P-AVLV
Series AVLV Low Air Velocity Transmitter ® Specifications - Installation and Operating Instructions

Bulletin P-AVLV

3-49/64 [95.71]

1/2 NPS 2-43/64 [67.92]

3-3/16 [80.81]
1-19/32 [40.59]

31/32 24.58

3-33/64 [89.13]

7-41/64 [194.07]

7-17/64 [184.60]
39/64 [15.32]

Ø15/32 [11.84]

2-5/32 [54.82]

The Series AVLV Low Air Velocity Transmitter quickly and accurately measures air velocity or volumetric flow in imperial or metric units. Simultaneous current and voltage outputs on all models provide universal inputs to monitoring equipment while the output range, units, and 0-5/10 VDC output can be configured via local DIP switches. The optional integral display, or the portable remote display tool, provide a convenient way to locally monitor process values and configure the unit.
Models are available in 1% and 2% accuracy models and low velocity ranges to suit a variety of needs, and the optional BACnet MS/TP or Modbus® RTU/ASCII communication protocol allows units to be daisy-chained while providing access to all of the velocity and flow data, as well as additional information such as air temperature. The lower ranges in these high accuracy units allow for applications in quality intensive environments, such as the pharmaceutical industry.

ACCURACY CHART

Velocity Range

Accuracy Rating*

20 to 100 FPM (0.15 to 0.5 m/s) ± (2% of reading + 0.04 m/s [7.9 FPM])

± (1% of reading + 0.04 m/s [7.9 FPM])

20 to 200 FPM (0.15 to 1.0 m/s) ± (2% of reading + 0.04 m/s [7.9 FPM])

± (1% of reading + 0.04 m/s [7.9 FPM])

20 to 300 FPM (0.15 to 1.5 m/s) ± (2% of reading + 0.05 m/s [9.8 FPM])

± (1% of reading + 0.05 m/s [9.8 FPM])

20 to 400 FPM (0.15 to 2.0 m/s) ± (2% of reading + 0.06 m/s [11.8 FPM])

± (1% of reading + 0.06 m/s [11.8 FPM])

*Accuracy dependent on model selected when ordering.

SPECIFICATIONS
Service: Clean air and non-combustible, compatible gases. Wetted Materials: Consult factory. Range: 100, 200, 300, 400 FPM (0.5, 1, 1.5, 2.0 m/s); field selectable. Accuracy: See chart. Temperature Limits: 32 to 122°F (0 to 50°C). Power Requirements: 24 VDC ±20% or 24 VAC ±20%. Humidity Limits: 5 to 95% RH, non-condensing. Output Signals: 4-20 mA, 0-5 VDC, 0-10 VDC. Response Time (90%): 4 s, typical; 1 s at constant temperature. Zero and Span Adjustments: Digital push buttons. Output Load Resistance: Current output: 0 to 1100  max.; Voltage output: Minimum load resistance 1 k.
Current Consumption: 60 mA max. Display: 5 digit LCD (optional). Electrical Connections: Analog: Power and output: four wire removable European style terminal block for 16 to 26 AWG; Communication: Connections: BACnet MS/ TP or Modbus® RTU/ASCII: three wire removable European style terminal block for
16 to 26 AWG.
Supported Communication Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200 (optional).
Device Load: 1/8 unit load. Electrical Entry: 1/2 NPS thread; Accessory: Cable gland for 5 to 10 mm diameter cable, A-151.
Enclosure Rating: NEMA 4X (IP66). Mounting Orientation: Flow direction must be parallel to the sensor tip. Weight: 6.0 oz (160 g). Agency Approval: BTL, CE.

DWYER INSTRUMENTS, LLC
P.O. BOX 373 · MICHIGANCITY, INDIANA 46360, U.S.A.

