User Manual for SOFAR models including: 5KTL-3PH, 6KTL-3PH, 8KTL-3PH, 10KTL-3PH, 10KTL-3PH-A, 15KTL-3PH, 20KTL-3PH, HYD 5-20KTL-3PH Three Phase Hybrid Inverter, HYD 5-20KTL-3PH, Three Phase Hybrid Inverter, Phase Hybrid Inverter, Hybrid Inverter, Inverter

ABOUT THIS MANUAL

[PDF] ABOUT THIS MANUAL - Sofar Solar

In this configuration, the battery unit can be added later. ... 21/CEI 0-16, C10/11, EN50438/EN50549,. G83/G59/G98/G99, UTE C15-712-1 ...


File Info : application/pdf, 128 Pages, 5.79MB

PDF preview unavailable. Download the PDF instead.

1748397623841082966
ABOUT THIS MANUAL

Shenzhen SOFARSOLAR Co., Ltd. 11/F, Gaoxinqi Technology Building, District 67, XingDong Community, XinAn Street, Bao'An District, Shenzhen, China
Email: service@SOFAR.com Web: www.sofarsolar.com
Document number Issue 26 | 5.2025 English

CONTENT

CONTENT

1 About this manual

1

1.1

Copyright declaration

1

1.2

Presentation of warnings

2

1.3

Presentation of action instructions

3

1.4

Note

3

2 Basic safety information

4

2.1

Safety information

4

2.2

Symbols and signs

8

3 Product features

11

3.1

Product information

11

3.2

Product dimensions

12

3.3

Labelling on the device

13

3.4

Functional features

13

3.5

Application modes

14

3.6

Connecting GTX 3000-H batteries (AMASS)

20

3.7

Connecting BTS 5K batteries

21

4 Installation

23

4.1

Installation information

23

4.2

Installation procedure

24

4.3

Examination before installation

24

4.4

Connections

27

4.5

Tools

28

4.6

Installation Environment Requirements

29

4.7

Installation location

29

4.8

Unpacking the inverter

31

4.9

Installation of the inverter

32

5 Electrical connections

34

5.1

Safety instructions

34

5.2

Wiring overview

37

HYD 5-20KTL-3PH

I

ABOUT THIS MANUAL

5.3

System overview

38

5.4

Electrical connection

46

5.5

Connecting the PE cables

46

5.6

Connecting the DC lines for the PV modules and battery

47

5.7

Connecting the AC power cables

51

5.8

AC connector installation

52

5.9

Communication interfaces

55

5.10

Feed-in limitation function

73

5.11

System monitoring

73

5.12

Installation of the WiFi, or Ethernet stick

74

6 Commissioning the inverter

78

6.1

Safety test before commissioning

78

6.2

Double Check

78

6.3

Starting the inverter

79

6.4

Initial setup

79

6.5

Smartphone app SOFAR View

84

7 Operation of the device

85

7.1

Control panel and display field

85

7.2

Standard display

86

7.3

Energy storage modes

87

7.4

Menu structure

93

7.5

Firmware update

102

8 Troubleshooting handling

103

8.1

Troubleshooting

103

8.2

Error list

105

8.3

Maintenance

119

9 Technical Data

120

II

HYD 5-20KTL-3PH

ABOUT THIS MANUAL
1 About this manual
This Installation and user manual (hereinafter referred to as the manual) describes the installation, electrical connection, commissioning, maintenance and fault elimination procedures of following products: HYD 5KTL-3PH, HYD 6KTL-3PH, HYD 8KTL-3PH, HYD 10KTL-3PH, HYD 10KTL-3PH-A, HYD 15KTL-3PH, HYD 20KTL-3PH.
 Carefully read this manual before use and retain it for future reference!  Treat this manual as an integral component of the device.  Keep this manual in close proximity to the device, including when it is
handed over to another user or moved to a different location.
This manual contains important safety information on installation, operation and maintenance of the device.  Read and observe all given safety information. The products, services or features you purchased shall be subject to the company`s commercial contracts and terms. All or part of the products and services described in this document may not within the scope of your purchase. Unless additional terms and conditions in your contract, the company does not make any statement or guarantee on the contents of this document.
1.1 Copyright declaration
The copyright of this manual is owned by SOFAR. It may not be copied ­ neither partially nor completely ­ by companies or individuals (including software, etc.) and must not be reproduced or distributed in any form, or with the appropriate means. SOFAR reserves the right to final interpretation. This manual may be amended following feedback from users or customers. Consult our website at: https://www.SOFAR.com for the latest version.

HYD 5-20KTL-3PH

1

1.2 Presentation of warnings

ABOUT THIS MANUAL

This manual contains information on safe operation and uses symbols to ensure the safety of persons and property as well as the efficient operation of the inverter.  Read through the following symbol explanations carefully in order to
prevent injury or property damage.

1.2.1 Warnsymbol
The general danger symbol warns of risk of serious injury when used with the signal words CAUTION, WARNING, and DANGER.

1.2.2 Signalwords DANGER WARNING CAUTION NOTICE

Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Indicates a danger that results in damage to or destruction of the inverter.

1.2.3 Sectional warnings
Sectional warnings refer to a complete section and are structured as follows:
WARNING
Type and source of danger Consequences for non observance  Avoiding the danger

1.2.4 Embedded warnings
Embedded warnings are part of an action sequence and are placed right before the dangerous step.
Combination of type/source of danger, consequences for non observance and avoiding the danger.

2

HYD 5-20KTL-3PH

ABOUT THIS MANUAL
1.3 Presentation of action instructions

This table shows the sequence of Action steps:

Symbol

Function



This describes an action requirement

1.

2.

This is the sequence of action steps that must be followed step by step

3.



This is a single action step



This describes the result of the action

1.4 Note
Notes are presented in a grey bar.  Provides tips essential to the optimal operation of the product.

HYD 5-20KTL-3PH

3

BASIC SAFETY INFORMATION
2 Basic safety information

 If you have any questions or problems after reading the following information, please contact SOFAR
This chapter details the safety information pertaining to the installation and operation of the device.
2.1 Safety information
Read and understand the instructions within this manual and familiarise yourself with the relevant safety symbols in this chapter before beginning with the installation of the device and eliminating any faults. Before connecting to the power grid, you must obtain official authorisation from the local power grid operator in accordance with the corresponding national and state requirements. Furthermore, operation may only be carried out by qualified electricians. Please contact the nearest authorised service centre if any maintenance or repairs are required. Please contact your dealer to obtain information about your nearest authorised service centre. Do NOT carry out repairs on the device yourself; this may lead to injury or property damage. Before installing the device or carrying out maintenance on it, you must open the DC switch in order to interrupt the DC voltage of the PV generator. You can also switch off the DC voltage by opening the DC switch in the generation junction box. Not doing this may result in serious injury.

4

HYD 5-20KTL-3PH

BASIC SAFETY INFORMATION 2.1.1 Qualified personnel
Personnel tasked with the operation and maintenance of the device must have the qualifications, competence and experience required to perform the described tasks, while also being capable of fully understanding all instructions contained within the manual. For safety reasons, this inverter may only be installed by a qualified electrician who:  -has received training on occupational safety, as well as the installation
and commissioning of electrical systems  -is familiar with the local laws, standards and regulations of the grid
operator. SOFAR assumes no responsibility for the destruction of property or any injuries to personnel caused by improper usage.
2.1.2 Installation requirements
Please install the inverter according to the information contained in the following section. Mount the inverter to a suitable object with a sufficient load-bearing capacity (e.g. walls, PV frames etc.) and ensure that the inverter is upright. Choose a suitable place for the installation of electrical devices. Ensure that there is sufficient space for an emergency exit which is suitable for maintenance. Ensure sufficient ventilation in order to guarantee an air circulation for the cooling of the inverter.
2.1.3 Transport requirements
The factory packaging is specifically designed to prevent transport damage, i.e. violent shocks, moisture and vibrations. However, the device must not be installed if it is visibly damaged. In this case, notify the responsible transport company immediately.

HYD 5-20KTL-3PH

5

2.1.4 Storage requirements

BASIC SAFETY INFORMATION

If the equipment is no longer to be put into service or is to be stored for a long period, make sure that the packaging is intact. Store the equipment in a well-ventilated indoor area that will not cause damage to the equipment components. Store in a clean and dry place, away from dust and moisture. Do not subject to rain or ground water erosion. Do not tilt or invert the box. When stacking, place the inverter carefully to avoid personal injury or equipment damage caused by tipping the equipment. The maximum number of stacking layers must not exceed 4 layers. Keep the storage temperature around -40-70. Relative humidity 5.95% no condensation. When restarting equipment that has been out of service for a long period of time, the equipment shall be thoroughly inspected.

2.1.5 Labelling on the device
The labels must NOT be concealed by items and foreign objects (rags, boxes, devices, etc.); they must be regularly cleaned and kept clearly visible at all times.

2.1.6 Electrical connection
Observe all applicable electrical regulations when working with the Solar inverter.
DANGER

Dangerous DC voltage  Before establishing the electrical connection, cover the PV modules
using opaque material or disconnect the PV generator from the inverter. Solar radiation will cause dangerous voltage to be generated by the PV generator!

6

HYD 5-20KTL-3PH

BASIC SAFETY INFORMATION
DANGER
Danger through electric shock!  All installations and electrical connections may only be carried out by
trained electricians!

NOTICE
Authorisation for grid feed-in  Obtain authorisation from the local power grid operator before
connecting the inverter to the public power grid.

 Do not open the inverter or remove any of the labels. Otherwise, SOFAR shall assume no guarantee.

2.1.7 Operation

DANGER

Electric shock  Contact with the electrical grid or the device's terminals may result in
an electric shock or fire!  Do not touch the terminal or the conductor which is connected to the
electrical grid.  Follow all instructions and observe all safety documents that refer to
the grid connection.

CAUTION
Burning due to hot housing  While the inverter is being operated, several internal components will
become very hot.  Please wear protective gloves!  Keep children away from the device!

HYD 5-20KTL-3PH

7

2.1.8 Repair and maintenance

BASIC SAFETY INFORMATION

DANGER

Dangerous voltage!  Before carrying out any repair work, first switch off the AC circuit
breaker between the inverter and power grid, and then the DC switch.  After switching off the AC circuit breaker and the DC switch, wait a
minimum of 5 minutes before starting any maintenance or repair work.

NOTICE
Unauthorised repairs!  Following the elimination of any faults, the inverter should be fully
functional once more. Should any repairs be required, please contact a local authorised service centre.  The internal components of the inverter must NOT be opened without the relevant authorisation. Shenzhen SOFAR Co., Ltd. assumes no responsibility for any resulting losses or defects.
2.1.9 End-of-life requirements
When the inverter or any related components need to be disposed of, please ensure that the disposal is carried out in accordance with local waste handling regulations. Make sure to send the inverter to an appropriate disposal site in accordance with local regulations.

8

HYD 5-20KTL-3PH

BASIC SAFETY INFORMATION
2.2 Symbols and signs
CAUTION
Beware of burning hazards due to the hot housing!  While the inverter is in operation, only touch the display and the
buttons, as the housing can become hot.
NOTICE
Implement earthing!  The PV generator must be earthed in accordance with the
requirements of the local power grid operator!  For reasons of personal safety, we recommend that all PV module
frames and inverters of the PV system are reliably earthed.
WARNING
Damage due to overvoltage  Ensure that the input voltage does not exceed the maximum
permissible voltage. Overvoltage may cause long-term damage to the inverter, as well as other damage that is not covered by the warranty!

HYD 5-20KTL-3PH

9

2.2.1 Symbols on the inverter

BASIC SAFETY INFORMATION

Several symbols pertaining to safety can be found on the inverter. Please read and understand the content of these symbols before starting the installation.

Symbol

Description
Residual voltage is present in the inverter! Before opening the inverter, you should wait five minutes to ensure that the capacitor has been fully discharged.
Caution! Danger through electric shock

Caution! Hot surface
The product is compliant with EU guidelines
Earthing point
Please read the manual before installing the inverter
Device degree of protection according to EN 60529
Positive and negative poles of the DC input voltage
The inverter must always be transported and stored with the arrows pointing upward
RCM (Regulatory Compliance Mark) The product meets the requirements of the applicable Australian standards.

10

HYD 5-20KTL-3PH

PRODUCT FEATURES
3 Product features
This chapter describes the product features, dimensions and efficiency levels.
3.1 Product information
The HYD 5K-20KTL-3PH is a grid-coupled PV and energy storing inverter which can also supply energy in stand-alone operation. The HYD 5K-20KTL3PH has integrated energy management functions which cover a wide range of application scenarios.

Figure 3-1 HYD 5K-20KTL-3PH inverter system diagram
HYD 5K-20KTL-3PH inverters may only be used with photovoltaic modules which do not require one of the poles to be earthed. In normal operation, the operating current must not exceed the limits specified within the technical data. The selection of the optional inverter parts must be determined by a qualified technician who has good knowledge of the installation conditions.

HYD 5-20KTL-3PH

11

3.2 Product dimensions

PRODUCT FEATURES

Figure 3-2 Dimensions

12

HYD 5-20KTL-3PH

PRODUCT FEATURES
3.3 Labelling on the device
Labelling must not be covered or removed!

Figure 3-3 HYD 5K-20KTL-3PH appearance and label
3.4 Functional features
The DC output generated by the PV generator can be used for both grid feed-in and battery charging. The battery can supply the energy to the grid or the consumer. The emergency current supply mode (EPS) can provide inductive loads such as air conditioning systems or refrigerators with an automatic switchover time of less than 10 milliseconds, and a temporary overload of up to 10% is possible.
3.4.1 Functions
 Two MPP trackers with 1.5-fold DC overload.  Flexible switching between on-grid operation and energy storage
operation.  Maximum efficiency when charging and discharging the battery (97.8%).  Up to 2 battery strings with a combined maximum charging and
discharging current of 50 A.  Wide battery input voltage range (180­800 V).  The EPS output can be connected to unbalanced loads.  Up to 6 inverters can operate in parallel at the EPS connection and AC
connection.

