Raychem TCONTROL-05 Panel Mounted Regulator

Régulateur monté sur panneau

1. Introduction

1.1 Safety Instructions

General: This notice contains instructions to ensure your safety and prevent material damage. Instructions are supported by pictograms. Read this notice before putting the device into operation and keep it accessible. Do not perform any manipulations that could compromise your warranty if you encounter difficulties during commissioning.

Warning Symbols:

1.2 Proper Use

The device is designed for industrial environments as specified in the technical characteristics. Any other use is considered non-compliant. The device is manufactured according to applicable standards and directives. Improper use may cause personal injury or material damage. The device must only be used:

Even with appropriate use, the device can pose an application-related hazard due to incorrect settings or lack of safety devices.

1.3 Personnel Qualification

This document provides information for the intended use of the described modules. It is intended for technically qualified personnel with specialized training in automation. Correct interpretation and application of safety advice and warnings in the technical documentation are prerequisites for safe installation and operation.

1.4 Material Reception, Storage, and Transport

1.4.1 Delivery Check

1.4.2 Storage and Transport Advice

1.4.3 Material Return

For repair, return the device clean and complete using original packaging.

Protection Against Electrostatic Discharge (ESD)

To prevent ESD damage, handle, pack, and store electronic modules/components in a protected environment. Refer to EN 61340-5-1 and EN 61340-5-2 for protection measures. Use conductive plastic packaging for sensitive components. Chemelex is not liable for ESD damage.

1.4.4 Waste Disposal

Device Disposal: After use, the device or replaced parts must not be thrown in the bin. They are made of recyclable materials. Dispose of the device and packaging materials in an environmentally friendly manner according to regulations.

Packaging Material Disposal: All packaging material is fully recyclable (cardboard, paper, plastic film, and bag).

1.5 Device Identification

1.5.1 Nameplate

The nameplate is affixed to the device and contains important information such as:

DescriptionDesignation on NameplateExample
Device TypeTyp702114/81-4356-25/214
Article ReferenceTN00123456
Serial NumberF-Nr.0070033801217480006
Power Supply-20 to 30 V AC/DC, 48 to 63 Hz

1.5.2 Order References

The order reference uniquely characterizes a catalog item and is important for communication. The serial number includes the production date (year/week). For example, F-Nr = 0070033801217480006, where digits 12, 13, 14, and 15 indicate week 48 of 2017.

The order reference is composed of:

Example order code: 702114 / 8 - 4 3 5 6 - 23 / 214

1.5.3 Material Supplied

1.5.4 Accessories

1.6 Summary Description

The regulator series consists of five universal, freely configurable compact regulators in various DIN formats for controlling temperature, pressure, and other process variables. They feature simple, clear controls, two 18-segment LCD displays for process values and parameters, individual display elements for output status, manual mode, ramp, and timer functions. Four touch-sensitive keys allow operation. The devices are protected to IP65 for use in harsh environments. Depending on the hardware, they can function as 2-point, 3-point, or proportional controllers. Base execution includes auto-optimization, ramp, programmer, manual mode, limit value monitoring, digital inputs, and an intervention counter. Optional features include mathematical/logical functions and user-created applications via structured text (ST code). Configuration is user-friendly using the Setup program (including ST editor). No external power supply is needed for USB configuration.

1.7 Synoptic

The synoptic diagram illustrates the device's inputs and outputs:

1.8 Device Types

Type 702110 (format 132) is shown with an example display.

1.9 Available Technical Documentation

In addition to this brief notice, the following documents are available as PDF files:

2. Mounting

2.1 Mounting Instructions

WARNING! The device must not be used in explosion-risk zones.

Mounting Location

The device is designed for mounting in a cut-out of a control cabinet panel. The front and housing have different protection ratings (see Technical Characteristics).

Climatic Conditions

Ambient temperature and relative humidity at the mounting location must comply with the technical specifications. Aggressive gases and vapors shorten the device's lifespan. The mounting location must be free of dust, flour, and suspended matter.