Phone:219/879-8000 Fax:219/872-9057

www.dwyer-inst.com e-mail:info@dwyermail.com

INSTALLATION
Duct Mount: The transmitter should be mounted away from fans, corners, heating and cooling coils, and other equipment that will effect the measurement of the air velocity. It is recommended that the AVLV is mounted 10 duct diameters downstream of any disturbances and 5 duct diameters upstream of any disturbances, if possible. 1. Mark and drill a 0.750-0.938 (20-24 mm) diameter hole into the duct. 2. Insert and center the duct mount flange in the previously drilled hole and mark
location of the three mounting screw holes. 3. Remove the mounting flange and drill or punch the mounting holes in the marked
locations. 4. Fasten the flange to the duct using three #8 x 1/2 pan head sheet metal screws. Do
not over tighten screws. 5. Insert the AVLV probe into the ducts mount flange and set the desired insertion
depth. 6. Note the flow direction and unit alignment as shown on sensor tip and product label,
tighten probe retention set screw on the duct mount flange screw to affix the probe in place.
Electrical Connection: The Series AVLV is powered and simultaneously transmits a two-wire 4-20 mA current output and a three-wire 0-5 VDC or 0-10 VDC voltage output via a removable four conductor terminal block. The transmitter power supply common is used to reference the current and voltage outputs so either current, voltage, or current and voltage may be wired according to the application. The range of the voltage output can be selected using the on board DIP switches as described in the Analog DIP Switch Settings section of this manual.
Power Supply Choose a power supply with a voltage and current rating sufficient to meet the power specifications under all operating conditions. If the power supply is unregulated, make sure the output voltage remains within the required voltage range under all power line conditions. Ripple on the supply should not exceed 100 mV.

CAUTION

DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.

Current Output Operation

CAUTION

DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.

The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. As the power supply and outputs share the same common signal (GND), the outputs may have separate wires but must effectively join at terminal 2 of the transmitter, as shown in Figure 1. The connections to the transmitter are made to terminals 1, 2, and 3 (PWR, GND, and IOUT respectively) on the terminal block as shown in Figure 4.

Although low loop resistances are recommended, the absolute maximum current loop load resistance, RMAX , is defined by the following the equation:

RMAX = (VPS ­ 2.0) / 0.02 where VPS is the power supply voltage

For a 24 VDC nominal power supply, this evaluates to RMAX = 1100 ohms.

Shielded two wire cable is recommended for current output loop wiring. Ground the shield at the power supply end only.

The maximum length of connecting wire between the current transmitter and the receiver is a function of wire size and receiver resistance. That portion of the total current loop resistance represented by the resistance of the connecting wires themselves should not exceed 10% of the receiver resistance. For extremely long runs (over 1,000 ft.), it is desirable to select receivers with higher resistances in order to keep the size and cost of the connecting leads as low as possible. In installations where the connecting run is no more than 100 ft, connecting lead wire as small as No. 22 Ga. can be used.

Voltage Output Operation

CAUTION

DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.

The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. The voltage output and the power supply must have separate wire leads that are only joined at terminal 2 of the transmitter, as shown in Figure 2. Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver. The connections to the transmitter are made to terminals 1, 2, and 4 (PWR, GND, and VOUT respectively) on the terminal block as shown in Figure 4.

SW1

ZERO

SPAN

POWER

VOLTAGE RECEIVER

SW1

Figure 2: Voltage output wiring

PWR GND IOUT VOUT D1(+) D0(-) COM
PWR GND IOUT VOUT D1(+) D0(-) COM

ZERO

SPAN

POWER

CURRENT RECEIVER Figure 1: Current output wiring

The minimum receiver load is 1 k. The resistance due to the wire should be low compared to the receiver load resistance. While the voltage at the terminal block remains unchanged with a 10 mA current flow, resistive losses in the wiring do cause errors in the voltage delivered to the receiver. For a 1% accurate gauge, the resistance of the wires should be less than 0.1% of the value of the receiver load resistance. This will keep the error caused by the current flow below 0.1%.