HYD 5-20KTL-3PH

13

PRODUCT FEATURES  Monitoring via RS485 and WiFi, optionally via Bluetooth. 3.4.2 Electrical block diagram

Figure 3-4 Electrical schematic diagram
3.5 Application modes
3.5.1 Typical energy storage system
A typical energy storage system with PV panels and battery unit(s), connected to the grid.

Figure 3-5 Typical energy storage system

14

HYD 5-20KTL-3PH

PRODUCT FEATURES 3.5.2 System without PV connection
In this configuration, there are no PV panels connected and the battery is charged through the grid connection.
Figure 3-6 System without PV connection
3.5.3 System without battery
In this configuration, the battery unit(s) can be added later.

Figure 3-7 System without battery

HYD 5-20KTL-3PH

15

3.5.4 Back-up mode (off-grid)

PRODUCT FEATURES

When there is no grid connection, the PV panels and the battery will provide electricity to the critical load.

Figure 3-8 Back-up mode (Off- Grid)
3.5.5 System with multiple inverters (5­20 kW)
Up to 6 inverters can be connected in parallel, to the grid and EPS connections, resulting in an EPS output of up to 200 kVA.

Figure 3-9 System with multiple inverter

16

HYD 5-20KTL-3PH

PRODUCT FEATURES
 Multiple inverters connected in parallel shall be of the same power model with the same power and battery configuration.
 The energy meter or CTs are connected to the Master inverter. Control of all inverters takes place via the link cable.
 For the parallel switching of several devices, it is recommended to use a joint AC load break switch for the connected loads at the LOAD connection.
 For the parallel switching of several devices, it is recommended to use a joint AC load break switch for the connected loads at the GRID connection.
 In order to evenly distribute the loads among the inverters, the cable length between each output and the load must be the same.
 If the maximum apparent power of a load is greater than 110% of the inverter' s rated output, the device must not be connected via the AC LOAD terminal, but rather directly to the grid.

HYD 5-20KTL-3PH

17

3.5.6 AC retrofit system

PRODUCT FEATURES

In this system configuration, the hybrid system for an already existing PV system is supplemented with a solar inverter of any brand. By installing a second smart meter, the PV production can be taken into account and used for charging the battery.

 The communication address of meter 1 should be set to 1. Similarly, the communication address of meter 2 should be set to 2.

Figure 3-10 AC retrofit system

18

HYD 5-20KTL-3PH

PRODUCT FEATURES 3.5.7 Unbalanced load
By enabling the " Unbalanced load " option, the inverter compensates unbalanced loads either in EPS mode or on-grid mode.
Figure 3-11 Unbalanced load (EPS mode)

Figure 3-12 Unbalanced load (On Grid)

HYD 5-20KTL-3PH

19

PRODUCT FEATURES
3.6 Connecting GTX 3000-H batteries (AMASS)
Using SOFAR's own battery system GTX 3000-H is a way to build scalable battery systems. A GTX 3000H battery module has a nominal capacity of 2,5 kWh, allowing multiple configurations for one tower from 10 kWh (GTX 3000H4) to 25 kWh (GTX 3000-H10), The series battery is rated at 25A and the individual battery is rated at 51.2V. The HYD 5 ... 8KTL-3PH models have one battery input (max. current 25 A), and the HYD 10 ... 20KTL-3PH models have two battery inputs (max. current 25 A / 25 A).

COM 16pin connector BAT1+ BAT1-
BAT2+ BAT2CAN matching resister

(Orange)

PIN8 PIN7

P-

(White orange) P+

Link Port In

Link Port Out

...... PP+
...
Link Port In
...

Link Port Out P-
P+ Link Port In

......

Link Port Out

PP+

....
Link Port In
...

Link Port Out

Battery Address: 0

Battery Address: 1...3

Battery Address: 4

Battery Address: 5...7

Battery pack 1

Battery pack 2...4

Battery pack 5

Battery pack 6...8

Figure 3-13 GTX 3000-H connecting in 4 Towers in Parallel

 If a battery input is unused, ensure to set this in the inverter's system settings, for example:
 System Settings ­ Input Channel Config ­ Bat Channel2 ­ Not Used.  Configuration of the battery setup should only be done when the
inverter is in standby mode!  Advanced Settings ­ 10. Switch on / off ­ Switch Off  The battery inputs of different inverters should not be connected in
parallel  Each battery tower corresponds to a unique battery address. Each
battery address can be configured from 00­15 or not used

20

HYD 5-20KTL-3PH

PRODUCT FEATURES
 The other battery parameters should be set according to the battery specifications
3.7 Connecting BTS 5K batteries
Using SOFAR's own battery module BTS 5K is a way to build scalable battery systems. A BTS E5-DS5 battery system has a nominal capacity of 5.12 kWh, allowing multiple configurations for one tower from 5.12 kWh (BTS E5-DS5) to 20.48 kWh (BTS E20-DS5). The parallel battery are rated at 400V and the individual battery are rated at 7A. The HYD 5 ... 8KTL-3PH models have one battery input (max. current 25 A), and the HYD 10 ... 20KTL-3PH models have two battery inputs (max. current 25 A / 25 A). Below diagram is an example of how to connect the BTS battery system to SOFAR's HYD 5 ... 20KTL-3PH.

Figure 3-14 System with BTS 5K battery

HYD 5-20KTL-3PH

21

PRODUCT FEATURES
Below is the schematic connection diagram of a system where the neutral line and ground line are connected together.

Figure 3-15 System with BTS 5K battery in Australian N-Grid with N-EPS connected
 Configuration of the battery setup should only be done when the inverter is in standby mode!
 Advanced Settings ­ 10. Switch on / off ­ Switch Off  If a battery input is unused, ensure to set this in the inverter's system
settings, for example:  System Settings ­ Input Channel Config ­ Bat Channel2 ­ Not Used.  The battery inputs of different inverters should not be connected in
parallel  Each battery tower corresponds to a unique battery address. "Auto
Config. Address" will detect the number and addresses of the connected batteries automatically within 2-3 Minutes.  In certain regions there are specific local safety requirements of the power grid. Ensure to comply with all local safety requirements.  According to the Australian safety regulations, the neutral cables on the grid-connected side and EPS side must be connected together. Otherwise the EPS cannot be used.

22

HYD 5-20KTL-3PH

INSTALLATION
4 Installation
4.1 Installation information
DANGER
Fire hazard  Do NOT install the inverter on flammable material.  Do NOT install the inverter in an area in which flammable or explosive
material is stored.
CAUTION
Burning hazard  Do NOT install the inverter in places where it can be accidentally
touched. The housing and heat sink may become very hot while the inverter is being operated.
NOTICE
Weight of the device  Take into account the weight of the inverter when transporting and
moving it.  Choose a suitable installation location and surface.  Commission a minimum of two persons for the installation of the
inverter.  Do not set down the inverter overhead.

HYD 5-20KTL-3PH

23

4.2 Installation procedure
Mechanical installation is performed as follows: 1. Examine the inverter before installation 2. Prepare the installation 3. Select an installation location 4. Transport the inverter 5. Mount the rear panel 6. Install the inverter

INSTALLATION

4.3 Examination before installation

4.3.1 Checking the external packaging materials
Packaging materials and components may become damaged during transportation. Therefore, the external packaging materials must be examined before the inverter is installed. Check the external packaging material for damage, e.g. holes and cracks. If you discover any damage, do not unpack the inverter and contact the transport company and/or dealer immediately. It is recommended that the packaging material should be removed within 24 hours before installing the inverter.

4.3.2 Checking the delivery scope
After unpacking the inverter, check that the delivery items are both intact and complete. In the event of any damage or missing components, contact the wholesaler.

No.

Image

Description

01

Inverter HYD 5K ... 20KTL-

3PH

02

Wall bracket

Quantity

5...8kW

10...20kW

1

1

24

HYD 5-20KTL-3PH

INSTALLATION

No.

Image

03 04

05

Description PV+ input terminal PV- input terminal MC4 connector contact PV+

Quantity

5...8kW

10...20kW

2

4

2

4

2

4

06

MC4 connector contact PV-

2

4

07

BAT- input connector

1

2

08

BAT+ input connector

1

2

09

BAT- connector contact

1

2

10

BAT+ connector contact

1

2

11

2

M6 hexagon screw

12

M8*80 expansion screws

4

(wall bracket)

13

AC grid connection

1

14

AC load connection

1

15

Link port connection

1

HYD 5-20KTL-3PH

25

No.

Image

Description

16

8-pole terminal

Terminal resistance for parallel system

17

DRMs connection

18

6-pole connector for CT

19 Three-phase smart meter

INSTALLATION

Quantity

5...8kW

10...20kW

1

1 1 1

20

1

COM communication cable

21

USB acquisition stick (WIFI)

1

22

Temperature sensor NTC

1

(5m) when using Lead-acid

battery

23

1

Manual

24

1

Warranty card

25

1

Quality certificate

26

1

Test report, output test

27

2

Connector accessories

26

HYD 5-20KTL-3PH

INSTALLATION
4.4 Connections
CAUTION
Damage during transportation  Please check the product packaging and connections carefully prior to
installation.

Figure 4-1 HYD 5K-20KTL-3PH inverter overview

 Battery connection

 DC switch

 PV input terminals

 AC load connection

 AC grid connection



 DRMs



 Link port 1





Current sensor connection (CT)



USB/WiFi Communication connection Link port 0 LCD display

 The number of Battery input terminals depends on the Rated Power: HYD 5K...8KTL-3PH 2pcs HYD 10K...20KTL-3PH 4pcs

HYD 5-20KTL-3PH

27

INSTALLATION

 The number of PV input terminals depends on the Rated Power: HYD 5K...8KTL-3PH 4pcs HYD 10K...20KTL-3PH 8pcs

4.5 Tools

Prepare the tools required for the installation and the electrical connection.

No.

Tool

Model

Function

Hammer drill

01

Recommended drill diameter:

Used to drill holes in the wall.

8mm

02

Screwdriver

Wiring

03

Phillips screwdriver

Used to remove and install the screws of the AC terminal

04

Removal tool

Used to remove the PV , battery terminal

05

Wire stripper

Used to strip the wire

06

6mm Allen key

Used to turn the screw to connect the rear panel to

the inverter

07

Crimping tool

Used to crimp power cables

08

Multimeter

Used to check the earthing

09

Marker

Used for marking

10

Measuring tape

Used to distances

measure

28

HYD 5-20KTL-3PH

INSTALLATION 11 12

Spirit level ESD gloves

Used to align the wall bracket
for the installer

13

Safety goggles

for the installer

14

Anti-dust respiratory mask

for the installer

4.6 Installation Environment Requirements
 Choose a dry, clean, and tidy place, convenient for installation.  Ambient temperature range: -30­60°C.  Relative humidity: 0­100% (non-condensed).  The inverter shall be installed in a well-ventilated place.  Do not place the inverter close to flammable or explosive materials.  The AC overvoltage category of the inverter is category II.  Maximum altitude: 4000m  Pollution degree: 4
4.7 Installation location
Choose a suitable position for the installation of the inverter. Ensure that the following requirements have been fulfilled:

HYD 5-20KTL-3PH

29

INSTALLATION

Figure 4-2 Installation Position of HYD 5-20KTL-3PH
Minimum distances for individual HYD 5-20KTL-3PH inverters:

Figure 4-3 Minimum distances for individual inverter
Minimum distances for several HYD 5K-20KTL-3PH inverters:

30

HYD 5-20KTL-3PH

INSTALLATION

1000 mm 300 mm

200 mm Figure 4-4 Minimum distances for several inverter

200 mm

4.8 Unpacking the inverter

1. Open the packaging and grip underneath the inverter at the sides with both hands.

Figure 4-5 Moving the inverter
2. Lift the inverter out of the packaging and move it to its installation position.

HYD 5-20KTL-3PH

31

INSTALLATION
NOTICE
Mechanical damage  In order to prevent injuries and damage to the device, ensure that the
inverter is kept balanced while it is being moved - it is very heavy.  Do not place the inverter on its connections, as these are not designed
to bear its weight. Place the inverter horizontally on the ground.  When you place the inverter on the ground, place foamed material or
paper underneath it in order to protect its housing.
4.9 Installation of the inverter
1. Hold the wall bracket in the desired place and mark the four holes. Put the wall bracket aside and drill the holes.
2. Guide the spread screw M8*80 into the hole vertically and ensure that its insertion depth is sufficient.
3. Align the wall bracket with the hole positions and fasten by tightening the spread screw with the nuts.







Figure 4-6 Installing HYD 5-20KTL-3PH(a)

4. Place the inverter in the wall bracket and fasten it with the M6 hexagon screw.
5. You can secure the inverter to the wall bracket using a lock.

32

HYD 5-20KTL-3PH

INSTALLATION





Figure 4-7 Installing HYD 5-20KTL-3PH(b)

HYD 5-20KTL-3PH

33

5 Electrical connections

ELECTRICAL CONNECTIONS

5.1 Safety instructions
This topic describes the electrical connections of the inverter HYD 5- 20KTL3PH. Read this section thoroughly and carefully before connecting the cables.

DANGER
Electrical voltage at the DC connections  Ensure that the DC switch is OFF before establishing the electrical
connection. The reason is that the electrical charge remains in the capacitor after the DC switch has been switched off. Therefore, at least 5 minutes must lapse before the capacitor has been electrically discharged.

