User Manual for KRUEGER models including: KBHD Blower Coils Direct Drive, KBHD, Blower Coils Direct Drive, Coils Direct Drive, Direct Drive, Drive
BLOWER COILS | DIRECT DRIVE INTRODUCTION Krueger model KBHD and KBVD direct drive blower coils offer a wide range of application flexibility, while maintaining a simple, easy to install unit design. These units are intended to provide comfort cooling and heating within a small footprint. They may be applied in many types of building structures including schools, office buildings, hospitals, condominiums, assisted living facilities, apartments or stores. Applications can be constant or variable volume with several control options. There are many applications the KBHD and KBVD direct drive blower coils can be utilized based on the control option selected. Some examples are listed below. SINGLE-SPEED: · Constant volume · Field balanced · Manually adjustable · Direct Expansion (DX) split systems · Static environments (such as service areas) · Available with all other catalog coil configurations MULTI-SPEED: · Four discrete speeds (high-medium-low-idle) · Field balanced · Manually adjustable · Functional with multiple operators: - Building Management System (BMS) - Thermostats - 3-Speed switch · Static environments (such as service areas) · Great for setting electric heat minimum CFM VARIABLE-SPEED: · Multiple remote signal options: - 0 10VDC - 2 10VDC - 4 20mA · BMS Compatible · Upstream of Variable-Air-Volume (VAV) systems · Constant pressure · BMS turn down for energy efficiency MODELS KBHD - Horizontal Direct Drive Blower Coil Unit KBVD - Vertical Direct Drive Blower Coil Unit KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive KBHD KBVD KBHD, KBVD © Copyright Krueger 2021 F2-73 KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive BLOWER COILS | DIRECT DRIVE KBHD, KBVD PRODUCT DESCRIPTION | GENERAL INFORMATION ACOUSTICS Control of noise within both occupied and unoccupied spaces has become increasingly important to designers and building owners/occupants. Proper consideration must be given to placement of indoor air conditioning units, particularly in the occupied space. Inherent flexibility of the fan and coil combination in the vertical configuration makes it a great solution for sound sensitive areas. In such instances, a fan running at a low speed with a high capacity coil normally yields satisfactory results. It also may be desirable to select a larger nominal capacity unit and operate it at a less than nominal airflow for further acoustical benefits. Being able to choose between single or dual blower configurations for the size 30 and 40 units allows for greater flexibility when trying to optimize the selection for both sound and performance. Even better, the enhanced control options also allow for a quieter turndown and the direct drive design also eliminates any noise issues caused by squeaky belts. It is also recommended to use 3-phase motors for sound sensitive applications to avoid potential 1-phase motor hum. INSTALLATION These floor mounted or ceiling hung units can be installed with external vibration isolation on a base rail (KBHD or KBVD) or hanger rods (KBHD only) at the corner points. This requires flex connections at the corner brackets, ductwork, electrical connections, and piping connections. One of the most important and basic IAQ issues is condensate management. The first step to trouble-free operation is proper installation. It is very important that the unit be mounted high enough so that the condensate drain from the unit may be properly trapped. Please refer to the IOM manual found at www.krueger-hvac.com for specifics on this issue. As with all HVAC systems, these units should be installed according to all applicable ASHRAE standards, SMACNA, and local code requirements. When selected and installed properly, the units are seismically certified. OPERATING LIMITATIONS Krueger direct drive blower coil units offer unmatched performance capabilities across a broad range of airflow and static pressure requirements. Units must not be operated above maximum fan speed or unit airflow as listed in the Fan Performance section of this catalog. Unit operation at greater than maximum fan speed could drastically reduce bearing life and may result in a catastrophic wheel failure. Operating at greater than the maximum allowable airflow in the cooling mode may result in unsatisfactory operation due to moisture carryover from the coil. In addition, it is often not economical to operate a unit at its maximum fan speed due to the greater motor power requirements. F2-74 Units with electric heat should not be operated with a leaving air temperature greater than 104°F (40°C) to prevent electric heat limit trips and room stratification. To prevent excessive leaving air temperatures and limit trips, a hydronic (or steam) coil and electric heat should not be operated simultaneously. Electric heat units are equipped with a high limit lockout switch that disables the electric heater if the temperature of the hydronic coil is greater than 104°F (40°C). Water coils must not be operated above a fluid velocity of 8 ft/sec to reduce the possibility of velocity induced erosion and flow noise. Water coils must not be operated below a fluid velocity of 1 ft/sec to prevent degraded coil performance caused by laminar flow. These high or low fluid flow rates may not be included in the AHRI coil certification. DESIGNED FOR MAXIMUM FLEXIBILITY Both horizontal and vertical direct drive blower coils are designed to maximize flexibility of selection and installation. The units will exceed the stringent quality standards of the institutional markets, while remaining cost competitive in the light commercial markets. COMPONENT OPTIONS The extensive variety of standard options available on the KBHD and KBVD units are where you find the versatility to fit any HVAC system designer's needs. Options include mixing boxes with standard low-leak dampers, high-efficiency filter sections