Mounting Position

The mounting position is arbitrary. The maximum permissible ambient temperature applies only to vertical display orientation.

Technical Characteristics

Refer to chapter 5 "Technical Characteristics", Page 25.

2.2 Cleaning

The front of the device (flush keys) can be cleaned with standard detergents.

ATTENTION! The front is not resistant to aggressive acids and alkalis, scouring agents, or high-pressure cleaning. Use only suitable products.

2.3 Dimensions

The TCONTROL-05 has dimensions of 77.9 mm width, 48 mm height, and 44.5 mm depth. The panel cut-out according to CEI 61554 is 48 mm x 48 mm, with minimum edge spacings of 15 mm horizontally and 30 mm vertically for side-by-side mounting.

2.4 Mounting on Symmetrical Rail

Special fixing elements for symmetrical rail (35 mm, DIN EN 60715) are available as an option. This includes a base plate fixed to the rail and a device support. Follow these instructions:

  1. Place the base plate onto the symmetrical rail from above and press down until it clicks.
  2. Place the fixing frame (supplied with the device) into the device support from the front.
  3. Place the device (without control panel gasket) into the device support from the front and secure it with the fixing frame. Ensure sufficient fixation.
  4. Perform electrical connection. For easier connection, the device support can be hooked vertically from its lower part into the base plate (connection terminals at the top). It is also possible to hook the device support horizontally so that the connection terminals are accessible from the front. After connection, remove the device support from this position.
  5. Place the device support with its rear notches into the lateral recesses of the base plate and press down until it clicks.

2.5 Mounting in Control Panel

  1. Place the device into the panel cut-out from the front, ensuring the gasket is correctly positioned.
  2. Push the fixing frame from behind the panel onto the device body and press with the springs against the back of the control panel until the notches engage in the provided slots, ensuring sufficient fixation.

ATTENTION! Front and housing have different protection ratings! IP65 protection (front) is guaranteed only with a uniformly adhering gasket. Use the fixing frames and/or the two fixing elements as described and ensure uniform fixation.

3. Electrical Connection

3.1 Installation Instructions

Personnel Requirements

Cables, Shielding, and Grounding

Electrical Safety

Additional Warnings

Interface Setup

The USB Setup interface is not intended for permanent connection. Always disconnect the USB cable after using the Setup software.

3.2 Connection Elements

The device has connection terminals for a 48 mm x 48 mm dimension.

TerminalsConnection
1, 2Output 1 (relay)
3, 4Output 2 (relay)
5-8Analog input
8, 10Input 2 (for contact sec)
9, 10Input 1 (for contact sec) or Output 3 (digital output)
11, 12(1) = Option 1: Output 4 (relay, digital output) or RS485 port
13, 14(2) = Option 2: Output 5 (relay, digital output or analog)
L1(L+), N(L-)Power Supply
Setup (USB)PC (Setup program)

3.3 Connection Diagram

ATTENTION! Under unfavorable conditions, the temperature at the terminals can exceed 60°C, potentially damaging cable insulation. Use cables rated for at least 80°C.

REMARK! An individual connection diagram corresponding to the ordered execution is affixed to the housing.

3.3.1 Analog Input

The analog input execution is identical for all types. Supported sensors/signals include Thermocouples (Fe-CuNi, Cu-CuNi, NiCr-Ni, NiCr-CuNi, NiCrSi-NiSi), Pt10Rh-Pt, Pt13Rh-Pt, Pt30Rh-Pt6Rh, W5Re-W26Re, W3Re-W25Re, W5Re-W20Re, Chromel®-Copel, Chromel®-Alumel®, resistance/potentiometers, and rheostats. Voltage (0(2)-10 V DC) and current (0(4)-20 mA) signals are also supported.

