Toester Product Data

Hydronic Kickspace Heaters

Kickspace heaters are designed for use with forced hot water residential heating systems. They feature a copper tube, aluminum finned heating element, and an electric motor and blower with a unique cross-flow design. These units deliver a comfortable stream of warmed air at or near floor level and are compact for easy installation. The Type K heater is ideal for horizontal floor installation in enclosures like kitchen counter cabinets or bathroom sinks. They are suitable for radiant systems with a low-temperature aquastat set to turn on at 110°F. Type W is for vertical mounting, recessed in wall studs, with upward air discharge through a flush-mounted, louvered front panel. Type F is for surface-mounted wall units, with air discharged evenly upward through a louvered front panel. All models utilize heating elements with 1/2" nominal (5/8" O.D.) copper tube connections and a 115V electric blower motor. Each unit is interwired with a 120°F (49°C) reverse-acting aquastat that ensures operation only when hot water is circulating. These units are not intended for one or two-pipe steam systems. For gravity-fed systems, a separate circulator pump is recommended for the kickspace heater.

Heating Capacity (BTU/Hr.*) for All Models

Entering Water Temperature (°F) 1 Gal. 2 Gal. 3 Gal.
Model 42 Model 84 Model 120 Model 42 Model 84 Model 120 Model 42 Model 84 Model 120
**110 1480 3370 8425 1520 3440 8535 1560 3515 8730
120 1800 4055 8875 1840 4145 8995 1875 4230 9205
130 2175 4770 9330 2220 4875 9455 2260 4980 9680
140 2590 5540 9780 2640 5670 9915 2690 5795 10150
150 3050 6300 10230 3120 6440 10375 3190 6585 10625
160 3510 7000 10685 3590 7155 10835 3670 7310 11100
170 3895 7730 11135 3980 7900 11295 4065 8070 11570
180 4278 8460 11585 4375 8650 11755 4470 8840 12045

Coils tested at 150 PSI.

*Based on 65°F entering air temperature with fan at high speed, including the heating effect factor. Ratings reduced by 15% at low speed.

**Blower operates at water temperature above 120°F with standard self-contained aquastat. Optional low temperature aquastat available for low temperature applications.

Supply and return connections are 1/2" nominal. Units are not recommended for use with steam.

Standard Aquastat Range 120°F - 105°F

Low Temp Aquastat Range 110°F - 95°F

Specifications

MOTOR INFORMATION

MODEL AMP WATT RPM HP VOLTAGE CFM (HIGH SPEED)
42 .50 30.7 3200 .034 115 53
84 .50 30.7 3200 .034 115 103
120 .74 66.8 3200 .068 115 127

FRICTION LOSS (HEAD)

MODEL 1 GALLON 2 GALLONS 3 GALLONS
42 .17' .22' .43'
84 .8' .95' 1.45'
120 1.2' 1.5' 2.97'

[ETL Listed Mark]

Dimensional Data

Dimensions shown in English and metric ( ).

FIGURE A - MODEL 42

FIGURE B - MODEL 84

FIGURE C - MODEL 120

Electrical Connections

Must use wires suitable for at least 194°F (90°C).

WIRING DIAGRAM 1 Direct 115V line

WIRING DIAGRAM 2 Line voltage type room thermostat

Connection through a circulator or zone auxiliary switch may also be used to permit instant shutdown of the blower as the circulator stops (see diagram #3).

WIRING Diagram 3

Installation Kits (Optional)

Recessed W42 • W84 • W120

Recessed kits fit into wall recesses, ideal for narrow hallways, mud rooms, laundry areas, and other tight locations. The smaller Model W42 fits between standard 16" center studs.

Surface F42 • F84 • F120

Surface kits install quickly and easily directly to a wall surface. They add warmth to cold hallways, bathrooms, kitchens, laundry rooms, family rooms, work shops, and additions.

Floor FK42 • FK84 • FK120

For areas with glassed-in walls or sliders, Floor kits install easily between standard floor joists. The grille offers a choice of forward or rear directional air flow and easy accessibility for routine maintenance.

Optional Accessories

Piping Charts

ONE PIPE SYSTEM

UP FEED

[Diagram of One Pipe System - Up Feed]

DOWN FEED

[Diagram of One Pipe System - Down Feed]

TWO PIPE SYSTEM

[Diagram of Two Pipe System]

[Diagram of Steam Condensate]

NOTE: In an up feed system, the unit is located above the hot water supply line. In a down feed system, the unit is located below the hot water supply line.

For One Pipe System Down Feed, two directional flow tees should be used, spaced 12 to 18 inches apart. The directional arrow on the directional flow ‘T’ at the return side should point towards the supply directional flow 'T'.

Maintenance and Service

Properly installed, the Kickspace heater requires minimal attention. The heating element is constructed and tested to be durable and non-ferrous, requiring no service. The cross-flow blower is engineered for 10,000 hours of bearing life. As with any electrical rotating device, a yearly inspection and cleaning is recommended. Air movement can cause dust and lint accumulation on rotor blades and air passages. Regular cleaning with a vacuum cleaner tool is advised, with frequency determined by prevailing conditions. Ensure the air grille is not blocked by foreign objects or materials.