for 2" prefilter and 4" final filter, and blow thru electric heat with single point power connection. All electric heat units are listed with ETL as an assembly and carry the cETLus label. Disconnects and fusing mean easier coordination between mechanical and electrical trades. Direct drive fans eliminate noise and reduce maintenance time caused by belts. All KBHD and KBVD direct drive blower coils have the option of foil faced or closed cell foam insulation. COIL OPTIONS Coil options allow for 3, 4, or 6-row cooling coils. Water coils have optional circuiting that can be used to reduce water pressure drop, which may also allow for pipe size reductions and lower material cost. Hot water or standard steam coils may be placed in the preheat or reheat positions. © Copyright Krueger 2021 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive PRODUCT DESCRIPTION | GENERAL INFORMATION (CONTINUED) QUALITY PRODUCT KBHD and KBVD direct drive blower coils are built from 18 gage galvanized steel. This metal surpasses the ASTM 125 hour salt spray test for corrosion and rust. Standard insulation is 1" thick fiberglass, complying with UL 181 and NFPA 90A. All units, with or without electric heat, are cETLus listed and labeled. All wiring is in compliance with NEC, assuring safety and quality for the owner. BEST IN CLASS PERFORMANCE Krueger direct drive blower coils feature class leading airflow, coil capacity, and pressure capabilities. The single and dual blower configuration options for the size 30 and 40 units also allow for greater flexibility when configuring for sound and performance. LOWER INSTALLED COST All KBHD or KBVD direct drive blower coils are shipped completely assembled, reducing field installation time and labor. All units are thoroughly inspected and tested prior to shipment, eliminating potential problems at startup. Standard wiring allows for single point power connection and all wiring is in compliance with NEC, ensuring safety and quality. A wide variety of fan discharge configurations allow for increased flexibility and easier installation on the jobsite, resulting in cost reductions by eliminating expensive elbows, etc. KBHD, KBVD © Copyright Krueger 2021 F2-75 KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive BLOWER COILS | DIRECT DRIVE KBHD, KBVD PRODUCT DESCRIPTION | FEATURES STANDARD FEATURES Construction · Galvanized steel cabinet construction, minimum 18 gage · 1" thick fiberglass insulation · 1" supply duct collars · Gasketed, removable access panels sized for easy handling · IAQ galvanized steel drain pan (not included with heating-only units) · Left and right hand arrangements Fan Assembly · Forward curved (double width, double inlet) fans · Solid steel shafting · Statically and dynamically balanced Fan Motor and Drive · Directly driven motor and blower · Electronically commutated 1 and 3-phase motors with electronic protection Electrical Control · 1-speed motor controls accessible from exterior of control enclosure · Three different control options to choose from: 1. Variable 1-speed with manual adjustment 2. Variable multi-speed with manual adjustment 3. Proportional speed (2-10VDC, 0-10VDC or 4-20mA remote signal) with external adjustment Coils · Coils are designed, manufactured and tested by Krueger · AHRI 410 certified and labeled · 1/2" O.D. seamless copper tubes · High efficiency aluminum surface for optimizing heat transfer, pressure drop, and carryover · Mechanically expanded copper tubes are leak tested to a minimum 450 PSIG air pressure underwater · 450 PSIG working pressure at 200°F (93°C) · Evaporator coils are factory sealed and charged with a minimum of 5 PSIG nitrogen or refrigerated dry air · Steam coils rated at 15 PSIG maximum operating pressure at about 35°F (2°C) · 0.016" tube wall thickness (0.025" on steam) Piping Packages · Factory assembled, shipped loose · 1/2", 3/4", 1", 1-1/4" & 1-1/2" piping size OPTIONAL FEATURES Construction · IAQ stainless steel drain pan with 1" MPT galvanized pipe outlet · External rubber-in-shear or spring type vibration isolators, hangers, or floor mount · Scrim reinforced foil faced insulation · Closed cell foam insulation · 1" double wall construction · Hinged access panels with lift and turn fasteners · Base rails with rigging slots are factory assembled and installed · Auxiliary (secondary) drain connections Fan Motor and Drive · Directly driven motor and blower · Electronically commutated 1- and 3-phase motors with electronic protection Coils · 3, 4 and 6-row chilled water or DX coils · 1 and 2-row hot water or standard steam coils · Heating coil in preheat or reheat position · Coil connections opposite handing · Stainless steel coil casings · Automatic air vents on water coils · Heat pump compatible cooling coils · 0.025" tube wall thickness Filters · 2" pleated filter · Spare throwaway or pleated filters · High efficiency filter rack with 2" and 4" filters Inlet Damper Section · Factory assembled and installed · Heavy gage galvanized steel formed blade dampers · Low-leak dampers with extruded vinyl blade seals and flexible metal jamb seals · Parallel blade operation · Interconnecting damper linkage Electrical · Door interlocking disconnect switch (non-fused) · Hand-Off-Auto (HOA) switch · Main fusing · Remote mounted digital display and programmable thermostats Filters and Filter Rack · Hinged side access flat filter rack · Standard size 2" nominal throwaway filters · Filter rack designed to accept 2" filters Electrical Heat Section · Factory mounted electric heater with single point power connection, cETLus listed as an assembly Electrical · Fan motor wired and terminated to junction box · All units cETLus listed in compliance with UL/ANSI Standard 1995 F2-76 © Copyright Krueger 2021 KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive PRODUCT DESCRIPTION | FEATURES DETAIL MODEL KBHD Direct drive fan and EC motor Optional closed cell foam insulation 3, 4, or 6 row cooling coil with 1 or 2 row heating coil in preheat