The output across VOUT and COM will be either 0-5 VDC, 0-10 VDC, or the inverse depending on the DIP switch setting. See the Analog DIP Switch Settings section for more information.

Simultaneous Current and Voltage Output Operation

CAUTION

DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT.

The terminal block is removable, and each of the terminals are labeled underneath the terminal block on the circuit board. The voltage output and the power supply must have separate wire leads that are only joined at terminal 2 of the transmitter, as shown in Figure 3. Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver. The connections to the transmitter are made to terminals 1, 2, 3 and 4 (PWR, GND, IOUT, and VOUT respectively) on the terminal block as shown in Figure 4, which reflects both the 4-20 mA and 0-5/10 VDC outputs in the same circuit. Details of each output are detailed in their electrical connection sections.

Setting the Engineering Units

SW1

The Series AVLV can be configured to indicate velocity in imperial (FPM, CFM) or

metric (m/s, m3/h) units using DIP switches 4 and 5 on SW1, and Table 2 shows the

values. The units will be displayed on the optional LCD display if connected.

ZERO

SPAN

DIP Switch SW1 Units

4

5

Velocity Mode

ON

ON

FPM

ON

OFF m/s

OFF ON

m/s

OFF OFF m/s

Air Flow Mode
CFM m3/h m3/h m3/h

Table 2: DIP switch SW1 settings for units

PWR GND IOUT VOUT D1(+) D0(-) COM

POWER

VOLTAGE RECEIVER

CURRENT RECEIVER
Figure 3: Simultaneous current and voltage output wiring
ANALOG DIP SWITCH SETTINGS The analog output DIP switches (SW1) are located above the terminal blocks on the left are as shown in Figure 4. A small screw driver or pen can be used to change the position of the switches as required. DIP switch positions for SW2 and SW3 are RESERVED or have no affect.
CAUTION All power should be turned off to the transmitter before adjusting the DIP switch settings to avoid electrical shock.

SW1

ZERO

SPAN

SW1

PWR GND IOUT VOUT D1(+) D0(-) COM

RANGE

UNITS

5V

10V

REV

DIR

KEY Figure 4: Analog dip switches

Factory Default Settings (DIP SW1 ­ All Switches ON) Range = Highest Range Setting (400 FPM) Units = Imperial (FPM) Voltage Output Range = 0-10 VDC Direct / Reverse Output Action = Direct
Setting the Air Velocity Range The range of the instrument is selected by using DIP switches 1 and 2 on SW1. Table 1 shows the maximum full scale value for the selected range and unit. Refer to Setting the Engineering Units section for information on setting the unit.

The default operating mode is velocity, but changes can be made, such as flow mode, via the menu system while an optional display or remote display accessory is connected. Please refer to Appendix III for a full menu flow chart.

Setting the Output Voltage Range Voltage Output can be either 0-5 VDC or 0-10 VDC depending on the position of DIP
Switch 6 ON SW1.

· When the switch is in the ON position, the output will be 0-10 VDC. · When the switch is in the OFF position, the output will be 0-5 VDC.

Setting the Input / Output Action The output will either follow the process directly (DIRECT) or inverted (REVERSED)
based on the position of DIP Switch 7 on SW1.

· When the switch is in the ON position, the output directly follows the input (i.e. output increases as the input increases).
· When the switch is in the OFF position, the output acts in reverse of the input (i.e. output decreases as the input increases).

CALIBRATION

NOTICE

There is a 5 second delay from the time the zero or span calibration

buttons are released until the time that the change in calibration

takes place. This delay is used to reduce vibration or disturbances

of the user related to the button presses.

NOTICE

The security level that is set in the Programming Menu section of the manual will determine which calibrations, if any, may be adjusted by the user.

Zero Calibration The zero calibration can be set by covering the sensor to ensure no air flow and
pressing the zero button for 3 seconds. If either the remote or local LCD is present, the display will read ZEro and then sequence back to the home display.

