User Manual for SOFAR models including: 5KTL-3PH, 6KTL-3PH, 8KTL-3PH, 10KTL-3PH, 10KTL-3PH-A, 15KTL-3PH, 20KTL-3PH, HYD 5-20KTL-3PH Three Phase Hybrid Inverter, HYD 5-20KTL-3PH, Three Phase Hybrid Inverter, Phase Hybrid Inverter, Hybrid Inverter, Inverter
In this configuration, the battery unit can be added later. ... 21/CEI 0-16, C10/11, EN50438/EN50549,. G83/G59/G98/G99, UTE C15-712-1 ...
File Info : application/pdf, 128 Pages, 5.79MB
DocumentDocumentABOUT THIS MANUAL Shenzhen SOFARSOLAR Co., Ltd. 11/F, Gaoxinqi Technology Building, District 67, XingDong Community, XinAn Street, Bao'An District, Shenzhen, China Email: service@SOFAR.com Web: www.sofarsolar.com Document number Issue 26 | 5.2025 English CONTENT CONTENT 1 About this manual 1 1.1 Copyright declaration 1 1.2 Presentation of warnings 2 1.3 Presentation of action instructions 3 1.4 Note 3 2 Basic safety information 4 2.1 Safety information 4 2.2 Symbols and signs 8 3 Product features 11 3.1 Product information 11 3.2 Product dimensions 12 3.3 Labelling on the device 13 3.4 Functional features 13 3.5 Application modes 14 3.6 Connecting GTX 3000-H batteries (AMASS) 20 3.7 Connecting BTS 5K batteries 21 4 Installation 23 4.1 Installation information 23 4.2 Installation procedure 24 4.3 Examination before installation 24 4.4 Connections 27 4.5 Tools 28 4.6 Installation Environment Requirements 29 4.7 Installation location 29 4.8 Unpacking the inverter 31 4.9 Installation of the inverter 32 5 Electrical connections 34 5.1 Safety instructions 34 5.2 Wiring overview 37 HYD 5-20KTL-3PH I ABOUT THIS MANUAL 5.3 System overview 38 5.4 Electrical connection 46 5.5 Connecting the PE cables 46 5.6 Connecting the DC lines for the PV modules and battery 47 5.7 Connecting the AC power cables 51 5.8 AC connector installation 52 5.9 Communication interfaces 55 5.10 Feed-in limitation function 73 5.11 System monitoring 73 5.12 Installation of the WiFi, or Ethernet stick 74 6 Commissioning the inverter 78 6.1 Safety test before commissioning 78 6.2 Double Check 78 6.3 Starting the inverter 79 6.4 Initial setup 79 6.5 Smartphone app SOFAR View 84 7 Operation of the device 85 7.1 Control panel and display field 85 7.2 Standard display 86 7.3 Energy storage modes 87 7.4 Menu structure 93 7.5 Firmware update 102 8 Troubleshooting handling 103 8.1 Troubleshooting 103 8.2 Error list 105 8.3 Maintenance 119 9 Technical Data 120 II HYD 5-20KTL-3PH ABOUT THIS MANUAL 1 About this manual This Installation and user manual (hereinafter referred to as the manual) describes the installation, electrical connection, commissioning, maintenance and fault elimination procedures of following products: HYD 5KTL-3PH, HYD 6KTL-3PH, HYD 8KTL-3PH, HYD 10KTL-3PH, HYD 10KTL-3PH-A, HYD 15KTL-3PH, HYD 20KTL-3PH. Carefully read this manual before use and retain it for future reference! Treat this manual as an integral component of the device. Keep this manual in close proximity to the device, including when it is handed over to another user or moved to a different location. This manual contains important safety information on installation, operation and maintenance of the device. Read and observe all given safety information. The products, services or features you purchased shall be subject to the company`s commercial contracts and terms. All or part of the products and services described in this document may not within the scope of your purchase. Unless additional terms and conditions in your contract, the company does not make any statement or guarantee on the contents of this document. 1.1 Copyright declaration The copyright of this manual is owned by SOFAR. It may not be copied neither partially nor completely by companies or individuals (including software, etc.) and must not be reproduced or distributed in any form, or with the appropriate means. SOFAR reserves the right to final interpretation. This manual may be amended following feedback from users or customers. Consult our website at: https://www.SOFAR.com for the latest version. HYD 5-20KTL-3PH 1 1.2 Presentation of warnings ABOUT THIS MANUAL This manual contains information on safe operation and uses symbols to ensure the safety of persons and property as well as the efficient operation of the inverter. Read through the following symbol explanations carefully in order to prevent injury or property damage. 1.2.1 Warnsymbol The general danger symbol warns of risk of serious injury when used with the signal words CAUTION, WARNING, and DANGER. 1.2.2 Signalwords DANGER WARNING CAUTION NOTICE Indicates a hazardous situation which, if not avoided, will result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Indicates a danger that results in damage to or destruction of the inverter. 1.2.3 Sectional warnings Sectional warnings refer to a complete section and are structured as follows: WARNING Type and source of danger Consequences for non observance Avoiding the danger 1.2.4 Embedded warnings Embedded warnings are part of an action sequence and are placed right before the dangerous step. Combination of type/source of danger, consequences for non observance and avoiding the danger. 2 HYD 5-20KTL-3PH ABOUT THIS MANUAL 1.3 Presentation of action instructions This table shows the sequence of Action steps: Symbol Function This describes an action requirement 1. 2. This is the sequence of action steps that must be followed step by step 3. This is a single action step This describes the result of the action 1.4 Note Notes are presented in a grey bar. Provides tips essential to the optimal operation of the product. HYD 5-20KTL-3PH 3 BASIC SAFETY INFORMATION 2 Basic safety information If you have any questions or problems after reading the following information, please contact SOFAR This chapter details the safety information pertaining to the installation and operation of the device. 2.1 Safety information Read and understand the instructions within this manual and familiarise yourself with the relevant safety symbols in this chapter before beginning with the installation of the device and eliminating any faults. Before connecting to the power grid, you must obtain official authorisation from the local power grid operator in accordance with the corresponding national and state requirements. Furthermore, operation may only be carried out by qualified electricians. Please contact the nearest authorised service centre if any maintenance or repairs are required. Please contact your dealer to obtain information about your nearest authorised service centre. Do NOT carry out repairs on the device yourself; this may lead to injury or property damage. Before installing the device or carrying out maintenance on it, you must open the DC switch in order to interrupt the DC voltage of the PV generator. You can also switch off the DC voltage by opening the DC switch in the generation junction box. Not doing this may result in serious injury. 4 HYD 5-20KTL-3PH BASIC SAFETY INFORMATION 2.1.1 Qualified personnel Personnel tasked with the operation and maintenance of the device must have the qualifications, competence and experience required to perform the described tasks, while also being capable of fully understanding all instructions contained within the manual. For safety reasons, this inverter may only be installed by a qualified electrician who: -has received training on occupational safety, as well as the installation and commissioning of electrical systems -is familiar with the local laws, standards and regulations of the grid operator. SOFAR assumes no responsibility for the destruction of property or any injuries to personnel caused by improper usage. 2.1.2 Installation requirements Please install the inverter according to the information contained in the following section. Mount the inverter to a suitable object with a sufficient load-bearing capacity (e.g. walls, PV frames etc.) and ensure that the inverter is upright. Choose a suitable place for the installation of electrical devices. Ensure that there is sufficient space for an emergency exit which is suitable for maintenance. Ensure sufficient ventilation in order to guarantee an air circulation for the cooling of the inverter. 2.1.3 Transport requirements The factory packaging is specifically designed to prevent transport damage, i.e. violent shocks, moisture and vibrations. However, the device must not be installed if it is visibly damaged. In this case, notify the responsible transport company immediately. HYD 5-20KTL-3PH 5 2.1.4 Storage requirements BASIC SAFETY INFORMATION If the equipment is no longer to be put into service or is to be stored for a long period, make sure that the packaging is intact. Store the equipment in a well-ventilated indoor area that will not cause damage to the equipment components. Store in a clean and dry place, away from dust and moisture. Do not subject to rain or ground water erosion. Do not tilt or invert the box. When stacking, place the inverter carefully to avoid personal injury or equipment damage caused by tipping the equipment. The maximum number of stacking layers must not exceed 4 layers. Keep the storage temperature around -40-70. Relative humidity 5.95% no condensation. When restarting equipment that has been out of service for a long period of time, the equipment shall be thoroughly inspected. 2.1.5 Labelling on the device The labels must NOT be concealed by items and foreign objects (rags, boxes, devices, etc.); they must be regularly cleaned and kept clearly visible at all times. 2.1.6 Electrical connection Observe all applicable electrical regulations when working with the Solar inverter. DANGER Dangerous DC voltage Before establishing the electrical connection, cover the PV modules using opaque material or disconnect the PV generator from the inverter. Solar radiation will cause dangerous voltage to be generated by the PV generator! 6 HYD 5-20KTL-3PH BASIC SAFETY INFORMATION DANGER Danger through electric shock! All installations and electrical connections may only be carried out by trained electricians! NOTICE Authorisation for grid feed-in Obtain authorisation from the local power grid operator before connecting the inverter to the public power grid. Do not open the inverter or remove any of the labels. Otherwise, SOFAR shall assume no guarantee. 2.1.7 Operation DANGER Electric shock Contact with the electrical grid or the device's terminals may result in an electric shock or fire! Do not touch the terminal or the conductor which is connected to the electrical grid. Follow all instructions and observe all safety documents that refer to the grid connection. CAUTION Burning due to hot housing While the inverter is being operated, several internal components will become very hot. Please wear protective gloves! Keep children away from the device! HYD 5-20KTL-3PH 7 2.1.8 Repair and maintenance BASIC SAFETY INFORMATION DANGER Dangerous voltage! Before carrying out any repair work, first switch off the AC circuit breaker between the inverter and power grid, and then the DC switch. After switching off the AC circuit breaker and the DC switch, wait a minimum of 5 minutes before starting any maintenance or repair work. NOTICE Unauthorised repairs! Following the elimination of any faults, the inverter should be fully functional once more. Should any repairs be required, please contact a local authorised service centre. The internal components of the inverter must NOT be opened without the relevant authorisation. Shenzhen SOFAR Co., Ltd. assumes no responsibility for any resulting losses or defects. 2.1.9 End-of-life requirements When the inverter or any related components need to be disposed of, please ensure that the disposal is carried out in accordance with local waste handling regulations. Make sure to send the inverter to an appropriate disposal site in accordance with local regulations. 8 HYD 5-20KTL-3PH BASIC SAFETY INFORMATION 2.2 Symbols and signs CAUTION Beware of burning hazards due to the hot housing! While the inverter is in operation, only touch the display and the buttons, as the housing can become hot. NOTICE Implement earthing! The PV generator must be earthed in accordance with the requirements of the local power grid operator! For reasons of personal safety, we recommend that all PV module frames and inverters of the PV system are reliably earthed. WARNING Damage due to overvoltage Ensure that the input voltage does not exceed the maximum permissible voltage. Overvoltage may cause long-term damage to the inverter, as well as other damage that is not covered by the warranty! HYD 5-20KTL-3PH 9 2.2.1 Symbols on the inverter BASIC SAFETY INFORMATION Several symbols pertaining to safety can be found on the inverter. Please read and understand the content of these symbols before starting the installation. Symbol Description Residual voltage is present in the inverter! Before opening the inverter, you should wait five minutes to ensure that the capacitor has been fully discharged. Caution! Danger through electric shock Caution! Hot surface The product is compliant with EU guidelines Earthing point Please read the manual before installing the inverter Device degree of protection according to EN 60529 Positive and negative poles of the DC input voltage The inverter must always be transported and stored with the arrows pointing upward RCM (Regulatory Compliance Mark) The product meets the requirements of the applicable Australian standards. 10 HYD 5-20KTL-3PH PRODUCT FEATURES 3 Product features This chapter describes the product features, dimensions and efficiency levels. 