or reheat 1" duct collar allows for quick connection of duct work Hanger holes in top and bottom panels for thru rod installation BLOWER COILS | DIRECT DRIVE KBHD, KBVD Three different EC motor control options with access external to control enclosure Disconnect MODEL KBVD Multi-bend construction for optimum strength and rigidity 18 gage galvanized steel casing withstanding 125 hour salt spray test per ASTM B-117 Filter rack design allows for 2" filter Auxiliary drain pan connection Factory mounted electric heater with single point power connection, cETLus listed as an assembly NEMA 1 control enclosure houses disconnect, fusing, and more Optional hinged access panels with lift and turn fasteners Coil panels have oversized holes with pipe insulation (cooling coils only) extended to coil header Hinged filter access on both sides © Copyright Krueger 2021 Drain connection F2-77 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive COILS | GENERAL INFORMATION COILS Krueger offers hot water, chilled water and direct expansion (DX) coils for specific application with all Model KBHD and KBVD direct drive blower coils. AHRI 410 certified and labeled, and strict on-site inspection before, during, and after installation guarantees the highest quality and performance available. STANDARD FEATURES · Coils are designed, manufactured and tested by Krueger · AHRI 410 certified and labeled · 1/2" O.D. seamless copper tubes · High efficiency aluminum fin surface for optimizing heat transfer, pressure drop and carryover · Mechanically expanded copper tubes leak tested to a minimum 450 PSIG air pressure under water · Manual air vent plug on all water coils · Copper ODM sweat connections · 450 PSIG working pressure at 200°F · Evaporator coils are factory sealed and charged with a minimum of 5 PSIG nitrogen or refrigerated dry air · Refrigerant coils are provided with distributor (metering device field- provided) · Steam coils rated at 15 PSIG maximum operating pressure at about 35°F · 0.016" tube wall thickness (0.025" on steam) OPTIONAL FEATURES · Stainless steel coil casings · Automatic air vents on water coils · Heat pump compatible cooling coils · 0.025" tube wall thickness COILS | FILTER INFORMATION UNIT SIZE COIL FACE AREA 2" FLAT FILTERS (QUANTITY) & SIZE 08 2.1 (0.20) 12 2.7 (0.25) 16 3.5 (0.33) (1) 15.75" x 19.75" x 2" (400 x 502 x 51) (1) 15.75" x 24.75" x 2" (400 x 629 x 51) (2) 15.75" x 19.75" x 2" (400 x 502 x 51) 20 4.9 (0.46) (1) 15.75" x 19.75" x 2" (400 x 502 x 51) (1) 15.75" x 24.75" x 2" (400 x 629 x 51) 30 6.5 (0.60) (2) 24.75" x 15.75" x 2" (629 x 400 x 51) (1) 24.75" x 19.75" x 2" (629 x 502 x 51) 40 8.4 (0.78) (3) 24.75" x 19.75" x 2" (629 x 502 x 51) NOTES: 1. Standard filters are 2" throwaway. 2. Filter sizes are nominal and standard size, measure in inches (millimeters). 3. Coil and filter face areas are measured in square feet (square meters). 4. Cooling and heating coils have same face area. FILTER FACE AREA 2.2 (0.20) 2.7 (0.25) 4.3 (0.40) 4.9 (0.46) 8.8 (0.82) 10.2 (0.95) KBHD, KBVD F2-78 © Copyright Krueger 2021 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive COILS | COMPONENT STATIC PRESSURE LOSS ("WG) UNIT SIZE NOMINAL CFM CABINET FILTER (2" T/A) 1-ROW 2-ROW COIL 3-ROW 600 0.05 0.08 0.03 0.05 0.12 700 0.07 0.11 0.04 0.07 0.15 08 800 0.09 0.15 0.04 0.09 0.19 900 0.11 0.19 0.05 0.11 0.23 1000 0.14 0.23 0.06 0.12 0.27 1000 0.06 0.14 0.04 0.08 0.17 1100 0.08 0.17 0.50 0.10 0.19 12 1200 0.09 0.20 0.06 0.11 0.22 1300 0.11 0.24 0.06 0.12 0.25 1400 0.12 0.28 0.07 0.14 0.28 1400 0.08 0.11 0.05 0.09 0.20 1500 0.09 0.13 0.05 0.10 0.22 16 1600 0.10 0.15 0.06 0.11 0.25 1700 0.11 0.17 0.06 0.12 0.27 1800 0.13 0.19 0.07 0.14 0.30 1600 0.07 0.11 0.03 0.07 0.15 1800 0.09 0.14 0.04 0.08 0.18 20 2000 0.11 0.18 0.05 0.10 0.21 2200 0.13 0.21 0.06 0.11 0.25 2400 0.16 0.26 0.07 0.13 0.28 2600 0.11 0.09 0.05 0.09 0.19 2800 0.12 0.11 0.05 0.10 0.22 30 3000 0.14 0.12 0.06 0.12 0.24 3200 0.16 0.14 0.07 0.13 0.27 3400 0.18 0.16 0.07 0.14 0.29 3600 0.13 0.13 0.05 0.10 0.21 3800 0.14 0.15 0.06 0.11 0.22 40 4000 0.16 0.16 0.06 0.12 0.24 4200 0.18 0.18 0.07 0.13 0.26 4400 0.19 0.20 0.07 0.14 0.28 NOTES: 1. All static pressures are at nominal CFM. 2. Coil static pressure for standard coil, 10FPI at 80/67 EAT and 45° EWT with 10° rise. 3. For 8, 12 or 14 FPI, refer to Selection Software®, available at www.krueger-hvac.com. 4. Filter static pressure based on 50% loaded filter. 5. If pleated filters are used in lieu of throwaway, the filter static pressure loss is 0.35. 4-ROW 0.16 0.20 0.25 0.30 0.35 0.24 0.28 0.32 0.36 0.40 0.26 0.30 0.33 0.36 0.39 0.18 0.22 0.26 0.31 0.35 0.27 0.30 0.34 0.34 0.38 0.30 0.33 0.35 0.38 0.41 6-ROW 0.24 0.31 0.38 0.46 0.54 0.36 0.42 0.47 0.54 0.60 0.37 0.42 0.46 0.51 0.56 0.30 0.36 0.41 0.48 0.55 0.41 0.43 0.47 0.53 0.58 0.43 0.47 0.51 0.55 0.59 MIXING BOX ELECTRIC HEAT SECTION 0.02 0.01 0.03 0.02 0.04 0.02 0.05 0.02 0.06 0.02 0.04 0.02 0.05 0.02 0.06 0.02 0.07 0.02 0.08 0.03 0.07 0.02 0.08 0.02 0.09 0.02 0.10 0.02 0.11 0.03 0.03 0.02 0.04 0.02 0.05 0.02 0.06 0.02 0.07 0.02 0.06 0.02 0.07 0.02 0.08 0.02 0.09 0.03 0.10 0.03 0.06 0.02 0.06 0.02 0.07 0.02 0.08 0.03 0.08 0.03 KBHD, KBVD © Copyright Krueger 2021 F2-79 KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive BLOWER COILS | DIRECT DRIVE KBHD, KBVD ELECTRIC HEAT FEATURES & CAPACITIES ELECTRIC HEAT STANDARD FEATURES · Flanged construction for direct unit mounting, in blow thru configuration · Listed for zero clearance installation · Meets National Electrical Code requirements · Ni-Chrome wire in ceramic insulators · Stainless steel element terminals and hardware · Element support brackets on maximum 3 1/2" centers · Solid cover with continuous full height hinge · Over temperature protection · All internal wiring rated for 105°C minimum · Airflow switch · Incoming line power distribution block · cETL Listed in compliance with UL/ANSI Standard 1995 · Single point power connection · Heater factory mounted to unit with cETL listing as