Installation Guide for Schneider Electric models including: PowerLogic HDPM6000 Series, CT Models for High Accuracy and Split Core Variants, PowerLogic HDPM6000 Series CT Models for High Accuracy and Split Core Variants

PowerLogic DPM000 Series CT Models for igh Accuracy and Split-Core ...

schneider-electric.com Z208152-0C 08/2021 PowerLogic DPM000 Series CT Models for igh Accuracy Installation Guide and Split-Core ariants 20A 4000A For Use with the DPM000 Power uality Metering System

HDPM6000 Sentran CT Z208152-0C

Difference among Rogowski coils, LVCTs and conventional CTs | Schneider Electric South Africa

  Installation Guide

Square D (Schneider Electric) METSEHD1200A30 Split Core Current Transformer HDPM6000, 1200A, 4 In. X 6 In. , 30Ft Lead | Graybar Store


File Info : application/pdf, 9 Pages, 573.60KB

PDF preview unavailable. Download the PDF instead.

f53013ecddbbea8c9991ee83c6bd2d683f4fe2e5
PowerLogicTM HDPM6000 Series CT Models for High Accuracy and Split-Core Variants (20A ­ 4000A)
For Use with the HDPM6000 Power Quality Metering System
Installation Guide
Z208152-0C 08/2021
schneider-electric.com

PowerLogic HDPM6000 Series CT Models for High Accuracy and Split-Core Variants (20A ­ 4000A)
Safety Information
Important information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of either symbol to a "Danger" or "Warning" safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.

Please note

Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction, installation and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

© 2021 Schneider Electric All Rights Reserved.

PowerLogic HDPM6000 Series CT Models for High Accuracy and Split-Core Variants (20A ­ 4000A)
Safety Precautions
Installation, wiring, testing and service must be performed in accordance with all local and national electrical codes.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See NFPA 70E in the USA or applicable local standards. · Th
electrical personnel. · Turn off all power supplying equipment before working on or inside
the equipment. · Product may use multiple voltage/power sources. Disconnect all sources of power
before servicing. · Al · Do not depend on this product for voltage indication. · Current transformer secondaries must be shorted or connected to a burden at all
times. · Products rated for basic insulation must be installed on insulated conductors. · Replace all doors, covers, and protective devices before powering the equipment. · In · This product is not intended for life or safety applications. Failure to follow these instructions will result in death or serious injury.
WARNING
RISK OF INJURY OR EQUIPMENT DAMAGE Do not apply current transducers to circuits having a phase-to-phase voltage greater than their voltage rating unless adequate additional insulation is applied between the primary conductor and the current transducers.
equipment damage.
Schneider Electric assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings.

© 2021 Schneider Electric All Rights Reserved.

iii

PowerLogic HDPM6000 Series CT Models for High Accuracy and Split-Core Variants (20A ­ 4000A)

Introduction Ordering Information

Schneider Electric PowerLogic High Accuracy and Split-Core Current Transducers (CTs) provide secondary voltage AC proportional to the primary (sensed) current. For use with the HDPM6000 platform only, these CTs provide a means to transform electrical service amperages to a voltage compatible with monitoring equipment.
These CTs range from 20A to 4000A voltage ratings with 0.2% to 1% accuracy.

Model Number SUN2 METSEHDPM20A12H METSEHDPM20A30H SUN3 METSEHDPM75A12H METSEHDPM75A4H METSEHDP150A12H METSEHDP150A30H SUN4 METSEHDP300A12H METSEHDPM300A30H METSEHDPM400A12H METSEHDPM400A30H SUS4 METSEHDPM150A12 METSEHDPM150A30 METSEHDPM150A60 METSEHDPM150A5 METSEHDPM150A16 METSEHDPM300A12 METSEHDPM300A30 METSEHDPM300A60 METSEHDPM300A5 METSEHDPM300A16 METSEHDPM400A12 METSEHDPM400A30 METSEHDPM400A60 METSEHDPM400A5 METSEHDPM400A16 METSEHDPM600A12 METSEHDPM600A30 METSEHDPM600A60 METSEHDP600A5H METSEHDP600A16H SUSF METSEHD150A12 METSEHD150A30 METSEHD150A60 METSEHD300A12 METSEHD300A30

Description

Accuracy

20A, High Accuracy Split-Core CT, 12' lead 20A, High Accuracy Split-Core CT, 30' lead

0.2% 0.2%

75A, High Accuracy Split-Core CT, 12' lead 75A, High Accuracy Split-Core CT, 30' lead 150A, High Accuracy Split-Core CT, 12' lead 150A, High Accuracy Split-Core CT, 30' lead

