Hyfire HFW-PA-05 Bi-Directional Wireless Addressable Dual Path Optical Smoke Detector with Variable Sensitivity

Overview

This detector model samples the air in the protected area. An alarm condition is raised when the detected environmental smoke quantity exceeds the alarm threshold.

Compatibility

This detector is compatible only with wireless systems based on the Sagittarius protocol. For more specific information concerning compatibility refer to your fire security system supplier.

Installation - Important Notes

For detector spacing, placement and special applications refer to your specific national standards. Mount the detector as far as possible from metal objects, metal doors, metal window openings, etc. as well as cable conductors, cables (especially from computers), otherwise the operating distance may greatly drop. The detector must NOT be installed near electronic devices and computer equipment that can interfere with its wireless link quality. This detector must be installed according precisely to the procedures described in this manual. Test this detector after installation.

Before Installing the Detector

  1. Extract the batteries cover from the back of the detector.
  2. Power-up the detector by removing the isolating tab in the battery housing. LED indicators signal "Power up".
  3. Link the detector to the Sagittarius wireless system (LINKING).
  4. Check the WIRELESS LINK QUALITY.
  5. SELECT A GOOD LOCATION FOR THE DETECTOR.
  6. Tag device's loop and address data (IDENTIFICATION).
  7. Fix the detector supporting base to the wall (BASE INSTALLATION).

LED Indicators

Picture 1 illustrates the LED indicators, providing visual indication for functional conditions and battery levels as detailed in Table 1.

Picture 1 Description: Shows the detector with two marked LED indicator locations.

Detector's statusLEDs indication
Power up1 second GREEN, then 4 X 0.5 second RED blink
Linking to the systemBlinking GREEN until linking is completed
Link failureRED on (continuous)
Normal conditionLEDs off
AlarmBlinking RED: 0.5 second on and 0.5 second off
Battery 1 fault0.1 second ORANGE blink, then 5 seconds off
Battery 2 fault0.1 second GREEN blink, then 5 seconds off
Both batteries fault0.1 second ORANGE, then 5 seconds off; 0.1 second GREEN, then 5 seconds off
Other faultsequential ORANGE / GREEN 0.5 second blinking
TamperLEDs off
Lost link with wire to wireless translator / wireless expanderLEDs off
Test Mode - Detector is more reactiveBlinking GREEN every 1 second for 1 minute

Linking

The system is waiting to achieve a wireless child device. For further information, refer to the translator's or the Wirelex configuration software's literature.

  1. Move the link switch's cursor from ON to the opposite side of its run (referred to as BLANK, as it carries no indication). LED indicators signal "Linking to the system" (Picture 2).

Linking is successful when: a) the translator indicates so (check translator's literature) OR b) the Wirelex software indicates so (check the Wirelex's literature).

If linking is unsuccessful:

  1. Check if evident mistakes were made.
  2. Perform the LINKING RECOVERY.

Linking Recovery

  1. Take out both batteries from their holders.
  2. Move alternatively the link switch to ON / BLANK five times (Picture 2).
  3. Move the link switch to ON.
  4. Reinsert both batteries into their holders, oriented as per polarity marks.
  5. Perform the LINKING procedure.

Picture 2 Description: Illustrates the detector's internal compartment showing batteries and a link switch.

Important Note: During the linking phase, the detector must be positioned close to the aerial (within a few centimeters) of the translator or expander to which it is being linked.

Detector Sensitivity Settings

During installation using the Wirelex software, it is possible to set the smoke sensitivity of the detector (see Table 4). Otherwise, if the installation is performed manually through the translator keyboard, default settings will be applied.

Wireless Link Quality

It is possible to check wireless link quality between the detector and its linked-to translator or expander:

  1. Move the link switch to the ON position.
  2. LED indicators will start blinking according to Table 2.
Communication qualityAssessmentDevice's indication
No communicationFailTwo red blinks
Communication quality: 0 dB - 10 dB (Mark 2)Poor, not acceptableOne red blink
Communication quality: 10 dB - 20 dB (Mark 3)Medium-low, not recommendedOne green blink
Communication quality: 20 dB - 30 dB (Mark 4)GoodTwo green blinks
Communication quality: > 30 dB (Mark 5)ExcellentTwo green blinks

Note: Ensure the link switch is returned to the "BLANK" (operational) position on completion of testing.