3.1 Product information The HYD 5K-20KTL-3PH is a grid-coupled PV and energy storing inverter which can also supply energy in stand-alone operation. The HYD 5K-20KTL3PH has integrated energy management functions which cover a wide range of application scenarios. Figure 3-1 HYD 5K-20KTL-3PH inverter system diagram HYD 5K-20KTL-3PH inverters may only be used with photovoltaic modules which do not require one of the poles to be earthed. In normal operation, the operating current must not exceed the limits specified within the technical data. The selection of the optional inverter parts must be determined by a qualified technician who has good knowledge of the installation conditions. HYD 5-20KTL-3PH 11 3.2 Product dimensions PRODUCT FEATURES Figure 3-2 Dimensions 12 HYD 5-20KTL-3PH PRODUCT FEATURES 3.3 Labelling on the device Labelling must not be covered or removed! Figure 3-3 HYD 5K-20KTL-3PH appearance and label 3.4 Functional features The DC output generated by the PV generator can be used for both grid feed-in and battery charging. The battery can supply the energy to the grid or the consumer. The emergency current supply mode (EPS) can provide inductive loads such as air conditioning systems or refrigerators with an automatic switchover time of less than 10 milliseconds, and a temporary overload of up to 10% is possible. 3.4.1 Functions Two MPP trackers with 1.5-fold DC overload. Flexible switching between on-grid operation and energy storage operation. Maximum efficiency when charging and discharging the battery (97.8%). Up to 2 battery strings with a combined maximum charging and discharging current of 50 A. Wide battery input voltage range (180800 V). The EPS output can be connected to unbalanced loads. Up to 6 inverters can operate in parallel at the EPS connection and AC connection. HYD 5-20KTL-3PH 13 PRODUCT FEATURES Monitoring via RS485 and WiFi, optionally via Bluetooth. 3.4.2 Electrical block diagram Figure 3-4 Electrical schematic diagram 3.5 Application modes 3.5.1 Typical energy storage system A typical energy storage system with PV panels and battery unit(s), connected to the grid. Figure 3-5 Typical energy storage system 14 HYD 5-20KTL-3PH PRODUCT FEATURES 3.5.2 System without PV connection In this configuration, there are no PV panels connected and the battery is charged through the grid connection. Figure 3-6 System without PV connection 3.5.3 System without battery In this configuration, the battery unit(s) can be added later. Figure 3-7 System without battery HYD 5-20KTL-3PH 15 3.5.4 Back-up mode (off-grid) PRODUCT FEATURES When there is no grid connection, the PV panels and the battery will provide electricity to the critical load. Figure 3-8 Back-up mode (Off- Grid) 3.5.5 System with multiple inverters (520 kW) Up to 6 inverters can be connected in parallel, to the grid and EPS connections, resulting in an EPS output of up to 200 kVA. Figure 3-9 System with multiple inverter 16 HYD 5-20KTL-3PH PRODUCT FEATURES Multiple inverters connected in parallel shall be of the same power model with the same power and battery configuration. The energy meter or CTs are connected to the Master inverter. Control of all inverters takes place via the link cable. For the parallel switching of several devices, it is recommended to use a joint AC load break switch for the connected loads at the LOAD connection. For the parallel switching of several devices, it is recommended to use a joint AC load break switch for the connected loads at the GRID connection. In order to evenly distribute the loads among the inverters, the cable length between each output and the load must be the same. If the maximum apparent power of a load is greater than 110% of the inverter' s rated output, the device must not be connected via the AC LOAD terminal, but rather directly to the grid. HYD 5-20KTL-3PH 17 3.5.6 AC retrofit system PRODUCT FEATURES In this system configuration, the hybrid system for an already existing PV system is supplemented with a solar inverter of any brand. By installing a second smart meter, the PV production can be taken into account and used for charging the battery. The communication address of meter 1 should be set to 1. Similarly, the communication address of meter 2 should be set to 2. Figure 3-10 AC retrofit system 18 HYD 5-20KTL-3PH PRODUCT FEATURES 3.5.7 Unbalanced load By enabling the " Unbalanced load " option, the inverter compensates unbalanced loads either in EPS mode or on-grid mode. Figure 3-11 Unbalanced load (EPS mode) Figure 3-12 Unbalanced load (On Grid) HYD 5-20KTL-3PH 19 PRODUCT FEATURES 3.6 Connecting GTX 3000-H batteries (AMASS) Using SOFAR's own battery system GTX 3000-H is a way to build scalable battery systems. A GTX 3000H battery module has a nominal capacity of 2,5 kWh, allowing multiple configurations for one tower from 10 kWh (GTX 3000H4) to 25 kWh (GTX 3000-H10), The series battery is rated at 25A and the individual battery is rated at 51.2V. The HYD 5 ... 8KTL-3PH models have one battery input (max. current 25 A), and the HYD 10 ... 20KTL-3PH models have two battery inputs (max. current 25 A / 25 A). COM 16pin connector BAT1+ BAT1- BAT2+ BAT2CAN matching resister (Orange) PIN8 PIN7 P- (White orange) P+ Link Port In Link Port Out ...... PP+ ... Link Port In ... Link Port Out P- P+ Link Port In ...... Link Port Out PP+ .... Link Port In ... Link Port Out Battery Address: 0 Battery Address: 1...3 Battery Address: 4 Battery Address: 5...7 Battery pack 1 Battery pack 2...4 Battery pack 5 Battery pack 6...8 Figure 3-13 GTX 3000-H connecting in 4 Towers in Parallel If a battery input is unused, ensure to set this in the inverter's system settings, for example: System Settings Input Channel Config Bat Channel2 Not Used. Configuration of the battery setup should only be done when the inverter is in standby mode! Advanced Settings 10. Switch on / off Switch Off The battery inputs of different inverters should not be connected in parallel Each battery tower corresponds to a unique battery address. Each battery address can be configured from 0015 or not used 20 HYD 5-20KTL-3PH PRODUCT FEATURES The other battery parameters should be set according to the battery specifications 3.7 Connecting BTS 5K batteries Using SOFAR's own battery module BTS 5K is a way to build scalable battery systems. A BTS E5-DS5 battery system has a nominal capacity of 5.12 kWh, allowing multiple configurations for one tower from 5.12 kWh (BTS E5-DS5) to 20.48 kWh (BTS E20-DS5). The parallel battery are rated at 400V and the individual battery are rated at 7A. The HYD 5 ... 8KTL-3PH models have one battery input (max. current 25 A), and the HYD 10 ... 20KTL-3PH models have two battery inputs (max. current 25 A / 25 A). Below diagram is an example of how to connect the BTS battery system to SOFAR's HYD 5 ... 20KTL-3PH. Figure 3-14 System with BTS 5K battery HYD 5-20KTL-3PH 21 PRODUCT FEATURES Below is the schematic connection diagram of a system where the neutral line and ground line are connected together. Figure 3-15 System with BTS 5K battery in Australian N-Grid with N-EPS connected Configuration of the battery setup should only be done when the inverter is in standby mode! Advanced Settings 10. Switch on / off Switch Off If a battery input is unused, ensure to set this in the inverter's system settings, for example: System Settings Input Channel Config Bat Channel2 Not Used. The battery inputs of different inverters should not be connected in parallel Each battery tower corresponds to a unique battery address. "Auto Config. Address" will detect the number and addresses of the connected batteries automatically within 2-3 Minutes. In certain regions there are specific local safety requirements of the power grid. Ensure to comply with all local safety requirements. According to the Australian safety regulations, the neutral cables on the grid-connected side and EPS side must be connected together. Otherwise the EPS cannot be used. 22 HYD 5-20KTL-3PH INSTALLATION 4 Installation 4.1 Installation information DANGER Fire hazard Do NOT install the inverter on flammable material. Do NOT install the inverter in an area in which flammable or explosive material is stored. CAUTION Burning hazard Do NOT install the inverter in places where it can be accidentally touched. The housing and heat sink may become very hot while the inverter is being operated. NOTICE Weight of the device Take into account the weight of the inverter when transporting and moving it. Choose a suitable installation location and surface. Commission a minimum of two persons for the installation of the inverter. Do not set down the inverter overhead. HYD 5-20KTL-3PH 23 4.2 Installation procedure Mechanical installation is performed as follows: 1. Examine the inverter before installation 2. Prepare the installation 3. Select an installation location 4. Transport the inverter 5. Mount the rear panel 6. Install the inverter INSTALLATION 4.3 Examination before installation 4.3.1 Checking the external packaging materials Packaging materials and components may become damaged during transportation. Therefore, the external packaging materials must be examined before the inverter is installed. Check the external packaging material for damage, e.g. holes and cracks. If you discover any damage, do not unpack the inverter and contact the transport company and/or dealer immediately. It is recommended that the packaging material should be removed within 24 hours before installing the inverter. 4.3.2 Checking the delivery scope After unpacking the inverter, check that the delivery items are both intact and complete. In the event of any damage or missing components, contact the wholesaler. No. Image Description 01 Inverter HYD 5K ... 20KTL- 3PH 02 Wall bracket Quantity 5...8kW 10...20kW 1 1 24 HYD 5-20KTL-3PH INSTALLATION No. Image 03 04 05 Description PV+ input terminal PV- input terminal MC4 connector contact PV+ Quantity 5...8kW 10...20kW 2 4 2 4 2 4 06 MC4 connector contact PV- 2 4 07 BAT- input connector 1 2 08 BAT+ input connector 1 2 09 BAT- connector contact 1 2 10 BAT+ connector contact 1 2 11 2 M6 hexagon screw 12 M8*80 expansion screws 4 (wall bracket) 13 AC grid connection 1 14 AC load connection 1 15 Link port connection 1 HYD 5-20KTL-3PH 25 No. Image Description 16 8-pole terminal Terminal resistance for parallel system 17 DRMs connection 18 6-pole connector for CT 19 Three-phase smart meter INSTALLATION Quantity 5...8kW 10...20kW 1 1 1 1 20 1 COM communication cable 21 USB acquisition stick (WIFI) 1 22 Temperature sensor NTC 1 (5m) when using Lead-acid battery 23 1 Manual 24 1 Warranty card 25 1 Quality certificate 26 1 Test report, output test 27 2 Connector accessories 26 HYD 5-20KTL-3PH INSTALLATION 4.4 Connections CAUTION Damage during transportation Please check the product packaging and connections carefully prior to installation. Figure 4-1 HYD 5K-20KTL-3PH inverter overview Battery connection DC switch PV input terminals AC load connection AC grid connection DRMs Link port 1 Current sensor connection (CT) USB/WiFi Communication connection Link port 0 LCD display The number of Battery input terminals depends on the Rated Power: HYD 5K...8KTL-3PH 2pcs HYD 10K...20KTL-3PH 4pcs HYD 5-20KTL-3PH 27 INSTALLATION The number of PV input terminals depends on the Rated Power: HYD 5K...8KTL-3PH 4pcs HYD 10K...20KTL-3PH 8pcs 4.5 Tools Prepare the tools required for the installation and the electrical connection. No. Tool Model Function Hammer drill 01 Recommended drill diameter: Used to drill holes in the wall. 8mm 02 Screwdriver Wiring 03 Phillips screwdriver Used to remove and install the screws of the AC terminal 04 Removal tool Used to remove the PV , battery terminal 05 Wire stripper Used to strip the wire 06 6mm Allen key Used to turn the screw to connect the rear panel to the inverter 07 Crimping tool Used to crimp power cables 08 Multimeter Used to check the earthing 09 Marker Used for marking 10 Measuring tape Used to distances measure 28 HYD 5-20KTL-3PH INSTALLATION 11 12 Spirit level ESD gloves Used to align the wall bracket for the installer 13 Safety goggles for the installer 14 Anti-dust respiratory mask for the installer 4.6 Installation Environment Requirements Choose a dry, clean, and tidy place, convenient for installation. Ambient temperature range: -3060°C. Relative humidity: 0100% (non-condensed). The inverter shall be installed in a well-ventilated place. Do not place the inverter close to flammable or explosive materials. The AC overvoltage category of the inverter is category II. Maximum altitude: 4000m Pollution degree: 4 4.7 Installation location Choose a suitable position for the installation of the inverter. Ensure that the following requirements have been fulfilled: HYD 5-20KTL-3PH 29 INSTALLATION Figure 4-2 Installation Position of HYD 5-20KTL-3PH Minimum distances for individual HYD 5-20KTL-3PH inverters: Figure 4-3 Minimum distances for individual inverter Minimum distances for several HYD 5K-20KTL-3PH inverters: 30 HYD 5-20KTL-3PH INSTALLATION 1000 mm 300 mm 200 mm Figure 4-4 Minimum distances for several inverter 200 mm 4.8 Unpacking the inverter 1. Open the packaging and grip underneath the inverter at the sides with both hands. Figure 4-5 Moving the inverter 2. Lift the inverter out of the packaging and move it to its installation position. HYD 5-20KTL-3PH 31 INSTALLATION NOTICE Mechanical damage In order to prevent injuries and damage to the device, ensure that the inverter is kept balanced while it is being moved - it is very heavy. Do not place the inverter on its connections, as these are not designed to bear its weight. Place the inverter horizontally on the ground. When you place the inverter on the ground, place foamed material or paper underneath it in order to protect its housing. 4.9 Installation of the inverter 1. Hold the wall bracket in the desired place and mark the four holes. Put the wall bracket aside and drill the holes. 2. Guide the spread screw M8*80 into the hole vertically and ensure that its insertion depth is sufficient. 3. Align the wall bracket with the hole positions and fasten by tightening the spread screw with the nuts. Figure 4-6 Installing HYD 5-20KTL-3PH(a) 4. Place the inverter in the wall bracket and fasten it with the M6 hexagon screw. 