Installation and Operation Manual Back-UPSTM BR1200G-GR/BR1500G-GR
Inventory
Important Safety Messages
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. · This UPS is intended for indoor use only. · Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity. · Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation. · The battery typically lasts for three to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality AC power, and frequent short duration discharges will shorten battery life. · Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE · Replace the battery at least every 5 years or at the end of its service life, whichever is earlier. · Replace the battery immediately when the UPS indicates battery replacement is necessary. · Replace batteries with the same number and type of batteries as originally installed in the equipment. · Replace the battery immediately when the UPS indicates a battery over-temperature condition, or when
there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced. Failure to follow these instructions can result in minor or moderate injury and equipment damage. For the recycling battery information, please go to apc.com/recycle · CAUTION: Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions. · CAUTION: Do not dispose of batteries in a fire. The batteries may explode. · CAUTION: Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic. · CAUTION: Before replacing batteries, remove conductive jewelry such as chains, wrist watches, and rings. High energy through conductive materials could cause severe burns. · CAUTION: Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces. · CAUTION: A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries: ­ Disconnect the charging source prior to connecting or disconnecting battery terminals. ­ Do not wear any metal objects including watches and rings. ­ Do not lay tools or metal parts on top of batteries.

­ Use tools with insulated handles.
­ Wear rubber gloves and boots.
­ Determine if battery is either intentionally or inadvertently grounded. Contact with any part of a grounded battery can result in electric shock and burns by high short-circuit current. The risk of such hazards can be reduced if grounds are removed during installation and maintenance by a skilled person.
· This manual can be downloaded from APC by Schneider Electric Website www.apc.com.

Connect the Battery







b u059a

bu057a

bu055a





Charge the battery for at least 16 hours before use.

bu058a

bu060a

PowerChuteTM Personal Edition Software
Overview
PowerChute Personal Edition Software allows you to use your computer to access additional power protection and management features of the Back-UPS.
Using PowerChute, you can:
· Preserve work in progress during a power outage by putting your computer into Hibernate mode. When the power returns, the computer will appear exactly as it did before the power outage.
· Configure the Back-UPS management features, such as power-saving outlets, shutdown parameters, audible alarms, and more. · Monitor and view the status of the Back-UPS, including the estimated runtime, power consumption, power event history, and
more. Available features will vary by Back-UPS model and operating system.
If you choose not to install PowerChute, the Back-UPS will still provide backup power and power protection to connected equipment. However, you will only be able to configure a limited number of features using the display interface.
Compatibility
PowerChute is compatible with Windows operating systems only. For a detailed list of supported operating systems, go to www.apc.com, select Software & Firmware.
For Mac operating systems, we recommend using the native shutdown application (within System Preferences) which recognizes your battery backup and allows you to configure shutdown of your system during power outages. To access this application, connect a USB cable from the Back-UPS DATA PORT (POWERCHUTE PORT) to a USB port on your computer, and see the documentation provided with your computer.
Installation
Use the USB cable to connect the Data port on the UPS to the USB and Serial port on your computer. Download PowerChuteTM Personal Edition Software from www.apc.com/pcpe. Select the appropriate operating system and follow directions to download and install the software.

2

Back-UPS BR1200G-GR/BR1500G-GR

Connect the Equipment
Battery Backup and Surge Protected outlets
When the Back-UPS is receiving input power, the Surge Protection only outlets and the Battery Backup with Surge Protection outlets will supply power to connected equipment. During a power outage or other utility problems, only the Battery Backup outlets receive power for a limited time from the Back-UPS.
Connect equipment such as printers, FAX machines, scanners, or other peripherals that do not need battery backup power to the Surge Protection Only outlets. These outlets provide full time protection from surges even if the Back-UPS is switched off.
Master and Controlled outlets
To conserve electricity, when the device connected to Master Outlet goes into Sleep or Standby mode, or turns off, the Controlled by Master device(s) will shut down as well, saving electricity.
Connect a master device, such as a desktop computer or audio/visual receiver to the Master outlet. Connect peripheral devices such as a printer, speakers, or a scanner to the Controlled by Master outlets.