DANGER
Electrical voltage  PV modules generate electrical energy when exposed to sunlight, and
this may present an electrical shock hazard. Therefore, cover the PV modules with an opaque sheet before connecting to the DC input power cable.

DANGER
Electrical voltage at the DC connections  Wear rubber gloves and protective clothing (safety goggles and boots)
when working on high voltage/high current systems such as inverter and battery systems.

34

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS
NOTICE
Qualification  The installation and maintenance of the inverter must be carried out
by an electrician.

 The open-circuit voltage of the modules connected in series must be lower than or equal to 1000 V.

The connected PV modules must be compliant with IEC 61730 class A.

Table 5-1 Relevant current parameters of each model

Model

Isc PV (absolute maximum)

Maximum output overvoltage protection

HYD 5KTL-3PH

8 A*3

HYD 6KTL-3PH

15 A/15 A

10 A*3

HYD 8KTL-3PH

13 A*3

HYD 10KTL-3PH

16 A*3

HYD 15KTL-3PH

30 A/30 A

24 A*3

HYD 20KTL-3PH

32 A*3

DC switch parameters Rated-Insulation Voltage Rated Impulse Withstand Voltage Suitability For Isolation Rated Operational Current (Ie) PV Utilization Category Rated Short Time Withstand Current (Icw) Rated Short-Circuit Making Capacity (Icm) Rated Making Capacity/Rated Breaking Capacity

1500V 8KV Yes 1100V/40A,800V/55A DC-PV2 0.76kA .1S 1.4kA 1.4kA

HYD 5-20KTL-3PH

35

ELECTRICAL CONNECTIONS

PV terminal parameters Rated-Insulation Voltage Rated Operational Current Protection Class Maximum Temperature Iimit

1000V 39A IP68 105

The DVC (decisive voltage classification) is the circuit voltage which constantly occurs between two arbitrary live parts during proper use in a worst-case scenario:

DVC
A B C

Table 5-2 Description of limits for DVC
Operating voltage limit(V)

Ac voltage (RMS)

Ac voltage (PK)

Dc voltage (AVG)

25 (16)

35.4 (22.6)

60 (35)

50 (33)

71 (46.7)

120 (70)

1000

4500

1500

 The values in brackets apply when the inverter is installed in a humid environment.

Table 5-3 The decisive voltage class (DVC)
Interface

DVC

PV input connection

DVCC

AC connection

DVCC

Battery connection

DVCC

Load connection

DVCC

USB/WiFi interface

DVCA

COM interface

DVCA

CT interface

DVCA

DRMs

DVCA

Link port

DVCA

36

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

5.2 Wiring overview

Component

Table 5-4 Cable description
Description

Recommended cable type

+ : Connect the positive cable of

the lithium battery
- : Connect the negative cable of the lithium battery

Outdoor multicore copper cable (4...6mm²)

Load Grid

+ : Connect the positive cable of the PV array

- : Connect the negative cable of the PV array

PV cable (4...6mm2)

Connection method: male and female terminals are inserted into each other.
Connection method: male and female terminals are inserted into each other.

L1

L2

Outdoor multicore copper cable

L3 5K...8KTL-3PH 6...10mm²

N 10K...20KTL-3PH

8-10mm² PE

L1

L2

Outdoor multicore copper cable 5K...8KTL-

L3 3PH

6...10mm²

N 10K...20KTL-3PH 8-10mm²

PE

HYD 5-20KTL-3PH

37

5.3 System overview

ELECTRICAL CONNECTIONS

There are different system configurations possible depending on the user's requirements, existing electrical infrastructure and local regulations. The distribution box must be configured to comply to the grid operator requirements. The inverter has an integrated AC relay to disconnect all phases and Neutral from the grid in case of grid fault or grid outage. The inverter's generation and feed-in limitation functions require the use of an external measurement device to obtain grid information. There are 3 system configurations:  System A: direct measurement of energy with CTs (up to 300 A)  System B: measurement of energy with energy meter + CTs (default)  System C: measurement of energy with directly connected energy meter

 For System B, customers can choose different CTs based on the installation. The secondary current must be 5 A.
 To ensure neutral continuity, the neutral of AC GRID must be connected together with the neutral of AC LOAD and must not be interrupted by switch.
 If the Main Switch is used residual current protection device, it is recommended to choose type A protector for RCD with leakage current of 100mA or above (it is better to adjust according to the size of the system).
 If the grounding type of the grid power distribution system requires the ground wire and the neutral wire to be connected together, a short-circuit bar needs to be used to short-circuit the neutral wire and the ground wire in the power distribution where the inverter output is connected to the grid.And circuit breakers and fuses are not allowed to be installed on the grounding wire.

38

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

CAUTION

In the following three situations, the system must be connected to the fuse first and then to the machine's input terminal:
 Lead-acid battery  Lithium battery without BMS  Multiple lithium batteries connected to one input

HYD 5-20KTL-3PH

39

ELECTRICAL CONNECTIONS 5.3.1 System A: direct measurement with CTs

Figure 5-1 Electrical connections (Plan A: CTs)

40

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS 5.3.2 System B: measurement with energy meter + CTs (default)

Figure 5-2 Electrical connections (Plan B: Meter+CT)

HYD 5-20KTL-3PH

41

ELECTRICAL CONNECTIONS
5.3.3 System C: measurement with directly connected energy meter

Figure 5-3 Electrical connections (Plan C: Meter)

42

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

Energy Meter through CTs:

Table 5-5 Smart Meter with CTs
Technical Data

Voltage

AC 3×230/400 V

Current

1.5(6) A

Frequency

50/60 Hz

Pulse

6400 imp / kWh

Power accuracy

Active Class 0.5S, Reactive Class 2

Directly connected Energy Meter:
Table 5-6 Directly connected Smart Meter
Technical Data

Voltage

AC 3×230/400 V

Current

5(80) A

Frequency

50/60 Hz

Pulse

400 imp / kWh

Power accuracy

Active Class 1, Reactive Class 2

To obtain grid information via System A: Connect the wires according to the wiring method as shown in 5.3.1" System A: direct measurement with CTs", and enable Anti-Reflux Power function and set the Reflux Power limit on the menu interface of the machine. Refer to <7.4 Advanced settings  3. Anti Reflux> in this manual for specific operation methods. There are two situations when CT is installed. One is to connect in the correct CT direction. The direction should refer to the figure below, from the inverter to the power grid. One is the random CT direction, and then the use of CT calibration function for calibration. CT calibration procedures refer to this manual 7.4 Advanced settings>>9.CT calibration. To obtain grid information via Plan B or C:

HYD 5-20KTL-3PH

43

ELECTRICAL CONNECTIONS
Wiring according to the wiring method as shown in 5.3.2"System B: measurement with energy meter + CTs" or 5.3.3"System C: measurement directly connected energy meter", and enable Anti-Reflux Power function and set the Reflux Power limit on the menu interface of the machine. Refer to <7.4 Advanced settings  3. Anti Reflux> in this manual for specific operation methods. Only installers and distributors have the permission to use the Bluetooth APP for setting, enabling/disabling settings, and setting up the Reflux Power limit. Refer to <7.4 Advanced settings3. Anti Reflux> in this manual for specific operation methods. Please Note: Generation and Export Limit Control functions are set as follows: User can set and check through LCD menu. Refer to <7.4 Advanced settings 3. Anti Reflux> and <7.4 System information1. Inverter Info> . Settings Main interface---Advanced Settings---Input 0001---Anti Reflux--Anti Reflux Mode---Control Mode---Control Type---Power limit .

Main interface

Back 1.System Settings 2.Advanced Settings 3.Energy Statistics 4.System Information 5.Event List 6.Software Update

Input 0001 1.Battery Parameter 2.Battery Active 3.Anti Reflux ...

1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit

1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit
1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit

Disable Anti Reflux Three phase limit
Soft limit Hard limit Both

1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit
1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit

Generation limit Three phase limit
***KW(VA)

44

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS Checking Main interface---System Information---Inverter Info---Anti Reflux.

Main interface

Back

1.System Settings 2.Advanced Settings 3.Energy Statistics 4.System Information 5.Event List 6.Software Update

1.Inverter Info 2.Battery Info 3.Safety Param.

Inverter Info (1) ... Inverter Info (6) Anti Reflux (enable or disable)

Anti-Reflux Power function =Generation or Export Limit Control function Generation (or Export) limit =Generation (or Export) limit control Reflux Power limit = (active or apparent) Power limit When Anti-Reflux Power function is enabled, the reflux power of point of common coupling (PCC) will be limited to the set Reflux Power limit. Both Hard limit control and soft limit control can be used together. However, when Hard limit control is enabled, Anti-Reflux power cannot exceed the Reflux power limit. If the Reflux power exceeds the Reflux power limit, the inverter disconnects from the grid and triggers overload protection. When communication signal with the electricity meter is lost, the output power of the inverter is limited to the value of soft limit control and does not trigger fault protection. When Hard limit control is enabled, a loss of communication with the meter will trigger the inverter into a fault protection state.

HYD 5-20KTL-3PH

45

5.4 Electrical connection

ELECTRICAL CONNECTIONS

The electrical connection is established as follows: 1. Connect PE cable 2. Connect DC input cable 3. Connect battery cable 4. Connect AC output power cable 5. Connect communication cable (optional

5.5 Connecting the PE cables
Connect the inverter to the equipotential bonding bar by using the protective earth cable (PE) for grounding.

NOTICE
Pole earthing not permissible!  As the inverter is transformerless, the plus and minus poles of the PV
generator must NOT be earthed. Otherwise, the inverter will malfunction. In the PV system, not all live metal parts (e.g. PV module frames, PV frame, generator connection box housing, inverter housing) require earthing.

1. Remove the insulation of the cable. For outside use, cables of  4mm² are recommended for earthing).

Figure 5-4 Connecting PGND cable(a)
 L2 is 2 to 3 mm longer than L1.

46

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS 2. Crimp the cable to the ring terminal:
Figure 5-5 Connecting PGND cable(b)
3. Install the crimped ring terminal and the washer with the M6 screws and tighten these with a torque of 3 Nm using an Allen key:

Figure 5-6 Connecting PGND cable(c)



M6 Screws



Threaded hole



Ring terminal

5.6 Connecting the DC lines for the PV modules and battery
 The connection steps of the battery and PV are the same, only the terminal specifications are different. The colour of the battery terminal is blue, the colour of PV terminal is black.
 If only one set of batteries is required, ensure it is connected to the BAT 1 port, not the BAT 2 port.
Please observe the recommended cable dimensions:

HYD 5-20KTL-3PH

47

ELECTRICAL CONNECTIONS

Cable cross-section (mm2)

Range

Recommended value

Outer diameter of cable (mm)

4.0 ... 6.0

4.0

4.5 ... 7.8

1. Remove the crimp contacts from the positive and negative connections. 2. Remove the insulation of the cables:

Figure 5-7 Connecting PV(a)

 Positive DC cable

 Negative DC cable

 L2 is 2 to 3 mm longer than L1
3. Insert the positive and negative DC cables into the corresponding cable glands.
4. Crimp the DC cables. The crimped cable must be able to withstand a tractive force of 400 Nm.

48

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

Figure 5-8 Connecting PV(b)
CAUTION
Danger of reverse polarity!  Ensure that the polarity is correct before plugging into the DC
connections!
5. Insert the crimped DC cables into the corresponding connector housing until you hear a "clicking" sound.

Figure 5-9 Connecting PV(c)



Positive power cable



Negative power cable

HYD 5-20KTL-3PH

49

ELECTRICAL CONNECTIONS 6. Re-screw the cable glands to the connector housing.
Figure 5-10 Connecting PV(d)
7. Insert the positive and negative connectors into the corresponding DC input terminals of the inverter until you hear a "clicking" sound.

Figure 5-11 Connecting PV(e)



Locking

 Insert the protective caps into the unused DC connections.
CAUTION
Danger of DC arcing  Before removing the plus and minus connector, ensure that the DC
switch has been set to OFF.

50

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS
In order to remove the plus and minus connection from the inverter, insert a removal key into the locking and press on the key with the adequate force as shown in the following illustration:

Figure 5-12 Connecting PV(f)
5.7 Connecting the AC power cables
The AC power cables are used to connect the inverter to the critical loads (through the EPS port), and the AC power distributor or the power grid.
CAUTION
AC connection  Each inverter must have its own circuit breaker.  The AC disconnecting device must be easily accessible.
 The inverter HYD 5K-20KTL-3PH has a built-in AFI (univ. sensitive residual current protection). If an external AFI is required, we recommend an AFI type A featuring a residual current of 100 mA or higher.
 Please follow the national rules and regulations for the installation of external relais or circuit breakers!
The AC cable should be correctly dimensioned in order to ensure that the loss of power in the AC cable is less than 1% of the rated output. If the AC cable resistance is too high, then the AC voltage will increase; this may cause

HYD 5-20KTL-3PH

51

ELECTRICAL CONNECTIONS
the inverter to become disconnected from the power grid. The relationship between the leakage power in the AC cable and the cable length, the cable cross-section, is displayed in the following illustration:

Figure 5-13 The relationship between the leakage power and cable length
5.8 AC connector installation
CAUTION
Electrical voltage  Ensure that the grid has been switched off before removing the AC
connector
Please follow below steps to install the AC connector. 1. Select the suitable cable in accordance with above diagram. Remove
the insulating layer of the AC output cable using a wire stripper and in accordance with the following illustration:

A = 30 ...50 mm B = 3...5 mm

52

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS
2. Disassemble the connector in accordance with the following illustration. Guide the AC output cable through the cable gland.