an assembly OPTIONAL HEATER CONTROL · Main incoming power disconnect (non-fused) · Fusing (main) (per stage) · Magnetic contactors wired for disconnecting operation · Fan control package with heater interlock contacts (required for single point power connection) Altitude Considerations: Reduce by 0.034 for each 1000 ft. of altitude above sea level. Example: 5000 ft. / 1000 ft. = 5 5 x 0.034 = 0.17 1.085 - 0.17 = 0.915 ELECTRICAL CALCULATIONS INFORMATION · Refer to MCA/MOP Calculator at www.krueger-hvac. com for MCA and/or MOP calculations. · Non-Fused Door Interlock Disconnect Switch shall be sized according to MCA. · Main Fusing shall be sized according to MOP. VOLTAGE 115 / 1 208 / 1 230 / 1 277 / 1 208 / 3 230 / 3 480 / 3 HEATER AMP CALCULATION AMPS PER KW 8.70 4.81 4.35 3.61 2.78 2.51 1.26 USEFUL FORMULAS kW* = (kW* = CFM x T x 1.085**) / 3413 1Ø AMPs = (kW x 1000) / Volts * 1kW = 3413 BTU/H ** Capacity at sea level ELECTRIC HEAT kW LIMITS UNIT SIZE UNIT VOLTAGE AND PHASE 08 12 16 20 30 40 30 (SINGLE BLOWER) (SINGLE BLOWER) (DUAL BLOWER) SINGLE PHASE MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX kW 3.0 5.0 3.0 5.0 3.0 5.0 3.0 5.0 3.0 5.0 3.0 5.0 5.0 5.5 115 AMPs 26.1 43.5 26.1 43.5 26.1 43.5 26.1 43.5 26.1 43.5 26.1 43.5 3.5 47.8 kW 3.0 9.0 3.0 9.0 3.0 9.0 3.0 9.0 3.0 9.0 3.0 9.0 6.0 11.0 208 AMPs 14.4 43.3 14.4 43.3 14.4 43.3 14.4 43.3 14.4 43.3 14.4 43.3 28.8 52.9 kW 3.0 11.0 3.0 11.0 3.0 11.0 3.0 11.0 3.0 11.0 3.0 11.0 6.0 13.0 230 AMPs 13.0 47.8 13.0 47.8 13.0 47.8 13.0 47.8 13.0 47.8 13.0 47.8 26.1 56.5 kW 3.0 13.0 3.0 13.0 3.0 13.0 3.0 13.0 3.0 13.0 3.0 13.0 6.0 17.0 277 AMPs 10.8 46.9 10.8 46.9 10.8 46.9 10.8 46.9 10.8 46.9 10.8 46.9 21.7 61.4 kW 3.0 13.0 3.0 16.0 3.0 16.0 3.0 16.0 3.0 16.0 3.0 16.0 6.0 24.0 208 AMPs 8.3 36.1 8.3 44.4 8.3 44.4 8.3 44.4 8.3 44.4 8.3 44.4 16.7 66.6 kW 3.0 13.0 3.0 18.0 3.0 18.0 3.0 18.0 3.0 18.0 3.0 18.0 6.0 26.0 230 AMPs 7.5 32.6 7.5 45.2 7.5 45.2 7.5 45.2 7.5 45.2 7.5 45.2 15.1 65.3 kW 3.0 13.0 3.0 20.0 3.0 20.0 3.0 26.0 3.0 26.0 3.0 26.0 6.0 38.0 480 AMPs 3.8 16.3 3.8 25.1 3.8 25.1 3.8 32.6 3.8 32.6 3.8 32.6 7.5 47.7 THREE PHASE NOTES: 1. Factory certified submittals available upon request. 2. Standard heater kW limits are maximum per unit size and voltage. 3. Heater should be sized for a maximum leaving air temperature of 104 °F. 4. Electric heaters are only available in fan arrangement 3. 40 (DUAL BLOWER) MIN MAX 5.0 5.5 43.5 47.8 6.0 11.0 28.8 52.9 6.0 13.0 26.1 56.5 6.0 17.0 21.7 61.4 6.0 24.0 16.7 66.6 6.0 26.0 15.1 65.3 6.0 38.0 7.5 47.7 F2-80 © Copyright Krueger 2021 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive MOTOR ELECTRICAL INFORMATION MAXIMUM MOTOR AMPERAGE HORSEPOWER VOLTAGE/PHASE 115/1 208/1 230/1 277/1 1/2 7.7 5.0 5.0 4.1 1 12.8 9.4 9.4 6.9 1 1/2 19.23 14.63 14.63 11.03 2 25.63 18.83 18.83 13.83 3 -- -- -- -- NOTES: 1. Actual motor nameplate AMPs may vary, but will not exceed values shown. 2. Consult factory for applications requiring special motors. 3. Amp values are total amp values for (2) motors. 208/3 2.0 3.7 4.4 7.43 8.83 230/3 2.0 3.7 4.4 7.43 8.83 480/3 1.0 1.7 2.2 3.43 4.43 WEIGHTS UNIT WEIGHTS COMPONENT UNIT SIZE 08 12 16 20 30 (SINGLE BLOWER) BASE UNIT MIXING BOX BLOW THRU ELECTRIC HEATER 1 ROW - DRY 115 (52) 46 (21) 42 (19) 12 (5) 133 (60) 54 (25) 42 (19) 14 (6) 152 (69) 65 (30) 55 (25) 17 (8) 1 ROW - WET 14 (6) 16 (7) 20 (9) 2 ROW - DRY 17 (8) 21 (10) 26 (12) 2 ROW - WET 21 (10) 26 (12) 32 (15) COIL ROWS 3 ROW - DRY 23 (10) 28 (13) 35 (16) 3 ROW - WET 29 (13) 36 (16) 44 (20) 4 ROW - DRY 29 (13) 35 (16) 44 (20) 4 ROW - WET 37 (17) 45 (20) 56 (25) 6 ROW - DRY 40 (18) 49 (22) 62 (28) 6 ROW - WET 52 (24) 64 (29) 81 (37) NOTES: Unit weight data is shipping weight in pounds (kilograms). 175 (79) 90 (41) 55 (25) 21 (10) 25 (11) 33 (15) 42 (19) 45 (20) 59 (27) 57 (26) 74 (34) 81 (37) 106 (48) 287 (130) 105 (48) 55 (25) 26 (12) 32 (15) 42 (19) 54 (24) 57 (26) 75 (34) 73 (33) 96 (44) 104 (47) 138 (63) 40 (SINGLE BLOWER) 305 (139) 105 (48) 125 (57) 26 (12) 32 (15) 42 (19) 54 (24) 57 (26) 75 (34) 73 (33) 96 (44) 104 (47) 138 (63) MOTOR/DRIVE WEIGHTS TYPE MOTOR HORSEPOWER 1/2 1 1 1/2 2 SINGLE PHASE THREE PHASE 13 19 38 38 14 18 43 36 NOTES: Unit weight data is shipping weight in pounds (kilograms). 30 (DUAL BLOWER) 357 (162) 162 (74) 55 (25) 32 (15) 41 (19) 52 (24) 69 (31) 72 (33) 95 (43) 91 (41) 121 (55) 132 (60) 178 (81) 40 (DUAL BLOWER) 375 (170) 162 (74) 125 (57) 32 (15) 41 (19) 52 (24) 69 (31) 72 (33) 95 (43) 91 (41) 121 (55) 132 (60) 178 (81) 3 -106 KBHD, KBVD © Copyright Krueger 2021 F2-81 BLOWER COILS | DIRECT DRIVE TOTAL STATIC PRESSURE (IN WG.) KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive FAN CURVES | SIZES 08 & 12 1-PHASE, SINGLE BLOWER 1.8 1.7 Single 1/2 HP Fan - 1 1.6 Single 1 HP Fan - 1 1.5 1.4 1.3 1.2 1.1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 AIRFLOW (CFM) TOTAL STATIC PRESSURE (IN WG.) 3-PHASE, SINGLE BLOWER 3.2 3 Single 1/2 HP Fan - 3 Single 1 HP Fan - 3 2.8 2.6 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 AIRFLOW (CFM) KBHD, KBVD F2-82 © Copyright Krueger 2021 TOTAL STATIC PRESSURE (IN WG.) BLOWER COILS | DIRECT DRIVE FAN CURVES | SIZES 16, 20, 30 & 40 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive 1-PHASE, SINGLE BLOWER Single 1/2 HP Fan - 1 Single 1 HP Fan - 1 AIRFLOW (CFM) 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 KBHD, KBVD TOTAL STATIC PRESSURE (IN WG.) 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3.2 3 2.8 2.6 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 © Copyright Krueger 2021 3-PHASE, SINGLE BLOWER Single 1/2 HP Fan - 3 Single 1 HP Fan - 3 Single 1.5 HP Fan - 3 AIRFLOW (CFM) F2-83 TOTAL STATIC PRESSURE (IN WG.) 