Consumer Unit Design 50 Flush Switch Disconnector
For the distribution of power in a residential application, conforming to BS EN 61439-3 including Annex ZB (16kA rating).
The Design 50 has been created to fulfil market requirements for an aesthetically pleasing consumer unit. It meets the requirements of the wiring regulations (BS 7671) and allows the consumer unit to be installed flush at the height stated in the building regulations (Part M), with minimum impact on the area.
When fitted with RCBO on outgoing circuits, the board is designed to allow compliance with BS 7671:2008 regulations, specifically: 411.3.3 for additional protection by means of a 30mA RCD, 314.1&2 for segregation of circuits to avoid danger and minimise inconvenience in the event of a fault, and 522.6.202 for protection of wiring concealed in walls or partitions.
The curved lines remove the harsh appearance of a surface mounted enclosure on the wall. The ability to provide bespoke colour and pattern finishes allows the board to become part of the interior design, either by blending in or making a statement.
An image shows the Hager Design 50 flush mounted consumer unit with its door open, revealing internal components and wiring. A smaller inset diagram shows a switch labeled 'Sw/D/I'.
Incomer Options
Description | Size | Cat Ref. |
10 Way 100A Switch Disconnector Incomer | 4 | VSR110 |
14 Way 100A Switch Disconnector Incomer | 5 | VSR114 |
20 Way 100A Switch Disconnector Incomer | 7 | VSR120 |
Device Options
Single Pole, Single Mod RCBO 6kA, 6A - 45A (Cat Ref: ADN***)
Single Pole, Single Mod Reduced Height RCBO 6kA, 6A - 32A (Cat Ref: ADA3**G)
Features & Benefits
- Cable clamp: Secures supply cables on entry to the main incoming device, preventing any movement being transmitted through metertails to the device.
- Rear Knockouts: For ease of cable entry, with a Cable protector plate (VM02CE) provided.
- 2-piece base: Allows for first fix, second fix option.
- Adjustable Depth Base: Base assembly is adjustable from 72mm to 92mm. At 72mm, it allows for 60mm studwork and 12mm plasterboard.
- Full metal DIN rail: Provides secure and stable attachment of devices.
- Quick release clip on MCB/RCBO: Allows removal of MCB/RCBO with the busbar still in place.
- Optimised cabling space: The DIN rail position allows maximum cabling space.
- Top mounted terminal rail: Makes the wiring of the neutral and earth connections neat and simple.
- Health and Safety lock: Allows the door to be secured with circuits isolated during construction (via accessory, see overleaf).
- Torque settings: Displayed inside the front cover for easy access by the electrician.
- Lockable front door: Available via an accessory (see overleaf).
- Customisation: Available in a full range of colours, anodised finishes, and vinyl wrap options. Contact the Estimation Team on 01952 675600.
Technical Characteristics
Characteristic | Value |
Standards | BS EN 61439-3 |
Classification | Consumer Unit |
Rated & Operational Voltage (Un/Ue) | 230V a.c 50 Hz |
Rated Insulation Voltage (Ui) | 320V a.c. 50Hz |
Rated Frequency (fn) | 50 Hz |
Rated impulse withstand voltage (Uimp) | 4kV |
Rated Current of the Assembly (Ina) | 100A |
Rated Current of an Outgoing Circuit InC | MCB 6A - 63A (Marked Rated Current on Device) |
Rated Conditional Short Circuit of the Assembly (Icc) | Annex ZB: 16kA rms at 250V, power factor 0.6 with equipment and arrangements specified in Hager's technical documentation/catalogue |
Rated Current of outgoing unit (Inc) | RCCB 63A - 80A (marked rated current on device) |
Protection against electric shock | Consumer Unit shall be installed in an electrical system conforming to IEC 60364 / BS 7671 |
Rated Diversity Factor (RDF) / Values of assumed loading | 6 way - 9 way = 0.6 10 way and above - 0.5 |
Note on RDF | RDF only applies to continuously and simultaneously loaded circuits. In principle, this means adjacent circuit breakers having a load on time exceeding 30 minutes or where a load not exceeding 30 minutes has an 'off' time less than the 'on' time will need to have the rated diversity factor applied as indicated. |
Pollution Degree | 2 |
Types of System Earthing for which the assembly is designed | TNC-S and TN-S when installed in an electrical system conforming to BS 7671 |
Intended locations | Indoor use only |
Stationary assembly | Yes |
Degree of protection | IP2XC with door open / closed and full compliment of devices / blanks fitted. Note: Where cables are installed through the top wall of the enclosure, gaps of IP4X to be maintained. |
Intended use | Intended for use in domestic (residential) or similar premises |
Electromagnetic compatibility (EMC) classification | EMC environment B |
External design | Wall mounted, flush type, enclosed assembly. |
Mechanical impact protection | IK05 |
Type of construction | Fixed parts |
Incoming Line/Neutral terminal | 50mm² |
Incoming Earth Terminal | 16mm² |
Warranty | Hager undertakes to replace or repair at its discretion products should they become inoperable within the time periods as stated - 2 Years. |
Accessories
Accessory | Description | Cat Ref. |
Design 50 Locking bracket | Provides the ability to lock the consumer unit during the installation process | VSRHBL |
Design 50 Padlock | Used with VSRHBL | JK25A |
Design 50 Door Lock | Allows door to be lockable | VSRLOCK |
38mm Open Grommet | Allows protection of cables entering top or bottom of the enclosure | VMGROM |
Grommet strip | For protecting cables against damage when entering the board | VM05GS |
Dimensions and Knockouts
A diagram illustrates the dimensions of the Design 50 enclosure, with labels for Height, Width, Depth, and specific measurement points D, E, and F. Another diagram shows the location and size of knockouts on the top, bottom, back, and left faces of the enclosure.
Enclosure Size | 4 | 5 | 6 | 7 |
Height (mm) | 284 | 284 | 284 | 284 |
Width (mm) | 359 | 431 | 467 | 539 |
Depth (mm) | 105 | 105 | 105 | 105 |
D (mm) | 298 | 370 | 406 | 478 |
E (mm) | 252 | 252 | 252 | 252 |
F (mm) | 72 | 72 | 72 | 72 |
Number of Knockouts | 4 | 5 | 6 | 7 |
Top Face 50 x 20 (mm) | 4 | 5 | 6 | 7 |
Bottom Face 50 x 20 (mm) | 4 | 5 | 6 | 7 |
Back 100 x 50 (mm) | 2 | 2 | 2 | 3 |
Left Face 20.8 (mm) | 1 | 1 | 1 | 1 |
Adjustable Depth Base: The base assembly is adjustable from 72mm to 92mm. At 72mm this allows for a 60mm studwork and 12mm of plasterboard.
Manufacturer Information
Hager Ltd.
Hortonwood 50, Hortonwood, Telford, TF1 7FT
Phone: 01952 675 675