3. Connect the AC cable in accordance with the following requirements and tighten the terminal using the Allen key.

Connection

Cable

L1

Phase 1 (brown)

L2

Phase 2 (black)

L3

Phase 3 (grey)

N

Neutral conductor (blue)

PE

Earthing cable (yellow-green)

4. Assemble the connector housing and screw the cable gland tight.

5. Connect the AC connector to the AC connection of the inverter by turning it clockwise until it locks into place.

HYD 5-20KTL-3PH

53

ELECTRICAL CONNECTIONS
 Remove the AC connector by turning it anticlockwise.  When you use the meter connection function, make sure that the AC
terminal cable corresponds to the meter cable one by one( L1, L2, L3, N, and PE cables)
6. Connector accessories are divided into upper and lower parts. Attach the connector accessories to the connector and fasten. Use a cross screwdriver.

54

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS
5.9 Communication interfaces
The positions of the communications interfaces of the HYD 5K ... 20KTL-3PH are displayed below:

No.

Connection

Function



USB/WiFi

USB port for firmware update and safety parameter import; Port to connect Stick Logger (WiFi)



DRMs

Demand Response Modes/Logic Interface to control the inverter



COM

Multifunctional Communication Port



Link port 1

Master/Slave operation of multiple inverters



Link port 0



Current sensor connection (CT)

For configurations according to System A, CTs are directly connected to the inverter without an energy meter.

HYD 5-20KTL-3PH

55

ELECTRICAL CONNECTIONS 5.9.1 Multifunctional Communication Port
Please refer to the following table for the specific PIN assignments.









PIN

Definition

Function

Note

1

RS485A1-1

RS485differential signal+

2

RS485A1-2

RS485differential signal+

Wired monitoring or inverter

3

RS485B1-1

RS485differential signal­

cascade monitoring

4

RS485B1-2

RS485differential signal­

5

RS485A2

RS485differential signal+

Communicate

with electricity

6

RS485B2

RS485differential signal-

meters

56

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

PIN

Definition

7

CAN0_H

8

CAN0_L

9

GND.S

10

485TX0+

11

485TX0-

12

GND.S

13

BAT_Temp

14

DCT1

15

DCT2

16

VCC

Function
CAN high data
CAN low data
BMS communication
GND RS485differential
signal+ RS485differential
signal-
Signal GND
Battery temperature
sampling
Dry Contact1
Dry Contact2
Communication VCC

Note
Used for communication with lithium battery BMS, the inverter can automatically identify the battery BMS communication as CAN or RS485 communication
Inner BMS battery temperature sampling
Providing electrical switching function
12V power supply

HYD 5-20KTL-3PH

57

5.9.2 RS485

ELECTRICAL CONNECTIONS

For the monitoring and control of several inverters, you connect the RS485 wires in daisy-chain. At the first and the last inverters, you need to terminate the bus with an 120 Ohm resistor between Pin 1 and 4.

Figure 5-14 RS485 communication connection
5.9.3 Smart meter
The integrated energy management functions integrated of the HYD 520KTL-3PH require to measure the power flow at the point of grid interconnection. There are different system configurations possible. It can be measured using directly connected smart meter or using smart meter with CTs. Please refer to below table for the PIN assignments for the RS485 connection between the inverter and the smart meter.

Please refer to below table for the PIN assignments for the RS485 connection

between the inverter and the energy meter.

Inverter COM Port Pin Function

Meter Pin

Pin 5

RS485+ (A2)

Pin 24

Pin 6

RS485- (B2)

Pin 25

58

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS
 The Smart meter shows a positive power value for feed-in to the grid, and a negative value for energy purchase from the grid.
 Use the shielded twisted pair cable.  The copper outer diameter should be more than 0.5 mm².  Keep away from power cables or other electric fields.  Use termination resistors at the ends of the RS485 line to improve
signal quality.

Connect the grid phases to the Smart Meter Pins according to below drawing for correct functionality of the inverter. Smart meter with directly connection (System C, default configuration)

Smart meter pins

24 25

PIN5

AB RS485

PIN6

1 3 4 6 7 9 10

L1

A

L2

B

L3

C

N

N

*Meter does not need to be reconfigured

Inverter
L1 L2 L3 N

PIN: Signal:

6

5

RS485- RS485+

369

1 0

2425

1

47

1 0

499k

499k

24 25
Figure 5-15 Directly Meter

A B C N
Grid

HYD 5-20KTL-3PH

59

ELECTRICAL CONNECTIONS
 No additional configuration required for direct-connected meters  Up to 80 A measurement  Accuracy class and load rating (VA/):1 class  Rated operating voltage: AC 0.66KV (Equivalent to 0.69KV GB156-
2003)  Rated frequency: 50-60Hz  Ambient temperature: -25~75  Altitude: 3000m Smart meter with CTs connection (System B)
Smart meter pins

24 25

PIN5

AB RS485

PIN6

P1 P2 Grid

2 5 8 10 1 3 4 6 7 9

L1

A

L2

B

L3

C

N

N

Inverter
L1 L2 L3 N

PIN: Signal:

6

5

RS485- RS485+

499k

36 9

1 0

2 58

Smart Meter DTSU 666

24 25

1 47

1 0

A B C N
Grid

499k

24 25
Figure 5-16 RS485 communication connection and smart meter with CTs
 The arrows on the current transformers direct to the grid.  Up to 200 A measurement  Accuracy class and load rating (VA/):1 class

60

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS  Rated operating voltage: AC 0.66KV (Equivalent to 0.69KV GB1562003)  Rated frequency: 50-60Hz  Ambient temperature: -40...85  Altitude: 3000m
Smart Meter Configuration The smart meter is preconfigured to be used with the inverter with these settings:  Modbus Address: 1  Baud Rate: 9600  Current Ratio: 40:1
In case you want to change or check the settings, please refer to below procedure: Modbus Address and Baud Rate setting
Current Ratio setting

HYD 5-20KTL-3PH

61

ELECTRICAL CONNECTIONS
 The inverter connected to the meter is a power generation device, and the function of the meter connected to the traditional load (electrical device) is opposite. Therefore, for our product, when the power is output to the grid, the electricity meter will show a positive value, and when the power is purchased from the grid, it will show a negative value.
 The smart meter comes with 2 terminal resistors, In the actual configuration, the customer can parallel a terminal resistor at each end of the cable to reduce signal reflection in the communication cable.
5.9.4 Temperature Sensor
For batteries without a BMS (for example lead-acid batteries), you need to connect the temperature sensor which is within the scope of supply. Place the sensor at the battery.
5.9.5 BMS connection
For batteries with a BMS (for example Li-Ion batteries), you need to connect either the CAN Bus or RS485 with the battery management system. The inverter will use the CAN Bus or RS485 Bus according to the battery selection in the inverter's menu.

Connecting GTX 3000-H

For connecting the GTX 3000-H battery to the inverter, please follow the

below pin assignments:

Inverter COM Port

Function

GTX 3000-H communication cable

Battery "Link In"
Port

Pin 7

CAN0_H

White-orange

Pin 2

Pin 8

CAN0_L

Orange

Pin 4

62

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

Connecting the BTS 5K battery

For connecting the BTS 5K battery to the inverter, please follow the below

pin assignments:

Inverter COM Port

Function

BTS communication cable

Battery "Link In"
Port

Pin 7

CAN0_H

Blue

Pin 4

Pin 8

CAN0_L

Blue-white

Pin 5

5.9.6 Dry Contact
The dry contact signals the on-grid and EPS mode through a signal voltage of 12 VDC. Alternatively, the switch contact can start and stop a generator to charge the battery.
 This function is available from Firmware V10

The dry contact settings must be set accordingly in the menu Advanced settings ­ Dry Contact Control.
On-grid / EPS mode Below is the diagram for switching mode 1 (Relay Open In EPS) and how it can be used to switch a N-PE connection during off-grid mode:

HYD 5-20KTL-3PH

63

ELECTRICAL CONNECTIONS On-grid (relay mode 1 "Relay Open In EPS"):
EPS mode (relay mode 1 "Relay Open In EPS"):

Relay mode 2 (Relay Close In EPS) switches the contact in the opposite direction, i.e. in the on-grid mode there is no voltage, in the EPS mode there is voltage.

64

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS Generator charging Please refer to below diagram for connecting a generator:
The settings are explained in the menu structure.
5.9.7 Communication power supply
The power supply can be used for the external power supply, or for the switching contact. Max. 400 mA / 5 W.
5.9.8 CT Interface
For configurations according to System A, CTs are directly connected to the inverter without an energy meter. These CTs must be purchased separately and need to have a max. current rating of 100 mA at the inverter connection. Please refer to the table below for the specific PIN connections.

HYD 5-20KTL-3PH

65

Pin

Definition

1

Ict_R-

2

Ict_R+

3

Ict_S-

4

Ict_S+

5

Ict_T-

6

Ict_T+

ELECTRICAL CONNECTIONS
Function Phase R ­ (Phase L1 -) Phase R + (Phase L1 +) Phase S ­ (Phase L2 -) Phase S + (Phase L2 +) Phase T ­ (Phase L3 -) Phase T + (Phase L3 +)

Follow below steps to install the CTs.
1. Fix the cables on the terminals according to above table, and put the connector housing over the terminals.

2. Connect and lock the connector by turning it clockwise.

66

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS 5.9.9 Link Port
In systems with multiple inverters, you can connect the devices in a Master/Slave configuration. In this configuration, only one energy meter is connected to the Master inverter for the system control.

 The first and last inverter need to be connected with the 8 Pin connection terminals!
Pin Connections

Pin

Definition

Function

1

IN_SYN0

Synchronising signal 0

2

CANL

CAN low data

3

SYN_GND0

Synchronising signal GND 0

4

CANH

CAN high data

HYD 5-20KTL-3PH

67

ELECTRICAL CONNECTIONS

5

IN_SYN1

Synchronising signal1

6

SYN_GND1

Synchronising signal GND 1

7

SYN_GND2

Synchronising signal GND 2

8

IN_SYN2

Synchronising signal 2

Installation 1. Connect and lock the connector by turning clockwise:

68

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS 5.9.10 DRMs/Logic interface
The DRMs/Logic interface is used to control the inverters feed-in or purchases power by external signals, usually provided from grid operators with ripple control receivers or other means. The DRM0 can be used for a switch off signal from external grid protection devices. The logic interface pins are defined according to different standard requirements. Please consider the following PIN assignment.

Connector inverter

RJ45 Cable (clip is below)

Please follow below installation steps. 1. Press the wire terminals in colour sequence:
2. Route the cable terminal through the cable gland and insert the communication cable into the RJ45 connector.

HYD 5-20KTL-3PH

69

ELECTRICAL CONNECTIONS 3. Lock the connector by turning clockwise:

DRMs for AS/NZS 4777.2:2015 and AS/NZS 4777.2:2020

Also known as Inverter Demand Response Modes (DRMs).

The inverter recognises all supported Demand Response commands and

initiates the reaction within two seconds. The inverter will continue to

respond while the mode remains asserted.

Supported DRM commands: DRM0, DRM5, DRM6, DRM7, DRM8.

Pin

Colour

Function

1

orange/white

DRM1/5

2

orange

DRM2/6

3

green/white

DRM3/7

4

blue

DRM4/8

5

blue/white

DRM0

6

green

RefGen

7

brown/white

8

brown

Internally shorted

70

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

Demand response modes (DRMs)

Demand response mode

Real current limit (referenced to inverter rated per
phase current)

DRM0

0

Reactive current limit (referenced to inverter rated per phase current)
0

Switching time limit
2 s

DRM 1 DRM 2 DRM3 DRM4 DRM5 DRM6 DRM7 DRM8

Import =0 Import<50% Import<75% Not limited Generate=0 Generate<50% Generate<75% Not limited

0

2 s

As per Clauses 5.5,6.2 and DRM 3 and 2 s
DRM 7

Within 5%of set-point per Clause 6.2

2 s

As per Clauses 5.5,6.2 and DRM 3 and 2 s
DRM 7

0

2 s

As per Clauses 5.5,6.2 and DRM 3 and

DRM 7

2 s

Within 5%of set-point per Clause 6.2

2 s

As per Clauses 5.5,6.2 and DRM 3 and 2 s
DRM 7

 For DRM 0, DRM 1 and DRM 5, current draw due to sensing and DRED circuits is allowable (see Clause 7.2).

Logic interface for VDE-AR-N 4105:2018-11 This function serves to control and/or limit the output power of the inverter. The inverter can be connected to a radio ripple control receiver in order to dynamically limit the output power of all inverters within the system.

The inverter is preconfigured on the following power levels:

HYD 5-20KTL-3PH

71

Pin

Name

1

L1

2

L2

3

L3

4

L4

6

G

ELECTRICAL CONNECTIONS

Inverter
Relay 1 input Relay 2 input Relay 3 input Relay 4 input
Ground

Radio ripple control receiver
K1 - output relay 1
K2 - output relay 2
K3 - output relay 3
K4 - output relay 4
Relay, common ground

Logic interface for EN50549-1:2019 The active power output can be ended within five seconds following a command to the input interface.

Functional description of the terminal

Pin

Name

Inverter

Radio ripple control receiver

1

L1

Relay 1 input

K1 - output relay 1

6

G

Ground

Relay, common ground

The inverter is preconfigured on the following power levels. Relay status: Closing is 1, opening is 0

72

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

L1

Active power

1

0%

0

100%

Power drop rate < 5 seconds /

Cos () 1 1

5.10 Feed-in limitation function
The feed-in limitation function can be used to limit the power fed back into the grid. For this function, a power measurement device must be installed according to system A, B, or C.

Feed-in limitation: The sum of the feeding-in phases must not exceed the set power limitation value. The power of phases drawing power from the grid is disregarded here.