5. You can secure the inverter to the wall bracket using a lock. 32 HYD 5-20KTL-3PH INSTALLATION Figure 4-7 Installing HYD 5-20KTL-3PH(b) HYD 5-20KTL-3PH 33 5 Electrical connections ELECTRICAL CONNECTIONS 5.1 Safety instructions This topic describes the electrical connections of the inverter HYD 5- 20KTL3PH. Read this section thoroughly and carefully before connecting the cables. DANGER Electrical voltage at the DC connections Ensure that the DC switch is OFF before establishing the electrical connection. The reason is that the electrical charge remains in the capacitor after the DC switch has been switched off. Therefore, at least 5 minutes must lapse before the capacitor has been electrically discharged. DANGER Electrical voltage PV modules generate electrical energy when exposed to sunlight, and this may present an electrical shock hazard. Therefore, cover the PV modules with an opaque sheet before connecting to the DC input power cable. DANGER Electrical voltage at the DC connections Wear rubber gloves and protective clothing (safety goggles and boots) when working on high voltage/high current systems such as inverter and battery systems. 34 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS NOTICE Qualification The installation and maintenance of the inverter must be carried out by an electrician. The open-circuit voltage of the modules connected in series must be lower than or equal to 1000 V. The connected PV modules must be compliant with IEC 61730 class A. Table 5-1 Relevant current parameters of each model Model Isc PV (absolute maximum) Maximum output overvoltage protection HYD 5KTL-3PH 8 A*3 HYD 6KTL-3PH 15 A/15 A 10 A*3 HYD 8KTL-3PH 13 A*3 HYD 10KTL-3PH 16 A*3 HYD 15KTL-3PH 30 A/30 A 24 A*3 HYD 20KTL-3PH 32 A*3 DC switch parameters Rated-Insulation Voltage Rated Impulse Withstand Voltage Suitability For Isolation Rated Operational Current (Ie) PV Utilization Category Rated Short Time Withstand Current (Icw) Rated Short-Circuit Making Capacity (Icm) Rated Making Capacity/Rated Breaking Capacity 1500V 8KV Yes 1100V/40A,800V/55A DC-PV2 0.76kA .1S 1.4kA 1.4kA HYD 5-20KTL-3PH 35 ELECTRICAL CONNECTIONS PV terminal parameters Rated-Insulation Voltage Rated Operational Current Protection Class Maximum Temperature Iimit 1000V 39A IP68 105 The DVC (decisive voltage classification) is the circuit voltage which constantly occurs between two arbitrary live parts during proper use in a worst-case scenario: DVC A B C Table 5-2 Description of limits for DVC Operating voltage limit(V) Ac voltage (RMS) Ac voltage (PK) Dc voltage (AVG) 25 (16) 35.4 (22.6) 60 (35) 50 (33) 71 (46.7) 120 (70) 1000 4500 1500 The values in brackets apply when the inverter is installed in a humid environment. Table 5-3 The decisive voltage class (DVC) Interface DVC PV input connection DVCC AC connection DVCC Battery connection DVCC Load connection DVCC USB/WiFi interface DVCA COM interface DVCA CT interface DVCA DRMs DVCA Link port DVCA 36 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS 5.2 Wiring overview Component Table 5-4 Cable description Description Recommended cable type + : Connect the positive cable of the lithium battery - : Connect the negative cable of the lithium battery Outdoor multicore copper cable (4...6mm²) Load Grid + : Connect the positive cable of the PV array - : Connect the negative cable of the PV array PV cable (4...6mm2) Connection method: male and female terminals are inserted into each other. Connection method: male and female terminals are inserted into each other. L1 L2 Outdoor multicore copper cable L3 5K...8KTL-3PH 6...10mm² N 10K...20KTL-3PH 8-10mm² PE L1 L2 Outdoor multicore copper cable 5K...8KTL- L3 3PH 6...10mm² N 10K...20KTL-3PH 8-10mm² PE HYD 5-20KTL-3PH 37 5.3 System overview ELECTRICAL CONNECTIONS There are different system configurations possible depending on the user's requirements, existing electrical infrastructure and local regulations. The distribution box must be configured to comply to the grid operator requirements. The inverter has an integrated AC relay to disconnect all phases and Neutral from the grid in case of grid fault or grid outage. The inverter's generation and feed-in limitation functions require the use of an external measurement device to obtain grid information. There are 3 system configurations: System A: direct measurement of energy with CTs (up to 300 A) System B: measurement of energy with energy meter + CTs (default) System C: measurement of energy with directly connected energy meter For System B, customers can choose different CTs based on the installation. The secondary current must be 5 A. To ensure neutral continuity, the neutral of AC GRID must be connected together with the neutral of AC LOAD and must not be interrupted by switch. If the Main Switch is used residual current protection device, it is recommended to choose type A protector for RCD with leakage current of 100mA or above (it is better to adjust according to the size of the system). If the grounding type of the grid power distribution system requires the ground wire and the neutral wire to be connected together, a short-circuit bar needs to be used to short-circuit the neutral wire and the ground wire in the power distribution where the inverter output is connected to the grid.And circuit breakers and fuses are not allowed to be installed on the grounding wire. 38 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS CAUTION In the following three situations, the system must be connected to the fuse first and then to the machine's input terminal: Lead-acid battery Lithium battery without BMS Multiple lithium batteries connected to one input HYD 5-20KTL-3PH 39 ELECTRICAL CONNECTIONS 5.3.1 System A: direct measurement with CTs Figure 5-1 Electrical connections (Plan A: CTs) 40 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS 5.3.2 System B: measurement with energy meter + CTs (default) Figure 5-2 Electrical connections (Plan B: Meter+CT) HYD 5-20KTL-3PH 41 ELECTRICAL CONNECTIONS 5.3.3 System C: measurement with directly connected energy meter Figure 5-3 Electrical connections (Plan C: Meter) 42 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS Energy Meter through CTs: Table 5-5 Smart Meter with CTs Technical Data Voltage AC 3×230/400 V Current 1.5(6) A Frequency 50/60 Hz Pulse 6400 imp / kWh Power accuracy Active Class 0.5S, Reactive Class 2 Directly connected Energy Meter: Table 5-6 Directly connected Smart Meter Technical Data Voltage AC 3×230/400 V Current 5(80) A Frequency 50/60 Hz Pulse 400 imp / kWh Power accuracy Active Class 1, Reactive Class 2 To obtain grid information via System A: Connect the wires according to the wiring method as shown in 5.3.1" System A: direct measurement with CTs", and enable Anti-Reflux Power function and set the Reflux Power limit on the menu interface of the machine. Refer to <7.4 Advanced settings 3. Anti Reflux> in this manual for specific operation methods. There are two situations when CT is installed. One is to connect in the correct CT direction. The direction should refer to the figure below, from the inverter to the power grid. One is the random CT direction, and then the use of CT calibration function for calibration. CT calibration procedures refer to this manual 7.4 Advanced settings>>9.CT calibration. To obtain grid information via Plan B or C: HYD 5-20KTL-3PH 43 ELECTRICAL CONNECTIONS Wiring according to the wiring method as shown in 5.3.2"System B: measurement with energy meter + CTs" or 5.3.3"System C: measurement directly connected energy meter", and enable Anti-Reflux Power function and set the Reflux Power limit on the menu interface of the machine. Refer to <7.4 Advanced settings 3. Anti Reflux> in this manual for specific operation methods. Only installers and distributors have the permission to use the Bluetooth APP for setting, enabling/disabling settings, and setting up the Reflux Power limit. Refer to <7.4 Advanced settings3. Anti Reflux> in this manual for specific operation methods. Please Note: Generation and Export Limit Control functions are set as follows: User can set and check through LCD menu. Refer to <7.4 Advanced settings 3. Anti Reflux> and <7.4 System information1. Inverter Info> . Settings Main interface---Advanced Settings---Input 0001---Anti Reflux--Anti Reflux Mode---Control Mode---Control Type---Power limit . Main interface Back 1.System Settings 2.Advanced Settings 3.Energy Statistics 4.System Information 5.Event List 6.Software Update Input 0001 1.Battery Parameter 2.Battery Active 3.Anti Reflux ... 1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit 1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit 1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit Disable Anti Reflux Three phase limit Soft limit Hard limit Both 1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit 1.Anti Reflux Mode 2.Control Mode 3.Control Type 4.Power limit Generation limit Three phase limit ***KW(VA) 44 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS Checking Main interface---System Information---Inverter Info---Anti Reflux. Main interface Back 1.System Settings 2.Advanced Settings 3.Energy Statistics 4.System Information 5.Event List 6.Software Update 1.Inverter Info 2.Battery Info 3.Safety Param. Inverter Info (1) ... Inverter Info (6) Anti Reflux (enable or disable) Anti-Reflux Power function =Generation or Export Limit Control function Generation (or Export) limit =Generation (or Export) limit control Reflux Power limit = (active or apparent) Power limit When Anti-Reflux Power function is enabled, the reflux power of point of common coupling (PCC) will be limited to the set Reflux Power limit. Both Hard limit control and soft limit control can be used together. However, when Hard limit control is enabled, Anti-Reflux power cannot exceed the Reflux power limit. If the Reflux power exceeds the Reflux power limit, the inverter disconnects from the grid and triggers overload protection. When communication signal with the electricity meter is lost, the output power of the inverter is limited to the value of soft limit control and does not trigger fault protection. When Hard limit control is enabled, a loss of communication with the meter will trigger the inverter into a fault protection state. HYD 5-20KTL-3PH 45 5.4 Electrical connection ELECTRICAL CONNECTIONS The electrical connection is established as follows: 1. Connect PE cable 2. Connect DC input cable 3. Connect battery cable 4. Connect AC output power cable 5. Connect communication cable (optional 5.5 Connecting the PE cables Connect the inverter to the equipotential bonding bar by using the protective earth cable (PE) for grounding. NOTICE Pole earthing not permissible! As the inverter is transformerless, the plus and minus poles of the PV generator must NOT be earthed. Otherwise, the inverter will malfunction. In the PV system, not all live metal parts (e.g. PV module frames, PV frame, generator connection box housing, inverter housing) require earthing. 1. Remove the insulation of the cable. For outside use, cables of 4mm² are recommended for earthing). Figure 5-4 Connecting PGND cable(a) L2 is 2 to 3 mm longer than L1. 46 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS 2. Crimp the cable to the ring terminal: Figure 5-5 Connecting PGND cable(b) 3. Install the crimped ring terminal and the washer with the M6 screws and tighten these with a torque of 3 Nm using an Allen key: Figure 5-6 Connecting PGND cable(c) M6 Screws Threaded hole Ring terminal 5.6 Connecting the DC lines for the PV modules and battery The connection steps of the battery and PV are the same, only the terminal specifications are different. The colour of the battery terminal is blue, the colour of PV terminal is black. If only one set of batteries is required, ensure it is connected to the BAT 1 port, not the BAT 2 port. Please observe the recommended cable dimensions: HYD 5-20KTL-3PH 47 ELECTRICAL CONNECTIONS Cable cross-section (mm2) Range Recommended value Outer diameter of cable (mm) 4.0 ... 6.0 4.0 4.5 ... 7.8 1. Remove the crimp contacts from the positive and negative connections. 2. Remove the insulation of the cables: Figure 5-7 Connecting PV(a) Positive DC cable Negative DC cable L2 is 2 to 3 mm longer than L1 3. Insert the positive and negative DC cables into the corresponding cable glands. 4. Crimp the DC cables. The crimped cable must be able to withstand a tractive force of 400 Nm. 48 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS Figure 5-8 Connecting PV(b) CAUTION Danger of reverse polarity! Ensure that the polarity is correct before plugging into the DC connections! 5. Insert the crimped DC cables into the corresponding connector housing until you hear a "clicking" sound. Figure 5-9 Connecting PV(c) Positive power cable Negative power cable HYD 5-20KTL-3PH 49 ELECTRICAL CONNECTIONS 6. Re-screw the cable glands to the connector housing. Figure 5-10 Connecting PV(d) 7. Insert the positive and negative connectors into the corresponding DC input terminals of the inverter until you hear a "clicking" sound. Figure 5-11 Connecting PV(e) Locking Insert the protective caps into the unused DC connections. CAUTION Danger of DC arcing Before removing the plus and minus connector, ensure that the DC switch has been set to OFF. 50 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS In order to remove the plus and minus connection from the inverter, insert a removal key into the locking and press on the key with the adequate force as shown in the following illustration: Figure 5-12 Connecting PV(f) 5.7 Connecting the AC power cables The AC power cables are used to connect the inverter to the critical loads (through the EPS port), and the AC power distributor or the power grid. CAUTION AC connection Each inverter must have its own circuit breaker. The AC disconnecting device must be easily accessible. The inverter HYD 5K-20KTL-3PH has a built-in AFI (univ. sensitive residual current protection). If an external AFI is required, we recommend an AFI type A featuring a residual current of 100 mA or higher. Please follow the national rules and regulations for the installation of external relais or circuit breakers! The AC cable should be correctly dimensioned in order to ensure that the loss of power in the AC cable is less than 1% of the rated output. If the AC cable resistance is too high, then the AC voltage will increase; this may cause HYD 5-20KTL-3PH 51 ELECTRICAL CONNECTIONS the inverter to become disconnected from the power grid. The relationship between the leakage power in the AC cable and the cable length, the cable cross-section, is displayed in the following illustration: Figure 5-13 The relationship between the leakage power and cable length 5.8 AC connector installation CAUTION Electrical voltage Ensure that the grid has been switched off before removing the AC connector Please follow below steps to install the AC connector. 