User Manual for netvox models including: R718PA1, Wireless CO Sensor

R718PA1 User Manual ENG 20210105

alina netvox NETVOX

Wireless CO Sensor R718PA1 User Manual

PDF preview unavailable. Download the PDF instead.

R718PA1Usermanual
ModelR718PA1
Wireless CO Sensor

Model: R718PA1

Wireless CO Sensor R718PA1
User Manual

Copyright©Netvox Technology Co., Ltd. This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The specifications are subject to change without prior notice.

Table of Content
1. Introduction....................................................................................................................................... 2 2. Appearance........................................................................................................................................ 3 3. Main Feature ..................................................................................................................................... 3 4. Set Up Instruction ............................................................................................................................. 4 5. Data Report ....................................................................................................................................... 5 6. Installation ........................................................................................................................................ 7 7. Important Maintenance Instruction................................................................................................... 7
1

1. Introduction
R718PA1 is a Class A device based on the LoRaWANTM protocol of Netvox and is compatible with the LoRaWAN protocol. R718PA1 can be connected to a corresponding carbon monoxide sensor (RS485) to report the concentration of carbon monoxide collected by the device to the corresponding gateway. The device is compatible with the LoRaWAN protocol. LoRa Wireless Technology: LoRa is a wireless communication technology dedicated to long distance and low power consumption. Compared with other communication methods, LoRa spread spectrum modulation method greatly increases to expand the communication distance. Widely used in long-distance, low-data wireless communications. For example, automatic meter reading, building automation equipment, wireless security systems, industrial monitoring. Main features include small size, low power consumption, transmission distance, anti-interference ability and so on. LoRaWAN: LoRaWAN uses LoRa technology to define end-to-end standard specifications to ensure interoperability between devices and gateways from different manufacturers.
2

2. Appearance
CO Senser Indicator
Function Key
Adaptor
3. Main Feature
 Adopt SX1276 wireless communication module  12V DC power supply  CO detection  The base is attached with a magnet that can be attached to a ferrous object  Main body protection level IP65 / IP67 (optional)  Compatible with LoRaWANTM Class A  Frequency hopping spread spectrum  Configuring parameters and reading data via third-party software platforms, and set alarms via
SMS text and email (optional)  Applicable to third-party platforms: Actility/ThingPark, TTN, MyDevices/Cayenne
3

4.Set Up Instruction

On/Off Power on Turn on Turn off (Restore to factory setting) Power off
Note:
Network Joining

DC12V adapter DC12V power supply, the green indicator flashing once means turn on successfully. Press and hold the function key for 5 seconds till the green indicator flashes 20 times. Remove DC12V adapter. 1. The first 5 seconds after power on, the device will be in engineering
test mode. 2. On/off interval is suggested to be about 10 seconds to avoid the
interference of capacitor inductance and other energy storage components.

Turn on the device to search the network to join.

Never joined the network

The green indicator stays on for 5 seconds: success

The green indicator remains off: fail

Turn on the device to search the previous network to join. Had joined the network
The green indicator stays on for 5 seconds: success (Not restore to the factory setting)
The green indicator remains off: fail

Fail to join the network Function Key

Suggest to check the device verification information on the gateway or consult your platform server provider.

Press and hold for 5 seconds Press once

Restore to factory setting / Turn off The green indicator flashes 20 times: success The green indicator remains off: fail The device is in the network: the green indicator flashes once and sends a report The device is not in the network: the green indicator remains off
4

5. Data Report

The device will send a version package report immediately after power-on. Then, it will send a report data with the concentration of carbon monoxide after it is powered on for 20s. The device sends data according to the default configuration before any other configuring.
Default setting: MaxTime: Max Interval = 3min = 180s MinTime: The MinTime configuration is not available. *But the software has restriction, MinTime must be configured a number greater than 0.

Note: 1. The cycle of the device sending the data report is according to the default. 2. R718PA1 reports the concentration of carbon monoxide.

Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver http://loraresolver.netvoxcloud.com:8888/page/index to resolve uplink data.
Example of ConfigureCmd FPort0x07

Bytes

1 CmdID

1 DeviceType

Var (Fix =9 Bytes) NetvoxPayLoadData

CmdID­ 1 byte DeviceType­ 1 byte ­ Device Type of Device NetvoxPayLoadData­ var bytes (Max=9bytes)

5

Description

Device

Cmd Device ID Type

NetvoxPayLoadData

ConfigReport Req

0x01

MinTime

MaxTime

(2bytes Unit: s) (2bytes Unit: s)

Reserved (5Bytes,Fixed 0x00)

ConfigReport Rsp
ReadConfig ReportReq

R718PA1

0x81 0x02

ReadConfig ReportRsp

0x82

0x57

Status (0x00_success)

Reserved (8Bytes, Fixed 0x00)

Reserved (9Bytes, Fixed 0x00)

MinTime

MaxTime

(2bytes Unit: s) (2bytes Unit: s)

Reserved (5Bytes,Fixed 0x00)

(1) Configure the report MaxTime = 1min (The MinTime configuration is useless, but it needs to be set greater than 0 because of the software limitation.) Downlink: 0157000A003C0000000000 Device Return: 8157000000000000000000 (configuration is success) 8157010000000000000000 (configuration is failure)

(2) Read device configuration parameters Downlink: 0257000000000000000000 Device Return: 8257000A003C0000000000 (device current configuration parameter)

6

6.Installation

1. R718PA1 has a built-in magnet (as the figure below). It can be attached to the surface of an iron object conveniently and quickly when it is installed.

2. The device periodically reports the data according to Max Time. The default Max Time is 3min.

In order to make the device installation more secure, use screws (purchased) to fix the device to the wall or other surface (such as the installation diagram). The device is screwed by two screws in the middle (purchased by users).
Note: Do not install the device in a metal shielded box or in an environment with other electrical equipment around it to avoid affecting the wireless transmission of the device.

Note: Max Time can be modified by the downlink command, but it is not recommended to set this time too short.
3. The device can be used in scenarios such as:
 Boiler room  Parking lot  Gas water heater  Mine environment monitoring

7

7.Important Maintenance Instruction
Kindly pay attention to the following in order to achieve the best maintenance of the product:
· Keep the equipment dry. Rain, moisture and various liquids or water may contain minerals that can corrode electronic circuits. In case the device is wet, please dry it completely.
· Do not use or store in dusty or dirty areas. This way can damage its detachable parts and electronic components.
· Do not store in excessive heat place. High temperatures can shorten the life of electronic devices, destroy batteries, and deform or melt some plastic parts.
· Do not store in excessive cold place. Otherwise, when the temperature rises to normal temperature, moisture will form inside which will destroy the board.
· Do not throw, knock or shake the device. Treating equipment roughly can destroy internal circuit boards and delicate structures.
· Do not wash with strong chemicals, detergents or strong detergents. · Do not paint the device. Smudges can make debris block detachable parts up and affect normal
operation. · Do not throw the battery into the fire to prevent the battery from exploding. Damaged batteries may also explode.
All the above suggestions apply equally to your device, batteries and accessories. If any device is not operating properly. Please take it to the nearest authorized service facility for repairing.
8


alina netvox Adobe PDF Library 11.0