3-phase limit: The sum of the feed-in power of all three phases must not exceed the set power limit value. This setting is suitable for balancing metering, as is common in Germany, for example.

 For the 3-phase limit setting, the current sensors must be correctly assigned to phases L1, L2 and L3 on the electricity meter!
 If communication with the smart meter is interrupted, the inverter limits its output power to the set power limit value.
5.11 System monitoring
The HYD 5-20KTL-3PH inverters provide various communication methods for the system monitoring: RS485 or WiFi stick (standard), or Ethernet stick (optional).
5.11.1 RS485
You can connect RS485-linked devices to your PC or a data logger via an RS485 USB adapter. Please refer to the pin assignment in paragraph 5.9.2.

HYD 5-20KTL-3PH

73

ELECTRICAL CONNECTIONS
 The RS485 line may not be any longer than 1000 m  Assign each inverter its own modbus address (1 to 31) via the LCD
display

RS485

RS485

RS485

RS485/USB

5.11.2 WiFi, Ethernet stick
When you have installed the stick logger, the inverters can directly upload your operating, energy and alarm data in the SolarMAN monitoring portal.

5.12 Installation of the WiFi, or Ethernet stick
1. Remove the protective cap from the USB interface. 2. Install the WiFi/Ethernet stick. 3. Tighten the connecting nut.

74

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

5.12.1 Configuration of the WiFi stick via the web browser
Preparation: The WiFi stick is installed in accordance with the previous section and the SOFAR inverter must be in operation. Carry out the following steps in order to configure the WiFi stick: 1. Connect your PC or smartphone with the WiFi network of the WiFi stick.
The name of this WiFi network is "AP", followed by the serial number of the WiFi stick (see rating plate). When you are prompted for a password, you can find it on the label of the WiFi stick (PWD). 2. Open an Internet browser and enter the address 10.10.100.254. 3. Recommended browsers: Internet Explorer 8+, Google Chrome 15+, Firefox 10+ 4. Enter the username and password, which are both set to "admin" by default. The "Status" page will be opened. 5. Click on the "Wizard" in order to configure the WiFi stick for Internet access.  The WiFi stick begins to send data to SolarMAN.
Register your system at the website home.solarmanpv.com. For this, enter the serial number found on the stick logger. Installers use the portal at pro.solarmanpv.com

HYD 5-20KTL-3PH

75

ELECTRICAL CONNECTIONS 5.12.2 Setting up the WiFi stick with the app
To download the app, search for "SOLARMAN" in the Apple or Google Play store, or use the following QR codes:  SOLARMAN Smart (for end customers):
 SOLARMAN Business (for installers):

Configuration steps 1. After starting the app, register as a new user or enter the current
solarMAN access data. 2. Create a new system and save the system data. 3. Scan the barcode of the stick logger to assign an inverter to the system. 4. Go to the newly created system in order to configure the stick logger
(device/logger) 5. Press the button on the WiFi stick for 1 second to activate the WPS mode
of the stick so that the smartphone can be connected to the WiFi stick. 6. Now, select your local WiFi network for Internet access and enter your
WiFi password. 7. The WiFi stick is configured with the access data.

76

HYD 5-20KTL-3PH

ELECTRICAL CONNECTIONS

WiFi stick status

The LEDs on the WiFi stick provide information regarding the status:

LED

Status

Description

NET COM READY

Communicatio n with the router
Communicatio n with inverter
Logger status

On: Connection to server successful Flashing (1 sec.): Connection to router successful Flashing (0.1 sec.): WPS mode active Off: No connection to router Flashing (1 sec.): Communication with inverter On: Logger connected to inverter Off: No connection to inverter Flashing (1 sec.): Normal status Flashing (0.1 sec.): Reset running Off: Error status

Reset button Keystroke 1 sec. 5 sec. 10 sec.

Description WPS mode
Restart Restart (reset)

5.12.3 Setting up the Ethernet stick
The Ethernet stick is delivered with DHCP as standard, so it automatically gets an IP address from the router. If you wish to set up a fixed IP address, connect a PC to the Ethernet stick and open the configuration page via the web address 10.10.100.254.

HYD 5-20KTL-3PH

77

COMMISSIONING THE INVERTER
6 Commissioning the inverter
6.1 Safety test before commissioning
NOTICE
Check the voltage range  Ensure that the DC and AC voltages are within the permissible range
of the inverter.
6.2 Double Check
Please ensure that the inverter and all the wiring are installed correctly, securely, and reliably, and that all environment requirements are met.
1. Inverter is firmly fastened to the mounting bracket on the wall. 2. PV+/PV- wires are firmly connected, polarity and voltage are correct. 3. BAT+/BAT- wires are firmly connected, polarity and voltage are correct. 4. DC isolator is correctly connected between battery & inverter, DC isolator:
OFF. 5. GRID / LOAD cables are firmly / correctly connected. 6. AC circuit breaker is correctly connected between inverter GRID port &
GRID, circuit breaker: OFF. 7. AC circuit breaker is correctly connected between inverter LOAD port &
critical load, circuit breaker: OFF. 8. For lithium battery, please ensure that the communication cable has
been correctly connected. 9. For the lead-acid battery, please ensure that the NTC wire has been
correctly connected.

78

HYD 5-20KTL-3PH

COMMISSIONING THE INVERTER
6.3 Starting the inverter
Please follow below steps to switch the inverter ON. 1. Make sure there's no power generation in inverter from grid. 2. Turn ON DC switch. 3. Switch ON the battery. Turn ON DC isolator between battery & inverter. 4. Turn ON AC circuit breaker between the inverter GRID port & GRID. 5. Turn ON AC circuit breaker between the inverter LOAD port & critical
load. 6. Inverter should start to operate now.

6.4 Initial setup

You need to set the following parameters before inverter starts to operate.

Parameter

Note

1. Language setting 2. System time setting 3. Safety parameter import
4. Set the input channel Bat Channel1 Bat Channel2
5. Set battery parameters

The default is English
If you are connected to the server or using the App, the time is set to the local time automatically
You need to read the Country Code setting from a USB drive. Alternatively, the mobile app "Sofar View" can be used for this setting, if you are logged in as a validated installer
With the Input Channel Configuration you define if PV and / or batteries are connected and in what configuration. If an input channel is not used, select (Not use)
If a battery is connected to BAT1 input, select "Bat Input1", otherwise "Not Use" if a second battery is connected to BAT2 independently, select "Bat Input2" If one battery is connected in parallel to BAT1 and BAT2, select "Bat Input1", otherwise "Not Use"
Default values can be set according to the input channel configuration in

HYD 5-20KTL-3PH

79

COMMISSIONING THE INVERTER
Menu Advanced Settings ­ Battery Parameter: Select Battery Type Max. charging current (25A) Max. discharging current (25A) Discharge Depth80% The default operating mode is the Self-use Mode. EPS Mode, Unbalanced Support, Anti-Reflux Mode, IV-Curve Scan and Logic interface are disabled.
6.4.1 Configuring the battery setup
The HYD 5-8KTL-3PH models have one battery input (max. current 25 A). The HYD 10-20KTL-3PH models have two battery inputs (max. current 25 A / 25 A). Battery inputs can be connected and set in parallel mode to reach 50 A / 70 A.
6.4.2 Configuring Parallel Inverter System
To increase the system's EPS and grid power, the HYD 5-20KTL-3PH can be parallelly connected at the Grid port and the EPS port. For the communication setup, please follow the following steps: 1. Set the Master unit 2. Set the Slave units
 Each inverter must have a unique parallel address Setting the country code
 Different distribution network operators in various countries have differing requirements for the grid connection of grid-coupled PV inverters.
 Ensure that you have selected the correct country code according to regional authority requirements, and consult a qualified electrician or employees of electrical safety authorities.

80

HYD 5-20KTL-3PH

COMMISSIONING THE INVERTER
 SOFARSOLAR is not responsible for the consequences of selecting the incorrect country code.
 The selected country code influences the device grid monitoring. The inverter continuously checks the set limits and, if required, disconnects the device from the grid.

 For an updated list of country codes according to the Firmware version, just you can check the document under this link: https://sofarsolar.jianguoyun.com/p/DeanPg4Q4c_MChi404MGIAA

For The Australian Market: For compliance with AS/NZS 4777.2:2020 please select from 002-000 Australia A (Australia Region A) 002-008 Australia B (Australia Region B) 002-009 Australia C (Australia Region C) Please contact your local grid operator for which option to select.
 By selecting 002-000 Australia A, 002-008 Australia B or 002-009 Australia C the power quality response mode and grid protection settings will be reset to their default values for Australia Region A, B, C respectively.

Default grid settings for different regions are shown in the following table:

Protective function

Protective function limit

Trip delay time

Maximum disconnection
time

Undervoltage 2(V<<)

70V

1s

2s

Undervoltage 1(V<)

180V

10s

11s

Overvoltage 1(V>)

265V

1s

2s

Overvoltage 2(V>)

275V

-

0.2s

HYD 5-20KTL-3PH

81

Underfrequency 1(F<)
Overfrequency 1(F>)

Region
Protective function limit value
Trip delay time
Maximum disconnection time Protective function limit value
Trip delay time
Maximum disconnection time

Australia A
47Hz
1s
2s

COMMISSIONING THE INVERTER

Australia B 47Hz

Australia C 45Hz

New Zealand
45Hz

1s

5s

1s

2s

6s

2s

52Hz -
0.2s

52Hz -
0.2s

55Hz -
0.2s

55Hz -
0.2s

Default volt-watt settings for different regions are shown in the following

table:

Region

Default value

VL2

VL1

VW1

VW2

Australia A
Australia B
Australia C

Voltage
Inverter output (P) % of Srated
Voltage
Inverter output (P) % of Srated
Voltage
Inverter output (P) % of Srated

207 20% 195 0% 207 20%

215 100%
215 100%
215 100%

253 100% 250 100% 253 100%

260 20% 260 20% 260 20%

Default volt-var settings for different regions are shown in the following table:

Region

Default value

VV1

VV2

VV3

VV4

Australia A

Voltage
Inverter reactive output (Q) % of Srated

207

220

240

258

44% supplying

0%

0%

60% sinking

82

HYD 5-20KTL-3PH

COMMISSIONING THE INVERTER

Region

Default value

VV1

VV2

VV3

VV4

Australia B

Voltage
Inverter reactive output (Q) % of Srated

205

220

235

255

30% supplying

0%

0%

40% sinking

Australia C

Voltage
Inverter reactive output (Q) % of Srated

215

230

240

255

44% supplying

0%

0%

60% sinking

HYD 5-20KTL-3PH

83

COMMISSIONING THE INVERTER
6.5 Smartphone app SOFAR View

The app is available for Android and iOS systems and allows for easy initial

setup as well as advanced configurations.

Download link:

iOS

Android

After switching on the inverter, the app finds the unit via Bluetooth under its serial number. The app password for the installation is 6868, for the end customer 8888.
 If the Bluetooth connection does not work, please carry out a firmware update of the inverter.

84

HYD 5-20KTL-3PH

OPERATION OF THE DEVICE
7 Operation of the device
This chapter describes the LCD and LED displays of the HYD 5K ... 20KTL-3PH inverter.
7.1 Control panel and display field
7.1.1 Buttons and display lights

Buttons Button

Name Back

Description Previous screen, enter menu

Up Down Enter

Select previous menu item, increase setting value
Select next menu item, decrease setting value
Enter Menu item, select next digit, confirm setting

HYD 5-20KTL-3PH

85

LEDs State
On-grid
Off-grid Alarm

OPERATION OF THE DEVICE

Colour Green Green (flashing) Green Green (flashing)
Red

State Normal Standby Normal Standby
Error

7.2 Standard display
The screen shows all relevant information of the inverter:

Press Up button, to show PV Information like voltage, power and frequency
Press Up button again to show Grid Output Information like voltage, power and frequency
Press Up button again to show Grid Information such as power and IMPORT PF
Press Up button again to show Load Information like Load Power
Press Up button again to show Battery Information(BAT1) like current, power, state of charge etc.

86

HYD 5-20KTL-3PH

OPERATION OF THE DEVICE Press Up button again to show Battery Information(BAT2) like current, power, state of charge etc.
7.3 Energy storage modes
The HYD 5-20KTL-3PH comes with several integrated energy management modes.
7.3.1 Self-use
In the Self-use mode, the inverter will automatically charge and discharge the battery according to the following rules:
If PV generation equals the load consumption (P < 100 W), the inverter won't charge or discharge the battery
If PV generation is larger than the load consumption, the surplus power is stored in the battery
If the battery is full or at maximum charging power, the excess power will be exported to the grid

HYD 5-20KTL-3PH

87

OPERATION OF THE DEVICE
If the PV generation is less than the load consumption, it will discharge the battery to supply power to the load.
If PV generation plus Battery discharge power is less than the load, the inverter will import power from the grid.

88

HYD 5-20KTL-3PH

OPERATION OF THE DEVICE
The priority of power supply: PV, Battery, Grid The priority of power consumption: Loads, Battery, Grid

 If it is not allowed to export power to the grid, an energy meter and/or CT needs to be installed, and the "feed-in limitation" function needs to be enabled.
7.3.2 Time-of-Use
With the Time-of-Use mode, the inverter can be set to charge the battery in defined intervals of time, date or weekday, depending on the State of Charge of the battery. Up to 4 rules (rule 0, 1, 2 and 3) can be set. If more than one rule is valid for any given time, the rule with the lower number is active. Each rule can be enabled or disabled.

In below example, the battery will be charged with 1 kW, if the SOC is below 70%, between 2 and 4 o'clock at night, from 22nd Dec till 21st March:

Set Time-of-use Mode

Rule 0:

Enabled / Disabled

From

To

SOC

02 h 00 m - 04 h 00 m

070%

Effective

date

Dec.22

-

Mar.21

Weekday

select

Mon. Tue. Wed. Thu. Fri. Sat. Sun.