1. Select the suitable cable in accordance with above diagram. Remove the insulating layer of the AC output cable using a wire stripper and in accordance with the following illustration: A = 30 ...50 mm B = 3...5 mm 52 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS 2. Disassemble the connector in accordance with the following illustration. Guide the AC output cable through the cable gland. 3. Connect the AC cable in accordance with the following requirements and tighten the terminal using the Allen key. Connection Cable L1 Phase 1 (brown) L2 Phase 2 (black) L3 Phase 3 (grey) N Neutral conductor (blue) PE Earthing cable (yellow-green) 4. Assemble the connector housing and screw the cable gland tight. 5. Connect the AC connector to the AC connection of the inverter by turning it clockwise until it locks into place. HYD 5-20KTL-3PH 53 ELECTRICAL CONNECTIONS Remove the AC connector by turning it anticlockwise. When you use the meter connection function, make sure that the AC terminal cable corresponds to the meter cable one by one( L1, L2, L3, N, and PE cables) 6. Connector accessories are divided into upper and lower parts. Attach the connector accessories to the connector and fasten. Use a cross screwdriver. 54 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS 5.9 Communication interfaces The positions of the communications interfaces of the HYD 5K ... 20KTL-3PH are displayed below: No. Connection Function USB/WiFi USB port for firmware update and safety parameter import; Port to connect Stick Logger (WiFi) DRMs Demand Response Modes/Logic Interface to control the inverter COM Multifunctional Communication Port Link port 1 Master/Slave operation of multiple inverters Link port 0 Current sensor connection (CT) For configurations according to System A, CTs are directly connected to the inverter without an energy meter. HYD 5-20KTL-3PH 55 ELECTRICAL CONNECTIONS 5.9.1 Multifunctional Communication Port Please refer to the following table for the specific PIN assignments. PIN Definition Function Note 1 RS485A1-1 RS485differential signal+ 2 RS485A1-2 RS485differential signal+ Wired monitoring or inverter 3 RS485B1-1 RS485differential signal cascade monitoring 4 RS485B1-2 RS485differential signal 5 RS485A2 RS485differential signal+ Communicate with electricity 6 RS485B2 RS485differential signal- meters 56 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS PIN Definition 7 CAN0_H 8 CAN0_L 9 GND.S 10 485TX0+ 11 485TX0- 12 GND.S 13 BAT_Temp 14 DCT1 15 DCT2 16 VCC Function CAN high data CAN low data BMS communication GND RS485differential signal+ RS485differential signal- Signal GND Battery temperature sampling Dry Contact1 Dry Contact2 Communication VCC Note Used for communication with lithium battery BMS, the inverter can automatically identify the battery BMS communication as CAN or RS485 communication Inner BMS battery temperature sampling Providing electrical switching function 12V power supply HYD 5-20KTL-3PH 57 5.9.2 RS485 ELECTRICAL CONNECTIONS For the monitoring and control of several inverters, you connect the RS485 wires in daisy-chain. At the first and the last inverters, you need to terminate the bus with an 120 Ohm resistor between Pin 1 and 4. Figure 5-14 RS485 communication connection 5.9.3 Smart meter The integrated energy management functions integrated of the HYD 520KTL-3PH require to measure the power flow at the point of grid interconnection. There are different system configurations possible. It can be measured using directly connected smart meter or using smart meter with CTs. Please refer to below table for the PIN assignments for the RS485 connection between the inverter and the smart meter. Please refer to below table for the PIN assignments for the RS485 connection between the inverter and the energy meter. Inverter COM Port Pin Function Meter Pin Pin 5 RS485+ (A2) Pin 24 Pin 6 RS485- (B2) Pin 25 58 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS The Smart meter shows a positive power value for feed-in to the grid, and a negative value for energy purchase from the grid. Use the shielded twisted pair cable. The copper outer diameter should be more than 0.5 mm². Keep away from power cables or other electric fields. Use termination resistors at the ends of the RS485 line to improve signal quality. Connect the grid phases to the Smart Meter Pins according to below drawing for correct functionality of the inverter. Smart meter with directly connection (System C, default configuration) Smart meter pins 24 25 PIN5 AB RS485 PIN6 1 3 4 6 7 9 10 L1 A L2 B L3 C N N *Meter does not need to be reconfigured Inverter L1 L2 L3 N PIN: Signal: 6 5 RS485- RS485+ 369 1 0 2425 1 47 1 0 499k 499k 24 25 Figure 5-15 Directly Meter A B C N Grid HYD 5-20KTL-3PH 59 ELECTRICAL CONNECTIONS No additional configuration required for direct-connected meters Up to 80 A measurement Accuracy class and load rating (VA/):1 class Rated operating voltage: AC 0.66KV (Equivalent to 0.69KV GB156- 2003) Rated frequency: 50-60Hz Ambient temperature: -25~75 Altitude: 3000m Smart meter with CTs connection (System B) Smart meter pins 24 25 PIN5 AB RS485 PIN6 P1 P2 Grid 2 5 8 10 1 3 4 6 7 9 L1 A L2 B L3 C N N Inverter L1 L2 L3 N PIN: Signal: 6 5 RS485- RS485+ 499k 36 9 1 0 2 58 Smart Meter DTSU 666 24 25 1 47 1 0 A B C N Grid 499k 24 25 Figure 5-16 RS485 communication connection and smart meter with CTs The arrows on the current transformers direct to the grid. Up to 200 A measurement Accuracy class and load rating (VA/):1 class 60 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS Rated operating voltage: AC 0.66KV (Equivalent to 0.69KV GB1562003) Rated frequency: 50-60Hz Ambient temperature: -40...85 Altitude: 3000m Smart Meter Configuration The smart meter is preconfigured to be used with the inverter with these settings: Modbus Address: 1 Baud Rate: 9600 Current Ratio: 40:1 In case you want to change or check the settings, please refer to below procedure: Modbus Address and Baud Rate setting Current Ratio setting HYD 5-20KTL-3PH 61 ELECTRICAL CONNECTIONS The inverter connected to the meter is a power generation device, and the function of the meter connected to the traditional load (electrical device) is opposite. Therefore, for our product, when the power is output to the grid, the electricity meter will show a positive value, and when the power is purchased from the grid, it will show a negative value. The smart meter comes with 2 terminal resistors, In the actual configuration, the customer can parallel a terminal resistor at each end of the cable to reduce signal reflection in the communication cable. 5.9.4 Temperature Sensor For batteries without a BMS (for example lead-acid batteries), you need to connect the temperature sensor which is within the scope of supply. Place the sensor at the battery. 5.9.5 BMS connection For batteries with a BMS (for example Li-Ion batteries), you need to connect either the CAN Bus or RS485 with the battery management system. The inverter will use the CAN Bus or RS485 Bus according to the battery selection in the inverter's menu. Connecting GTX 3000-H For connecting the GTX 3000-H battery to the inverter, please follow the below pin assignments: Inverter COM Port Function GTX 3000-H communication cable Battery "Link In" Port Pin 7 CAN0_H White-orange Pin 2 Pin 8 CAN0_L Orange Pin 4 62 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS Connecting the BTS 5K battery For connecting the BTS 5K battery to the inverter, please follow the below pin assignments: Inverter COM Port Function BTS communication cable Battery "Link In" Port Pin 7 CAN0_H Blue Pin 4 Pin 8 CAN0_L Blue-white Pin 5 5.9.6 Dry Contact The dry contact signals the on-grid and EPS mode through a signal voltage of 12 VDC. Alternatively, the switch contact can start and stop a generator to charge the battery. This function is available from Firmware V10 The dry contact settings must be set accordingly in the menu Advanced settings Dry Contact Control. On-grid / EPS mode Below is the diagram for switching mode 1 (Relay Open In EPS) and how it can be used to switch a N-PE connection during off-grid mode: HYD 5-20KTL-3PH 63 ELECTRICAL CONNECTIONS On-grid (relay mode 1 "Relay Open In EPS"): EPS mode (relay mode 1 "Relay Open In EPS"): Relay mode 2 (Relay Close In EPS) switches the contact in the opposite direction, i.e. in the on-grid mode there is no voltage, in the EPS mode there is voltage. 64 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS Generator charging Please refer to below diagram for connecting a generator: The settings are explained in the menu structure. 5.9.7 Communication power supply The power supply can be used for the external power supply, or for the switching contact. Max. 400 mA / 5 W. 5.9.8 CT Interface For configurations according to System A, CTs are directly connected to the inverter without an energy meter. These CTs must be purchased separately and need to have a max. current rating of 100 mA at the inverter connection. Please refer to the table below for the specific PIN connections. HYD 5-20KTL-3PH 65 Pin Definition 1 Ict_R- 2 Ict_R+ 3 Ict_S- 4 Ict_S+ 5 Ict_T- 6 Ict_T+ ELECTRICAL CONNECTIONS Function Phase R (Phase L1 -) Phase R + (Phase L1 +) Phase S (Phase L2 -) Phase S + (Phase L2 +) Phase T (Phase L3 -) Phase T + (Phase L3 +) Follow below steps to install the CTs. 1. Fix the cables on the terminals according to above table, and put the connector housing over the terminals. 2. Connect and lock the connector by turning it clockwise. 66 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS 5.9.9 Link Port In systems with multiple inverters, you can connect the devices in a Master/Slave configuration. In this configuration, only one energy meter is connected to the Master inverter for the system control. The first and last inverter need to be connected with the 8 Pin connection terminals! Pin Connections Pin Definition Function 1 IN_SYN0 Synchronising signal 0 2 CANL CAN low data 3 SYN_GND0 Synchronising signal GND 0 4 CANH CAN high data HYD 5-20KTL-3PH 67 ELECTRICAL CONNECTIONS 5 IN_SYN1 Synchronising signal1 6 SYN_GND1 Synchronising signal GND 1 7 SYN_GND2 Synchronising signal GND 2 8 IN_SYN2 Synchronising signal 2 Installation 1. Connect and lock the connector by turning clockwise: 68 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS 5.9.10 DRMs/Logic interface The DRMs/Logic interface is used to control the inverters feed-in or purchases power by external signals, usually provided from grid operators with ripple control receivers or other means. The DRM0 can be used for a switch off signal from external grid protection devices. The logic interface pins are defined according to different standard requirements. Please consider the following PIN assignment. Connector inverter RJ45 Cable (clip is below) Please follow below installation steps. 1. Press the wire terminals in colour sequence: 2. Route the cable terminal through the cable gland and insert the communication cable into the RJ45 connector. HYD 5-20KTL-3PH 69 ELECTRICAL CONNECTIONS 3. Lock the connector by turning clockwise: DRMs for AS/NZS 4777.2:2015 and AS/NZS 4777.2:2020 Also known as Inverter Demand Response Modes (DRMs). The inverter recognises all supported Demand Response commands and initiates the reaction within two seconds. The inverter will continue to respond while the mode remains asserted. Supported DRM commands: DRM0, DRM5, DRM6, DRM7, DRM8. Pin Colour Function 1 orange/white DRM1/5 2 orange DRM2/6 3 green/white DRM3/7 4 blue DRM4/8 5 blue/white DRM0 6 green RefGen 7 brown/white 8 brown Internally shorted 70 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS Demand response modes (DRMs) Demand response mode Real current limit (referenced to inverter rated per phase current) DRM0 0 Reactive current limit (referenced to inverter rated per phase current) 0 Switching time limit 2 s DRM 1 DRM 2 DRM3 DRM4 DRM5 DRM6 DRM7 DRM8 Import =0 Import<50% Import<75% Not limited Generate=0 Generate<50% Generate<75% Not limited 0 2 s As per Clauses 5.5,6.2 and DRM 3 and 2 s DRM 7 Within 5%of set-point per Clause 6.2 2 s As per Clauses 5.5,6.2 and DRM 3 and 2 s DRM 7 0 2 s As per Clauses 5.5,6.2 and DRM 3 and DRM 7 2 s Within 5%of set-point per Clause 6.2 2 s As per Clauses 5.5,6.2 and DRM 3 and 2 s DRM 7 For DRM 0, DRM 1 and DRM 5, current draw due to sensing and DRED circuits is allowable (see Clause 7.2). Logic interface for VDE-AR-N 4105:2018-11 This function serves to control and/or limit the output power of the inverter. The inverter can be connected to a radio ripple control receiver in order to dynamically limit the output power of all inverters within the system. The inverter is preconfigured on the following power levels: HYD 5-20KTL-3PH 71 Pin Name 1 L1 2 L2 3 L3 4 L4 6 G ELECTRICAL CONNECTIONS Inverter Relay 1 input Relay 2 input Relay 3 input Relay 4 input Ground Radio ripple control receiver K1 - output relay 1 K2 - output relay 2 K3 - output relay 3 K4 - output relay 4 Relay, common ground Logic interface for EN50549-1:2019 The active power output can be ended within five seconds following a command to the input interface. Functional description of the terminal Pin Name Inverter Radio ripple control receiver 1 L1 Relay 1 input K1 - output relay 1 6 G Ground Relay, common ground The inverter is preconfigured on the following power levels. Relay status: Closing is 1, opening is 0 72 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS L1 Active power 1 0% 0 100% Power drop rate < 5 seconds / Cos () 1 1 5.10 Feed-in limitation function The feed-in limitation function can be used to limit the power fed back into the grid. For this function, a power measurement device must be installed according to system A, B, or C. Feed-in limitation: The sum of the feeding-in phases must not exceed the set power limitation value. The power of phases drawing power from the grid is disregarded here. 3-phase limit: The sum of the feed-in power of all three phases must not exceed the set power limit value. This setting is suitable for balancing metering, as is common in Germany, for example. For the 3-phase limit setting, the current sensors must be correctly assigned to phases L1, L2 and L3 on the electricity meter! If communication with the smart meter is interrupted, the inverter limits its output power to the set power limit value. 