Select a Good Location for the Detector

Choose a placement position for the detector that:

  • Complies with your specific standards.
  • Is reached by a strong wireless signal from its linked-to translator or expander module.
  • Is not interfered by environmental factors.

Identification

For identification purposes, analogue loop number and device's address can be recorded on the plastic tag supplied with the base (Picture 3). Extract the plastic tag from the bottom of the base, write or label identification data on it, and finally, insert it in the side slot of the base.

Picture 3 Description: Depicts the detector base with an arrow pointing to a slot for an identification tag.

Base Installation

Fix the base to the wall with the provided screws (Picture 4).

Picture 4 Description: Shows the detector base being fixed to a wall using screws.

Detector Placement

  1. Install the batteries cover.
  2. Position the detector centrally on the base, ensuring it is level.
  3. Rotate clockwise applying gentle pressure. The detector will drop into its keyed location.
  4. Continue to rotate clockwise a few degrees until the detector has fully engaged in the base.
  5. When the detector is firmly engaged, check the alignment of the raised reference marks on the detector and on the base (Picture 5).

Picture 5 Description: Illustrates the detector being rotated onto its base, highlighting alignment marks.

Important Note: Dust covers do NOT provide complete protection against contamination; detectors should be removed before construction, major re-decoration, or other dust-producing work is started. Dust covers MUST be removed before the system can be made operational.

Detector Locking

To lock the detector to the base, screw in the provided security screw; screw entry is located on the side of the detector's base (Picture 6).

Picture 6 Description: Shows the side of the detector base with an arrow indicating the location for the security screw.

Tamper Detection

When the detector is detached from the base, a tamper message event is sent to the control panel.

Testing

Test this detector after installation. After each test, reset the fire security system from the control panel, as per your control panel instructions.

Test 1 - Magnet Test

  1. Hold a suitable magnet in correspondence of the indicated area (Picture 7).
  2. LED indicator will signal "Test Mode" (blinking GREEN every 1 second).
  3. Apply again the magnet in correspondence of the indicated area (Picture 7).
  4. If it works, LED indicator will signal "Alarm".

Test 2 - Aerosol Test

  1. Hold a suitable magnet in correspondence of the indicated area (Picture 7).
  2. LED indicator will signal "Test Mode" (blinking GREEN every 1 second).
  3. By following its specific instructions, apply the aerosol test device to the detector.
  4. Wait a few seconds.
  5. If it works, LED indicator will signal "Alarm".

Picture 7 Description: Depicts the detector with an arrow indicating the specific area for magnet application during testing.

Maintenance - Cleaning

  1. Remove the detector from its base.
  2. Smoke entry areas: use a small, soft bristle brush to dislodge any obvious contaminants such as insects, spider webs, hairs, etc.
  3. Smoke entry areas: use a small vacuum tube or dry, clean, compressed air to suck up or blow away any remaining small particles.
  4. Wipe the exterior housing of the detector with a clean, damp, lint-free cloth to remove any surface film that can later attract airborne contaminants.
  5. Install the detector onto its base again.
  6. Test the detector.

Maintenance - Battery Replacement

When a low battery condition is indicated, both batteries must be changed altogether. During this procedure, the linking switch must NOT be touched at all!

  1. Detach the detector from its base.
  2. Extract the batteries cover.
  3. Extract the batteries.
  4. Insert the new batteries into their holders, oriented as per polarity marks.
  5. Reinstall the batteries cover.
  6. Reinstall the detector onto its base.
  7. Test the detector.

Technical Specifications

ParameterValueNotes
Communication range with the translator or expander200 mOpen space
Operating frequency868 MHz
Operating frequency channels7
Radiated power≤ 14 dBm (25 mW)
Batteries type *Type CR123A (3 Vdc)8.2 years life
Parent expander's check-up period60 seconds (default setting)
Dimensions110 mm x 65 mmBase and batteries included
Weight190 g
IP rating40
Max tolerated humidity (no condensing)95% RH
Operating temperature rangeFrom -10 °C to +55 °C

* When a low battery condition is indicated, both batteries must be changed for new cells. Lifespan of batteries indicated is subject to standard environmental conditions, default monitor settings and excellent link quality.