SPAN Calibration The span calibration can be adjusted only after setting the zero adjustment. It must
be completed within 5 minutes of the last zero calibration. The span calibration button
will be ignored until the zero calibration is completed. Place the sensor in airflow that
matches the maximum selected range of the transmitter. Press and hold the span
button for 3 seconds. If either the remote or local LCD is present, the display will read SPAn and then sequence back to the home display. If the span calibration is attempted before adjusting the zero calibration, the FAiL error message will be displayed briefly
before returning to the home display.

LCD Display The Series AVLV can be ordered with an optional, integral LCD. It comes with a housing cover and overlay to protect the display. The display will plug into the pins as shown in Figure 5. If the display is not needed for normal operation, the transmitter can be ordered without the LCD.

DIP Switch SW1 Full Scale Range

1

2

Imperial (FPM) Metric (m/s)

ON

ON

400

2

ON

OFF 300

1.5

OFF ON

200

1

OFF OFF 100

0.5

Table 1: DIP switch SW1 settings for full scale range

SW1

ZERO

SPAN

PWR GND IOUT VOUT D1(+) D0(-) COM

Figure 5: Pluggable display diagram
Another option for models that do not have a display would be to use a Model A-435-A remote display tool which can plug into the connector shown in Figure 6. The remote display tool has two buttons that function identically to the buttons on the PCB.

ZERO

SW1 SPAN

PWR GND IOUT VOUT D1(+) D0(-) COM

Figure 6: Remote display diagram

Display Error Messages ovEr = The air velocity is greater than the maximum span value causing an Over Range Error UndEr = The air velocity is less than the minimum span value causing an Under Range Error FAiL = When the span or zero buttons are pressed, the air velocity value is out of the range to allow a correct setting. This may be due to a sensor failure. Err1 = The sensor is damaged.
PROGRAMMING MENUS
Home Menu During normal operation, the display will be in the Home Menu and will display the current measured pressure and the engineering units.
Menu Access Security While in the Home Menu, press and hold the Zero and Span buttons simultaneously until SECUr appears on the display in order to access the other programming menus. Upon releasing the buttons, the display will indicate the current security level.
If the current security level is the security level desired (i.e. Security Level 0), press and hold the span button for 3 seconds to enter the Velocity or Air Flow Menu.
If the security level is not the desired level, the security level can be changed temporarily to a lower security level or permanently to a higher level of security by pressing the zero button. A security code will appear on the display, and it can be changed to one of the codes listed in Table 3. The span button chooses which digit and the zero button increments the value of that digit. Pressing and holding the span button will store the value.
The level of access to the programming menus and the calibration is limited based on the security level. Table 3 details the level of access for each security level.

Security

Access

Level Setting View Menu Edit Menu Span Zero

0

000 Yes

Yes

Yes Yes

1

111

Yes

No

No Yes

2

222 No

No

No No

3

333 No

No

No No

Table 3: Security settings

Mode Selection / Digital Dampening Menu From the home display, pressing the span and zero button simultaneously for 3 seconds will access the Menu Security Level. If the level is set to 0 or 1, pressing and holding the span button for 3 seconds, a second time, will access the Mode Selection Menu. The display will default to air velocity when first powered up. Pressing the zero button will cycle to air flow.
Once the desired mode is displayed, pressing and holding the span button for 3 seconds will save the selected mode and display the digital dampening or averaging parameter. This parameter stabilizes the output and the display by averaging the readings. There are 2.5 readings taken each second and the user can select the number of seconds that they would like to average, up to 240 seconds. The display and the output will continue to update at a rate of 2.5 updates per second, but the moving average is used for these updates.

Velocity Mode K-Factor Adjustment If the Velocity Mode was selected, pressing and holding the span after adjusting the digital dampening will enter the Velocity Mode and the transmitter will display the engineering unit that has been selected by the DIP switch. Pressing and holding the span button for 3 seconds will enter the K ­ Factor adjustment. The K ­ Factor can be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for 3 seconds will enter the Maximum Output Adjustment parameter.

