Trane Rotary Spring Return Actuators 62 lb-in Series Installation Instructions

Installation Instructions

Rotary Spring Return Actuators

62 lb-in Series

Graphics in this document are for representation only. Actual model may differ in appearance.

⚠️ SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

August 2024

PART-SVN264A-EN

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

⚠️ WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
⚠️ CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
ℹ️ NOTICE
Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

Safety and Compliance

⚠️ WARNING

Proper Field Wiring and Grounding Required! Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

⚠️ WARNING

Personal Protective Equipment (PPE) Required! Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

  • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
  • When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
  • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

⚠️ WARNING

Follow EHS Policies! Failure to follow instructions below could result in death or serious injury.

  • All Trane personnel must follow the company's Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
  • Non-Trane personnel should always follow local regulations.

General Information

Note: Keep these instructions with the actuator or with the plant documentation.

Parts List

Table 1. Parts list

Item Description Qty
1 Actuator 1
2 Self-centering shaft adapter 1
3 Auxiliary switch adjustment tool 1
4 Shaft adapter locking clip 1
5 3 mm hex wrench 1
6 Mounting bracket 1
7 Mounting screws 2

Figure 1. Parts list. Diagram shows the actuator unit (1), a self-centering shaft adapter (2), an auxiliary switch adjustment tool (3), a shaft adapter locking clip (4), a 3mm hex wrench (5), a mounting bracket (6), and mounting screws (7). The screws are labeled with dimensions 4.8 x 13 DIN 7981.

Required Tools

Qty Description
1 4 mm hex wrench (provided)
1 Drill
1 4 mm (5/32-in.) drill bit
1 3 mm hex wrench (provided)
1 Phillips screwdriver
1 Small flat-blade screwdriver
1 Marker or pencil

Mounting Position

Figure 2. Mounting position. Diagrams illustrate acceptable mounting positions for the actuator. One shows the actuator mounted vertically with the shaft horizontal, allowing for angles less than 45 degrees from vertical. Another shows the actuator mounted horizontally with the shaft vertical, at 90 degrees. Ratings IP 54 and NEMA 3R are indicated. Further diagrams show the actuator with the shaft adapter attached, indicating the manual override feature.

Installation

Note: Actuator is shipped with 5° preload. When power is applied to the actuator, the preload is released. To manually release the preload, insert the 3 mm hex key in the override opening and turn the key in the direction of the arrow. See "Manual Override,” p. 8.

The expected installation time is 30 minutes.

Important:

  • Do not open actuator.
  • Do not turn the 3 mm hex key against the direction of the arrow.

Step 1-3: Shaft length and shaft adapter mounting location

Figure 3. Shaft length and shaft adapter mounting location. Diagrams show the process of attaching the shaft adapter. Step 1 illustrates measuring the shaft length, indicating a minimum of 77 mm (3 inches) and a range of 20 mm to 77 mm (3/4 inch to 3 inches) for the shaft adapter engagement. Step 2 shows aligning the self-centering shaft adapter with the 'SHAFT ADAPTER ALIGNMENT MARK' on the actuator. Step 3 shows inserting the shaft adapter locking clip to secure the adapter.

Step 4: Close the damper

Figure 4. Close damper. Diagram shows the actuator connected to a damper shaft, with an arrow indicating the action of closing the damper. Note: If the damper fail-safe position is open, change the actuator preload from the preset 5° to 85°. See "Manual Override,” p. 8.

Step 5: Mount the actuator onto the shaft

Figure 5. Mount actuator. Diagram shows the actuator being mounted onto the damper shaft.

Step 6: Prepare mounting bracket

Using 4 mm (5/32-in.) drill bit, drill two holes one at each end of the mounting bracket. See Figure 6, p. 8.

Step 7: Install mounting bracket

Figure 6. Install mounting bracket. Diagram shows drilling two holes at each end of the mounting bracket using a 4 mm (5/32-in.) drill bit. It then shows attaching the mounting bracket with mounting screws.

Step 8: Fasten shaft adapter

Figure 7. Fasten shaft adapter. Diagram shows using a 4 mm hex wrench to fasten the shaft adapter to the damper shaft, with a torque specification of 7.5-9 lb-ft (10-12 Nm).

Manual Override

To manually override or set preload:

  1. Insert the 3 mm hex key in the override opening.
  2. Turn the key in the direction of the arrow until it reaches the desired degree of opening.
  3. Hold the key in place.
  4. Insert a small flat-blade screwdriver into the gear train lock pin. Turn the screwdriver in the same direction as the arrow until it clicks or meets slight resistance (approximately 5 degrees rotation).

NOTICE Equipment Damage! To avoid stripping the gear train lock pin, do not turn past the click or point of resistance.

To release manual override or preload:

  1. Insert the 3 mm hex key in the override opening.
  2. Turn the key only a short distance in the direction of the arrow.
  3. Remove the key. The actuator will return to 0 (fail-safe) position.

Note: Applying power and sending a control signal will release manual override.

Figure 8. Manual override. Diagrams illustrate the manual override process. 'Rotating' shows inserting a 3mm hex wrench into the override opening and turning it. 'Locking in place' shows holding the key and inserting a small flat-blade screwdriver into a lock pin. 'Releasing when power is absent' shows removing the key.

Wiring

  • All wiring must conform to NEC and local codes and regulations.
  • Use earth ground isolating step-down Class 2 transformers. Do not use autotransformers.