BR1200G-GR
USB & Serial
Tel In
Tel Out

BR1500G-GR
USB & Serial
Tel In
Tel Out

TVSS GND
TVSS GND

Battery Backup

Surge Only

MASTER

Controlled by MASTER

Circuit Breaker Push to Reset

Controlled by MASTER

Controlled by MASTER

Battery Backup

Surge Only

MASTER

Controlled by MASTER

Circuit Breaker Push to Reset

Controlled by MASTER

Controlled by MASTER

bu218a

bu219a

 USB and Serial Data port  Telephone ports  Ground screw
 Surge Protection outlets, Controlled by Master outlet
 Surge Protection outlets
 AC Power Cable

To use PowerChute Personal Edition, connect the supplied USB software cable or serial cable.
Connect a telephone cable to the In port, and a modem to the Out port.
Connect the ground wire from another surge suppression device such as a network or data line surge protector to the ground screw on the Back-UPS.
These outlets provide surge protection during a power outage. These outlets will disconnect from A/C power during a power outage, or in the event that the Master outlet goes into Sleep mode.
These outlets provide full-time surge protection, when the unit is turned on or off. Connect a printer, scanner or other devices that do not require battery backup protection.
Connect the Back-UPS to A/C power.

Back-UPS BR1200G-GR/BR1500G-GR

3

 Battery Backup outlets with Surge Protection
 Battery Backup, Controlled by Master outlet with Surge Protection

During a power outage or other utility problems, these outlets provide power from the Back-UPS battery. Connect essential equipment such as desktop computer, computer monitor, modem or other data sensitive devices to these outlets.
During a power outage or other utility problems, these outlets provide power from the Back-UPS battery.

These outlets will disconnect from A/C power during a power outage, or in the event that the Master outlet goes into Sleep mode.

 Master outlet  Gigabit Ethernet
surge-protected ports  External Battery Pack connector
BR1500G-GR model only

Connect essential equipment such as desktop computer, computer monitor, modem or other data sensitive devices to these outlets. Connect the master device to this outlet, in most scenarios, this will be the main computer. Use an Ethernet cable to connect a modem to the IN port, and a computer to the OUT port.
Connect an external battery pack to provide additional battery backup runtime.

4

Back-UPS BR1200G-GR/BR1500G-GR

Operation
Power-Saving Function
To conserve electricity, configure the Back-UPS to recognize a Master device, such as a desktop computer or an A/ V receiver, and Controlled peripheral devices, such as a printer, speakers, or a scanner. When the Master device goes into Sleep or Standby mode, or is switched OFF, the Controlled device(s) will be switched off as well, saving electricity.

Enable the Power-Saving function. Press and hold MUTE and DISPLAY simultaneously for two seconds. The Back-UPS will beep to indicate that the feature is enabled. The leaf icon on the display will illuminate.

Disable the Power-Saving function. Press and hold MUTE and DISPLAY simultaneously for two seconds. The Back-UPS will beep to indicate that the feature is disabled. The leaf icon on the display will go dark.

Setting the threshold. The amount of power used by a device in Sleep or Standby mode varies between devices. It may be necessary to adjust the threshold at which the Master outlet signals the Controlled outlets to shut down.

1. Be sure a master device is connected to the Master outlet. Put that device into Sleep or Standby mode, or turn it OFF. 2. Press DISPLAY and MUTE simultaneously and hold for six seconds, until the leaf icon flashes three times and the Back-UPS
beeps three times.
3. The Back-UPS will now recognize the threshold level of the Master device and save it as the new threshold setting.
Power-Saving Display
The display interface can be configured to be continuously illuminated, or to save energy, it can be configured to go dark after a period of inactivity.

1. Full Time Mode: Press and hold DISPLAY for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full-Time mode.
2. Power-Saving Mode: Press and hold DISPLAY for two seconds. The display will go dark and the Back-UPS will beep to confirm the Power-Saving mode. While in Power-Saving Mode, the display will illuminate if a button is pressed, it goes dark after 60 seconds of no activity.
Unit sensitivity
Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the more often the Back-UPS will switch to battery power.

