I. The gateway is used externally to connect with Beijer HMI's communication port (Modbus TCP). II. The main controller is in charge of the management and ...


File Info : application/pdf, 13 Pages, 1.54MB

iO-GRID M Modbus TCP Connection Operating Manual(Beijer) EN
2302EN V2.0.0
and Beijer HMI Modbus TCP Connection
Operating Manual

Table of Contents

1.

Remote I/O Module Configuration List............................................................................... 3

1.1 Product Description.............................................................................................................. 3

2.

Gateway Parameter Settings ................................................................................................ 4

2.1 i-Designer Program Setup .................................................................................................... 4

3.

Beijer HMI Connection Setup.............................................................................................. 9

3.1 Beijer HMI Hardware Connection ....................................................................................... 9

3.2 Beijer HMI IP Address and Connection Setup .................................................................. 10

2

1. Remote I/O Module Configuration List

Part No.

Specification

GFGW-RM01N Modbus TCP-to-Modbus RTU/ASCII, 4 Ports

GFMS-RM01S Master Modbus RTU, 1 Port

GFDI-RM01N Digital Input 16 Channel

GFDO-RM01N Digital Output 16 Channel / 0.5A

GFPS-0202

Power 24V / 48W

GFPS-0303

Power 5V / 20W

Description Gateway Main Controller Digital Input Digital Output Power Supply Power Supply

1.1 Product Description
I. The gateway is used externally to connect with Beijer HMI's communication port (Modbus TCP)
II. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
III. The power module is standard for remote I/Os and users can choose the model or brand of power module they prefer.

3

2. Gateway Parameter Settings
This section details how to connect to Beijer HMI. For detailed information, please refer to the iO-GRID M Series Product Manual
2.1 i-Designer Program Setup
I. Make sure that the module is powered and connected to the gateway module using an Ethernet cable
II. Click to launch the software
4

III. Select "M Series Module Configuration" IV. Click on the "Setting Module" icon
5

V. Enter the "Setting Module" page for M-series VI. Select the mode type based on the connected module
6

VII. Click on "Connect" VIII. Gateway Module IP Settings
Note: The IP address must be in the same domain as the controller equipment
7

IX. Gateway Module Operational Modes
Note: Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N)
8

3. Beijer HMI Connection Setup
This chapter explains how to use the iX Developer program to connect Beijer HMI to the gateway and add a remote I/O. For detailed information, please refer to iX Developer User Manual
3.1 Beijer HMI Hardware Connection
I. The connection port is on the right at the bottom of the machine. There are LAN A and LAN B
II. Connect the port at the bottom of the machine to the gateway's port
9

3.2 Beijer HMI IP Address and Connection Setup
I. Once HMI is powered, press on the HMI screen to enter the service menu and then click on "IP Settings".
II. Click on "Specify an IP Address" and set "IP Address" to the same domain as the gateway domain at 192.168.1.XXX.
10

III. Launch iX Developer and select "MODICON" and "Modbus Master" to add a new controller
IV. Click on the "Controller" tab to enter the controller setup page. Select the controller and then click on "Settings"
11

V. Connection method setup
 From the "Communication mode" drop-down menu, select "Ethernet TCP/ IP"  Setup the default station number  From the "Modbus protocol" drop-down menu, select "RTU"  From the "32-bit World mapping" drop-down menu, select "Little-endian"  From the "Force function code 0x10" drop-down menu, select "Enable"  From the "String swap" drop-down menu, select "Disable"
12

VI. Click on "Stations" and set the "Station" and "IP Address" the same as the gateway
VII. Click on "Tab" to enter the tab setting page. Next, click on "New" and set up the tab register's location
 iO-GRID M 's first GFDI-RM01N has the initial address at 44096  iO-GRID M 's first GFDO-RM01N has the initial address at 48192
13