Flow Mode K-Factor Adjustment If the Flow Mode was selected, pressing and holding the span after adjusting the digital dampening will enter the Flow Mode and the transmitter will display the engineering unit that has been selected by the DIP switch. Pressing and holding the span button for 3 seconds will enter the K­Factor adjustment. The K­Factor can be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for 3 seconds will enter the Area Adjustment parameter.

Area Adjustment For flow applications, the area is multiplied by the velocity to determine the volumetric air flow. The area will be listed in either CFM or m3/h depending on the DIP switch settings. The units will appear on the display at the time of adjustment. The area can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for 3 seconds will enter the Maximum Output Adjustment parameter.

Maximum Output Adjustment The maximum output can be equivalent to air velocity or air flow. After adjusting the K-Factor, the display will indicate if the adjustment is set for velocity or air flow. Pressing the zero button will toggle between the selections. Pressing and holding the span button for 3 seconds will enter the maximum output adjustment. The maximum output can be adjusted by pressing the span button to select the digit and pressing the zero button to increment the value of the digit. Pressing and holding the span button for 3 seconds will save this value and go to the Security Update Menu.

Security Update / Save Changes Menu The Security Update Menu allows the security level to be set either higher or lower than the current security level setting. This security level will be displayed the next time the Menus are accessed from the home screen. Pressing the zero button cycles through the security levels. Pressing and holding the span button for 3 seconds accepts the new security level and gives the option to save all the menu changes. Pressing the zero button will toggle between yes and no. Yes will save the changes made to all menu items and no will discard all the changes made to all menu items. If the display is set to yes, pressing and holding the span will save the menu items and return the display to the home position.

FACTORY DEFAULT PROCEDURE In order to reset all of the menu settings back to their factory programmed values,
press and hold both the span and zero buttons simultaneously for 10 seconds until FACt is displayed on the LCD. Upon releasing the buttons, the unit will be factory
defaulted. Since resetting the transmitter will wipe out all changes, it is necessary to
zero (and possibly span) the transmitter before taking measurements.

MAINTENANCE/REPAIR Upon final installation of the Series AVLV Air Velocity Transmitter, no routine maintenance is required besides zeroing the transmitter occasionally. Besides routine calibration and installation of the LCD, the Series AVLV is not field serviceable, and it is not possible to repair the unit. Field repair should not be attempted and may void warranty.

WARRANTY/RETURN Refer to "Terms and Conditions of Sales" in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.

APPENDIX I: Air Velocity / Air Flow Calculations

Velocity in m/s is then calculated from the equation:

Velocity (m/s) = Velocity (FPM) x 0.00508

Flow in m3/h is then calculated using the below equation: Flow (CFM) = Area (ft2) x K-Factor x Velocity (FPM) Flow (m3/h) = Flow (CFM) x 1.6992

APPENDIX II: Maximum Flow

Max Flow

Max K Factor x Area

CFM

m3/h

CFM Range m3/h Range

5885000 9999000 14712.5

1388.75

Table 4: Maximum flow values

APPENDIX III: Menu Flow Chart BUTTON PRESS LEGEND ZERO = PRESS ZERO BUTTON SPAN = PRESS SPAN BUTTON ZERO = PRESS AND HOLD ZERO BUTTON SPAN = PRESS AND HOLD SPAN BUTTON ZERO = PRESS AND HOLD ZERO AND SPAN BUTTONS SPAN
Averaging Menu

MENU CONVENTIONS IN HOME POSITION:
ZERO CALIBRATE UNIT TO ZERO PRESSURE. SPAN CALIBRATE UNIT TO SPAN PRESSURE.