1. Be sure the Back-UPS is connected to A/C power, but is OFF.
2. Press and hold the POWER button for six seconds. The LOAD CAPACITY bar will flash on and off, indicating that the Back-UPS is in programming mode.
3. Press POWER again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to confirm the selection.Front Panel Buttons and Display Interface

Low sensitivity

Medium sensitivity (Default)

High sensitivity

156-300 Vac

176-294 Vac

Input voltage is extremely low or high. (Not recommended for computers.)

The Back-UPS frequently switches to battery power.

176-288 Vac
The connected equipment is sensitive to voltage fluctuations.

Back-UPS BR1200G-GR/BR1500G-GR

5

Use the three buttons on the front panel of the Back-UPS and the display interface to configure the Back-UPS.
Front panel  Mute button  Power On/Off button  Display button  Display interface

bu044a bu002a

On Line: The Back-UPS is supplying conditioned A/C power to connected equipment
Power-Saving: Master and Controlled outlets are enabled, saving power when the master device goes into sleep or standby mode
Load Capacity: The load is indicated by the number of sections illuminated, one to five. Each bar represents 20% of the load. Battery Charge: The battery charge level is indicated by the number of sections illuminated. When all five blocks are illuminated, the Back-UPS is at full charge. When one block is filled, the Back-UPS is near the end of its battery capacity, the indicator will flash and the Back-UPS will beep continuously. Overload: The power demand from the load has exceeded the capacity of the Back-UPS.
Event: The event counter shows the number of events that occurred that caused the Back-UPS to switch to on-battery operation.
Automatic Voltage Regulation: The Back-UPS can compensate for high or low input voltage.
When illuminated, the Back-UPS is compensating for low input voltage.
When illuminated, the Back-UPS is compensating for high input voltage. Input voltage. Output voltage. System Events: The system has a detected fault. The event number will illuminate on the display interface. See "System Events" on page 7.
Mute: If the line through the speaker icon is illuminated, the audible alarm has been turned off.
Replace Battery: The battery is not connected or is nearing the end of its useful life. Replace the battery.
On Battery: The Back-UPS is supplying battery backup power to the connected equipment, it will beep four times every 30 seconds.

6

Back-UPS BR1200G-GR/BR1500G-GR

Alerts and System Events
Audible Alerts

Four Beeps Every 30 Seconds Continuous Beeping
Continuous tone Chirps for 1 Minute every 5 hours

Back-UPS is running on battery. You should consider saving any work in progress. Low battery condition and battery run-time is very low. Promptly save any work in progress, exit all open applications, and shut down the operating system. Battery Backup outputs are overloaded. Battery is not able to pass the automatic diagnostic test and should be replaced.

Event Icons

If these icons are illuminated

This may be the problem
The Back-UPS is operating on A/C power, but is overloaded. Disconnect one of the items connected to the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no longer overloaded and will continue to operate normally.

The Back-UPS is operating on battery power, but is overloaded. Disconnect one of the items connected to the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no longer overloaded and will continue to operate normally.

The Back-UPS is operating on A/C power, but the battery is not functioning properly. Contact APC Customer Service to order a replacement battery. See "Replace Battery" on page 10.

The Back-UPS is operating on battery power and the battery power is getting low. Shut down all connected equipment to avoid losing unsaved data. When possible, connect the Back-UPS to A/C power to recharge the battery.

System Events
The Back-UPS will display these event messages. Contact APC Technical Support.

