Isolated Quad Loop Adder Module

ALCN-792MISO/D

Features
· Isolated
· Dedicated Central Processor Unit (CPU) per module
· Expands system capacity to 636 addressable devices on 2 loops, 159/159 per loop
· With the addition of the ALCN-792D this expands module an additional 2 loops bringing module capacity to 1272 addressable devices.

ALCN-792MISO
Description
The ALCN-792MISO Isolated Quad Loop Adder Module provides two addressable loops plus an additional two loops as part of the daughter board ALCN-792D which is mounted over the ALCN-792MISO. The quad loop adder module provides Signaling Line Circuits (SLC) to the Flex-Net Addressable Fire Alarm system consisting of 159 Sensors and 159 Addressable Modules per loop.
Each ALCN-792MISO Loop Controller Module has a dedicated Central Processor Unit (CPU) and will support two fully loaded SLC lines which will provide up to 318 addressable devices per SLC line, for a total of up to 636 addressable devices per ALCN-792MISO Quad Loop Controller module.
The ALCN-792MISO occupies one module space on any FleX-Net FX-2000N Series control panel chassis
The ALCN-792D daughter board provides two additional SLC lines for up to 318 addressable devices per SLC line, for a total of up to 1,272 addressable devices per combination ALCN-792MISO with ALCN-792D.

S7010

S7010

5948 CATALOG NUMBER
NOT TO BE USED FOR INSTALLATION PURPOSES. Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
firealarmresources.com

Wiring Diagram

Four mounting holes (mount to ALCN-792MISO board with screws and spacers provided)

+ - + - SS + - + -

B A
LOOP (3)

B

COM (-)

A

SHIELD LOOP (4)

JW2 - Normally set to 1-2, can be set to 2-3 to prevent noise from CLIP System Sensor sounder bases on Loop 3

P1 To Main Board
Connector P6

JW1 - Normally set to 1-2, can be set to 2-3 to prevent noise from CLIP System Sensor sounder bases on Loop 4
Connect ribbon cable from this board to the ALCN-792MISO board P6

EARTH GROUND
RS-485 Green flashing OUT P3
RS-485 heartbeat LED

SHIELD

LOOP 1

LOOP 2 NOT USED

+ - + - SS + - + -

B

B

A

COM (-)

A

ALARM OUT

Loop 1 Active LED

Loop 2 Active LED

USB PORT (Factory use only)

RS-485

JW3

IN

P4

JW6

JW1 - leave open JW2 - leave closed

Daughter Board Connector
P6

Green flashing

heartbeat LED for on board processor ADDRESS 1

DIP SWITCHES ARE FOR THIS BOARD'S ADDRESS. SW1-1

DIP SWITCH8 SW1

IS THE LEAST SIGNIFICANT DIGIT (BINARY). ACTIVE POSITION IS ON.

JW4
Four shaded mounting holes are for Daughter board ALCN-792D
Top 2 holes and bottom 2 holes are used for the ALCN792MISO Quad Loop Adder module mounting

POWER CABLE (OUT)

POWER CABLE (IN)

P2 P1

ALCN-792MISO with ALCN-792D Electrical Specifications

Power Limited:

24VDC, 400mA max, 10kHz frequency Max loop resistance: 40 ohms

Current Consumption: Standby: 200mA Alarm: 213 mA

Notes for ALCN-792MISO :

All circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable. Loop wiring: maximum loop resistance is 40 ohms total. These lines are power limited and fully supervised.

Refer to wiring instructions in the Network Fire Alarm Manual

Ordering Information

Model ALCN-792MISO ALCN-792D

Description Isolated Quad Loop Adder Module Daughter Board

NOT TO BE USED FOR INSTALLATION PURPOSES. Distributed by:

Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113

U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113

Web page: http://www.mircom.com Email: mail@mircom.com

firealarmresources.com

CAT. 5948 Rev.0

