User Guide for matt E models including: SP-EVCP-MC60, SP-EVCP-MC Single Phase Voltage Monitoring, SP-EVCP-MC, Single Phase Voltage Monitoring, Voltage Monitoring, Monitoring

Richard

65-4118 v1

matt:e SP-EVCP-MC60 Single phase connection centre with 32A double pole MCB, load curtailment at 60A. – UK EV Installers Shop

SP-EVCP-MC


File Info : application/pdf, 2 Pages, 233.76KB

PDF preview unavailable. Download the PDF instead.

65-4118 v1
SP-EVCP-MC
Single-phase Voltage Monitoring and protection devices with built-in current limiting
The SP-EVCP-MC from matt:e incorporates our unique monitoring device that disconnects all poles including CPC in the event of a broken Neutral fault in line with Regulation 722.411.4.1 (iv) and has the additional functionality for load curtailment in line with Regulation 722.311.201, isolating the charge point from the supply once the house consumption rises above the pre-set limit and automatically restores the power to the charge point when the load falls back within a satisfactory level. Creating a simple, single connection centre that allows for connection to the existing PME earthing facility without the use of Earth electrodes that saves time during survey and installation while offering a safe alternative for your work force.
Product Features
· Built in matt:e technology · BS:7671 2018 Amendment 1 2020 compliant · NO EARTH ELECTRODES REQUIRED · Load management with hard wired CT, factory set at 60A,80A or 100A · CT with simple plug and play connection · Built in 32amp Double Pole 32amp MCB · Standard 3 Year parts warranty · Mild steel IP2X enclosure · Designed and Built in the UK
...Simplifying EV connection
t: 01543 227290 e: info@matt-e.co.uk w: www.matt-e.co.uk matt:e Ltd, Unit 5 Common Barn Farm Tamworth Road Lichfield WS14 9PX

DimSePn-sEioVnsCP-MC
Dimensions and Specifications

Description Input Volts Max Load Load Management CT Cable Length Cable Entry Facility Terminal Capacity
Dimensions ( H x W x D ) Weight Enclosure Ingress Protection Warranty

Single-phase Voltage Monitoring and Protection Unit Nominal input voltage single-phase 230V 50Hz 32 amps Pre set at 60A, 80, 100A 1m Bottom, 1 x 42mm 2 x 25mm 1 x 16mm

In L/N: 2.5mm2 -25mm2 E: 2.5mm2 --16mm2

Out L/N 2.5mm2 - 10mm2 E: 2.5mm2 - 10mm2

169mm x 182mm x 111mm

Approximately 3kG

Mild Steel Powder Coated

IP2X