DISPLAY IS NOT NECESSARY

ZERO ENTER MENU DISPLAY
SPAN

IN MENU DISPLAY: SPAN SEQUENCES TO NEXT MAIN MENU ITEM, AND IF A MENU ITEM IS CHANGED TEMPORARILY SAVES THE SELECTION

ZERO SEQUENCES THROUGH SUB MENU SELECTIONS OR INCREMENTS DIGITS

SPAN SEQUENCE TO NEXT DIGIT. ACTIVE DIGIT WILL BLINK.

= BLINKING DIGIT

HOME POSITION

SECURITY LEVEL SELECTION
USE DEFAULT DIP SWITCH SETTINGS

ZERO
SPAN WHILE BUTTONS ARE PRESSED

HOLD 7 SECONDS

FACTORY SETTINGS RESTORED, THEN RETURNS TO HOME POSITION

WHEN BUTTONS ARE RELEASED DISPLAYS CURRENT SECURITY LEVEL
ZERO TO CHANGE SECURITY LEVEL

ZERO SPAN

ZERO

INCREMENT DIGIT

SPAN

SELECT DIGIT

SECURITY LEVEL 0 1 2 3

SETTING 000 111 222 333

SPAN

IF SECURITY IS SET TO

0, 1, OR 2

SPAN IF SECURITY IS SET TO 3

HOME POSITION

PRESS ANY KEY OR WAIT 5 SECONDS

ZERO

SPAN

SPAN

ZERO

MODE SELECTION VELOCITY OR FLOW
SPAN

ZERO

ZERO SPAN

BLINKING UNITS AS SELECTED BY DIP SWITCHES

ADJUST AVERAGING
AVG

ZERO

INCREMENT DIGIT

SPAN

SELECT DIGIT

SPAN

TO "VELOCITY OR FLOW" MENUS

Velocity Mode Menu

FROM AVERAGING MENU

ADJUST DISPLAY K FACTOR

SPAN SPAN UPON RELEASE

K
SPAN

SELECT MAXIMUM OUTPUT SET BY PRESSURE OR VELOCITY
ADJUST VELOCITY OUTPUT HIGH

SPAN UPON RELEASE SPAN UPON RELEASE

TO "UPDATE SECURITY AND SAVE" MENU

SPAN

ZERO

FPM

SPAN

FPM OR M/S BASED ON DIP SWITCH SETTING

ZERO

M/S SPAN

INCREMENT DIGIT SELECT DIGIT
INCREMENT DIGIT SELECT DIGIT

SPAN

Flow Mode Menu

FROM AVERAGING MENU

ADJUST DISPLAY K FACTOR

SPAN

SPAN UPON RELEASE SPAN UPON RELEASE

K
SPAN

ZERO

INCREMENT DIGIT

AREA

F

SPAN

SELECT DIGIT

SQ. FEET OR SQ. METERS BASED ON DIP SWITCH SETTING

AREA

M

SPAN

SELECT MAXIMUM OUTPUT SET BY PRESSURE OR FLOW
ADJUST FLOW OUTPUT HIGH

SPAN UPON RELEASE SPAN UPON RELEASE

TO "UPDATE SECURITY AND SAVE" MENU

SPAN

ZERO

CFM

SPAN

FPM OR M/S BASED ON DIP SWITCH SETTING

ZERO

M3/H

SPAN

INCREMENT DIGIT SELECT DIGIT
INCREMENT DIGIT SELECT DIGIT

SPAN

Security Menu

FROM "UPDATE SECURITY AND SAVE" MENU

UPDATE SECURITY LEVEL

ZERO

SPAN

SPAN

ZERO SPAN

ZERO
ZERO SPAN

SAVE CHANGES

SPAN UPON RELEASE

ZERO

ZERO

SPAN

SPAN

HOME POSITION

Modbus® is a registered trademark of Schneider Electric USA, Inc.

©Copyright 2023Dwyer Instruments, LLC

Printed in U.S.A. 5/23