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000 4200 4400 4600 4800 5000 5200 5400 KBHD, KBVD 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000 4200 4400 4600 4800 BLOWER COILS | DIRECT DRIVE TOTAL STATIC PRESSURE (IN WG.) KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive FAN CURVES | SIZES 30 & 40 1-PHASE, DUAL BLOWER 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 AIRFLOW (CFM) 3.2 3 2.8 2.6 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 F2-84 3-PHASE, DUAL BLOWER AIRFLOW (CFM) Dual 3/4 HP Fan - 1 Dual 1 HP Fan - 1 Dual 1 HP Fan - 3 Dual 1.5 HP Fan - 3 © Copyright Krueger 2021 BLOWER COILS | DIRECT DRIVE DIMENSIONAL DATA | KBHD | SINGLE BLOWER KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive 9/16 (14) DIA. MOUNTING HOLES TYP (4) PLACES WITHOUT BASE RAIL 1 1/4 (32) TYP. 1 1/4 (32) TYP TYP, SEE NOTE 5 TYP, SEE NOTE 5 D TYP. J G W E TYP. 8 1/8 (206) 5/8 (16) DIA. MOUNTING HOLES TYP (4) PLACES. SEE NOTE 5 TOP VIEW SEE NOTE 4 4 (102) TYP SEE NOTE 5 10 (254) MAX ACCESS PANEL BOTH SIDES CONTROL ENCLOSURE, SEE NOTE 3 K C A/F C F H 2 (51) 8 1/2 (216) HIGH EFFICIENCY FILTER RACK 2 (51) 4 1/2 (114) SIDE VIEWS L STANDARD FILTER RACK 2 (51) 3 (76) OPTIONAL BASE RAIL SIZE FAN SIZE L W H C D E F G J K 08 9" x 6" (229 x 152) 40" (1016) 30" (762) 21" (533) 16" (406) 20" (508) 5" (127) 10 3/8" (264) 8 3/8" (213) 10 7/8" (276) 2" (51) 12 9" x 6" (229 x 152) 40" (1016) 36" (914) 21" (533) 16" (406) 25" (635) 5 1/2" (140) 10 3/8" (264) 8 3/8" (213) 13 7/8" (352) 2" (51) 16 10" x 8" (254 x 203) 40" (1016) 44" (1118) 21" (533) 16" (406) 39 1/2" (1003) 2 1/4" (57) 11 1/2" (292) 10 5/8" (270) 16 5/8" (422) 2" (51) 20 10" x 8" (254 x 203) 40" (1016) 50" (1270) 21" (533) 16" (406) 44 1/2" (1130) 2 3/4" (70) 11 1/2" (292) 10 5/8" (270) 19 5/8" (498) 2" (51) 30 10" x 8" (254 x 203) 46" (1168) 59" (1499) 30" (762) 25" (635) 51" (1295) 4" (102) 11 1/2" (292) 10 5/8" (270) 24 1/4" (616) 9 3/4" (248) 40 10" x 8" (254 x 203) 46" (1168) 68" (1727) 30" (762) 25" (635) 59" (1499) 4 1/2" (114) 11 1/2" (292) 10 5/8" (270) 28 5/8" (727) 9 3/4" (248) NOTES: 1. All dimensions are in inches (millimeters). All dimensions are ±1/4" (6mm). Metric values are soft conversion. 2. Right hand unit shown, left hand unit opposite. Motor/drive location may be specified Left or Right Hand. Standard control enclosure location matches motor/drive position. 3. Provide sufficient clearance to permit access to controls and comply with applicable codes and ordinances. 4. See page F2-89 for filter rack details. 5. Base rail is optional on the base unit. Base rails must be used with mixing box. 6. See coil connection detail drawings for coil connection sizes and locations. 7. Drawings are not to scale and are not for installation purposes. KBHD, KBVD © Copyright Krueger 2021 F2-85 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive DIMENSIONAL DATA | KBVD | SINGLE BLOWER 1" (25) TYP, SEE NOTE 5 1" (25) TYP, SEE NOTE 5 J D TYP E TYP G W 8 1/8" (206) 5/8" (16) DIA. MOUNTING HOLES TYP (4) PLACES. SEE NOTE 5 TOP VIEW 4" (102) TYP, SEE NOTE 5 10" (254) MAX F ACCESS PANEL BOTH SIDES SEE NOTE 4 C A/F C K 2" (51) CONTROL ENCLOSURE, SEE NOTE 3 H 2" (51) 8 1/2" (216) HIGH EFFICIENCY FILTER RACK 2" (51) 4 1/2" (114) SIDE VIEWS L STANDARD FILTER RACK 3" (76) OPTIONAL BASE RAIL SIZE FAN SIZE L W H C D E F G J 08 9" x 6" (229 x 152) 24" (610) 30" (762) 44" (1118) 16" (406) 20" (508) 5" (127) 10 3/8" (264) 8 3/8" (213) 10 7/8" (276) 12 9" x 6" (229 x 152) 24" (610) 36" (914) 44" (1118) 16" (406) 25" (635) 5 1/2" (140) 10 3/8" (264) 8 3/8" (213) 13 7/8" (352) 16 10" x 8" (254 x 203) 24" (610) 44" (1118) 44" (1118) 16" (406) 39 1/2" (1003) 2 1/4" (57) 11 1/2" (292) 10 5/8" (270) 16 3/4" (425) 20 10" x 8" (254 x 203) 30" (762) 50" (1270) 50" (1270) 16" (406) 44 1/2" (1130) 2 3/4" (70) 11 1/2" (292) 10 5/8" (270) 19 3/4" (502) 30 10" x 8" (254 x 203) 30" (762) 59" (1499) 56" (1422) 25" (635) 51" (1295) 4" (102) 11 1/2" (292) 10 5/8" (270) 24 1/4" (629) 40 10" x 8" (254 x 203) 30" (762) 68" (1727) 59" (1499) 25" (635) 59" (1499) 4 1/2" (114) 11 1/2" (292) 10 5/8" (270) 28 3/4" (730) NOTES: 1. All dimensions are inches (millimeters). All dimensions are ±1/4" (6mm). Metric values are soft conversion. 2. Right hand unit shown, left hand unit opposite. Motor/drive location may be specified Left or Right Hand. Standard control enclosure location matches motor/drive position. 3. Provide sufficient clearance to permit access to controls and comply with applicable codes and ordinances. 4. Flat filter rack may be located at unit inlet as required. See page F2-89 for filter rack details. 5. Base rail is optional on the base unit. Base rails must be used with mixing box. 6. See coil connection detail drawings for coil connection sizes and locations. 7. Drawings are not to scale and are not for installation purposes. K 2 1/2" (64) 2 1/2" (64) 2 1/2" (64) 2 1/2" (64) 10" (254) 10" (254) KBHD, KBVD F2-86 © Copyright Krueger 2021 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive DIMENSIONAL DATA | BLOW THRU UNIT, ELECTRIC HEAT 10" 22" (559) (254) MAX 5/8" (16) TYP. A/F 11 7/8" (302) 22" (559) SINGLE BLOWER ELECTRIC HEAT SECTION 10" (254) MAX G ELECTRIC HEAT CONTROL ENCLOSURE, SEE NOTE 3 5/8" (16) TYP A/F 11 7/8" (302) SIDE VIEWS ELECTRIC HEAT CONTROL ENCLOSURE SEE NOTE 3 DUAL BLOWER ELECTRIC HEAT SECTION 34 1/4" (870) FRONT VIEWS UNIT SIZE 08 12 16 20 30 40 WEIGHT LBS (KG) SINGLE BLOWER 45" (20) 45" (20) 45" (20) 45" (20) 45" (20) 45" (20) DUAL BLOWER - 100" (45) 140" (64) G 8 3/4" (222) 8 3/4" (222) 10 3/4" (273) 10 3/4" (273) 10 3/4" (273) 10 3/4" (273) NOTES: 1. All dimensions are inches (millimeters). All dimensions are ± 1/4" (6mm). Metric values are soft conversion. 2. Motor/drive location may be specified left or right hand. Standard control enclosure location matches motor/drive position. 3. Provide sufficient clearance to permit access to controls and comply with applicable codes and ordinances. 4. Available for horizontal discharge only. 5. To prevent sweating for units configured with an uninsulated blow- thru heat section. ensure that insulation is field-installed prior to cooling mode operation. 