0.2% 0.2% 0.2% 0.2%

300A, High Accuracy Split-Core CT, 12' lead 300A, High Accuracy Split-Core CT, 30' lead 400A, High Accuracy Split-Core CT, 12' lead 400A, High Accuracy Split-Core CT, 30' lead

0.2% 0.2% 0.2% 0.2%

150A, Split-Core CT, 12' lead 150A, Split-Core CT, 30' lead 150A, Split-Core CT, 60' lead 150A, Split-Core CT, HDPM6000S, 5" lead with connector 150A, Split-Core CT, HDPM6000B, 16" lead 300A, Split-Core CT, 12' lead 300A, Split-Core CT, 30' lead 300A, Split-Core CT, 60' lead 300A, Split-Core CT, HDPM6000S, 5" lead with connector 300A, Split-Core CT, HDPM6000B 16" lead 400A, Split-Core CT, 12' lead 400A, Split-Core CT, 30' lead 400A, Split-Core CT, 60' lead 400A, Split-Core CT, HDPM6000S, 5" lead with connector 400A, Split-Core CT, HDPM6000B 16" lead 600A, Split-Core CT, 12' lead 600A, Split-Core CT, 30' lead 600A, Split-Core CT, 60' lead 600A, Split-Core CT, HDPM6000S, 5" lead with connector 600A, Split-Core CT, HDPM6000B 16" lead

0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5% 0.5%

150A, Split-Core CT, 1"x1", 12' lead

1%

150A, Split-Core CT, 1"x1", 30' lead

1%

150A, Split-Core CT, 1"x1", 60' lead

1%

300A, Split-Core CT, 1"x1", 12' lead

1%

300A, Split-Core CT, 1"x1", 30' lead

1%

i

© 2021 Schneider Electric All Rights Reserved.

PowerLogic HDPM6000 Series CT Models for High Accuracy and Split-Core Variants (20A ­ 4000A)

Model Number METSEHD300A60 METSEHD300A12L METSEHD300A30L METSEHD300A60L METSEHD400A12 METSEHD400A30 METSEHD400A60 METSEHD400A12L METSEHD400A30L METSEHD400A60L METSEHD600A12 METSEHD600A30 METSEHD600A60 METSEHD800A12 METSEHD800A30 METSEHD800A60 METSEHD1000A12 METSEHD1000A30 METSEHD1200A12 METSEHD1200A30 METSEHD1600A12 METSEHD1600A30 METSEHD1600A12L METSEHD1600A30L METSEHD2000A12 METSEHD2000A30 METSEHD2000A12L METSEHD2000A30L METSEHD3000A12 METSEHD3000A30 METSEHD3000A12L METSEHD3000A30L METSEHD3000A12XL METSEHD3000A30XL METSEHD4000A12 METSEHD4000A30

Description 300A, Split-Core CT, 1"x1", 60' lead 300A, Split-Core CT, 2"x2", 12' lead 300A, Split-Core CT, 2"x2", 30' lead 300A, Split-Core CT, 2"x2", 60' lead 400A, Split-Core CT, 1.25"x1.25", 12' lead 400A, Split-Core CT, 1.25"x1.25", 30' lead 400A, Split-Core CT, 1.25"x1.25", 60' lead 400A, Split-Core CT, 2.5"x2.5", 12' lead 400A, Split-Core CT, 2.5"x2.5", 30' lead 400A, Split-Core CT, 2.5"x2.5", 60' lead 600A, Split-Core CT, 3"x 3", 12' lead 600A, Split-Core CT, 3" x 3", 30' lead 600A, Split-Core CT, 3" x 3", 60' lead 800A, Split-Core CT, 4"x 4", 12' lead 800A, Split-Core CT, 4" x 4", 30' lead 800A, Split-Core CT, 4" x 4", 60' lead 1000A, Split-Core CT, 4"x 4", 12' lead 1000A, Split-Core CT, 4" x 4", 30' lead 1200A, Split-Core CT, 4"x 6", 12' lead 1200A, Split-Core CT, 4" x 6", 30' lead 1600A, Split-Core CT, 4"x 6", 12' lead 1600A, Split-Core CT, 4" x 6", 30' lead 1600A, Split-Core CT, 4.5"x 4.5", 12' lead 1600A, Split-Core CT, 4.5" x 4.5", 30' lead 2000A, Split-Core CT, 4"x 6", 12' lead 2000A, Split-Core CT, 4" x 6", 30' lead 2000A, Split-Core CT, 6"x 3", 12' lead 2000A, Split-Core CT, 6" x 3", 30' lead 3000A, Split-Core CT, 4"x 4", 12' lead 3000A, Split-Core CT, 4" x 4", 30' lead 3000A, Split-Core CT, 4"x 6", 12' lead 3000A, Split-Core CT, 4" x 6", 30' lead 3000A, Split-Core CT, 5"x 12", 12' lead 3000A, Split-Core CT, 5" x 12", 30' lead 4000A, Split-Core CT, 5"x 12", 12' lead 4000A, Split-Core CT, 5" x 12", 30' lead

