User Manual for SONBUS models including: SM1000C CAN Bus Intelligent DS18B20 Temperature Data Acquisition Module, SM1000C, CAN Bus Intelligent DS18B20 Temperature Data Acquisition Module

CAN bus intelligent DS18B20 temperature data acquisition module

CAN总线智能DS18B20温度数据采集模块-SM1000C 产品概述与介绍 [英文手册]      

SM1000C CAN bus intelligent DS18B20 temperature data acquisition module


File Info : application/pdf, 7 Pages, 752.23KB

PDF preview unavailable. Download the PDF instead.

SM1000C
SM1000C Us er Ma nual

http://www.sonbus.com/

SM1000C CAN bus intelligent DS18B20 temperature data acquisition
module
User Manual
File Version: V21.3.24

SM1000C using the standard CAN Bus,easy access to PLCDCS and other instruments or systems for monitoring temperaturex=64@1 state quantities.The internal use of high -precision sensing core and related devices to ensure high reliability and excellent long-term stability,can be customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and other output methods.
Technical Parameters

ShanghaiSonbest Industrial Co., Ltd

Page1

SM1000C Us er Ma nual

http://www.sonbus.com/

Technical parameter Brand Temperature measuring range Temperature measuring accuracy Communication Interface Default rate Power Running temperature Working humidity

Parameter value SONBEST -50~120 ±0.5 @25 CAN 50kbps DC9~24V 1A -40~80°C 5%RH~90%RH

Product Size

How to wiring?

ShanghaiSonbest Industrial Co., Ltd

Page2

SM1000C Us er Ma nual

http://www.sonbus.com/

Application solution
ShanghaiSonbest Industrial Co., Ltd

Page3

SM1000C Us er Ma nual

http://www.sonbus.com/

How to use?

ShanghaiSonbest Industrial Co., Ltd

Page4

SM1000C Us er Ma nual

http://www.sonbus.com/

Communication Protocol

The product uses the CAN2.0B standard frame format. The standard frame information is 11 bytes

including two parts of information and the first 3 bytes of the data part is the information part. The default

node number of the device is 1, the report The text identification code is ID.10-ID.3 in the CAN standard

frame, and the default rate is 50k. If other rates are required, it can be modified according to the

communication protocol.

The device can work directly with various CAN converters or USB acquisition modules. Users can also

choose our industrial grade USB-CAN converter (as shown above). The basic frame format and

composition are as follows: The table shows.

Bit

7

6

5

4

3

2

1

0

Byte 1 FF

FTR

X

X

DLC.3 DLC.2 DLC.1 DLC.0

Byte 2 ID.10

ID.9

ID.8

ID.7

ID.6

ID.5

ID.4

ID.3

Byte 3 ID.2

ID.1

ID.0

x

x

x

x

x

Byte 4 d1.7

d1.6

d1.5

d1.4

d1.3

d1.2

d1.1

d1.0

Byte 5 d2.7

d2.6

d2.5

d2.4

d2.3

d2.2

d2.1

d2.0

Byte 6 d3.7

d3.6

d3.5

d3.4

d3.3

d3.2

d3.1

d3.0

Byte 7 d4.7

d4.6

d4.5

d4.4

d4.3

d4.2

d4.1

d4.0

Byte 11 d8.7

d8.6

d8.5

d8.4

d8.3

d8.2

d8.1

d8.0

Byte 1 is frame information. The 7th bit (FF) indicates the frame format. In the extended frame, FF=1;

the 6th bit (RTR) indicates the type of the frame, and the RTR=0 indicates the data frame. RTR=1 indicates

the remote frame; DLC indicates the actual data length at the data frame. Bytes 2~3 are valid for the

message identification code 11 bits. Bytes 4~11 are the actual data of the data frame, and t he remote

frame is invalid. For example, if the hardware address is 1, as shown in the figure below, the frame ID is 00

00 00 01, and the data can be replied by sending the correct command.

