Operator Manual

Universal Input Controller | Programmable temperature controller


File Info : application/pdf, 3 Pages, 1.14MB

PDF preview unavailable. Download the PDF instead.

Product-027-OM
zenex 48X48 / 96X96
Universal PID Temperature Controller
with Programmable Timer

I / O CONFIGURATION PARAMETERS : PAGE-10

Parameters

Settings (Default Value)

Input Type

Refer Table 1 (Default : Type K)

Temperature Display Units Temperature Range Control Output Type

°C
°F (Default : °C)
Min. to Max. specified for the selected Input Type
(Refer Table 1) (Default : 1375)
Refer Table 2 (Default : Relay)

Control Mode Control Logic Hysteresis Setpoint Low Limit Setpoint High Limit

On-Off
PID (Default : PID)
Direct
Reverse (Default : Reverse)
1 to 999°C or 0.1 to 99.9°C (Default : 2 or 0.2)
Min. Range to Setpoint High for the selected Input Type
(Default : -200)
Setpoint Low to Max. Range for the selected Input Type
(Default : 1375)

Parameters Utility Option
Slave ID Baud Rate Communication Write Enable

Settings (Default Value)
None Serial Comm. Soak Start (Default : None) 1 to 127 (Default : 1)
1200, 2400, 4800, 9600 (Default : 9600)
No Yes (Default : Yes)

PID CONTROL PARAMETERS : PAGE-14

Parameters

Settings (Default Value)

% Output Power

Not Applicable (Default : Not Applicable)

Cycle Time Proportional Band

0.5 to 120.0 Seconds (in steps of 0.5 secs.)
(Default : 0.5)
0.1 to 999.9 (Default : 10.0)

Integral Time

0 to 1000 Seconds (Default : 100)

Derivative Time

0 to 250 Seconds (Default : 25)

SUPERVISORY PARAMETERS : PAGE-11

Parameters

Settings (Default Value)

Tune / Optimize Command

No

Yes

(Default : No)

Tune / Optimize Abort Command

No

Yes

(Default : No)

Overshoot Inhibit

Enable

Overshoot Inhibit Factor

Disable (Default : Disable)
1.0 to 2.0 (Default : 1.2)

Self-tune on Setpoint Change Offset for PV Digital Filter for PV Permission for OP2/OP3 Setpoint Editing on Operator Page Soak Abort Command on Operator Page Soak Time Adjustment on Operator Page

Enable
Disable (Default : Disable) -1999 to 9999 or
-199.9 to 999.9 (Default : 0)
0.5 to 25.0 Seconds in steps of 0.5 Seconds
(Default : 1.0)
Enable
Disable (Default : Enable)
Enable
Disable (Default : Enable)
Enable
Disable (Default : Enable)

OP2 FUNCTION PARAMETERS : PAGE-12

Parameters

Settings (Default Value)

Output-2 Function Selection

None

Alarm

Control

Type

Blower
Set point (Default : None) OP2 Function : Alarm-1
Process Low Process High

Deviation Band

Window Band

Setpoint Deviation Band Window Band

End of Soak
(Default : Process Low)
Min. to Max. Range for the selected Input type
(Default : 0)
-1999 to 9999 or -199.9 to 999.9
(Default : 0)
3 to 999 or 0.3 to 99.9 (Default : 3)

Logic

Normal

Inhibit

Reverse (Default : Normal)
Yes

Alarm Timer

No (Default : Yes)
5 to 250 Seconds (Default : 10)

Operation Manual
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

OP2 Function : Auxiliary Control

Parameters

Settings (Default Value)

Offset Value

(Min. Range - SP) to (Max. Range - SP) specified for the selected Input Type
(Default : 0)

Hysteresis

1 to 999 or 0.1 to 99.9 (Default : 2 or 0.2)

Control Logic

Normal

Reverse

(Default : Normal)

OP2 Function : Blower / Compressor Control

Offset Value

0 to 250 or 0.0 to 25.0 (Default : 0)

Hysteresis

1 to 250 or 0.1 to 25.0 (Default : 2 or 0.2)

Time Delay

00.00 to 10.00 Min. Sec (in steps of 5 Seconds)
(Default : 00.00)

OP3 FUNCTION PARAMETERS : PAGE-13

Parameters

Settings (Default Value)

Output-3 Function Selection

None

Alarm

Type

Control (Default : None) OP3 Function : Alarm-2
Process Low Process High

Deviation Band

Window Band

Setpoint Deviation Band Window Band

End of Soak (Default : Process Low)
Min. to Max. Range for the selected Input type
(Default : 0)
-1999 to 9999 or -199.9 to 999.9
(Default : 0)
3 to 999 or 0.3 to 99.9 (Default : 3)