If no rule applies, the Self-use Mode is active.

Charge 01000W

HYD 5-20KTL-3PH

89

7.3.3 Timing

OPERATION OF THE DEVICE

With the Timing Mode you can define fixed times of the day to charge or discharge the battery with a certain power. Up to 4 rules (rule 0, 1, 2 and 3) can be set. If more than one rule is valid for any given time, the rule with the lower number is active. Each rule can be enabled or disabled, also charging and discharging period for a rule can be enabled separately.

In below example, the battery will be charged with 2 kW between 22 and 4 o'clock at night, and discharged with 2,5 kW between 14 and 16 o'clock:

Timing Mode

Rule 0: Enabled / Disabled / Enabled charge / Enabled discharge

Charge Start

22 h 00 m

Charge End

05 h 00 m

Charge Power

02000 W

DisCharge Start

14 h 00m

DisCharge End

16 h 00m

DisCharge Power

02500 W

7.3.4 Passive
The passive mode is used in systems with external energy management systems. The inverter's operation will be controlled by the external controller using the Modbus RTU protocol. Please contact SOFAR if you need the Modbus protocol definition for this device.

90

HYD 5-20KTL-3PH

OPERATION OF THE DEVICE 7.3.5 Peak Shaving
Used to limit the maximum power priority purchased from the grid.The maximum purchasing power can be set in this mode. When the system preferentially buys more power from the grid than the set value,The battery starts discharging and stabilizes the system power at the set value. Application: Peak Shaving Mode allows the grid to supply power to the load first. Applicable to the occasions where electricity price is charged according to electricity consumption and the occasions where the power grid is weak. In the weak grid situation, batteries start only when the load power exceeds a certain value, which reduces the maximum power of the connecting point and prolongs the battery life.
7.3.6 Off-grid
When the SOC of the battery is sufficient and can be discharged, it is preferred to use the battery in off-grid load mode (even if the power grid exists). After the battery enters the state of power loss, it will be transferred to the power grid or generator for load, and the battery will be charged.
1. AC Source Grid charge: After the battery enters the state of power loss, it is transferred to the grid to carry the load and charge the battery. DG charge: After the battery enters the state of power loss, it is transferred to the generator to carry the load and charge the battery.
2. AC Charge AC Charge: The sum of the power input to the power grid or generator after battery loss and when charging the battery.
 When AC Source is set to DG charge, the generator can be started through Genset Mode in dry contact Control.

HYD 5-20KTL-3PH

91

OPERATION OF THE DEVICE
EODO: EPS Discharge Depth EPSbuffer: Safety Buffer Application: When the local power grid is unstable or generators are used.
7.3.7 Manual Genset
This mode activates manual recharging of the battery in the event of a grid failure via a power generator connected to AC GRID.
7.3.8 Feed-in Priority
In this mode, the PV system will prioritise the supply of power to the grid according to the set power after the loads have been satisfied, and will only charge the batteries when the grid supply target has been reached. Users need to pre-set the value of power they wish to deliver to the grid, and the system will intelligently allocate power accordingly. When the PV power generation is sufficient, the system will first protect the load power consumption, and the remaining power will be prioritised to meet the set grid power demand. If the actual power generation exceeds the set value, the excess will be charged for the battery; if the power generation is less than the set value, all the remaining power will be delivered to the grid, and the battery will not be charged at this time. When the PV power generation is insufficient, the system will be supplemented by the battery to meet the load power consumption gap. In this state, the inverter will not deliver any power to the grid, ensuring that local power demand is prioritised.

92

HYD 5-20KTL-3PH

OPERATION OF THE DEVICE
7.4 Menu structure
Press the button to
7.4.1 Main menu
1. System Settings 2. Advanced Settings 3. Energy Statistics 4. System information 5. Event list 6. Software update
7. Battery real-time Info

bring up the main menu. (only with the BTS battery system)

 The menu layout may vary according to different firmware versions.

7.4.2 "System Settings" menu

In this menu you can do the basic settings which are needed to operate the

device. 1. Language Settings

Sets the display language

2. Time

Sets the system time of the inverter

3. Safety Param.

Sets the country and grid code

4. Energy Storage Mode

(Battery channel is available and the inverter is not a slave.)

Select between Self-use mode (Standard), time-of-use mode, timing mode, passive mode. See "Storage Modes" chapter for details.

HYD 5-20KTL-3PH

93

5. Input Channel Config Bat Channel1 Bat Channel2
6. EPS Mode 7. Communication Addr.

OPERATION OF THE DEVICE
With the Input Channel Configuration you define if PV and / or batteries are connected and in what configuration.
If a battery is connected to BAT1 input, select "Bat Input1", otherwise "Not Use"
If a battery is connected to BAT1 input, select "Bat Input1", otherwise "Not Use"
Enable / Disable the emergency power supply mode (EPS). It is only available if a battery is connected
Enter the Modbus address (when several inverters require simultaneous monitoring), standard: 01 Baud Rate: The default baud rate is 9600

7.4.3 "Advanced Settings" menu
Password  Several settings require a password to be entered (the standard
password is 0001).

In this menu you can do advanced settings.

1. Battery Parameter

(Setting is only allowed if there is a battery channel.)
Set the battery parameters for Battery 1 and Battery 2. Depending on the selected Battery Type, more settings can be adjusted. See details below.

1.1. Battery 1 Battery Capacity (kWh) Battery address

Set the capacity of connected battery
(only for batteries with integrated BMS)

94

HYD 5-20KTL-3PH

OPERATION OF THE DEVICE
Nominal Battery Voltage (V) Battery Cell Type Max. charging current (A) Max. discharging current (A) Depth of Discharge (DOD)
on_gird DOD
off_grid DOD EPS Safety Buffer Enable Force Charge
Set Force Charge Time Forced recharge

Up to 4 battery addresses for each Battery Input Channel can be set. This is the CAN bus or Modbus ID of each battery stack connected to the Battery Input, depending on the bus type between inverter and the BMS.
Nominal DC voltage of the battery
(for inverter-integrated BMS)
Max. allowed charging current for the battery
Max. allowed discharging current for the battery
Max. allowed Depth of Discharge (DOD) for the battery. DOD of 80% means, a battery with 10 kWh capacity can be discharged to a minimum energy level of 2 kWh.
Max. Depth of Discharge (DOD) for grid-connected mode. Standard 80%.
When setting the BTS-5K battery discharge depth, the maximum limit is 90% to prevent the battery from being too low to recharge.
Depth of Discharge (DOD) for EPS mode. Standard: 80%
Standard:5%
Enable / Disable.
When the BTS-5K battery or GTX3000 battery is connected, if "Enable Forced Charge" is enabled, the inverter will forcibly charge until it is fully charged once a month according to the time set in "Set Forced Charge Time".
Define the time for the forced charge.
When connected to a BTS-5K battery, if the SOC for a month is less than 10%, the battery will be forced to charge to 10% SOC. When the SOC < 5% and the battery changes from sleep to normal state and the PV is stable online for 3 minutes or more, the battery will be forced to charge to 5% SOC.
When the GTX3000 battery is connected, if "Enable Force Charge Time" is enabled, the inverter will be

HYD 5-20KTL-3PH

95

1.2. Auto Configure Address 2. Battery Active
Auto Active Control
Force active 3. Set Feed-in Limit
Feed-in Limit PCC Limit Scheme Config

OPERATION OF THE DEVICE
forcibly charged once when the SOC of the battery falls below 8%.
When connecting other batteries, if SOC < (1-EOD)/2, the battery will be charged to SOC >= 1-EOD. If the BMS requests a recharge, the battery will be charged to 30%-31% stop.
Select "Auto configure address", you can see "Battery quantity" after entering, and you can configure the quantity by yourself.
(Only available for SOFAR battery
types.)
Enable / disable. If Automatic activation is enabled, the inverter will activate the battery when the inverter need to discharge or charge the battery according to the operational mode settings.
If automatic activation is disabled, the battery has to be activated manually by selection the "Force active" menu item.
Select "Force active" to activate a battery from standby mode.
Activates or deactivates the feed-in power function of the inverter and sets the maximum feed-in power. This function must be used together with an external current transformer or the smart meter. Details regarding this can be found in the "Communications interfaces" chapter of this manual
Disable: Do not use this function
Three phase limit: the sum of all phases is regulated (balancing counting as is common in Germany).
Feed-in Limit: the power of the feeding-in phases is limited.
PCC Limit bit: The PCC Limit Scheme Config function can be enabled by configuring it.
Device type: Sets whether the device type is a domestic or a non-domestic. (Domestic can be reset by "Reset flag bit", non-domestic into the state 3

96

HYD 5-20KTL-3PH

OPERATION OF THE DEVICE
4. IV Curve Scan Scan Control Scan Period Force Scan
5. Logic interface HYD 5-20KTL-3PH

(Low power state) cannot be reset within 4 hours.) current limit percent: Set the current limit for the current flowing to the GIRD. Lock enable bit: When the machine detects that the PCC point current exceeds the set current limit percentage and continues for a certain period of time, it will enter the low-power state. When the machine is set to the lock state, it needs to be manually reset to restore the anticounter-current state of the machine. (The Reset function is disabled after t he Reset flag bit is used for four times. )When the machine is set to the no lock state, the CLS returns to the normal state by itself as long as the machine detects that the PCC point current is below the current limit percentage for 1 minute. Reset flag bit: Reset the flag bit. When the status query is displayed as the fault state (you need to see the English display on the LCD), you can reset the flag bit to make the status become Normal state. Lock flag bit cleared: When lock enable bit is enabled, if the device is locked and cannot be reset, you need to enter password 5170 to clear the lock flag. status query: View the current status.(State 1: Normal state; State 2: Critical state; State 3: Low power state; State 4: Fault state)
(Only set with PV channel.) Cyclical scanning of the IV curve in order to find the global point of the maximum output. Advisable in the case of shaded solar generators
Enable / disable IV curve scan function
Set scan period in minutes
Manually start IV curve scanning
Activates or deactivates logical interfaces. Details regarding this can
97

6. Restore Factory Settings Clear energy Data Clear Events Restore Factory Settings
7. Parallel setting Parallel Control Parallel Primary-Replica Parallel Address Save
8. Reset Bluetooth 9. CT Calibration
10. witch On / Off
11. Unbalanced Support

OPERATION OF THE DEVICE
be found in the "Communications interfaces" chapter of this manual
Resets stored data in the inverter
Clears total power production
Clears historical events
Clears total power production and historical events
Defines configuration for parallel inverter operation (Master/Slave)
For inverters connected with Link port to each other, you set Parallel Control to "Enable"
One Inverter need to be set as Master (Primary), all other inverters need to be set to Slave (Replica)
Set each inverter with an individual parallel address. (It is an independent number from Modbus ID)
After changes, select "save" item to save the settings
Resets the Bluetooth interface of the inverter if the device is not found by the Sofar View App
This function is used to correct the direction and grid phase assignment of the CTs directly connected to the inverter. During CT Calibration, the inverter must be connected to a battery and the grid. It is recommended to turn off the load during calibration. If calibration fails, check if the battery can be charged/discharged correctly
The inverter can be switched on, switched off, set to standby or set to normal operating mode, which can be useful for installation or maintenance work
(After version V120002 it is possible to use this function in parallel.) Default setting: disabled In situations where the customer only wants to support the local loads or has a zero-export limit across all three

98

HYD 5-20KTL-3PH

OPERATION OF THE DEVICE
12. PCC Purchase Control
13. PCC power bias 14. EPS GFCI
NeutralPointGrounding
15. Dry Contact Control Disable Generators Mode RelayOpenIn EPS RelayCloseIn EPS

phases. When used in conjunction with the supplied three-phase energy meter and with this option set to "enable", the per phase output current of the inverter will respond independently. Important: for this function to operate properly, the phase on the energy meter must correlate to the corresponding phase when it is wired into the inverter.
PCC Buy Control: Control whether the PCC power control function is enabled. PCC Buy Power Control: Power upper limit, that is, the maximum power that can be purchased from the PCC. (When the load is greater than the maximum power purchased from the PCC, the load power priority is higher to meet the load power priority.)
Calibration for PCC power calculation.
Activates RCD type B monitoring in EPS mode (300 mA)
When using off-grid mode, ensure that neutral ground is enabled. For Australia, South Africa, and New Zealand, neutral ground is turned off by default, refer to 5.3 System Overview
(The inverter is not allowed to set for the slave machine.)
No use this function
can start and stop a generator
In EPS mode, the dry contact interface will output a 12V signal
In grid-tied mode, the dry contact interface will output a 12V signal

 The inverter (Available from hardware version V003) has built-in relays to control the short circuit of the load N line to ground when off-grid.

HYD 5-20KTL-3PH

99

OPERATION OF THE DEVICE

 When the inverter is off-grid and the load N line and PE line are shortconnected, if the power grid is restored and the load N line and PE line are still short-connected, leakage protection will be triggered and explosion hazard will not be caused.