6. Drawings are not to scale and are not for installation purposes. KBHD, KBVD © Copyright Krueger 2021 F2-87 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive DIMENSIONAL DATA | STANDARD MIXING BOX WB W B WB C 1" (25) 3" (76) SEE NOTE #2 A C SEE NOTE #2 TOP VIEWS 3" (76) H A A A/F H 3" (76) 1" (25) D TOP / REAR INLET 1" (25) A 3" (76) BASE RAIL 3" (76) 1" (25) D BOTTOM / REAR INLET SIDE VIEWS C SEE NOTE #2 3" (76) A A/F H 1" (25) A 3" (76) D TOP / BOTTOM INLET UNIT SIZE H W A B 08 21" (533) 30" (762) 9" (229) 18" (457) 12 21" (533) 36" (914) 9" (229) 24" (610) 16 21" (533) 44" (1118) 9" (229) 30" (762) 20 21" (533) 50" (1270) 12" (305) 36" (914) 30 30" (762) 59" (1499) 12" (305) 45" (1143) 40 30" (762) 68" (1727) 15" (381) 48" (1219) NOTES: 1. All dimensions are inches (millimeters). All dimensions are ± 1/4" (6mm). Metric values are soft conversion. 2. Damper drive rods are internal, located on both sides of unit. 3. Mixing box includes space for standard flat filter rack. 4. Base rails must be used with mixing box. 5. Drawings are not to scale and are not for installation purposes. C 6" (152) 6" (152) 7" (178) 7" (178) 7" (178) 10" (254) D 18" (457) 18" (457) 18" (457) 21" (533) 21" (533) 24" (610) KBHD, KBVD F2-88 © Copyright Krueger 2021 BLOWER COILS | DIRECT DRIVE DIMENSIONAL DATA | STANDARD FLAT FILTER RACK KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive B B C SEE NOTE #7 A/F A FILTER REMOVAL SPACE REQUIRED C TOP VIEWS A/F A FILTER REMOVAL SPACE REQUIRED 4 1/2" (114) STANDARD 8 1/2" (216) SIDE VIEWS HIGH EFFICIENCY NOTES: SIZE A B C QTY & SIZE FILTERS 1. All dimensions are inches (millimeters). All dimensions are ± 1/4" 08 16" (406) 12 16" (406) 20" (508) 25" (635) 20" (508) 25" (635) (1) 16" x 20" (1) 16" x 25" (6mm). Metric values are soft conversion. 2. Flat filter rack may be located at unit inlet as required. 3. Standard rack will accept 1" or 2" thick filters. 16 16" (406) 39 1/2" (1003) 20" (508) 20 16" (406) 44 1/2" (1130) 25" (635) (1) 16" x 20" (1) 16" x 20" (1) 16" x 25" 4. High efficiency rack will accept nominal 2" and/or 4" thick filters. 5. High efficiency rack not available on units with filter rack. 6. 1" duct connection space provided on entering side of rack for connection of field ductwork. 30 25" (635) 51" (1295) 25" (635) 40 25" (635) 59" (1499) 25" (635) (1) 16" x 25" (1) 20" x 25" (1) 20" x 25" 7. Hinged cover provided on both sides of externally mounted filter racks. Internal standard filter racks have pivoting bar type filter retainer. 8. See individual unit submittal for location of filter rack on unit. 9. Drawings are not to scale and are not for installation purposes. KBHD, KBVD © Copyright Krueger 2021 F2-89 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive SUGGESTED SPECIFICATION & CONFIGURATION GENERAL Furnish and install Krueger® Model KBHD & KBVD Blower Coil Units where indicated on the plans and specifications. Units shall be completely factory assembled and tested and shipped as one piece except where noted. All units shall be capable of meeting or exceeding the scheduled capacities for cooling, heating and air delivery. All unit dimensions for each model and size shall be considered maximums. All units shall be of "draw-thru" design with coils, fans, motor, and drain pan completely contained within the unit cabinet. Electric heat to be in the blow-thru configuration. Units shall be cETL listed in compliance with UL/ANSI Std. 1995. All unit coils shall meet or exceed the scheduled cooling and heating capacity, selected and rated in accordance with AHRI 410. CONSTRUCTION All units shall be fabricated of minimum 18 gage galvanized steel, able to withstand a 125 hour salt spray test per ASTM B-117. Panels shall be die-formed "multibend" construction for optimum strength and rigidity. All exterior panels shall be single wall insulated with 1" thick fiberglass insulation, rated for a maximum air velocity of 5000 f.p.m. Optional: Single wall with 1" thick, 1.6 pound per cubic foot density scrim reinforced foil faced insulation. Optional: Single wall with 1" thick closed cell foam insulation. Optional: 1" double wall construction. Insulation must meet all requirements of ASTM C1071 (including C665), UL181 for erosion, and carry a 25/50 rating for flame spread/smoke developed per ASTM E-84, UL723 and NFPA 90A. In addition to using adhesive complying with NFPA 90A, the insulation shall incorporate a secondary mechanical fastener attached to the unit casing wall. Adhesive as the only method of fastening the insulation to the casing is not acceptable. All access panels shall be fully insulated and attached with standard fasteners on at least two opposite sides. No single access panel shall be larger than 30" x 36" for safety and ease of handling. No coil or drain piping or electrical connections shall pass through any access panel. Each unit shall be furnished with a one-piece heavy gage. G90 steel or optional IAQ stainless steel drain pan with welded corner construction. Drain pan shall be insulated with minimum 1/8" closed cell foam. All units shall be provided with 9/16" diameter hanger rod holes in the top and bottom panels for "through-bolt" type suspension installation. Optional: Spring type unit mounting vibration isolators shall be provided by the unit manufacturer. Optional: Rubber-in-shear type unit mounting vibration isolators shall be provided by the unit manufacturer. Optional: Units to have factory assembled and installed base rails with rigging slots. All units shall have a minimum 1" duct collar on both the discharge and return. FAN & MOTOR ASSEMBLY All units shall be furnished with double inlet forward curved centrifugal blowers statically and dynamically balanced for smooth operation. Blower wheels shall be mounted directly on the motor shaft. Belt driven blowers are not acceptable. Fan motors shall be electronically commutated with thermal overload protection and a constant torque operation. RPM control shall not be acceptable. Motors shall feature permanently lubricated ball bearings and operate on three or single phase power. All motors to be installed, factory programmed and wired to the