Logic

Normal

Inhibit

Reverse (Default : Normal)
Yes

Alarm Timer

No (Default : Yes)
5 to 250 Seconds (Default : 10)

OP3 Function : Auxiliary Control

Offset Value Hysteresis

(Min. Range - SP) to (Max. Range - SP) specified for the selected Input Type
(Default : 0)
1 to 999 or 0.1 to 99.9 (Default : 2 or 0.2)

Control Logic

Normal

Reverse (Default : Normal)

SOAK TIMER PARAMETERS : PAGE-15

Parameters

Settings (Default Value)

Timer Enable

No

Time Units

Yes (Default : No)
Min:Sec

Hours:Min

Time Duration Timer-Start Band Holdback Strategy

Hours (Default : Min:Sec) 00.05 to 60:00 Min:Sec 00.05 to 99:55 Hrs:Min
1 to 999 Hours (Default : 00.10 Min:Sec)
0 to 9999 or 0.0 to 999.9 (Default : 5 or 0.5)
None

Up

Down

Hold Band Switch-Off Control Output at Timer End Power-fail Recovery Method

Both (Default : None)
1 to 9999 or 0.1 to 999.9 (Default : 5 or 0.5)
No
Yes (Default : No)
Continue
(Re)Start

Abort (Default : Continue)

OPERATOR PAGE AND PARAMETERS

Parameters

Settings

Timer Start Command

No

Yes

Timer Abort Command

No

Yes

Time Duration

00.05 to 60.00 M:S or 00.05 to 99.55 H:M or
1 to 999 Hours

OP2 Function : Alarm-1

Alarm-1 Setpoint

Min. to Max. Range for the Input Type

Alarm-1 Deviation Band

-1999 to 9999 or -199.9 to 999.9

Alarm-1 Window Band

3 to 999 or 0.3 to 99.9

OP2 Function : Auxiliary Control

Auxiliary Control Setpoint

(Min. Range - SP) to (Max. Range - SP) for selected Input

OP2 Function : Blower / Compressor Control

Blower / Compressor Setpoint

0 to 250 or 0.0 to 25.0

OP3 Function : Alarm-2

Parameters

Settings

Alarm-2 Setpoint

Min. to Max. Range for the Input Type

Alarm-2 Deviation Band

-1999 to 9999 or -199.9 to 999.9

Alarm-2 Window Band

3 to 999 or 0.3 to 99.9

OP3 Function : Auxiliary Control

Auxiliary Control Setpoint

(Min. Range SP) to
(Max. Range SP) for selected Input

Control Setpoint (SP) Locking

Setpoint Locking

No

Yes

Option

TABLE- 1 Range (Min. to Max.)

Resolution

J Type T/C

0 to +960°C / +32 to +1760°F

K Type T/C

-200 to +1375°C / -328 to +2508°F

T Type T/C

-200 to +385°C / -328 to +725°F

R Type T/C S Type T/C

0 to +1770°C / +32 to +3218°F Fixed
0 to +1765°C / +32 to +3209°F 1°C / 1°F

0 to +1825°C / +32 to +3092°F B Type T/C

0 to +1300°C / +32 to +2372°F N Type T/C

3-wire, RTD -199 to +600°C / -328 to +1112°F Pt100

3-wire, RTD -199.9 to 600.0°C / -199.9 to 999.9°F 0.1°C / 0.1°F Pt100

Option

TABLE- 2 What it means

Remarks

Relay

Applicable for OP1 as

SSR (Solid State Relay) Relay / SSR

NOTE : Applicable Only For Zenex DC Linear Version

Option

What it means

Remarks

0 to 20mA current 4 to 20mA current

Applicable for OP1 as DC Linear Current

0 to 5 Volts 0 to 10 Volts

Applicable for OP1 as DC Linear Voltage

101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar - 401 210. Sales : 8208199048 / 8208141446 Support : 07498799226 / 08767395333 E: sales@ppiindia.net, support@ppiindia.net

48X48

FRONT PANEL LAYOUT

Front Panel

PPI

zenex

Lower Readout
Output-2 Indicator Output-1 Indicator
PAGE Key
DOWN Key

S T OP1 OP2 OP3

96X96

Front Panel

PPI

zenex96

Upper Readout Soak Status Indicator Balance Soak Time Indicator Output-3 Indicator ENTER Key UP Key
Upper Readout

Soak Status

Indicator

S

T

Output-2 Indicator

Output-1 Indicator

OP1

OP2

OP3

PAGE Key DOWN Key

Lower Readout
Balance Soak Time Indicator Output-3 Indicator ENTER Key
UP Key

Symbol Key

Keys Operation Function

PAGE Press to enter or exit set-up mode.

DOWN

Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.

Press to increase the parameter value. Pressing once

UP

increases the value by one count; keeping pressed speeds up

the change.