Note: The maximum rating for a Class 2 stepdown transformer is 100 VA. Determine the supply transformer rating by summing the VA ratings of all actuators and all other components used. It is recommended that not more than 80% of the transformer VA be utilized. The 62 lb-in actuator consumes 8 VA or less.

Either AC line voltage from the same phase must be applied to all six outputs of the dual auxiliary switches, or UL-Class 2 voltage must be applied to all six outputs. Note: With Plenum cables, only UL-Class 2 voltage is permitted.

Table 2. Types of actuator

Actuator Operating Voltage Power Consumption Modulating Control
ACT00987 (Symbio™ Control) 24 VAC/DC 7 VA/5W
ACT00988 (ReliaTel Control) 24 VAC/DC 7 VA/5W

Table 3. Wire designations for 24 VAC/DC ACT00987 actuator

Pin Out Locations Function Terminal Connection Color Color Symbol
1 Supply (SP) G Red RD
4 Neutral (SN) G0 Black BK
3 Input Signal 2 to 10 VDC (ACT00987) Y Pink PK
2 Position Output 2 to 10 VDC (ACT00987) U Grey GY

Figure 9. Modulating 2 to 10 VDC control, 24 VAC/DC ACT00987. Diagram shows a simplified block diagram with connections labeled 1, 2, 3, 4.

Figure 10. Modulating 2 to 10 VDC control, 24 VAC/ DC: ACT00988. Diagram shows a more detailed wiring diagram for the ACT00988, illustrating connections to a motor (M) and terminal blocks with specific pin assignments (G, G0, Y, U) and corresponding wire colors (Red, Black, Pink, Grey).

Table 4. Wire designations for 24 VAC/DC ACT00988 actuator

Connector Pin Out Locations Function Terminal Connection Color Color Symbol
1 1 Supply (SP) G Red RD
2 Neutral (SN) G0 Black BK
2 1 Neutral (SN) G0 Black BK
2 Input Signal 2 to 10 VDC (ACT00988) Y Pink PK
3 1 Neutral (SN) G0 Black BK
2 Position Output 2 to 10 VDC (ACT00988) U Grey GY

Dimensions

Figure 11. Actuator and mounting bracket dimensions in inches (millimeters). Diagrams provide detailed dimensions for the actuator and mounting bracket in both inches and millimeters. Key dimensions include height, width, depth, shaft engagement length, and mounting hole spacing.

Notes

Notes section for additional information.

Models: PART-SVN264A, PART-SVN264A Rotary Spring Return Actuators, Rotary Spring Return Actuators, Spring Return Actuators, Return Actuators, Actuators

File Info : application/pdf, 16 Pages, 2.18MB

PDF preview unavailable. Download the PDF instead.

PART-SVN264A-EN 08262024

References

PDFlib PDI 9.0.6 (C /Win64)

Related Documents

Preview Trane Symbio 700 Controller User Guide and Installation Manual
This document provides comprehensive information on the Trane Symbio 700 controller, including its features, installation, operation, and troubleshooting. It details the standard and advanced configurations, the Symbio Service and Installation mobile application, and onboard display functionalities for managing HVAC equipment.
Preview Trane RTAC Rotary Chiller Tracer AdaptiView Display Upgrade Kit Installation Instructions
This document provides detailed installation instructions for the Trane Tracer AdaptiView Display Upgrade Kit for RTAC Rotary Chillers, replacing older DynaView systems. It covers safety, required tools, step-by-step procedures, and integration options.
Preview Trane Symbio 700 Controller Application Guide for Voyager 3 Rooftop Units
This application guide from Trane provides comprehensive information on the Symbio™ 700 controller, detailing its configuration, control capabilities, and troubleshooting for Voyager 3 packaged rooftop air conditioners.
Preview Trane Symbio 700 Controller User Guide
User guide for the Trane Symbio 700 controller, detailing its features, operation, mobile application usage, configuration, troubleshooting, and onboard display functions.
Preview Trane Symbio® 210 Programmable VAV Box Controller: Installation, Operation, and Maintenance
This manual details the installation, operation, and maintenance of the Trane Symbio® 210 Programmable Variable-Air-Volume (VAV) Box Controller. It covers features, wiring, diagnostics, and system integration for HVAC applications.
Preview Trane RCDB - Symbio 800 Controls Upgrade Kit Installation for RTAC CH530 Rotary Chiller
Detailed installation guide for the Trane RCDB - Symbio 800 Controls Upgrade Kit, designed for RTAC CH530 Rotary Chillers. Covers safety, parts, tools, and step-by-step procedures for upgrading chiller control systems.
Preview Trane Precedent™ High Efficiency Packaged Rooftop Heat Pumps: Product Catalog
Discover the Trane Precedent™ series of high-efficiency packaged rooftop heat pumps, designed for exceptional reliability and advanced comfort control. This catalog details features, specifications, and applications for units ranging from 12.5 to 25 tons, highlighting Trane's commitment to quality and performance in commercial HVAC solutions.
Preview Trane Precedent™ Packaged Heat Pump: Convertible 3-10 Tons | Features & Specs
Explore the Trane Precedent™ Packaged Heat Pump series, featuring convertible 3-10 ton capacities. Discover standard features, added flexibility, factory-installed options, and detailed specifications for efficient light commercial HVAC solutions.