control panel. All motors shall be isolated, depending on motor size, via belly band or torsion flex mount to the blower housing. All motor wiring is to be terminated in a junction box, external to the unit casing. All motors to be operated by single-speed or multi-speed local or remote controller. COILS All unit coils shall be rated in accordance with AHRI 410. All coils shall be 1/2" O.D. seamless copper tubes with collared aluminum fins. All tubes shall be mechanically expanded to provide an efficient bond between tube and fin. All water coils shall be provided with a manual air vent fitting to allow for coil venting. Valve core type vent fittings shall not be accepted. All chilled water, hot water, and direct expansion (DX) coils shall have aluminum fins and 0.016" tube wall thickness. KBHD, KBVD F2-90 © Copyright Krueger 2021 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive SUGGESTED SPECIFICATION & CONFIGURATION All coils shall be hydrostatically tested with air under water Motor Control Board Option 2: Four speed motor control at 450 PSIG minimum pressure and rated for a maximum shall be provided with potentiometer type adjustment. of 450 PSIG working pressure at 200°F. Unit to be compatible with three speed control thermostat. All steam coils shall have 0.025" tube wall thickness. All steams coils shall be suitable for 15 PSIG maximum operating pressure. Optional: Provide automatic air vents, in lieu of manual air vents. Optional: Provide 0.025" tube wall thickness. FILTER RACK ASSEMBLY All units shall be furnished with a flat filter rack with hinged access on both sides designed to accept a 2" nominal standard sized filters. All units shall be provided with nominal 2" throwaway filters factory installed. One complete set of spare throwaway filters shall be provided for each unit. Optional: Factory provided MERV 8 pleated filters. Optional: Unit shall have a High Efficiency filter rack suitable for a pleated 2" MERV 8 and a pleated 4" MERV 11, MERV 14 or MERV 15 filter. INLET DAMPER SECTION Where shown on the plans, the unit manufacturer shall furnish a fully insulated mixing box section (factory assembled and installed inlet damper section) to be mounted next to the unit on base rail (unit & mixing box). The mixing box section shall include heavy gage formed steel blade dampers in a heavy gage steel frame with extruded vinyl blade seals and flexible metal jamb seals. Damper drive linkage shall be factory furnished and installed by the unit manufacturer. A field furnished and installed damper actuator can be mounted directly to the damper shaft. ELECTRICAL CONTROL The unit fan motor shall be completely factory wired to an external electrical enclosure. Each unit shall include fan control package with 24 volt control voltage. Each unit shall include a motor control board, motor circuit fusing, control circuit transformer and terminal strip for connection of field wiring. Calibrated airflow curves shall be provided near the control box to aid in testing and balancing. A main incoming power non-fused disconnect switch with lock-out tag-out ready feature shall be factory furnished and wired by the unit manufacturer for single point power connection. ELECTRIC HEAT SECTION Where shown on the plans, the unit manufacturer shall furnish an electric resistance heating assembly with the heating capacity, voltage and stages as shown in the schedule. The heater assembly shall be designed and rated for installation to the blower coil unit in the blow thru configuration without the use of duct extensions or transitions between the unit and the heater assembly. The heater assembly shall be factory assembled to the air handling unit and completely factory wired. The heater/ unit assembly shall be listed for zero clearance meeting all N.E.C. requirements and be cETL listed in compliance with UL/ANSI Std. 1995. All heating elements shall be open coil design using NiChrome wire mounted in ceramic insulators and housed in an insulated heavy gage galvanized steel housing. All elements shall terminate in a machine staked stainless steel terminal secured with stainless steel hardware. The element support brackets shall be spaced no greater than 3-1/2" on center. All internal wiring shall be rated for 105°C minimum. All heaters shall include over temperature protection. All heaters shall include a non-adjustable airflow switch. An incoming line power distribution block shall be provided. The power distribution block shall be designed to accept incoming power wiring capable of carrying 125% of the calculated load current. In addition to the above, electric heaters shall include the following options: · Main incoming power disconnect (non-fused) · Main fusing · Magnetic contactors wired for disconnecting operation Motor Control Board Option 1: Motor control shall be provided by a single speed or proportional speed controller mounted on the exterior surface of the control box. Electric heat section available uninsulated or with insulated double wall construction. Opening the control box to adjust the fan speed shall not be required. KBHD, KBVD © Copyright Krueger 2021 F2-91 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive SUGGESTED SPECIFICATION & CONFIGURATION 1. SERIES: KBHD- Horizontal Direct Drive Blower Coil KBVD - Vertical Direct Drive Blower Coil 2. ARRANGEMENT: Fan Arr. 1 (Upblast Rear) Fan Arr. 2 (Upblast Front) Fan Arr. 3 (Horizontal Top Front) 3. INLET: High Efficiency Rack Mixing Box with Linkage 4. MIXING BOX DAMPER LOCATION: Bottom and Rear Inlet Top and Bottom Inlet Top and Rear Inlet 5. SIZE: 8, 12, 16, 20, 30, 40 12. COIL 1: 3-Row Cold Water 4-Row Cold Water 6-Row Cold Water 3-Row DX, Single Circuit 4-Row DX, Single Circuit 6-Row DX, Single Circuit 1-Row Hot Water 2-Row Hot Water 1-Row Steam 2-Row Steam 3-Row with Changeover 4-Row with Changeover 6-Row with Changeover 13. COIL 1 FPI: 8 FPI 10 FPI 12 FPI 14 FPI 6. MOTOR VOLTAGE: 115/1/60 ECM 208/1/60 ECM 230/1/60 ECM 277/1/60 ECM 208/3/60 ECM 230/3/60 