5.11 System monitoring The HYD 5-20KTL-3PH inverters provide various communication methods for the system monitoring: RS485 or WiFi stick (standard), or Ethernet stick (optional). 5.11.1 RS485 You can connect RS485-linked devices to your PC or a data logger via an RS485 USB adapter. Please refer to the pin assignment in paragraph 5.9.2. HYD 5-20KTL-3PH 73 ELECTRICAL CONNECTIONS The RS485 line may not be any longer than 1000 m Assign each inverter its own modbus address (1 to 31) via the LCD display RS485 RS485 RS485 RS485/USB 5.11.2 WiFi, Ethernet stick When you have installed the stick logger, the inverters can directly upload your operating, energy and alarm data in the SolarMAN monitoring portal. 5.12 Installation of the WiFi, or Ethernet stick 1. Remove the protective cap from the USB interface. 2. Install the WiFi/Ethernet stick. 3. Tighten the connecting nut. 74 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS 5.12.1 Configuration of the WiFi stick via the web browser Preparation: The WiFi stick is installed in accordance with the previous section and the SOFAR inverter must be in operation. Carry out the following steps in order to configure the WiFi stick: 1. Connect your PC or smartphone with the WiFi network of the WiFi stick. The name of this WiFi network is "AP", followed by the serial number of the WiFi stick (see rating plate). When you are prompted for a password, you can find it on the label of the WiFi stick (PWD). 2. Open an Internet browser and enter the address 10.10.100.254. 3. Recommended browsers: Internet Explorer 8+, Google Chrome 15+, Firefox 10+ 4. Enter the username and password, which are both set to "admin" by default. The "Status" page will be opened. 5. Click on the "Wizard" in order to configure the WiFi stick for Internet access. The WiFi stick begins to send data to SolarMAN. Register your system at the website home.solarmanpv.com. For this, enter the serial number found on the stick logger. Installers use the portal at pro.solarmanpv.com HYD 5-20KTL-3PH 75 ELECTRICAL CONNECTIONS 5.12.2 Setting up the WiFi stick with the app To download the app, search for "SOLARMAN" in the Apple or Google Play store, or use the following QR codes: SOLARMAN Smart (for end customers): SOLARMAN Business (for installers): Configuration steps 1. After starting the app, register as a new user or enter the current solarMAN access data. 2. Create a new system and save the system data. 3. Scan the barcode of the stick logger to assign an inverter to the system. 4. Go to the newly created system in order to configure the stick logger (device/logger) 5. Press the button on the WiFi stick for 1 second to activate the WPS mode of the stick so that the smartphone can be connected to the WiFi stick. 6. Now, select your local WiFi network for Internet access and enter your WiFi password. 7. The WiFi stick is configured with the access data. 76 HYD 5-20KTL-3PH ELECTRICAL CONNECTIONS WiFi stick status The LEDs on the WiFi stick provide information regarding the status: LED Status Description NET COM READY Communicatio n with the router Communicatio n with inverter Logger status On: Connection to server successful Flashing (1 sec.): Connection to router successful Flashing (0.1 sec.): WPS mode active Off: No connection to router Flashing (1 sec.): Communication with inverter On: Logger connected to inverter Off: No connection to inverter Flashing (1 sec.): Normal status Flashing (0.1 sec.): Reset running Off: Error status Reset button Keystroke 1 sec. 5 sec. 10 sec. Description WPS mode Restart Restart (reset) 5.12.3 Setting up the Ethernet stick The Ethernet stick is delivered with DHCP as standard, so it automatically gets an IP address from the router. If you wish to set up a fixed IP address, connect a PC to the Ethernet stick and open the configuration page via the web address 10.10.100.254. HYD 5-20KTL-3PH 77 COMMISSIONING THE INVERTER 6 Commissioning the inverter 6.1 Safety test before commissioning NOTICE Check the voltage range Ensure that the DC and AC voltages are within the permissible range of the inverter. 6.2 Double Check Please ensure that the inverter and all the wiring are installed correctly, securely, and reliably, and that all environment requirements are met. 1. Inverter is firmly fastened to the mounting bracket on the wall. 2. PV+/PV- wires are firmly connected, polarity and voltage are correct. 3. BAT+/BAT- wires are firmly connected, polarity and voltage are correct. 4. DC isolator is correctly connected between battery & inverter, DC isolator: OFF. 5. GRID / LOAD cables are firmly / correctly connected. 6. AC circuit breaker is correctly connected between inverter GRID port & GRID, circuit breaker: OFF. 7. AC circuit breaker is correctly connected between inverter LOAD port & critical load, circuit breaker: OFF. 8. For lithium battery, please ensure that the communication cable has been correctly connected. 9. For the lead-acid battery, please ensure that the NTC wire has been correctly connected. 78 HYD 5-20KTL-3PH COMMISSIONING THE INVERTER 6.3 Starting the inverter Please follow below steps to switch the inverter ON. 1. Make sure there's no power generation in inverter from grid. 2. Turn ON DC switch. 3. Switch ON the battery. Turn ON DC isolator between battery & inverter. 4. Turn ON AC circuit breaker between the inverter GRID port & GRID. 5. Turn ON AC circuit breaker between the inverter LOAD port & critical load. 6. Inverter should start to operate now. 6.4 Initial setup You need to set the following parameters before inverter starts to operate. Parameter Note 1. Language setting 2. System time setting 3. Safety parameter import 4. Set the input channel Bat Channel1 Bat Channel2 5. Set battery parameters The default is English If you are connected to the server or using the App, the time is set to the local time automatically You need to read the Country Code setting from a USB drive. Alternatively, the mobile app "Sofar View" can be used for this setting, if you are logged in as a validated installer With the Input Channel Configuration you define if PV and / or batteries are connected and in what configuration. If an input channel is not used, select (Not use) If a battery is connected to BAT1 input, select "Bat Input1", otherwise "Not Use" if a second battery is connected to BAT2 independently, select "Bat Input2" If one battery is connected in parallel to BAT1 and BAT2, select "Bat Input1", otherwise "Not Use" Default values can be set according to the input channel configuration in HYD 5-20KTL-3PH 79 COMMISSIONING THE INVERTER Menu Advanced Settings Battery Parameter: Select Battery Type Max. charging current (25A) Max. discharging current (25A) Discharge Depth80% The default operating mode is the Self-use Mode. EPS Mode, Unbalanced Support, Anti-Reflux Mode, IV-Curve Scan and Logic interface are disabled. 6.4.1 Configuring the battery setup The HYD 5-8KTL-3PH models have one battery input (max. current 25 A). The HYD 10-20KTL-3PH models have two battery inputs (max. current 25 A / 25 A). Battery inputs can be connected and set in parallel mode to reach 50 A / 70 A. 6.4.2 Configuring Parallel Inverter System To increase the system's EPS and grid power, the HYD 5-20KTL-3PH can be parallelly connected at the Grid port and the EPS port. For the communication setup, please follow the following steps: 1. Set the Master unit 2. Set the Slave units Each inverter must have a unique parallel address Setting the country code Different distribution network operators in various countries have differing requirements for the grid connection of grid-coupled PV inverters. Ensure that you have selected the correct country code according to regional authority requirements, and consult a qualified electrician or employees of electrical safety authorities. 80 HYD 5-20KTL-3PH COMMISSIONING THE INVERTER SOFARSOLAR is not responsible for the consequences of selecting the incorrect country code. The selected country code influences the device grid monitoring. The inverter continuously checks the set limits and, if required, disconnects the device from the grid. For an updated list of country codes according to the Firmware version, just you can check the document under this link: https://sofarsolar.jianguoyun.com/p/DeanPg4Q4c_MChi404MGIAA For The Australian Market: For compliance with AS/NZS 4777.2:2020 please select from 002-000 Australia A (Australia Region A) 002-008 Australia B (Australia Region B) 002-009 Australia C (Australia Region C) Please contact your local grid operator for which option to select. By selecting 002-000 Australia A, 002-008 Australia B or 002-009 Australia C the power quality response mode and grid protection settings will be reset to their default values for Australia Region A, B, C respectively. Default grid settings for different regions are shown in the following table: Protective function Protective function limit Trip delay time Maximum disconnection time Undervoltage 2(V<<) 70V 1s 2s Undervoltage 1(V<) 180V 10s 11s Overvoltage 1(V>) 265V 1s 2s Overvoltage 2(V>) 275V - 0.2s HYD 5-20KTL-3PH 81 Underfrequency 1(F<) Overfrequency 1(F>) Region Protective function limit value Trip delay time Maximum disconnection time Protective function limit value Trip delay time Maximum disconnection time Australia A 47Hz 1s 2s COMMISSIONING THE INVERTER Australia B 47Hz Australia C 45Hz New Zealand 45Hz 1s 5s 1s 2s 6s 2s 52Hz - 0.2s 52Hz - 0.2s 55Hz - 0.2s 55Hz - 0.2s Default volt-watt settings for different regions are shown in the following table: Region Default value VL2 VL1 VW1 VW2 Australia A Australia B Australia C Voltage Inverter output (P) % of Srated Voltage Inverter output (P) % of Srated Voltage Inverter output (P) % of Srated 207 20% 195 0% 207 20% 215 100% 215 100% 215 100% 253 100% 250 100% 253 100% 260 20% 260 20% 260 20% Default volt-var settings for different regions are shown in the following table: Region Default value VV1 VV2 VV3 VV4 Australia A Voltage Inverter reactive output (Q) % of Srated 207 220 240 258 44% supplying 0% 0% 60% sinking 82 HYD 5-20KTL-3PH COMMISSIONING THE INVERTER Region Default value VV1 VV2 VV3 VV4 Australia B Voltage Inverter reactive output (Q) % of Srated 205 220 235 255 30% supplying 0% 0% 40% sinking Australia C Voltage Inverter reactive output (Q) % of Srated 215 230 240 255 44% supplying 0% 0% 60% sinking HYD 5-20KTL-3PH 83 COMMISSIONING THE INVERTER 6.5 Smartphone app SOFAR View The app is available for Android and iOS systems and allows for easy initial setup as well as advanced configurations. Download link: iOS Android After switching on the inverter, the app finds the unit via Bluetooth under its serial number. The app password for the installation is 6868, for the end customer 8888. If the Bluetooth connection does not work, please carry out a firmware update of the inverter. 84 HYD 5-20KTL-3PH OPERATION OF THE DEVICE 7 Operation of the device This chapter describes the LCD and LED displays of the HYD 5K ... 20KTL-3PH inverter. 7.1 Control panel and display field 7.1.1 Buttons and display lights Buttons Button Name Back Description Previous screen, enter menu Up Down Enter Select previous menu item, increase setting value Select next menu item, decrease setting value Enter Menu item, select next digit, confirm setting HYD 5-20KTL-3PH 85 LEDs State On-grid Off-grid Alarm OPERATION OF THE DEVICE Colour Green Green (flashing) Green Green (flashing) Red State Normal Standby Normal Standby Error 7.2 Standard display The screen shows all relevant information of the inverter: Press Up button, to show PV Information like voltage, power and frequency Press Up button again to show Grid Output Information like voltage, power and frequency Press Up button again to show Grid Information such as power and IMPORT PF Press Up button again to show Load Information like Load Power Press Up button again to show Battery Information(BAT1) like current, power, state of charge etc. 86 HYD 5-20KTL-3PH OPERATION OF THE DEVICE Press Up button again to show Battery Information(BAT2) like current, power, state of charge etc. 7.3 Energy storage modes The HYD 5-20KTL-3PH comes with several integrated energy management modes. 7.3.1 Self-use In the Self-use mode, the inverter will automatically charge and discharge the battery according to the following rules: If PV generation equals the load consumption (P < 100 W), the inverter won't charge or discharge the battery If PV generation is larger than the load consumption, the surplus power is stored in the battery If the battery is full or at maximum charging power, the excess power will be exported to the grid HYD 5-20KTL-3PH 87 OPERATION OF THE DEVICE If the PV generation is less than the load consumption, it will discharge the battery to supply power to the load. If PV generation plus Battery discharge power is less than the load, the inverter will import power from the grid. 88 HYD 5-20KTL-3PH OPERATION OF THE DEVICE The priority of power supply: PV, Battery, Grid The priority of power consumption: Loads, Battery, Grid If it is not allowed to export power to the grid, an energy meter and/or CT needs to be installed, and the "feed-in limitation" function needs to be enabled. 