2021-12-28 — A 2” filter requires 40 GPM at 40 PSI to backwash properly. If this flow and pressure for backwash can't be maintained while irrigating, the flow to irrigation ...

PDF HN-G-01/ 02 Filter Series - Rain Bird

Quick Start Guide Rain Bird Corporation 6991 East Southpoint Rd. Tucson, AZ 85756 D42057 QR code links to digital manual. 1. Estimate flow rate and record pressure Place a 5 gallon bucket at the water source and allow it to flow without restriction into the bucket. Time how long it takes to fill to the 5 gallon point. ... 12/15/2021 3:23:47 PM ...

PDF preview unavailable. Download the PDF instead.

42057 15de21 hn g qs-guide-1
HN-G-01/ 02 Filter Series Quick Start Guide

NOTICE:
Changes or modifications not expressly approved by Rain Bird could void the user's authority to operate the equipment.
WARNING
It is extremely dangerous to open the filter, or control tubing while under pressure. Always depressureize before performing any maintenance or troubleshooting.
Rain Bird Corporation 6991 East Southpoint Rd.
Tucson, AZ 85756

D42057

QR code links to digital manual

1. Estimate flow rate and record pressure

Place a 5 gallon bucket at the water source and allow it to flow without restriction into the bucket. Time how long it takes to fill to the 5 gallon point.

Example

Volume of Bucket (in gallons) Time to fill bucket (in seconds)

5 x 60 =43 GPM
7

Backwash requirements A 1" filter requires 30 GPM at 40 PSI to backwash properly. A 2" filter requires 40 GPM at 40 PSI to backwash properly. If this flow and pressure for backwash can't be maintained while irrigating, the flow to irrigation must be stopped (using an optional controlled outlet valve) while the filter backwashes.

Static (and dynamic) pressures over 100 PSI require a pressure regulator.

2. Rank your water source
Flow is dependent on Water Source Quality and the micron size of the screen. The following chart defines the maximum flows allowable based on Water Source Quality and screen micron size. Most applications will follow the Average, Poor or Very Poor lines. Water source should be rated at worst case scenario if water quality varies during the year (such as algae blooms during summer). A general guide to Water Quality is also shown below.

Good

Average

Poor

Very Poor

Solids

< 20 ppm

< 40 ppm

< 80 ppm

< 110 ppm

Screen size

Example

Well Water, municipal supply or equal.

Very little, 100% clear, Contamination similar to drinking water
quality.

Filter Size
400 micron (47 mesh)
200 micron (88 mesh)
150 micron (100 mesh) 100 micron (150 mesh)

1"
40 GPM 9 m3/h 40 GPM 9 m3/h 40 GPM 9 m3/h 30 GPM 6.8 m3/h

2"
100 GPM 22.7 m3/h 100 GPM 22.7 m3/h 95 GPM 21.6 m3/h 75 GPM 17 m3/h

Clear lake water or equal
95% clear water, small contaminants. No real discolouration of the
water.

River water.
Light to medium discolouration.

Brown or green water (mud/algae).
Heavy discolouration. Medium algae, visible silt/
dirt etc.

Maximum Flow

1"

2"

1"

2"

1"

2"

40 GPM 9 m3/h 37 GPM 8.4 m3/h 33 GPM 7.5 m3/h 25 GPM 5.7 m3/h

100 GPM 22.7 m3/h 85 GPM 19.3 m3/h 70 GPM 15.9 m3/h 45 GPM 10.2 m3/h

36 GPM 8.2 m3/h 33 GPM 7.6 m3/h
Not recommended

55 GPM 12.5 m3/h 50 GPM 11.4 m3/h 40 GPM
9 m3/h
Not recommended

Not recommended

35 GPM 8 m3/h 30 GPM 6.8 m3/h
Not recommended

3. Installation Example
How your filter is installed will depend on how your system is structured and the specific requirements of your site. This example illustrates a stand-alone filter installation with minimal added components in discharge plumbing like what is located on a municipal feed water source (or pumped water where the pump is located remotely).

The drain line can be swivelled 360 degrees to any discharge direction by loosening the band clamp (remembering to tighten it afterward).
Gauges on the inlet and outlet are highly recommended to be able to monitor pressure differential visually.

1/4" Connection 1/4" Tubing Piston
1" Hydraulic drain valve Union fitting*

Drain should not discharge under water level, or in any way that would provide back pressure, as this will impede performance
The discharge needs to be unobstructed and if longer than 20 feet the discharge line should be up-sized to 1.25" or 1.5" PVC.

Union fitting* Union fitting*

Drain (to drain) Inlet (from pump)

Outlet (to irrigation)

* User to supply

Unions are required for ease of maintenance and in order to make installation easier. With unions, at all recommended spots, the filter may be removed for service and any threaded connections can also be easily accessed if any of these need to be tightened up or resealed due to movement during shipping or installation. The drain will be a 1" union. The inlet and outlet will be either 1" or 2" unions depending on the model ordered. Unions will make servicing and winterizing the filter much easier. A bypass loop with bypass valve is also recommended so that the filter can be bypassed during service if required.
Follow standard PVC solvent welding procedure to plumb the filter into the irrigation line.

The Inlet, Outlet and Drain line pipes need to be supported so that no stress is transferred to the filter. Pipe support is attached to pipe with a pipe attachment. Can take various forms like this:

4. Mechanical Installation

1.

2.

3.

Piston

Filter assembly

O-ring

1. The Filter unit ships without the piston installed 2. Ensure that the o-ring is in place on the threads of the cylinder. Push the piston into the main body of filter. Ensure that the push to
connect fitting at the top of the piston lines up with the 1/4: black tubing. 3. Push the 1/4" tubing into the push to connect fitting at the top of the Piston.

5. Electrical Installation

5.1 Battery

1.

2.

3.

1. Remove the top gray cover (push up the sides over the indent). 2. Remove the black battery tray and install the 4x "D Cell" batteries as shown. 3. The controller will come to life. It goes to sleep quickly, holding down any of the three lower buttons for a few seconds wakes it
back up. 4. Press the far right (M) button on backwash controller to test that the installation has been succesful, a Backwash sequence should
occur.
5.2 12v DC Power Adapter
5. Plug the power adapter (supplied) in to a 110v ac outlet (if outlet is outdoors a 4 gang weather protected GFCI should be used) 6. The controller will come to life. It goes to sleep quickly, holding down any of the three lower buttons for a few seconds wakes it
back up. 7. Press the far right (M) button on backwash controller to test that the installation has been succesful, a Backwash sequence should
occur.