1. Query data

ShanghaiSonbest Industrial Co., Ltd

Page5

SM1000C Us er Ma nual

http://www.sonbus.com/

Example: Query 1# device channel 1 all 2 data, the host computer sends the command: 01 03 00 00

00 02.

Frame type

Frame ID

Set address Function ID

Start Address Data length

00 01

01

01

03

00 00

02

Response frame: 01 03 04 07 3A 0F 7D.

Frame type

Frame ID

Set address Function ID

Data length

Data

Response

00 00

01

03

04

08 AD 0F 7D

In the above example query reply: 0x03 table is the command number, 0x4 table has 4 data, the first

data is 08 AD folded into decimal is: 2221, because the module resolution is 0.01, the The valu e needs to

be divided by 100, that is, the actual temperature value is 22.21 degrees. Each temperature value occupies

two bytes, that is, an integer variable. The actual value needs to be divided by 100 based on this value.

Similarly, 0F 7D is the second. The data has a value of 3965, which means the real value is 39.65% RH.

2. Change Frame ID

You can use the master station to reset the node number by command. The node number ranges from

1 to 200. After resetting the node number, you must reset the system. Because the communication is in

hexadecimal format, the data in the table Both are in hexadecimal format.

For example, if the host ID is 00 00 and the sensor address is 00 01, the current node 1 is changed to

the 2nd. The communication message for changing the device ID is as follows: 01 06 0B 00 00 02.

Frame type

Frame ID

Set Address Function id

fixed value

target frame ID

Command

00 01

01

06

0B 00

00 02

Return frame after correct setting: 01 06 01 02 61 88. The format is as shown in the table below.

Frame ID

Set Address Function id

source frame current frame CRC16

ID

ID

00 00

01

06

01

02

61 88

The command will not respond correctly. The following is the command and reply message to change

the Set Address to 2.

3. Change device rate

You can use the master station to reset the device rate by command. The rate number range is from 1

to 11. After resetting the node number, the rate takes effect immediately. Because the communication is in

hexadecimal format, the rate in the table. The numbers are all in hexadecimal format.

rate number

rate

rate number

rate

1

10kbps

2

20kbps

3

25kbps

4

40kbps

5

50kbps

6

100kbps

7

125kbps

8

200kbps

9

250kbps

A

400kbps

B

500kbps

C

1M (unused)

The rate not in the above range is not supported at the moment. If there is special demand, it can be

customized. For example, the device rate is 50k. According to the above table, the number is 05. To

change the rate to 40k, the 40k number is 04, the communication message of the operation is as follows:

01 06 0A 05 00 04, as shown below.

After the execution rate is modified, the rate will change immediately and the device will not return any

value. At this time, the CAN acquisition device also needs to switch the corresponding rate to communicate

normally.

ShanghaiSonbest Industrial Co., Ltd

Page6

SM1000C Us er Ma nual

http://www.sonbus.com/

4. Return frame ID and rate after power-on

After the device is powered on again, the device will return the corresponding Set Address and rate

information. For example, after the device is powered on, the reported message is as follows: 01 25 01 05

D1 80.

frame ID

Set Address Function id

current frame current rate

CRC16

ID

00 00

01

25

00 01

05

D1 80

In the response frame, 01 indicates that the current frame ID is 00 01, and speed value 05 indicates

that the current rate is 50 kbps, which can be obtained by looking up the table.

Disclaimer

This document provides all information about the product, does not grant any license to intellectual

property, does not express or imply, and prohibits any other means of granting any intellectual property

rights, such as the statement of sales terms and conditions of this product, other issues. No liability is

assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use

of this product, including the suitability for the specific use of the product, the marketability or the

infringement liability for any patent, copyright or other intellectual property rights, etc. Product

specifications and product descriptions may be modified at any time without notice.

Contact Us

Company: Shanghai Sonbest Industrial Co., Ltd

Address:Building 8,No.215 North east road,Baoshan District,Shanghai,China

Web: http://www.sonbest.com

Web: http://www.sonbus.com

SKYPE: soobuu

Email: sale@sonbest.com

Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077

ShanghaiSonbest Industrial Co., Ltd

Page7