Accuracy 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1%

© 2021 Schneider Electric All Rights Reserved.

1

PowerLogic HDPM6000 Series CT Models for High Accuracy and Split-Core Variants (20A ­ 4000A)

Specifications

Output at Rated Current Accuracy Operating Temperature Range Storage Temperature Range Frequency Range Leads Max. Voltage L-N Sensed Conductor Altitude of Operation Humidity Range Continuous current rating factor Installation Category Agency Approvals

0.25VAC 0.2% (SUN2/SUN3/SUN4), 0.5% (SUS4) and 1% (SUSF) -40 to 55 °C (-40 to 131 °F) -50 to +70 °C (-58 to 158 °F) 50/60 Hz B/W twisted pair 18 AWG, AWM, UL1015, 600V, 105 °C 600 VAC 2000 m max. 0 to 95% non-condensing 1 Cat III, Pollution Degree 2 UL2808, CE

Dimensions
SUN2, SUN3, SUN4 & SUS4

SUSF

Model SUN2

W Window
0.4 in (10.17 mm)

A Dimension 2.4 in (60.69 mm)

SUN3 SUN4 SUS4

0.7 in (17.80 mm) 1.25 in (31.75 mm) 1.25 in (31.75 mm)

3.0 in (76.19 mm) 3.3 in (83.81 mm) 3.3 in (83.81 mm)

B Dimension 1.65 in (41.91 mm)
2.4 in (60.96 mm) 3.1 in (78.74 mm) 3.1 in (78.74 mm)

C Dimension 0.85 to 1.1 in (21.58 to 27.94 mm) 1.1 in (27.94 mm) 1.3 in (31.04 mm) 1.3 in (31.04 mm)

2

© 2021 Schneider Electric All Rights Reserved.

PowerLogic HDPM6000 Series CT Models for High Accuracy and Split-Core Variants (20A ­ 4000A)

Busbar and Phase Orientation

· The white mark ensures orientation every time the top is attached.
· Typically, the white mark is on the top right side when looking at the product label.
· Refer to label for correct CT orientation.

Proper Size and Fitting

· The window of the CT should be big enough to fit the busbar without excess space.
· A split-core CT should not be oversized around the bus/conductor, resulting in an inaccurate/bad reading.
· The busbar should also be in the center of the CT window to allow the coils to energize evenly.

© 2021 Schneider Electric All Rights Reserved.

3

PowerLogic HDPM6000 Series CT Models for High Accuracy and Split-Core Variants (20A ­ 4000A)

Installation

Installation must be performed by a qualified electrician. Turn off and lock out power to the primary circuit before installing these CTs. Use a properly rated voltage sensing device to confirm that power is off.
In any application where fault currents can exceed 20 times the rated current of the CT, use wire ties or similar fasteners to secure both sides of the I-bar to the CT housing.
NOTICE
INCORRECT POLARITY Align CT arrow to point in the direction of the power flow. Failure to follow this instruction can result in incorrect readings.

· Remove the screws (or push-pins) from the CT and take the top off. · Slide the body of the CT over the busbar.
· Refer to label for correct CT orientation.
· Re-attach the top to the body of the CT, using the white mark to orient how the top will fit.
· Place the screws/push-pins back to secure the top to the CT.
· Once the CT is installed onto the busbar, terminate the leads to the metering device prior to turning on the power.

4

© 2021 Schneider Electric All Rights Reserved.

Schneider Electric
12345 SW Leveton Drive Tualatin, OR 97062 USA +1-503-598-4564 schneider-electric.com
Schneider Electric Limited Stafford Park 5 Telford TF3 3BL United Kingdom
© 2021 Schneider Electric. All Rights Reserved.
PowerLogic and Schneider Electric are trademarks or registered trademarks of Schneider Electric in France, the USA and other countries. Other companies' trademarks are the property of their respective owners.
As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this publication.
Z208152-0C 08/2021