7.3.2 Time-of-Use With the Time-of-Use mode, the inverter can be set to charge the battery in defined intervals of time, date or weekday, depending on the State of Charge of the battery. Up to 4 rules (rule 0, 1, 2 and 3) can be set. If more than one rule is valid for any given time, the rule with the lower number is active. Each rule can be enabled or disabled. In below example, the battery will be charged with 1 kW, if the SOC is below 70%, between 2 and 4 o'clock at night, from 22nd Dec till 21st March: Set Time-of-use Mode Rule 0: Enabled / Disabled From To SOC 02 h 00 m - 04 h 00 m 070% Effective date Dec.22 - Mar.21 Weekday select Mon. Tue. Wed. Thu. Fri. Sat. Sun. If no rule applies, the Self-use Mode is active. Charge 01000W HYD 5-20KTL-3PH 89 7.3.3 Timing OPERATION OF THE DEVICE With the Timing Mode you can define fixed times of the day to charge or discharge the battery with a certain power. Up to 4 rules (rule 0, 1, 2 and 3) can be set. If more than one rule is valid for any given time, the rule with the lower number is active. Each rule can be enabled or disabled, also charging and discharging period for a rule can be enabled separately. In below example, the battery will be charged with 2 kW between 22 and 4 o'clock at night, and discharged with 2,5 kW between 14 and 16 o'clock: Timing Mode Rule 0: Enabled / Disabled / Enabled charge / Enabled discharge Charge Start 22 h 00 m Charge End 05 h 00 m Charge Power 02000 W DisCharge Start 14 h 00m DisCharge End 16 h 00m DisCharge Power 02500 W 7.3.4 Passive The passive mode is used in systems with external energy management systems. The inverter's operation will be controlled by the external controller using the Modbus RTU protocol. Please contact SOFAR if you need the Modbus protocol definition for this device. 90 HYD 5-20KTL-3PH OPERATION OF THE DEVICE 7.3.5 Peak Shaving Used to limit the maximum power priority purchased from the grid.The maximum purchasing power can be set in this mode. When the system preferentially buys more power from the grid than the set value,The battery starts discharging and stabilizes the system power at the set value. Application: Peak Shaving Mode allows the grid to supply power to the load first. Applicable to the occasions where electricity price is charged according to electricity consumption and the occasions where the power grid is weak. In the weak grid situation, batteries start only when the load power exceeds a certain value, which reduces the maximum power of the connecting point and prolongs the battery life. 7.3.6 Off-grid When the SOC of the battery is sufficient and can be discharged, it is preferred to use the battery in off-grid load mode (even if the power grid exists). After the battery enters the state of power loss, it will be transferred to the power grid or generator for load, and the battery will be charged. 1. AC Source Grid charge: After the battery enters the state of power loss, it is transferred to the grid to carry the load and charge the battery. DG charge: After the battery enters the state of power loss, it is transferred to the generator to carry the load and charge the battery. 2. AC Charge AC Charge: The sum of the power input to the power grid or generator after battery loss and when charging the battery. When AC Source is set to DG charge, the generator can be started through Genset Mode in dry contact Control. HYD 5-20KTL-3PH 91 OPERATION OF THE DEVICE EODO: EPS Discharge Depth EPSbuffer: Safety Buffer Application: When the local power grid is unstable or generators are used. 7.3.7 Manual Genset This mode activates manual recharging of the battery in the event of a grid failure via a power generator connected to AC GRID. 7.3.8 Feed-in Priority In this mode, the PV system will prioritise the supply of power to the grid according to the set power after the loads have been satisfied, and will only charge the batteries when the grid supply target has been reached. Users need to pre-set the value of power they wish to deliver to the grid, and the system will intelligently allocate power accordingly. When the PV power generation is sufficient, the system will first protect the load power consumption, and the remaining power will be prioritised to meet the set grid power demand. If the actual power generation exceeds the set value, the excess will be charged for the battery; if the power generation is less than the set value, all the remaining power will be delivered to the grid, and the battery will not be charged at this time. When the PV power generation is insufficient, the system will be supplemented by the battery to meet the load power consumption gap. In this state, the inverter will not deliver any power to the grid, ensuring that local power demand is prioritised. 92 HYD 5-20KTL-3PH OPERATION OF THE DEVICE 7.4 Menu structure Press the button to 7.4.1 Main menu 1. System Settings 2. Advanced Settings 3. Energy Statistics 4. System information 5. Event list 6. Software update 7. Battery real-time Info bring up the main menu. (only with the BTS battery system) The menu layout may vary according to different firmware versions. 7.4.2 "System Settings" menu In this menu you can do the basic settings which are needed to operate the device. 1. Language Settings Sets the display language 2. Time Sets the system time of the inverter 3. Safety Param. Sets the country and grid code 4. Energy Storage Mode (Battery channel is available and the inverter is not a slave.) Select between Self-use mode (Standard), time-of-use mode, timing mode, passive mode. See "Storage Modes" chapter for details. HYD 5-20KTL-3PH 93 5. Input Channel Config Bat Channel1 Bat Channel2 6. EPS Mode 7. Communication Addr. OPERATION OF THE DEVICE With the Input Channel Configuration you define if PV and / or batteries are connected and in what configuration. If a battery is connected to BAT1 input, select "Bat Input1", otherwise "Not Use" If a battery is connected to BAT1 input, select "Bat Input1", otherwise "Not Use" Enable / Disable the emergency power supply mode (EPS). It is only available if a battery is connected Enter the Modbus address (when several inverters require simultaneous monitoring), standard: 01 Baud Rate: The default baud rate is 9600 7.4.3 "Advanced Settings" menu Password Several settings require a password to be entered (the standard password is 0001). In this menu you can do advanced settings. 1. Battery Parameter (Setting is only allowed if there is a battery channel.) Set the battery parameters for Battery 1 and Battery 2. Depending on the selected Battery Type, more settings can be adjusted. See details below. 1.1. Battery 1 Battery Capacity (kWh) Battery address Set the capacity of connected battery (only for batteries with integrated BMS) 94 HYD 5-20KTL-3PH OPERATION OF THE DEVICE Nominal Battery Voltage (V) Battery Cell Type Max. charging current (A) Max. discharging current (A) Depth of Discharge (DOD) on_gird DOD off_grid DOD EPS Safety Buffer Enable Force Charge Set Force Charge Time Forced recharge Up to 4 battery addresses for each Battery Input Channel can be set. This is the CAN bus or Modbus ID of each battery stack connected to the Battery Input, depending on the bus type between inverter and the BMS. Nominal DC voltage of the battery (for inverter-integrated BMS) Max. allowed charging current for the battery Max. allowed discharging current for the battery Max. allowed Depth of Discharge (DOD) for the battery. DOD of 80% means, a battery with 10 kWh capacity can be discharged to a minimum energy level of 2 kWh. Max. Depth of Discharge (DOD) for grid-connected mode. Standard 80%. When setting the BTS-5K battery discharge depth, the maximum limit is 90% to prevent the battery from being too low to recharge. Depth of Discharge (DOD) for EPS mode. Standard: 80% Standard:5% Enable / Disable. When the BTS-5K battery or GTX3000 battery is connected, if "Enable Forced Charge" is enabled, the inverter will forcibly charge until it is fully charged once a month according to the time set in "Set Forced Charge Time". Define the time for the forced charge. When connected to a BTS-5K battery, if the SOC for a month is less than 10%, the battery will be forced to charge to 10% SOC. When the SOC < 5% and the battery changes from sleep to normal state and the PV is stable online for 3 minutes or more, the battery will be forced to charge to 5% SOC. When the GTX3000 battery is connected, if "Enable Force Charge Time" is enabled, the inverter will be HYD 5-20KTL-3PH 95 1.2. Auto Configure Address 2. Battery Active Auto Active Control Force active 3. Set Feed-in Limit Feed-in Limit PCC Limit Scheme Config OPERATION OF THE DEVICE forcibly charged once when the SOC of the battery falls below 8%. When connecting other batteries, if SOC < (1-EOD)/2, the battery will be charged to SOC >= 1-EOD. If the BMS requests a recharge, the battery will be charged to 30%-31% stop. Select "Auto configure address", you can see "Battery quantity" after entering, and you can configure the quantity by yourself. (Only available for SOFAR battery types.) Enable / disable. If Automatic activation is enabled, the inverter will activate the battery when the inverter need to discharge or charge the battery according to the operational mode settings. If automatic activation is disabled, the battery has to be activated manually by selection the "Force active" menu item. Select "Force active" to activate a battery from standby mode. Activates or deactivates the feed-in power function of the inverter and sets the maximum feed-in power. This function must be used together with an external current transformer or the smart meter. Details regarding this can be found in the "Communications interfaces" chapter of this manual Disable: Do not use this function Three phase limit: the sum of all phases is regulated (balancing counting as is common in Germany). Feed-in Limit: the power of the feeding-in phases is limited. PCC Limit bit: The PCC Limit Scheme Config function can be enabled by configuring it. Device type: Sets whether the device type is a domestic or a non-domestic. (Domestic can be reset by "Reset flag bit", non-domestic into the state 3 96 HYD 5-20KTL-3PH OPERATION OF THE DEVICE 4. IV Curve Scan Scan Control Scan Period Force Scan 5. Logic interface HYD 5-20KTL-3PH (Low power state) cannot be reset within 4 hours.) current limit percent: Set the current limit for the current flowing to the GIRD. Lock enable bit: When the machine detects that the PCC point current exceeds the set current limit percentage and continues for a certain period of time, it will enter the low-power state. When the machine is set to the lock state, it needs to be manually reset to restore the anticounter-current state of the machine. (The Reset function is disabled after t he Reset flag bit is used for four times. )When the machine is set to the no lock state, the CLS returns to the normal state by itself as long as the machine detects that the PCC point current is below the current limit percentage for 1 minute. Reset flag bit: Reset the flag bit. When the status query is displayed as the fault state (you need to see the English display on the LCD), you can reset the flag bit to make the status become Normal state. Lock flag bit cleared: When lock enable bit is enabled, if the device is locked and cannot be reset, you need to enter password 5170 to clear the lock flag. status query: View the current status.(State 1: Normal state; State 2: Critical state; State 3: Low power state; State 4: Fault state) (Only set with PV channel.) Cyclical scanning of the IV curve in order to find the global point of the maximum output. Advisable in the case of shaded solar generators Enable / disable IV curve scan function Set scan period in minutes Manually start IV curve scanning Activates or deactivates logical interfaces. Details regarding this can 97 6. Restore Factory Settings Clear energy Data Clear Events Restore Factory Settings 7. Parallel setting Parallel Control Parallel Primary-Replica Parallel Address Save 8. Reset Bluetooth 9. CT Calibration 10. witch On / Off 11. Unbalanced Support OPERATION OF THE DEVICE be found in the "Communications interfaces" chapter of this manual Resets stored data in the inverter Clears total power production Clears historical events Clears total power production and historical events Defines configuration for parallel inverter operation (Master/Slave) For inverters connected with Link port to each other, you set Parallel Control to "Enable" One Inverter need to be set as Master (Primary), all other inverters need to be set to Slave (Replica) Set each inverter with an individual parallel address. (It is an independent number from Modbus ID) After changes, select "save" item to save the settings Resets the Bluetooth interface of the inverter if the device is not found by the Sofar View App This function is used to correct the direction and grid phase assignment of the CTs directly connected to the inverter. During CT Calibration, the inverter must be connected to a battery and the grid. It is recommended to turn off the load during calibration. If calibration fails, check if the battery can be charged/discharged correctly The inverter can be switched on, switched off, set to standby or set to normal operating mode, which can be useful for installation or maintenance work (After version V120002 it is possible to use this function in parallel.) Default setting: disabled In situations where the customer only wants to support the local loads or has a zero-export limit across all three 98 HYD 5-20KTL-3PH OPERATION OF THE DEVICE 12. PCC Purchase Control 13. PCC power bias 14. EPS GFCI NeutralPointGrounding 15. Dry Contact Control Disable Generators Mode RelayOpenIn EPS RelayCloseIn EPS phases. When used in conjunction with the supplied three-phase energy meter and with this option set to "enable", the per phase output current of the inverter will respond independently. Important: for this function to operate properly, the phase on the energy meter must correlate to the corresponding phase when it is wired into the inverter. PCC Buy Control: Control whether the PCC power control function is enabled. PCC Buy Power Control: Power upper limit, that is, the maximum power that can be purchased from the PCC. (When the load is greater than the maximum power purchased from the PCC, the load power priority is higher to meet the load power priority.) Calibration for PCC power calculation. Activates RCD type B monitoring in EPS mode (300 mA) When using off-grid mode, ensure that neutral ground is enabled. For Australia, South Africa, and New Zealand, neutral ground is turned off by default, refer to 5.3 System Overview (The inverter is not allowed to set for the slave machine.) No use this function can start and stop a generator In EPS mode, the dry contact interface will output a 12V signal In grid-tied mode, the dry contact interface will output a 12V signal The inverter (Available from hardware version V003) has built-in relays to control the short circuit of the load N line to ground when off-grid. HYD 5-20KTL-3PH 99 OPERATION OF THE DEVICE When the inverter is off-grid and the load N line and PE line are shortconnected, if the power grid is restored and the load N line and PE line are still short-connected, leakage protection will be triggered and explosion hazard will not be caused. 