F01 On-Battery Overload
F02 On-Battery Output Short
F03 On-Battery Xcap Overload F04 Clamp Short F05 Charge Status F06 Relay Welding F07 Temperature F08 Fan Condition F09 Internal Event

Turn the Back-UPS off. Disconnect non-essential equipment from the Battery Backup outlets and the turn Back-UPS on.
Turn the Back-UPS off. Disconnect non-essential equipment from the Battery Backup outlets and the turn Back-UPS on.
Events F03-F09 cannot be corrected by the user. Contact APC Technical Support for assistance.

bu088a

Back-UPS BR1200G-GR/BR1500G-GR

7

Function Button Quick Reference

Function Power
Power On

Button

Timing (seconds
)

UPS Status

Description

0.2

Off Press POWER to start receiving input A/C power. If A/C input power is not

available, the Back-UPS will run on battery power.

Power Off

2

On The Back-UPS is not receiving input A/C power, but is providing surge

protection.

Display Status Inquiry
Full-Time/Power-Saving mode
Mute Event Specific General Status Enable/Disable
Sensitivity
Master/Controlled outlet Enable/ Disable Master/Enable Threshold Calibration Self-Test (manual)
Event Reset
Status Reset

0.2

On Verify the status or condition of the Back-UPS. The LCD will illuminate for 60

seconds.

2

On The LCD will illuminate and the Back-UPS will beep to confirm the Full-Time

mode. The LCD will go dark and the Back-UPS will beep to confirm the

Power-Saving mode. While in Power-Saving Mode, the LCD will illuminate if

a button is pressed, then goes dark after 60 seconds of no activity.

0.2

On Disable any audible alarms caused by an event.

2

On Enable or disable the audible alarms. The Mute icon will illuminate and the

Back-UPS will beep one time. The Mute function will not activate unless the

Back-UPS is operating on battery power.

6

Off The Load Capacity icon will blink, indicating that the Back-UPS is in

programming mode. Use the POWER button to scroll through Low, Medium,

and High, stop at selected sensitivity. The Back-UPS will beep to confirm

selection. See Configuration for details.

2

On The leaf icon will go dark indicating that the Master Outlet feature is disabled

or illuminate to indicate the Master Outlet feature is enabled. The Back-UPS

will beep once.

6

On While calibrating the threshold setting, the device connected to the Master

Outlet should be turned off or placed in Standby or Sleep mode. Upon

completion, Power-Saving icon will flash 3 times and beep 3 times.

6

On The Back-UPS will perform a test of the internal battery. Note: This will

happen automatically when the Back-UPS is turned ON.

0.2

On

When the Event screen is visible, press and hold DISPLAY, then press POWER,

to clear the utility event counter.

2

Event After an event has been detected and identified, press POWER to remove the

detected visual indication and return to standby status.

8

Back-UPS BR1200G-GR/BR1500G-GR

Troubleshooting

Problem

Possible Cause

Corrective Action

Back-UPS will not turn on. The Back-UPS is not connected to A/C Be sure that the Back-UPS is securely connected to

power.

an A/C outlet.

The circuit breaker has been tripped.

Disconnect non-essential equipment from the Back-

UPS. Reset the circuit breaker. Re-connect

equipment one item at a time. If the circuit breaker is

tripped again, disconnect the device that caused the

trip.

The internal battery is not connected.

Connect the battery.

The A/C input voltage is out of range.

Adjust the transfer voltage and sensitivity range.

The Back-UPS does not

Be sure that essential equipment is not

Disconnect equipment from the SURGE ONLY outlet

provide power during an A/C plugged into a SURGE ONLY outlet.

and re-connect to a Battery Backup outlet.

power outage.

The Back-UPS is operating on The plug has partially pulled out of the wall Be sure that the plug is fully inserted into the wall

battery power, while

outlet, the wall outlet is no longer receiving outlet. Be sure that the wall outlet is receiving A/C

connected to A/C power.

A/C power, or the circuit breaker has been power by checking it with another device.

tripped.

The Back-UPS is performing an automatic No action is necessary.

self test.

The A/C input voltage is out of range, the Adjust the transfer voltage and sensitivity range.

frequency is out of range, or the waveform

is distorted.

The Back-UPS does not

Battery Backup outlets may be fully or Disconnect non-essential equipment from the

provide the expected amount improperly loaded.