7.4.4 "Energy Statistics" menu

Today Month Year Lifetime

Press Down button to move between items Shows PV, Load, Export, Import, Charge, Discharge Energy (kWh) for the selected period

7.4.5 "System Information" menu

1. Inverter Info Inverter Info (1) Inverter Info (2) Inverter Info (3) Inverter Info (4) Inverter Info (5) Inverter Info (6) Inverter Info (7)
2. Battery Info Bat1 Information (1)
Bat1 Information (2) Bat1 Information (3)

Serial number, Hardware Version, Power Level, Safety Firmware Version Software Version, Country, Country Code Version Bat Channel1, Bat Channel2, PV Channel1, PV Channel2 Energy Storage Mode, RS485 Address, EPS Mode, IV Curve Scan DRM0 Control, PF Time Setting, QV Time Setting, Power Factor Anti Reflux, Insulation resistance, Parallel Control, Unbalanced Support Battery Active
Battery Type, Discharge Depth EPS Safety Buffer The Start time and the End time of Force filling Battery Address

100

HYD 5-20KTL-3PH

OPERATION OF THE DEVICE Bat2 Information (1)
Bat2 Information (2)
Bat2 Information (3) 3. Safety Param.
Safety Param. (1) Safety Param. (2) Safety Param. (3) 4. debug Info bug info

Battery Type, Discharge Depth EPS Safety Buffer The Start time and the End time of Force filling Battery Address
Over- / under-voltage protection Over- / under-frequency protection 10 Min. overvoltage protection
DSP1 version, state1, state2, state3, state4, state5, state6

7.4.6 "Event List" menu

The event list is used to display the real time event recordings, including the total number of events and each specific ID no. and event time. The most recent events are listed at the top.
2. Event list

Current event

Show latest event

Event History

Show event history

Fault information

001 ID04 06150825
(display of the event sequence number, event ID number and time that the event takes place)

7.4.7 "Sofatware update" menu
The user can update the software via the USB flash drive. SOFAR will provide the firmware update when it is required.

HYD 5-20KTL-3PH

101

7.5 Firmware update

OPERATION OF THE DEVICE

 If you want to do a firmware update, please upgrade with PV input or grid status, the update will fail if only the battery is connected.
1. Insert the USB stick into the computer. 2. SOFAR will send the firmware update to the user. 3. Unzip the file and copy the original file to a USB stick. Attention: The
firmware update file must be in the "firmware" subfolder! 4. Press the "Back" on the main interface to enter the main menu page,
and select "2.Advanced Settings - Switch On/Off -Switch Off". Make the inverter shut down safely. 5. Insert the USB flash drive into the USB interface of the inverter. 6. Go to menu item "6.Software update" on the LCD display. 7. Enter the password (the standard password is 0715) and then select "Software Upgrade (PCS)". 8. The system will then successively update the main DSP, auxiliary DSP and ARM processors. Pay attention to the displays. 9. If an error message appears, please upgrade again.If this continues many times, contact technical support for help. 10. After the update is complete, Go to menu item "Advanced Settings Switch On/Off - Switch On" to make the inverter start up and run. 11. You can check the current software version in item "1.Inverter Info (2)" of the SystemInfo menu. Enter the password (the standard password is 0715) to see it.

102

HYD 5-20KTL-3PH

TROUBLESHOOTING HANDLING
8 Troubleshooting handling
8.1 Troubleshooting
This section contains information and procedures pertaining to the remedying of potential problems with the inverter. To carry out troubleshooting, proceed as follows:
 Check the warnings, error messages or error codes displayed on the screen of the inverter.
If no error information is displayed on the screen, check whether the following requirements have been fulfilled:  Has the inverter been set up in a clean, dry, well-ventilated area?  Is the DC switch set to ON?  Are the cables sufficiently dimensioned and short enough?  Are the input connections, output connections and the wiring all in good
condition?  Are the configuration settings for the relevant installation correct?  Are the display field and the communication cables correctly connected
and undamaged? Follow the steps below to view recorded problems: Press "Back" to enter the main menu in the normal interface. In the interface screen select "Event List", then press "OK" to enter events.

HYD 5-20KTL-3PH

103

8.1.1 Shutdown procedure

TROUBLESHOOTING HANDLING

If the inverter needs to be shut down for electrical inspection, please follow the following steps: 1. Press the "Back" on the main interface to enter the main menu page,
and select Advanced Settings - Switch On/Off - Switch Off. Make the inverter shut down safely.  after using the menu setting to shut down the inverter, the inverter
should be checked and reenergising, it still needs to be on the main menu page. Select advanced Settings - Switch On/Off- Switch On. start up to enable the inverter to start up and run. 2. Disconnect the AC circuit breaker connecting the inverter power grid port to the power grid. 3. Disconnect the AC breaker connecting the inverter load port to the emergency load. 4. Disconnect the PV side DC switch. 5. Turn off the battery and disconnect the DC switch between the battery and the inverter. 6. Wait for 5 minutes before checking the inverter.

8.1.2 Earth fault alarm
This inverter is compliant with IEC 62109-2 Clause 13.9 and AS/NZS 5033 for earth fault protection. If an earth fault alarm occurs, the error is displayed on the LCD screen, the red light illuminates and the error can be found in the error history log. When the inverter is connected to the battery system, when the battery system has ground fault/leak alarm in accordance with AS/NZS 5139, the inverter will also alarm. The alarm method is the same as above.

 In the case of devices equipped with a stick logger, the alarm information can be viewed on the monitoring portal and retrieved via the smartphone app.

104

HYD 5-20KTL-3PH

TROUBLESHOOTING HANDLING
8.2 Error list

8.2.1 Inverter error list

ID

Code Name Description

Solution

001 002 003
004
005

GridOVP GridUVP GridOFP
GridUFP
GFCI

The voltage of the power grid is too high The voltage of the mains is too low The mains frequency is too high
The mains frequency is too low
Charge Leakage Fault

If the alarm occurs occasionally, the possible cause is that the electric grid is abnormal occasionally. Inverter will automatically return to normal operating status when the electric grid's back to normal. If the alarm occurs frequently, check whether the grid voltage/frequency is within the acceptable range. If yes, please check the AC circuit breaker and AC wiring of the inverter. If the grid voltage/frequency is NOT within the acceptable range and AC wiring is correct, but the alarm occurs repeatedly, contact technical support to change the grid over-voltage, under-voltage, over-frequency, under-frequency protection points after obtaining approval from the local electrical grid operator.
Check for inverter and wiring.

008

IslandFault

Island protection fault

009010

GridOVPInsta nt1/2

Transient overvoltage of mains voltage 1/2

If the alarm occurs occasionally, the possible cause is that the electric grid is abnormal occasionally. Inverter will automatically return to normal operating status when the electric

HYD 5-20KTL-3PH

105

TROUBLESHOOTING HANDLING

ID

Code Name Description

Solution

grid's back to normal.

If the alarm occurs frequently, check

whether the grid voltage/frequency is

within the acceptable range. If yes,

please check the AC circuit breaker

and AC wiring of the inverter.

If the grid voltage/frequency is NOT

011

VGridLineFau Power grid line

lt

voltage error

within the acceptable range and AC

wiring is correct, but the alarm occurs

repeatedly, contact technical support

to change the grid over-voltage,

under-voltage, over-frequency,

under-frequency protection points

after obtaining approval from the

local electrical grid operator.

Internal faults of inverter, switch OFF

inverter, wait for 5 minutes, then

012

InvVoltFault

Inverter overvoltage

switch ON inverter. Check whether the problem is solved.

If no, please contact technical

support.

013

RefluxFault

Feed-in Limit function is faulty

014

VGridUnbalan unbalanced

ce

source voltage

027

PVLowImped PV- Low ground

ance

impedance

032

N-PE fault

Neutral ground fault

038

InvSoftStartF Inverter failed to

ail

output

039

ArcShutdown Arc shutdown

Alarm

protection

106

HYD 5-20KTL-3PH

TROUBLESHOOTING HANDLING

ID

Code Name Description

Solution

040

LowLightChk Low light

Fail

detection failed

041

RelayFail

Relay detection failure

Check the insulation resistance

Insulation

between the photovoltaic array and

042

IsoFault

resistance is too ground (ground), if there is a short

low circuit, the fault should be repaired in

time.

043

PEConnectFa ult

Earth fault

Check the PE conductor for function

044

InputConfigE rror

Incorrect input mode configuration

045 CTDisconnect CT error

046

ReversalConn ect

The battery is connected reversedly

Check the input mode (parallel/independent mode) Settings for the inverter. If not, change the input mode. Check that the wiring of the current transformer is correct.
Check whether the battery wiring is correct.

Master does not Check the parallel mode settings for

047 ParallelFault exist or is duplicate

the inverter. Check whether the wiring is correct.

For Inner BMS battery, make sure

that the battery NTC cable is properly

connected. Make sure the inverter is

Battery 049 TempErrBat temperature
error

installed where there is no direct sunlight. Please ensure that the inverter is installed in a cool/ wellventilated place. Ensure the inverter

is installed vertically and the ambient

temperature is below the inverter

temperature limit.

HYD 5-20KTL-3PH

107

TROUBLESHOOTING HANDLING

ID

Code Name Description

Solution

050055
057058

TempErrHeat Sink1-6
TempErrEnv1/ 2

Temperature error heat sink 16
Temperature error ambient temperature 1/2

For Inner BMS battery, make sure that the battery NTC cable is properly connected. Make sure the inverter is installed where there is no direct sunlight. Please ensure that the inverter is installed in a cool/ well-ventilated place. Ensure the inverter is installed vertically and the ambient temperature is below the inverter temperature limit.

059061

TempErrInv13

Module 1-3 Temperature protection

065

BusRmsUnba lance

Asymmetrical bus voltage RMS

The transient

066

BusInstUnbal value of the bus

ance

voltage is

Internal error of the inverter. Switch

unbalanced

off the inverter, wait 5 minutes and

The DC bus

then switch the unit on again.

voltage is too

If the error persists, contact technical

067

BusUVP

low during

mains

support.

connection

The DC bus

068

BusZVP

voltage is too

low

108

HYD 5-20KTL-3PH

TROUBLESHOOTING HANDLING

ID

Code Name Description

The PV input

069

PVOVP

voltage is too

high

070

BatOVP

Battery overvoltage

LLC Bus 071 LLCBusOVP overvoltage
protection

Inverter bus

072

SwBusRmsO voltage RMS

VP

Software

overvoltage

Inverter bus voltage 073 SwBusIOVP instantaneous Software overvoltage

Software

081

SwBatOCP

overcurrent protection of

the battery

082

DciOCP

Dci overcurrent protection

Solution Check whether the PV series voltage (Voc) is higher than the maximum input voltage of the inverter. If this is the case, adjust the number of PV modules in series. After the correction, the inverter automatically returns to its normal state. Check whether the voltage of the battery is higher than the maximum input voltage of the inverter. If this is the case, adjust the number of battery modules in series.
Internal error of the inverter. Switch off the inverter, wait 5 minutes and then switch the unit on again. If the error persists, contact technical support.
Internal error of the inverter. Switch off the inverter, wait 5 minutes and then switch the unit on again. If the error persists, contact technical support.

HYD 5-20KTL-3PH

109

TROUBLESHOOTING HANDLING

ID

Code Name Description

Solution

Instantaneous

083

SwIOCP

output current

protection

084

SwBuckBoost OCP

BuckBoost software sequence

085

SwAcRmsOC P

Output RMS current protection

086

SwPvOCPInst ant

PV overcurrent software protection

PV flows in 087 IpvUnbalance uneven
parallelism

088

IacUnbalance

Unbalanced output current

PV software

089

SwPvOCP overcurrent

protection

Balanced 090 IbalanceOCP current
protection

091

ResOver

Resonance protection

Software

092

SwAcCBCFau current limiting

lt

protection by

wave

PV branch

093

SwPvBranch OCP

software overcurrent (enabled by

default)

110

HYD 5-20KTL-3PH

TROUBLESHOOTING HANDLING

ID

Code Name Description

Solution

097

HwLLCBusOV P

LLC bus hardware overvoltage

Inverter bus 098 HwBusOVP hardware
overvoltage

099

HwBuckBoos tOCP

BuckBoost hardware overflows

Battery 100 HwBatOCP hardware
overflow

102

HwPVOCP

PV hardware overflows

Mains current is

too high and

103

HwACOCP has triggered

hardware

protection

105

MeterCommF ault

Communication fault with meter unit

Check communication to meter.

110112

Overload1-3

Overload protection 1-3

Please check whether the inverter is operating under overload.

Make sure that the inverter has been

installed in a cool and well-ventilated

The inverter has place without direct sunlight.

113

OverTempDe throttled due to

rating

too high a

Make sure the inverter is installed

temperature

vertically and the ambient

temperature is below the

temperature limit of the inverter.

Make sure that the mains frequency

114

FreqDerating

AC frequency is too high

and voltage are within the

permissible range.

HYD 5-20KTL-3PH

111

TROUBLESHOOTING HANDLING

ID

Code Name Description

Solution

116

VoltDerating

AC voltage is too high

Lightning

121

SpdFail(DC) Protection

Failure (DC)

Lightning

122

SpdFail(AC) Protection

failure (AC)

Internal error of the inverter. Switch off the inverter, wait 5 minutes and then switch the unit on again. If the error persists, contact technical support.

124

BatDchgProh The battery is

ibit

low

125

BatLowVoltS No battery

hut

protection

Please check if the battery voltage of the inverter is too low.

Internal error of the inverter. Switch Mains current is

129

PermHwAcO CP

too high and has caused an unrecoverable

hardware fault

off the inverter, wait 5 minutes and then switch the unit on again. If the error persists, contact technical

support.