7.4.4 "Energy Statistics" menu Today Month Year Lifetime Press Down button to move between items Shows PV, Load, Export, Import, Charge, Discharge Energy (kWh) for the selected period 7.4.5 "System Information" menu 1. Inverter Info Inverter Info (1) Inverter Info (2) Inverter Info (3) Inverter Info (4) Inverter Info (5) Inverter Info (6) Inverter Info (7) 2. Battery Info Bat1 Information (1) Bat1 Information (2) Bat1 Information (3) Serial number, Hardware Version, Power Level, Safety Firmware Version Software Version, Country, Country Code Version Bat Channel1, Bat Channel2, PV Channel1, PV Channel2 Energy Storage Mode, RS485 Address, EPS Mode, IV Curve Scan DRM0 Control, PF Time Setting, QV Time Setting, Power Factor Anti Reflux, Insulation resistance, Parallel Control, Unbalanced Support Battery Active Battery Type, Discharge Depth EPS Safety Buffer The Start time and the End time of Force filling Battery Address 100 HYD 5-20KTL-3PH OPERATION OF THE DEVICE Bat2 Information (1) Bat2 Information (2) Bat2 Information (3) 3. Safety Param. Safety Param. (1) Safety Param. (2) Safety Param. (3) 4. debug Info bug info Battery Type, Discharge Depth EPS Safety Buffer The Start time and the End time of Force filling Battery Address Over- / under-voltage protection Over- / under-frequency protection 10 Min. overvoltage protection DSP1 version, state1, state2, state3, state4, state5, state6 7.4.6 "Event List" menu The event list is used to display the real time event recordings, including the total number of events and each specific ID no. and event time. The most recent events are listed at the top. 2. Event list Current event Show latest event Event History Show event history Fault information 001 ID04 06150825 (display of the event sequence number, event ID number and time that the event takes place) 7.4.7 "Sofatware update" menu The user can update the software via the USB flash drive. SOFAR will provide the firmware update when it is required. HYD 5-20KTL-3PH 101 7.5 Firmware update OPERATION OF THE DEVICE If you want to do a firmware update, please upgrade with PV input or grid status, the update will fail if only the battery is connected. 1. Insert the USB stick into the computer. 2. SOFAR will send the firmware update to the user. 3. Unzip the file and copy the original file to a USB stick. Attention: The firmware update file must be in the "firmware" subfolder! 4. Press the "Back" on the main interface to enter the main menu page, and select "2.Advanced Settings - Switch On/Off -Switch Off". Make the inverter shut down safely. 5. Insert the USB flash drive into the USB interface of the inverter. 6. Go to menu item "6.Software update" on the LCD display. 7. Enter the password (the standard password is 0715) and then select "Software Upgrade (PCS)". 8. The system will then successively update the main DSP, auxiliary DSP and ARM processors. Pay attention to the displays. 9. If an error message appears, please upgrade again.If this continues many times, contact technical support for help. 10. After the update is complete, Go to menu item "Advanced Settings Switch On/Off - Switch On" to make the inverter start up and run. 11. You can check the current software version in item "1.Inverter Info (2)" of the SystemInfo menu. Enter the password (the standard password is 0715) to see it. 102 HYD 5-20KTL-3PH TROUBLESHOOTING HANDLING 8 Troubleshooting handling 8.1 Troubleshooting This section contains information and procedures pertaining to the remedying of potential problems with the inverter. To carry out troubleshooting, proceed as follows: Check the warnings, error messages or error codes displayed on the screen of the inverter. If no error information is displayed on the screen, check whether the following requirements have been fulfilled: Has the inverter been set up in a clean, dry, well-ventilated area? Is the DC switch set to ON? Are the cables sufficiently dimensioned and short enough? Are the input connections, output connections and the wiring all in good condition? Are the configuration settings for the relevant installation correct? Are the display field and the communication cables correctly connected and undamaged? Follow the steps below to view recorded problems: Press "Back" to enter the main menu in the normal interface. In the interface screen select "Event List", then press "OK" to enter events. HYD 5-20KTL-3PH 103 8.1.1 Shutdown procedure TROUBLESHOOTING HANDLING If the inverter needs to be shut down for electrical inspection, please follow the following steps: 1. Press the "Back" on the main interface to enter the main menu page, and select Advanced Settings - Switch On/Off - Switch Off. Make the inverter shut down safely. after using the menu setting to shut down the inverter, the inverter should be checked and reenergising, it still needs to be on the main menu page. Select advanced Settings - Switch On/Off- Switch On. start up to enable the inverter to start up and run. 2. Disconnect the AC circuit breaker connecting the inverter power grid port to the power grid. 3. Disconnect the AC breaker connecting the inverter load port to the emergency load. 4. Disconnect the PV side DC switch. 5. Turn off the battery and disconnect the DC switch between the battery and the inverter. 6. Wait for 5 minutes before checking the inverter. 8.1.2 Earth fault alarm This inverter is compliant with IEC 62109-2 Clause 13.9 and AS/NZS 5033 for earth fault protection. If an earth fault alarm occurs, the error is displayed on the LCD screen, the red light illuminates and the error can be found in the error history log. When the inverter is connected to the battery system, when the battery system has ground fault/leak alarm in accordance with AS/NZS 5139, the inverter will also alarm. The alarm method is the same as above. In the case of devices equipped with a stick logger, the alarm information can be viewed on the monitoring portal and retrieved via the smartphone app. 104 HYD 5-20KTL-3PH TROUBLESHOOTING HANDLING 8.2 Error list 8.2.1 Inverter error list ID Code Name Description Solution 001 002 003 004 005 GridOVP GridUVP GridOFP GridUFP GFCI The voltage of the power grid is too high The voltage of the mains is too low The mains frequency is too high The mains frequency is too low Charge Leakage Fault If the alarm occurs occasionally, the possible cause is that the electric grid is abnormal occasionally. Inverter will automatically return to normal operating status when the electric grid's back to normal. If the alarm occurs frequently, check whether the grid voltage/frequency is within the acceptable range. If yes, please check the AC circuit breaker and AC wiring of the inverter. If the grid voltage/frequency is NOT within the acceptable range and AC wiring is correct, but the alarm occurs repeatedly, contact technical support to change the grid over-voltage, under-voltage, over-frequency, under-frequency protection points after obtaining approval from the local electrical grid operator. Check for inverter and wiring. 008 IslandFault Island protection fault 009010 GridOVPInsta nt1/2 Transient overvoltage of mains voltage 1/2 If the alarm occurs occasionally, the possible cause is that the electric grid is abnormal occasionally. Inverter will automatically return to normal operating status when the electric HYD 5-20KTL-3PH 105 TROUBLESHOOTING HANDLING ID Code Name Description Solution grid's back to normal. If the alarm occurs frequently, check whether the grid voltage/frequency is within the acceptable range. If yes, please check the AC circuit breaker and AC wiring of the inverter. If the grid voltage/frequency is NOT 011 VGridLineFau Power grid line lt voltage error within the acceptable range and AC wiring is correct, but the alarm occurs repeatedly, contact technical support to change the grid over-voltage, under-voltage, over-frequency, under-frequency protection points after obtaining approval from the local electrical grid operator. Internal faults of inverter, switch OFF inverter, wait for 5 minutes, then 012 InvVoltFault Inverter overvoltage switch ON inverter. Check whether the problem is solved. If no, please contact technical support. 013 RefluxFault Feed-in Limit function is faulty 014 VGridUnbalan unbalanced ce source voltage 027 PVLowImped PV- Low ground ance impedance 032 N-PE fault Neutral ground fault 038 InvSoftStartF Inverter failed to ail output 039 ArcShutdown Arc shutdown Alarm protection 106 HYD 5-20KTL-3PH TROUBLESHOOTING HANDLING ID Code Name Description Solution 040 LowLightChk Low light Fail detection failed 041 RelayFail Relay detection failure Check the insulation resistance Insulation between the photovoltaic array and 042 IsoFault resistance is too ground (ground), if there is a short low circuit, the fault should be repaired in time. 043 PEConnectFa ult Earth fault Check the PE conductor for function 044 InputConfigE rror Incorrect input mode configuration 045 CTDisconnect CT error 046 ReversalConn ect The battery is connected reversedly Check the input mode (parallel/independent mode) Settings for the inverter. If not, change the input mode. Check that the wiring of the current transformer is correct. Check whether the battery wiring is correct. Master does not Check the parallel mode settings for 047 ParallelFault exist or is duplicate the inverter. Check whether the wiring is correct. For Inner BMS battery, make sure that the battery NTC cable is properly connected. Make sure the inverter is Battery 049 TempErrBat temperature error installed where there is no direct sunlight. Please ensure that the inverter is installed in a cool/ wellventilated place. Ensure the inverter is installed vertically and the ambient temperature is below the inverter temperature limit. HYD 5-20KTL-3PH 107 TROUBLESHOOTING HANDLING ID Code Name Description Solution 050055 057058 TempErrHeat Sink1-6 TempErrEnv1/ 2 Temperature error heat sink 16 Temperature error ambient temperature 1/2 For Inner BMS battery, make sure that the battery NTC cable is properly connected. Make sure the inverter is installed where there is no direct sunlight. Please ensure that the inverter is installed in a cool/ well-ventilated place. Ensure the inverter is installed vertically and the ambient temperature is below the inverter temperature limit. 059061 TempErrInv13 Module 1-3 Temperature protection 065 BusRmsUnba lance Asymmetrical bus voltage RMS The transient 066 BusInstUnbal value of the bus ance voltage is Internal error of the inverter. Switch unbalanced off the inverter, wait 5 minutes and The DC bus then switch the unit on again. voltage is too If the error persists, contact technical 067 BusUVP low during mains support. connection The DC bus 068 BusZVP voltage is too low 108 HYD 5-20KTL-3PH TROUBLESHOOTING HANDLING ID Code Name Description The PV input 069 PVOVP voltage is too high 070 BatOVP Battery overvoltage LLC Bus 071 LLCBusOVP overvoltage protection Inverter bus 072 SwBusRmsO voltage RMS VP Software overvoltage Inverter bus voltage 073 SwBusIOVP instantaneous Software overvoltage Software 081 SwBatOCP overcurrent protection of the battery 082 DciOCP Dci overcurrent protection Solution Check whether the PV series voltage (Voc) is higher than the maximum input voltage of the inverter. If this is the case, adjust the number of PV modules in series. After the correction, the inverter automatically returns to its normal state. Check whether the voltage of the battery is higher than the maximum input voltage of the inverter. If this is the case, adjust the number of battery modules in series. Internal error of the inverter. Switch off the inverter, wait 5 minutes and then switch the unit on again. If the error persists, contact technical support. Internal error of the inverter. Switch off the inverter, wait 5 minutes and then switch the unit on again. If the error persists, contact technical support. HYD 5-20KTL-3PH 109 TROUBLESHOOTING HANDLING ID Code Name Description Solution Instantaneous 083 SwIOCP output current protection 084 SwBuckBoost OCP BuckBoost software sequence 085 SwAcRmsOC P Output RMS current protection 086 SwPvOCPInst ant PV overcurrent software protection PV flows in 087 IpvUnbalance uneven parallelism 088 IacUnbalance Unbalanced output current PV software 089 SwPvOCP overcurrent protection Balanced 090 IbalanceOCP current protection 091 ResOver Resonance protection Software 092 SwAcCBCFau current limiting lt protection by wave PV branch 093 SwPvBranch OCP software overcurrent (enabled by default) 110 HYD 5-20KTL-3PH TROUBLESHOOTING HANDLING ID Code Name Description Solution 097 HwLLCBusOV P LLC bus hardware overvoltage Inverter bus 098 HwBusOVP hardware overvoltage 099 HwBuckBoos tOCP BuckBoost hardware overflows Battery 100 HwBatOCP hardware overflow 102 HwPVOCP PV hardware overflows Mains current is too high and 103 HwACOCP has triggered hardware protection 105 MeterCommF ault Communication fault with meter unit Check communication to meter. 