** Check latest version of document TDS-LOPXX for further data, obtainable from your supplier.

Smoke Sensitivity (EN 54)

Threshold levelWirelex settingNotes
Level 1High
Level 2Normaldefault
Level 3Low

Note of the Document

Argus Security Srl hereby declares that this detector is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. A copy of the original Declaration of Conformity (Document: DoC LI01) is made available to the user on website: www.argussecurity.it

Warnings and Limitations

Our devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace the devices to minimize the risk of reduced performance caused by external factors. Ensure that this device is only used with compatible control panels. Detection systems must be checked, serviced, and maintained on a regular basis to confirm correct operation. Smoke detectors may respond differently to various kinds of smoke particles, thus application advice should be sought for special risks. Detectors cannot respond correctly if barriers exist between them and the fire location and may be affected by special environmental conditions. Refer to and follow national codes of practice and other internationally recognized fire engineering standards. Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically.

Warranty

All devices are supplied with the benefit of a limited 3 years warranty relating to faulty materials or manufacturing defects, effective from the production date indicated on each product. This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage. Product must be returned via your authorized supplier for repair or replacement together with full information on any problem identified. Full details on our warranty and product's returns policy can be obtained upon request.

PDF preview unavailable. Download the PDF instead.

L20-LOPXX-1400 REV A Microsoft Publisher per Office 365

Related Documents

Preview Hyfire HFW-EM-01 Wireless Expander Module: Installation and Operation Guide
Comprehensive guide to the Hyfire HFW-EM-01 Wireless Expander Module, covering general description, positioning, installation, wiring, programming, technical specifications, and testing for fire detection systems.
Preview Hyfire HFI-TA-05 Analogue Category P Thermal Detector - Installation, Features, and Specifications
Detailed information on the Hyfire HFI-TA-05 Analogue Category P Thermal Detector, including general description, installation, wiring, programming, maintenance, technical specifications, and testing procedures. Designed for open area protection with Altair analogue-intelligent addressable communication.
Preview HFW-BSB-05 Wireless Sounder Base with Visual Indicator - Hyfire
Technical specifications, installation guide, and operational details for the Hyfire HFW-BSB-05 Wireless Sounder Base with Supplementary Visual Indicator. Features include wireless communication, LED indicators, battery specifications, and output settings.
Preview Hyfire HFW-CEM-02 Wireless Conventional System Expander Module Installation and Technical Guide
Detailed technical specifications, installation guide, and wiring instructions for the Hyfire HFW-CEM-02 Wireless Conventional System Expander Module, designed to integrate wireless devices into conventional fire alarm systems.
Preview Hyfire TAU-EXM-01 Taurus Expander Module User Instructions Manual
User instructions manual for the Hyfire TAU-EXM-01 Taurus Expander Module, detailing technical specifications, installation, wiring, programming, and testing for wireless fire security systems.
Preview Hyfire HFC-SBR-23-03 Conventional Wall Sounder + Visual Alarm Device Installation and Operation Manual
This document provides comprehensive installation, wiring, and operational guidance for the Hyfire HFC-SBR-23-03 Conventional Wall Sounder + Visual Alarm Device. It covers compatibility, mounting, terminal connections, tone and volume settings, testing procedures, technical specifications, and warranty information.
Preview Hyfire HFW-STK-03 Wireless Survey Kit User Manual
User manual for the Hyfire HFW-STK-03 Wireless Survey Kit. This guide provides essential information for installers on setting up, operating, and troubleshooting the kit to ensure optimal wireless link quality for fire detection systems. Includes technical specifications and component details.
Preview Hyfire HFW-RI-02 Static Wireless Remote Indicator User Manual
This document provides a comprehensive guide to the Hyfire HFW-RI-02 Static Wireless Remote Indicator, covering its general description, technical specifications, device power supply, linking procedures, battery management, tamper detection, testing, reset, maintenance, and placement guidelines. It details the device's function in signaling fire alarms and its integration with the Hyfire wireless system.