Bus voltage is too high and 130 PermBusOVP has caused a non-recoverable fault

Permanent bus

131

PermHwBus hardware failure

OVP

due to

overvoltage

Permanent

133

PermEPSBat OCP

battery overcurrent error in EPS

mode

112

HYD 5-20KTL-3PH

TROUBLESHOOTING HANDLING

ID

Code Name Description

Permanent

134

PermAcOCPI error due to

nstant

transient

overcurrent

Permanent

135

PermIacUnba unbalanced

lance

output current

error

136

PermInvStart Fail

The soft startup of the inverter fails

Permanent

137

PermInCfgErr input mode

or

configuration

error

Permanent

138

PermDCOCPI input

nstant

overcurrent

error

Permanent

139

PermHwDCO input hardware

CP

overcurrent

error

140

PermRelayFai l

Permanent error of the mains relay

The bus voltage

is unbalanced

141

PermBusUnb and has caused

alance

an

unrecoverable

error

142

PermSpdFail( surge

DC)

protection

Solution
Check the MPPT input mode setting (parallel mode/independent mode) of the inverter and correct it if necessary.
Internal error of the inverter. Switch off the inverter, wait 5 minutes and then switch the unit back on. If the error persists, contact technical support.
Check if the weather is normal. Switch off the inverter, wait 5 minutes and then switch the unit back on. If the error persists, contact technical support.

HYD 5-20KTL-3PH

113

TROUBLESHOOTING HANDLING

ID

Code Name Description

Solution

143

PermSpdFail( surge

AC)

protection

The safety

152

SafetyVerFaul t

version is inconsistent with the internal

Check whether safety regulations comply with local standards and

safety version

import correct safety parameters.

SCI 153 SCILose(DC) communication Upgrade software
error (DC)

SCI

154

SCILose(AC) communication Upgrade software

error (AC)

Inconsistent 156 SoftVerError software
versions

Download the latest firmware from the website and launch the software update. If the error persists, contact technical support.

Make sure your battery is compatible

with the inverter.

Lithium battery CAN communication is

157-

BMS1-

1-4

160 4CommFault communication recommended. Check the

error

communication line or the

connection of the battery and the

inverter for errors.

162

RemoteShutd Remote

own

shutdown

The inverter is shut down remotely.

163

Drms0Shutd DRM 0

own

shutdown

169175

FanFault1-7 Fan 1-7 fault

BMS

177

BMS OVP overvoltage

alarm

The inverter is running with a Drms0 shutdown. Check if the corresponding fan of the inverter is running normally.
Internal error in the connected lithium battery. Switch off the

114

HYD 5-20KTL-3PH

TROUBLESHOOTING HANDLING

ID

Code Name Description

Solution

inverter and the lithium battery, wait

BMS

5 minutes and then switch the

178

BMS UVP

Undervoltage

components on again.

alarm

If the error persists, contact technical

support.

BMS High

179

BMS OTP

temperature

warning

BMS low

180

BMS UTP

temperature

warning

BMS overload

181

BMS OCP

warning during charging and

discharging

182

BMS Short

BMS Short circuit alarm

Please contact technical support.

Check the ambient temperature and

the battery temperature on the LCD.

186

BatDischarge HTP

Battery overtemperatur e protection

Switch off the inverter, wait 5 minutes and then switch the unit back on.

If the error persists, contact technical

support.

Low

187

BatDischarge LTP

temperature protection for battery

discharge

Battery

188

BatChargeHT charging

P

overtemperatur

e protection

HYD 5-20KTL-3PH

115

TROUBLESHOOTING HANDLING

ID

Code Name Description

Solution

189
190
401402

AFCICommLo se

The arc device communication is faulty

BatChargeLT P

Low temperature protection for battery charging

AFCI0/1

Arc pulling fault

Internal error in the connected lithium battery. Switch off the inverter and the lithium battery, wait 5 minutes and then switch the components on again. If the error persists, contact technical support. Check the ambient temperature and the battery temperature on the LCD. Switch off the inverter, wait 5 minutes and then switch the unit back on. If the error persists, contact technical support. Internal error in the connected lithium battery. Switch off the inverter and the lithium battery, wait 5 minutes and then switch the components on again. If the error persists, contact technical support.

8.2.2 Battery error list

ID

Name

Description

HS1HighTe 808 mpWarnin
g

Radiator 1 high temperature alarm

EnvHighTe 809 mpWarnin
g

Ambient high temperature alarm

Solution Check whether the number of batteries is set correctly. If the setting is correct, please contact technical support to upgrade software. Please make sure the battery is installed in a cool well-ventilated place. If The battery is installed correctly,

116

HYD 5-20KTL-3PH

TROUBLESHOOTING HANDLING

ID

Name

Description

StopChgWa Charging

813

rning

prohibition alarm

StopDchg 814
Warning

Discharging prohibition alarm

HS1OverTe 864
mpFault

Over temperature protection of radiator 1

Over temperature

OverTempF protection of

865

ault_Env

ambient

temperature

Internal

SciCommF

866

communication

ault

failure of battery

Can1

Can1Comm

867

communication

Fault

failure

SwBusInsta Bus software

872

ntOVP

overvoltage

SwBusInsta Bus software

873

ntUVP

undervoltage

SwBatInsta Battery software

874

ntOVP

overvoltage

SwBatInsta Battery software

875

ntUVP

undervoltage

SwBatInsta Battery software

876

ntOCP

overcurrent

Solution If the battery is almost fully, no action is required. Otherwise, please contact technical support. If the battery is almost empty, no action is required. Otherwise, please contact technical support.
Power off and wait for 2 hours. If the problem is not solved, please contact technical support.
If this fault occurs occasionally, wait a few minutes to see whether the problem is solved. If this fault occurs frequently, please contact technical support. If this fault occurs occasionally, wait a few minutes to see whether the problem is solved. If this fault occurs frequently, please contact technical support.
If this fault occurs occasionally, wait a few minutes to see whether the problem is solved. If this fault occurs frequently, please contact technical support.

HYD 5-20KTL-3PH

117

TROUBLESHOOTING HANDLING

ID

Name

Description

Solution

879 HwOCP

Hardware overcurrent

unrecoverB Permanent bus

880

usAvgOV

overvoltage

Permanent

unrecoverB

881

battery

atAvgUV

undervoltage

Permanent

unrecoverO

882

Instant

CPInstant

overcurrent

Restart the battery and wait for minutes. If the problem is not resolved, please contact technical support.

Permanent

unrecoverH

883

hardware

wOCP

overcurrent

unrecoverB Permanent short-

893

Restart the battery and wait for

usSCP

circuit protection

minutes. If the problem is not

Permanent

unrecoverB

resolved, please contact technical

894

battery activation

atActFail

support.

failed

Permanent bus

unrecoverB

895

reverse

usRPP

connection

Check whether the wiring is correct and restart the battery. If the problem is not resolved, please contact technical support.

BMS overvoltage

BMSOVOC

899

and overcurrent

P

fault

If this fault occurs occasionally, wait a

Battery average

SwBatAvgO

few minutes to see whether the

900

overcurrent

CP

problem is solved. If this fault occurs

protection

frequently, please contact technical

SwAvgOverl Average overload

901

support.

oadP

protection

SwBusInsta Bus software

902

ntOCP

overcurrent

118

HYD 5-20KTL-3PH

TROUBLESHOOTING HANDLING

ID

Name

Description

Software CBC

903 SwCBCOCP overcurrent

protection

905 BusSCP

Start up short circuit protection

SwBusAvg 906
UVP

Bus average undervoltage

Solution
Restart the battery and wait for minutes, Check if the power line is short circuited ,If the problem is not resolved, please contact technical support. Restart the battery and wait for minutes. If the problem is not resolved, please contact technical support.

8.3 Maintenance
Inverters do not generally require daily or routine maintenance. Before carrying out cleaning, ensure that the DC switch and AC circuit breaker between the inverter and power grid have been switched off. Wait at least 5 minutes before carrying out cleaning.
8.3.1 Cleaning the inverter
Clean the inverter using an air blower and a dry, soft cloth or a soft bristle brush. Do NOT clean the inverter with water, corrosive chemicals, cleaning agents etc.
8.3.2 Cleaning the heat sink
In order to help guarantee correct long-term operation of the inverter, make sure that there is sufficient space for ventilation around the heat sink. Check the heat sink for blockages (dust, snow etc.) and remove them if present. Please clean the heat sink using an air blower and a dry, soft cloth or a soft bristle brush. Do NOT clean the heat sink with water, corrosive chemicals, cleaning agents etc.

HYD 5-20KTL-3PH

119

TECHNICAL DATA

9 Technical Data

Model
DC input (PV)
Recommended Max. PV input power
Max. input voltage

HYD
5KTL3PH

HYD
6KTL3PH

HYD
8KTL3PH

HYD
10KTL -3PH

HYD
10KTL -3PHA

HYD
15KTL -3PH

HYD
20KT L-3PH

7500Wp
 6000W p/
6000Wp 

9000Wp
 6600W p/
6600Wp 

12000Wp
 6600W p/
6600Wp 

15000Wp  7500Wp / 7500Wp
1000V

15000Wp  7500Wp /
7500Wp

22500Wp  11250Wp /
11250Wp

30000Wp
 15000W p/
15000Wp 

Start-up voltage
Rated input voltage
MPPT operating voltage range
Number of MPPT
Max inverter back feed current to array
Max. number of input strings per MPPT
Max. input current per MPPT
Max. short-circuit current per MPPT
AC output (on grid)
Rated output power
Rated output current
Rated grid voltage
Rated grid frequency
Max. output apparent power
Max. current output to grid
Max. AC current from grid
Output inrush current
Output fault current
Output overcurrent protectionRMS

1/1 12.5A/12.5A
15A/15A

200V 600V 180V~960V
2 0A

2/2 25A/25A 30A/30A

5000W
7.2A
5500 VA 8A 15A
10A

6000W
8.7A
6600 VA 10A 17A
12A

8000W

10000W

10000W

11.6A

14.5A

14.5A

3/N/PE, 230/400Vac

8800 VA
13A

50/60Hz
11000 VA
16A

10000 VA
16A

24A

29A

29A

100A/1s

80A/5s

15A

18A

18A

15000W
21.7A
16500 VA 24A 44A
26A

20000 W
29.0A
22000 VA 32A 58A
34A

120

HYD 5-20KTL-3PH

TECHNICAL DATA

Model
Output overcurrent protectionMAX
THDi

HYD 5KTL3PH
20.4A

Power factor

Battery Parameters

Battery type
Battery voltage range
Number of battery input channels
Max.charge/ discharge power
Max.charge/ discharge current
BMS communication mode
AC output (off grid)
Rated output power
Rated output current
Rated output voltage
Rated output frequency
Max. output apparent power
Peak output apparent power, time
Max. output current
THDv(@ linear load)
Switching time

1
5000W 25A
5000W
7.2A
5500VA 10000VA,
60s
8A

Efficiency
Max. MPPT efficiency
Max. efficiency
European efficiency

HYD 6KTL3PH 22.5A
1
6000W 25A
6000W
8.7A
6600V A
12000V A, 60s
10A
98% 97.5%

HYD 8KTL3PH
33.1A

HYD 10KTL -3PH
40.7A

HYD 10KTL -3PHA
40.7A

<3% 1 default (+/-0.8 adjustable)

HYD 15KTL -3PH
61.1A

HYD 20KT L-3PH
81.5A

Lithium-ion & Lead-acid 180V~800V

1

2

2

8000W

10000W

10000W

50A

50A

25A

(25A/25

(25A/25

A)

A)

CANRS485

2
15000W
50A (25A/25
A)

2
20000 W
50A (25A/25
A)

8000W

10000W

10000W

11.6A

14.5A

14.5A

3/N/PE, 230/400Vac

8800V A
16000V A, 60s
13A

50/60Hz
11000VA
20000V A, 60s
16A

10000V A
20000V A, 60s
16A

<3%

<10ms

15000W
21.7A

20000 W
29.0A

16500V A
22000V A, 60s
24A

22000V A
22000VA, 60s
32A

99.9%

98.2% 97.7%

HYD 5-20KTL-3PH

121

Model
Max. efficiency of charging/dischargi ng [1]
Protection

HYD
5KTL3PH

DC switch
PV reverse connection protection
Battery reverse connection protection
Output short circuit protection
Output overcurrent protection
Output overvoltage protection
Insulation impedance detection
Residual current detection
Anti-island protection
Surge protection

General Parameters
Operating temperature range
Relative humidity range
Max. operating altitude
Standby selfconsumption [2]
Topology
Installation method
Max. number of parallel units [3]
Degree of protection
Dimensions (W*H*D)
Cooling mode

HYD 6KTL3PH 97.6%
Natural

HYD
8KTL3PH

HYD
10KTL -3PH

TECHNICAL DATA

HYD
10KTL -3PHA

HYD
15KTL -3PH

97.8%

HYD
20KT L-3PH

Yes Yes Yes Yes Yes Yes Yes Yes Yes PV:Tyep AC:Type 
-30~60 5%~95% <4000m <20W
Transformerless Wall Mounted
6 pcs IP65 586.6*515*261.2mm
Forced airflow

122

HYD 5-20KTL-3PH

TECHNICAL DATA

Model Weight

HYD
5KTL3PH

HYD 6KTL3PH
33kg

HYD
8KTL3PH

HYD
10KTL -3PH

HYD
10KTL -3PHA

HYD
15KTL -3PH

37kg

HYD
20KT L-3PH

Communication

RS485/CAN/WiFi, Optional:Ethernet/4G

Display Standard

LCD & Bluetooth+APP
EN61000-1, EN61000-2, EN61000-3, EN61000-4, EN61000-4-16, EN61000-4-18, EN610004-29IEC62109-1, IEC62109-2, NB-T32004/IEC62040-1AS/NZS 4777, VDE V 0124-100, V0126-1-1, VDE-AR-N 4105, CEI 0-21/CEI 0-16, C10/11, EN50438/EN50549, G83/G59/G98/G99, UTE C15-712-1, UNE206 007-1

[1] Battery-AC maximum efficiency of battery charge and discharge [2] Standby loss at rated input voltage [3] Maximum number of parallel machines of the same model

HYD 5-20KTL-3PH

123

HYD 5-20KTL-3PH

124



References

Microsoft Word 2021 Microsoft Word 2021