting steps, and whether a manual reset is required.

Service/Troubleshooting

This section addresses common symptoms like incorrect superheat, unstable superheat, or valve issues. It provides potential causes and recommended actions, such as checking wiring, sensors, parameter settings, or valve size.

Upload/Download Key Function

The upload/download key allows for transferring configured parameters between identical systems for serial production. Procedures for both uploading (storing parameters to the key) and downloading (transferring parameters from the key to another controller) are described.

Models: EMERSON, EXD-SH1, 2 Controller, with, ModBus, communication

File Info : application/pdf, 30 Pages, 9.36MB

exd-sh1-2-controller-modbus-communication-capability-for-electrical-control-valves-operating-instructions-en-gb-3898448 Adobe PDF Library 20.6.74