ECM 460/3/60 ECM 7. MOTOR CONTROL: Solo - Manual Adjustment Select - 3 Speed Adjustable Sync - Remote Signal Adj 2-10VDC 8. MOTOR HAND: Left-hand Motor Right-hand Motor 9. SPEED SWITCH: Field Provided Unit Mounted 3 Speed Switch with Off Position Remote Mounted 3 Speed Switch with Off Position 10. AUTO SWITCH: Hand-Off Auto Switch 11. CONTROL ENCLOSURE LOCATION: Standard - Discharge End/Access Door Opens from Discharge End Alternate 1 - Top of Unit/Access Door Opens to Side Alternate 2 - Discharge End/Access Door Opens to Side 14. COIL 1 HAND: Right Hand Left Hand 15. COIL 1 AIR VENT: Manual Auto Air Vent 16. COIL 1 CASING: Galvanized Casing Stainless Steel Casing 17. COIL 1 TUBE WALL: 0.016" 0.025" 18. COIL 1 REFRIGERANT TYPE: R-410 19. COIL 1 DISTRIBUTOR: (See Krueger's selection software) 20. COIL 1 PIPING SIZE: 1/2", 3/4", 1", 1-1/4", 1-1/2" 21. COIL 1 PIPING VALVE: 2-Way Control Valve 3-Way Control Valve 3-Way with Balance ByPass Valve 22. COIL 1 PIPING PACKAGE: Manual Ball Valve w/ Memory Stop Manual Ball Valve w/ Memory Stop, Fixed Flow Ctrl Ball Valve in Bypass & Ball Valves w/ Memory Stop KBHD, KBVD F2-92 © Copyright Krueger 2021 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive SUGGESTED SPECIFICATION & CONFIGURATION 23. COIL 1 FIXED GPM: 1 /2" = 0.5 to 4.0 GPM in 0.5 GPM increments > 4.0 to 9.0 GPM in 1.0 GPM increments 3/4" = 4.0 to 15.0 GPM in 1.0 GPM increments 1" = 11.0 to 22.0 GPM in 1.0 GPM increments 1-1/4" = 18.0 to 29.0 GPM in 1.0 GPM increments 1-1/2" = 26.0 to 45.0 GPM in 1.0 GPM increments 24. COIL 1 UNIONS: Union 25. COIL 1 P/T PORTS: P/T Port 26. COIL 1 AQUASTAT BLEED LINE: Aquastat Bleed Line 27. COIL 1 Y-STRAINER: Y-Strainer Y-Strainer with blowdown 28. COIL 1 ACTUATOR TYPE: Field Provided by Others 2-Position Close-Off Factory Provided 2-Position Close-Off, NC MV, 2-Way, Floating Point, Fail-In-Place, 24V MV, 3-Way, Floating Point, Fail-In-Place, 24V HP Close-Off Actuator, 2-Way Valve-24/115/208V HP Close-Off Actuator, 2-Way Valve-230/277V 29. COIL 1 ACTUATOR POSITION: Normally Closed - 2-Pos Close Off Normally Open - 2-Pos Close Off Normally Closed - Modulating Normally Open - Modulating Fail in Place - Modulating Normally Closed - Proportional Normally Open - Proportional Fail in Place - Proportional 30. COIL 2: 3-Row Cold Water 4-Row Cold Water 6-Row Cold Water 3-Row DX, Single Circuit 4-Row DX, Single Circuit 6-Row DX, Single Circuit 1-Row Hot Water 2-Row Hot Water 1-Row Steam 2-Row Steam 31. COIL 2 FPI: 8 FPI 10 FPI 12 FPI 14 FPI 32. COIL 2 AUTO AIR VENT: Manual Auto Air Vent 33. COIL 2 CASING: Galvanized Casing Stainless Steel Casing 34. COIL 2 TUBE WALL: 0.016" 0.025" 35. COIL 2 REFRIGERANT TYPE: R-410 36. COIL 2 DISTRIBUTOR: (See Krueger's selection software) 37. COIL 2 PIPING SIZE: 1/2", 3/4", 1", 1-1/4", 1-1/2" 38. COIL 2 PIPING VALVE: 2-Way Control Valve 3-Way Control Valve 3-Way with Balance ByPass Valve 39. COIL 2 PIPING PACKAGE: Manual Ball Valve w/ Memory Stop Manual Ball Valve w/ Memory Stop, Fixed Flow Ctrl Ball Valve in Bypass & Ball Valves w/ Memory Stop 40. COIL 2 FIXED GPM: 1/2" = 0.5 to 4.0 GPM in 0.5 GPM increments > 4.0 to 9.0 GPM in 1.0 GPM increments 3/4" = 4.0 to 15.0 GPM in 1.0 GPM increments 1" = 11.0 to 22.0 GPM in 1.0 GPM increments 1-1/4" = 18.0 to 29.0 GPM in 1.0 GPM increments 1-1/2" = 26.0 to 45.0 GPM in 1.0 GPM increments 41. COIL 2 UNIONS: Union 42. COIL 2 P/T PORTS: P/T Port 43. COIL 2 AQUASTAT BLEED LINE: Aquastat Bleed Line 44. COIL 2 Y-STRAINER: Y-Strainer Y-Strainer with Blowdown KBHD, KBVD © Copyright Krueger 2021 F2-93 BLOWER COILS | DIRECT DRIVE KBHD, KBVD Blower Coils | Horizontal and Vertical Direct Drive SUGGESTED SPECIFICATION & CONFIGURATION 45. COIL 2 ACTUATOR TYPE: Field Provided by Others 2-Position Close-Off Factory Provided 2-Position Close-Off, NC MV, 2-Way, Floating Point, Fail-In-Place, 24V MV, 3-Way, Floating Point, Fail-In-Place, 24V HP Close-Off Actuator, 2-Way Valve-24/115/208V HP Close-Off Actuator, 2-Way Valve-230/277V 46. COIL 2 ACTUATOR POSITION: Normally Closed - 2-Pos Close Off Normally Open - 2-Pos Close Off Normally Closed - Modulating Normally Open - Modulating Fail in Place - Modulating Normally Closed - Proportional Normally Open - Proportional Fail in Place - Proportional 47. ELECTRIC HEAT CASING: Blow Through Uninsulated Blow Through Double Wall 48. ELECTRIC HEAT VOLTAGE: (See Krueger's selection software.) 49. ELECTRIC HEAT KW: (See Krueger's selection software.) 50. ELECTRIC HEAT HAND: Left-hand Right-hand 51. MAGNETIC CONTACTOR: Magnetic Contactor 52. FUSING PER STEP: Fusing per Step 53. DOOR DISCONNECT: Door Interlocking Fused Disconnect Door Interlocking Non-Fused Disconnect 54. MAIN FUSING: Main Fusing 55. DRAIN PAN: IAQ Galvanized Drain Pan IAQ Stainless Steel Drain Pan 56. SECONDARY DRAIN CONNECTION: None Drain Connection 57. DRAIN PAN HANDING: Right Hand Left Hand 58. DRAIN PAN FLOAT SWITCH None Drain Pan float Switch 59. FILTER: 2" Throwaway 2" 30% Pleated (Merv 8) 2" 30% Pleated (Merv 8), 4" 65% Pleated (MERV 11) 2" 30% Pleated (Merv 8), 4" 85% Pleated (MERV 14) 2" 30% Pleated (Merv 8), 4" 95% Pleated (MERV 15) 60. SPARE FILTER: 2" Throwaway Spare Filter 2" 30% Pleated Spare (Merv 8) 4" 65% Pleated Spare (MERV 11) 4" 85% Pleated Spare (MERV 14) 4" 95% Pleated Spare (MERV 15) 61. BASE RAILS: Base Rails 62. INSULATION TYPE: Standard Fiberglass Foil Faced Fiberglass Closed Cell Foam Double Wall 63. ACCESS DOOR: Standard Hinged Doors with Lift and Turn Fasteners 64. VIBRATION: Rubber in Shear Spring 65. AQUASTAT Aquastat 66. THERMOSTAT: D- Series Digital (No 7 Day program), On/Off Actuator P- Series Digital (7 day Program), On/Off Actuator N- Series Digital (Networking Compatible), On/Off Actuator F- Series Digital (Networking Compatible), Floating Point Actuator V- Series Digital (Networking Compatible), Proportional Actuator 67. THERMOSTAT LOCATION: Remote Mounted Thermostat Unit Mounted Thermostat KBHD, KBVD F2-94 © Copyright Krueger 2021Adobe PDF Library 15.0 Adobe InDesign 15.0 (Windows)