ENTER

Press to store the set parameter value and to scroll to the next parameter on the PAGE.

PV Error Indications

Message

PV Error Type
Over-range (PV above Max. Range)
Under-range (PV below Min. Range)
Open (Sensor open / broken)

Jan 2022

ELECTRICAL CONNECTIONS

ENCLOSURE ASSEMBLY

OUTPUT 1 RELAY
NC C NO

INPUT T/C Pt100

2 Output Version

SSR OUTPUT 1

6 7 8 9 10 -

5

11 +

4 3

48X48

12 L 13 N

AC DC

RS 485

2

14

1 18 17 16 15

+

SSR NO C NC RELAY OUTPUT 2

SUPPLY

INPUT
T/C Pt100

OUTPUT 1
RELAY

3 Output Version Output-1 : Relay / SSR
OUTPUT 3
NC C NO RELAY SSR

NO 6 C5 NC 4
3 2 1

789
48X48
18 17 16

10 11 12 L 13 N 14 15

NO C NC
OUTPUT 2

SSR RELAY

RS 485 85 ~ 265 V SSR
AC SUPPLY OUTPUT 1

INPUT T/C Pt100

OUTPUT 1 DC Linear

RS 485
SUPPLY

+
+

3 Output Version Output-1 : DC Linear

OUTPUT 3 NC C NO RELAY
SSR

+ 6 7 8 9 10

5

11

4 3

48X48

12 L 13 N

AC DC

2

14

1 18 17 16 15

+

SSR NO C NC RELAY OUTPUT 2

`UP' inscribed on topside

Removal

UP UP

INPUT OUTPUT 1 DC Linear

+ 6

NOCUTCPUT 3 NO

5 4 3 2 1

+

ON18UO47zT8ePC1UXn7T8N4eC28x169RSE1S1115S1L4RR1321SA0ERYLANLY

AC DC

T/C Pt100

RS 485 SUPPLY

Placing Back

Power Supply PCB

CPU PCB
Display PCB

zenex

S

PPI

T

OP3 OP2 OP1

Pullout Grip

MOUNTING DETAILS
OUTPUT-2 MODULE
Plug & Socket Connector
Output Module
Projected Parts

1 23
1 23

JUMPER SETTINGS
OUTPUT-2 & OUTPUT-3

A

B

B A

MOUNTING DETAILS
SERIAL COMM. MODULE

Power Supply Board

Serial Communication/ Auxiliary SP Selection Module
Plug & Socket Connectors

CPU Board
Front Label Upside-down

zenex

PPI

Slots

Relay/SSR Module

Output Type

Jumper Setting - A

Relay

123

SSR 123

Jumper Setting - B 123 123

zenex

PPI

Front Label Upside-down

OUTPUT-2

NO C NC
RELAY SSR

+

2 Output Version

9

18

8

17

7

16

6

15

5 96X96 14

4

13

3

12

2

11

1

10

LN

+

SSR 85 ~ 264V RS485

NO C NC
RELAY SSR

+

AC SUPPLY

OUTPUT-2

ELECTRICAL CONNECTIONS

NO C NC
RELAY SSR
OUTPUT-2

OUTPUT-3
SSR RELAY
NC C NO

RS485

OUTPUT-1
RELAY
NC C NO

3 Output Version Output 1 : Relay / SSR

9

18

8

17

7

16

6

15

5 96 X 96 14

4

13

3

12

2

11

1

10

85 ~ 265 V AC SUPPLY

LN

SSR

OUTPUT-1 OUTPUT-3 SSR

3 Output Version Output 1 : DC Linear

NC C NO

+9

18

RELAY

8

17

7

16

+6

15

DC Linear

5 96X96 14

4

13

3

12

2

11

1

10

AC SUPPLY

85 ~ 264V RS485

+

NC C NO

RELAY

LN

INPUT OUTPUT-1

INPUT
T/C Pt100

OUTPUT-1

INPUT
T/C Pt100

OUTPUT-1

Pt100

T/C

OUTPUT-2 & OUTPUT-3 : HARDWARE JUMPER SETTINGS

Output-2 Jumper Setting

A
1 23

B
1 23

Power-Supply PCB

Output-2 Jumper Settings
Output Type Jumper Setting - A Jumper Setting - B

Relay SSR

123 123

123 123

CN4

RLY

PPI

CN3
zenex96

Output-3 Jumper Settings
Output Type Jumper Setting - A Jumper Setting - B

Relay SSR

123 123

123 123

Output-3 Jumper Setting

PPI

zenex96

A
123

B
123

SERIAL COMMUNICATION MODULE

Serial Communication

8 Pin Female Socket

Module

8 Pin Male Plug

PPI

zenex96

Power-Supply PCB



References

Corel PDF Engine Version 17.6.0.1021 CorelDRAW X7