Battery Backup outlets and connect the equipment to

of backup time.

SURGE ONLY outlets.

The battery was recently discharged due to Charge the battery cartridge for 16 hours.

a power outage and has not fully recharged.

The battery has reached the end of its

Replace the battery.

useful life.

The REPLACE BATTERY

The battery has reached the end of its

Replace the battery.

indicator is illuminated.

useful life.

The OVERLOAD indicator is The equipment connected to the Back-UPS Disconnect non-essential equipment from the

illuminated.

is drawing more power than the Back-UPS Battery Backup outlets and connect the equipment to

can provide.

SURGE ONLY outlets.

The SYSTEM EVENT indicator There is an internal fault detected.

Determine which internal detected fault message is

is illuminated, all the front

displayed by matching the number displayed on the

panel indicators are flashing.

LCD with the corresponding event Message (see

System Events) and contact APC Technical Support.

Power is not supplied to some Power to the Controlled outlets has

Confirm that the correct peripherals are connected to

outlets.

intentionally been turned off.

Controlled outlets. If this feature is not desired,

disable the Power-Saving Master and Controlled

outlets.

The Controlled outlets are not The Master Outlet threshold may be

Adjust the threshold when the Master outlet signals

supplying power, even though incorrectly set.

the Controlled outlets to shut down.

the Master device is not in

sleep mode.

Back-UPS BR1200G-GR/BR1500G-GR

9

Specifications
t

Model

BR1200G-GR

BR1500G-GR

VA

1200 VA

1500 VA

Maximum Load

720 W

865 W

Nominal Input Voltage

230 V

Online Input Voltage Range

176 V- 294 V

Automatic Voltage Regulation

188 V- 216 V +11.2% 252 V- 282 V -11.2%

Frequency Range

50/60 Hz ± 1 Hz

On-battery wave shape

Step-approximated sine-wave

Typical Recharge Time

8 hours

Transfer Time Operating Temperature Storage Temperature

10 ms, maximum 0º to 40º C (32º to 104º F) 5º to 45º C (23º to 113º F)

Unit Dimensions

30.1 × 11.2 × 39 cm (11.9 × 4.4 × 15.3 in)

Unit Weight

12.8 kg (28.2 lbs)

13.4 kg (29.5 lbs)

Interface

Serial, USB

On-Battery Runtime

Go to: www.apc.com

Replacement Battery

The battery cartridge typically lasts 3 to 6 years. Environmental factors impact battery life. High temperatures, poor quality A/C power, and frequent, short deration discharges will shorten battery life. To order replacement battery cartridge, see Replace Battery.

Humidity

0 to 95% relative humidity, non-condensing

Pollution Degree

2

Overvoltage category

II

Applicable power grid distribution system

TN Power system

Applicable standards

IEC 62040-1

International Protection Code

IP20

Replace Battery
Deliver the used battery to a recycling facility.
Replace the used battery with an APC by Schneider Electric approved battery. Replacement batteries can be ordered through the APC by Schneider Electric Web site, www.apc.com. Battery replacement part for Back-UPS BR1200GGR and BR1500G-GR is APCRBC124.

10

Back-UPS BR1200G-GR/BR1500G-GR

Back-UPS BR1200G-GR/BR1500G-GR

11

APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.
Warranty
The standard warranty is two (2) years from the date of purchase. APC standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative. APC will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to APC. APC pays ground freight transportation costs to ship the replacement unit to the customer.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the TROUBLESHOOTING section of the manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.
b. Call APC Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free. d. Service procedures and returns may vary internationally. Refer to the APC Web site for
country specific instructions. 3. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in
transit is not covered under warranty. For the UPS, always DISCONNECT THE BATTERY before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery may remain in the unit. 4. Write the RMA# provided by Customer Support on the outside of the package. 5. Return the unit by insured, pre-paid carrier to the address provided by Customer Support.

© 2022 APC by Schneider Electric. APC, the APC logo, Back-UPS and PowerChute are owned by Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of their respective owners.

EN 990-3973B 02/2022