110112 Overload1-3 Overload protection 1-3 Please check whether the inverter is operating under overload. Make sure that the inverter has been installed in a cool and well-ventilated The inverter has place without direct sunlight. 113 OverTempDe throttled due to rating too high a Make sure the inverter is installed temperature vertically and the ambient temperature is below the temperature limit of the inverter. Make sure that the mains frequency 114 FreqDerating AC frequency is too high and voltage are within the permissible range. HYD 5-20KTL-3PH 111 TROUBLESHOOTING HANDLING ID Code Name Description Solution 116 VoltDerating AC voltage is too high Lightning 121 SpdFail(DC) Protection Failure (DC) Lightning 122 SpdFail(AC) Protection failure (AC) Internal error of the inverter. Switch off the inverter, wait 5 minutes and then switch the unit on again. If the error persists, contact technical support. 124 BatDchgProh The battery is ibit low 125 BatLowVoltS No battery hut protection Please check if the battery voltage of the inverter is too low. Internal error of the inverter. Switch Mains current is 129 PermHwAcO CP too high and has caused an unrecoverable hardware fault off the inverter, wait 5 minutes and then switch the unit on again. If the error persists, contact technical support. Bus voltage is too high and 130 PermBusOVP has caused a non-recoverable fault Permanent bus 131 PermHwBus hardware failure OVP due to overvoltage Permanent 133 PermEPSBat OCP battery overcurrent error in EPS mode 112 HYD 5-20KTL-3PH TROUBLESHOOTING HANDLING ID Code Name Description Permanent 134 PermAcOCPI error due to nstant transient overcurrent Permanent 135 PermIacUnba unbalanced lance output current error 136 PermInvStart Fail The soft startup of the inverter fails Permanent 137 PermInCfgErr input mode or configuration error Permanent 138 PermDCOCPI input nstant overcurrent error Permanent 139 PermHwDCO input hardware CP overcurrent error 140 PermRelayFai l Permanent error of the mains relay The bus voltage is unbalanced 141 PermBusUnb and has caused alance an unrecoverable error 142 PermSpdFail( surge DC) protection Solution Check the MPPT input mode setting (parallel mode/independent mode) of the inverter and correct it if necessary. Internal error of the inverter. Switch off the inverter, wait 5 minutes and then switch the unit back on. If the error persists, contact technical support. Check if the weather is normal. Switch off the inverter, wait 5 minutes and then switch the unit back on. If the error persists, contact technical support. HYD 5-20KTL-3PH 113 TROUBLESHOOTING HANDLING ID Code Name Description Solution 143 PermSpdFail( surge AC) protection The safety 152 SafetyVerFaul t version is inconsistent with the internal Check whether safety regulations comply with local standards and safety version import correct safety parameters. SCI 153 SCILose(DC) communication Upgrade software error (DC) SCI 154 SCILose(AC) communication Upgrade software error (AC) Inconsistent 156 SoftVerError software versions Download the latest firmware from the website and launch the software update. If the error persists, contact technical support. Make sure your battery is compatible with the inverter. Lithium battery CAN communication is 157- BMS1- 1-4 160 4CommFault communication recommended. Check the error communication line or the connection of the battery and the inverter for errors. 162 RemoteShutd Remote own shutdown The inverter is shut down remotely. 163 Drms0Shutd DRM 0 own shutdown 169175 FanFault1-7 Fan 1-7 fault BMS 177 BMS OVP overvoltage alarm The inverter is running with a Drms0 shutdown. Check if the corresponding fan of the inverter is running normally. Internal error in the connected lithium battery. Switch off the 114 HYD 5-20KTL-3PH TROUBLESHOOTING HANDLING ID Code Name Description Solution inverter and the lithium battery, wait BMS 5 minutes and then switch the 178 BMS UVP Undervoltage components on again. alarm If the error persists, contact technical support. BMS High 179 BMS OTP temperature warning BMS low 180 BMS UTP temperature warning BMS overload 181 BMS OCP warning during charging and discharging 182 BMS Short BMS Short circuit alarm Please contact technical support. Check the ambient temperature and the battery temperature on the LCD. 186 BatDischarge HTP Battery overtemperatur e protection Switch off the inverter, wait 5 minutes and then switch the unit back on. If the error persists, contact technical support. Low 187 BatDischarge LTP temperature protection for battery discharge Battery 188 BatChargeHT charging P overtemperatur e protection HYD 5-20KTL-3PH 115 TROUBLESHOOTING HANDLING ID Code Name Description Solution 189 190 401402 AFCICommLo se The arc device communication is faulty BatChargeLT P Low temperature protection for battery charging AFCI0/1 Arc pulling fault Internal error in the connected lithium battery. Switch off the inverter and the lithium battery, wait 5 minutes and then switch the components on again. If the error persists, contact technical support. Check the ambient temperature and the battery temperature on the LCD. Switch off the inverter, wait 5 minutes and then switch the unit back on. If the error persists, contact technical support. Internal error in the connected lithium battery. Switch off the inverter and the lithium battery, wait 5 minutes and then switch the components on again. If the error persists, contact technical support. 8.2.2 Battery error list ID Name Description HS1HighTe 808 mpWarnin g Radiator 1 high temperature alarm EnvHighTe 809 mpWarnin g Ambient high temperature alarm Solution Check whether the number of batteries is set correctly. If the setting is correct, please contact technical support to upgrade software. Please make sure the battery is installed in a cool well-ventilated place. If The battery is installed correctly, 116 HYD 5-20KTL-3PH TROUBLESHOOTING HANDLING ID Name Description StopChgWa Charging 813 rning prohibition alarm StopDchg 814 Warning Discharging prohibition alarm HS1OverTe 864 mpFault Over temperature protection of radiator 1 Over temperature OverTempF protection of 865 ault_Env ambient temperature Internal SciCommF 866 communication ault failure of battery Can1 Can1Comm 867 communication Fault failure SwBusInsta Bus software 872 ntOVP overvoltage SwBusInsta Bus software 873 ntUVP undervoltage SwBatInsta Battery software 874 ntOVP overvoltage SwBatInsta Battery software 875 ntUVP undervoltage SwBatInsta Battery software 876 ntOCP overcurrent Solution If the battery is almost fully, no action is required. Otherwise, please contact technical support. If the battery is almost empty, no action is required. Otherwise, please contact technical support. Power off and wait for 2 hours. If the problem is not solved, please contact technical support. If this fault occurs occasionally, wait a few minutes to see whether the problem is solved. If this fault occurs frequently, please contact technical support. If this fault occurs occasionally, wait a few minutes to see whether the problem is solved. If this fault occurs frequently, please contact technical support. If this fault occurs occasionally, wait a few minutes to see whether the problem is solved. If this fault occurs frequently, please contact technical support. HYD 5-20KTL-3PH 117 TROUBLESHOOTING HANDLING ID Name Description Solution 879 HwOCP Hardware overcurrent unrecoverB Permanent bus 880 usAvgOV overvoltage Permanent unrecoverB 881 battery atAvgUV undervoltage Permanent unrecoverO 882 Instant CPInstant overcurrent Restart the battery and wait for minutes. If the problem is not resolved, please contact technical support. Permanent unrecoverH 883 hardware wOCP overcurrent unrecoverB Permanent short- 893 Restart the battery and wait for usSCP circuit protection minutes. If the problem is not Permanent unrecoverB resolved, please contact technical 894 battery activation atActFail support. failed Permanent bus unrecoverB 895 reverse usRPP connection Check whether the wiring is correct and restart the battery. If the problem is not resolved, please contact technical support. BMS overvoltage BMSOVOC 899 and overcurrent P fault If this fault occurs occasionally, wait a Battery average SwBatAvgO few minutes to see whether the 900 overcurrent CP problem is solved. If this fault occurs protection frequently, please contact technical SwAvgOverl Average overload 901 support. oadP protection SwBusInsta Bus software 902 ntOCP overcurrent 118 HYD 5-20KTL-3PH TROUBLESHOOTING HANDLING ID Name Description Software CBC 903 SwCBCOCP overcurrent protection 905 BusSCP Start up short circuit protection SwBusAvg 906 UVP Bus average undervoltage Solution Restart the battery and wait for minutes, Check if the power line is short circuited ,If the problem is not resolved, please contact technical support. Restart the battery and wait for minutes. If the problem is not resolved, please contact technical support. 8.3 Maintenance Inverters do not generally require daily or routine maintenance. Before carrying out cleaning, ensure that the DC switch and AC circuit breaker between the inverter and power grid have been switched off. Wait at least 5 minutes before carrying out cleaning. 8.3.1 Cleaning the inverter Clean the inverter using an air blower and a dry, soft cloth or a soft bristle brush. Do NOT clean the inverter with water, corrosive chemicals, cleaning agents etc. 8.3.2 Cleaning the heat sink In order to help guarantee correct long-term operation of the inverter, make sure that there is sufficient space for ventilation around the heat sink. Check the heat sink for blockages (dust, snow etc.) and remove them if present. Please clean the heat sink using an air blower and a dry, soft cloth or a soft bristle brush. Do NOT clean the heat sink with water, corrosive chemicals, cleaning agents etc. HYD 5-20KTL-3PH 119 TECHNICAL DATA 9 Technical Data Model DC input (PV) Recommended Max. PV input power Max. input voltage HYD 5KTL3PH HYD 6KTL3PH HYD 8KTL3PH HYD 10KTL -3PH HYD 10KTL -3PHA HYD 15KTL -3PH HYD 20KT L-3PH 7500Wp 6000W p/ 6000Wp 9000Wp 6600W p/ 6600Wp 12000Wp 6600W p/ 6600Wp 15000Wp 7500Wp / 7500Wp 1000V 15000Wp 7500Wp / 7500Wp 22500Wp 11250Wp / 11250Wp 30000Wp 15000W p/ 15000Wp Start-up voltage Rated input voltage MPPT operating voltage range Number of MPPT Max inverter back feed current to array Max. number of input strings per MPPT Max. input current per MPPT Max. short-circuit current per MPPT AC output (on grid) Rated output power Rated output current Rated grid voltage Rated grid frequency Max. output apparent power Max. current output to grid Max. AC current from grid Output inrush current Output fault current Output overcurrent protectionRMS 1/1 12.5A/12.5A 15A/15A 200V 600V 180V~960V 2 0A 2/2 25A/25A 30A/30A 5000W 7.2A 5500 VA 8A 15A 10A 6000W 8.7A 6600 VA 10A 17A 12A 8000W 10000W 10000W 11.6A 14.5A 14.5A 3/N/PE, 230/400Vac 8800 VA 13A 50/60Hz 11000 VA 16A 10000 VA 16A 24A 29A 29A 100A/1s 80A/5s 15A 18A 18A 15000W 21.7A 16500 VA 24A 44A 26A 20000 W 29.0A 22000 VA 32A 58A 34A 120 HYD 5-20KTL-3PH TECHNICAL DATA Model Output overcurrent protectionMAX THDi HYD 5KTL3PH 20.4A Power factor Battery Parameters Battery type Battery voltage range Number of battery input channels Max.charge/ discharge power Max.charge/ discharge current BMS communication mode AC output (off grid) Rated output power Rated output current Rated output voltage Rated output frequency Max. output apparent power Peak output apparent power, time Max. output current THDv(@ linear load) Switching time 1 5000W 25A 5000W 7.2A 5500VA 10000VA, 60s 8A Efficiency Max. MPPT efficiency Max. efficiency European efficiency HYD 6KTL3PH 22.5A 1 6000W 25A 6000W 8.7A 6600V A 12000V A, 60s 10A 98% 97.5% HYD 8KTL3PH 33.1A HYD 10KTL -3PH 40.7A HYD 10KTL -3PHA 40.7A <3% 1 default (+/-0.8 adjustable) HYD 15KTL -3PH 61.1A HYD 20KT L-3PH 81.5A Lithium-ion & Lead-acid 180V~800V 1 2 2 8000W 10000W 10000W 50A 50A 25A (25A/25 (25A/25 A) A) CANRS485 2 15000W 50A (25A/25 A) 2 20000 W 50A (25A/25 A) 8000W 10000W 10000W 11.6A 14.5A 14.5A 3/N/PE, 230/400Vac 8800V A 16000V A, 60s 13A 50/60Hz 11000VA 20000V A, 60s 16A 10000V A 20000V A, 60s 16A <3% <10ms 15000W 21.7A 20000 W 29.0A 16500V A 22000V A, 60s 24A 22000V A 22000VA, 60s 32A 99.9% 98.2% 97.7% HYD 5-20KTL-3PH 121 Model Max. efficiency of charging/dischargi ng [1] Protection HYD 5KTL3PH DC switch PV reverse connection protection Battery reverse connection protection Output short circuit protection Output overcurrent protection Output overvoltage protection Insulation impedance detection Residual current detection Anti-island protection Surge protection General Parameters Operating temperature range Relative humidity range Max. operating altitude Standby selfconsumption [2] Topology Installation method Max. number of parallel units [3] Degree of protection Dimensions (W*H*D) Cooling mode HYD 6KTL3PH 97.6% Natural HYD 8KTL3PH HYD 10KTL -3PH TECHNICAL DATA HYD 10KTL -3PHA HYD 15KTL -3PH 97.8% HYD 20KT L-3PH Yes Yes Yes Yes Yes Yes Yes Yes Yes PV:Tyep AC:Type -30~60 5%~95% <4000m <20W Transformerless Wall Mounted 6 pcs IP65 586.6*515*261.2mm Forced airflow 122 HYD 5-20KTL-3PH TECHNICAL DATA Model Weight HYD 5KTL3PH HYD 6KTL3PH 33kg HYD 8KTL3PH HYD 10KTL -3PH HYD 10KTL -3PHA HYD 15KTL -3PH 37kg HYD 20KT L-3PH Communication RS485/CAN/WiFi, Optional:Ethernet/4G Display Standard LCD & Bluetooth+APP EN61000-1, EN61000-2, EN61000-3, EN61000-4, EN61000-4-16, EN61000-4-18, EN610004-29IEC62109-1, IEC62109-2, NB-T32004/IEC62040-1AS/NZS 4777, VDE V 0124-100, V0126-1-1, VDE-AR-N 4105, CEI 0-21/CEI 0-16, C10/11, EN50438/EN50549, G83/G59/G98/G99, UTE C15-712-1, UNE206 007-1 [1] Battery-AC maximum efficiency of battery charge and discharge [2] Standby loss at rated input voltage [3] Maximum number of parallel machines of the same model HYD 5-20KTL-3PH 123 HYD 5-20KTL-3PH 124