3.3.2 Digital Inputs

Digital input execution is identical for all types. Input 1 is for a potential-free contact (alternative to digital output 3). Input 2 is for a potential-free contact (only if analog input is not configured for 0(2)-10 V).

3.3.3 Analog Output

For types 702111 to 702114, Output 5 supports Option 2: DC 0/2 to 10 V or DC 0/4 to 20 mA (configurable).

3.3.4 Digital Outputs

OutputExecutionSymbol and Terminal Designation
1Relay (changeover)1, 2
2Relay (changeover) (for type 702110 Option 2)3, 4
3Digital output 0/14 V (alternative to digital input 1)9, 10
4Option 1 (alternative to RS485 port): Relay (changeover) or digital output 0/14 V11, 12
5Option 2 (alternative to analog output): Relay (changeover) or digital output 0/14 V13, 14

3.3.5 RS485 Port

Option 1 (alternative to digital output 4): RxD/TxD+ (terminal 11), RxD/TxD- (terminal 12).

3.3.6 Power Supply

Versions: AC 110 to 240 V (L1/L+, N/L-) and AC/DC 20 to 30 V (L1/L+, L-/N/L-).

REMARK! For configuration with Setup software, no separate power supply is needed as the device is powered via USB. For formats 108H, 108Q, or 104, standard digital outputs are active, and optional digital outputs are deactivated.

3.4 Galvanic Separation

The diagram shows galvanic separation for various inputs and outputs. Test voltages are according to EN 61010-1:2011-07. For Type 702110 (format 132), test voltage is 3000 V. Functional galvanic separation is for SELV or PELV circuits.

ATTENTION! No galvanic separation between measurement input and USB interface. Avoid USB connection if the sensor is earth-grounded, even if the PC is grounded.

The device is configured, parameterized, and controlled via four front keys. The available Setup program allows easy computer configuration. Some functions require the Setup program. Parameters are organized in different, lockable levels to prevent accidental or unauthorized manipulation.

4. Control

4.1 Display and Control

The TCONTROL-05 features two 18-segment LCD displays:

Key Functions:

Icons (Activity Displays)

IconOffOnFlashing
Ramp/Program FunctionFunction not active or configuredRamp or regulator programmed but not activeRamp or regulator programmed and active
TimerTimer not active or configuredTimer active but not functioningTimer is active (functioning)
Manual ModeManual mode not active (auto mode)Manual mode active. Outputs can be manually controlled via Up/Down keys (adjust modulation rate or open/close valve for 3-point step controllers).-

Key Functions and Combinations

Key or Combination (Duration)Base Mode FunctionNavigation FunctionEdit Mode Function
Up (▲)Increase setpoint. In manual mode: adjust modulation rate (or open/close valve for 3-point step controllers).Select menu point or preceding parameter.Increment value or scroll up list.
Down (▼)Decrease setpoint. In manual mode: reduce modulation rate (or close valve for 3-point step controllers).Select next menu point or parameter.Decrement value or scroll down list.
Back short (< 2 s)Configurable (factory setting: no function).Pass to higher menu level.Exit Edit mode without modification.
Back long (> 2s)Configurable (factory setting: enter/exit manual mode).--
Menu/OK short (< 2 s)Call main menu, enter sub-menu or enter Edit mode.-Exit Edit mode with modification.
Up + Down long (> 2 s)Start/stop auto-optimization.--
Down + Menu/OK very long (> 5 s)Call menu for level lockout.--

4.2 Language Selection

Upon first power-up, the user can validate the displayed language (flashing) with "OK" or select another language using "Up"/"Down" keys, then validate with "OK". To allow other users to select the language, the configuration parameter "Language selection enabled" must be set to "Yes" (Configuration > System Data). After language validation, this parameter is automatically set to "No". Device text language can be changed anytime in configuration settings.

4.3 Error Messages

DisplayPossible CauseMeasures
<<<<Below measurement range
Short circuit (sensor/line)
Rupture (sensor/line)
Polarity inversion
Check sensor and line (rupture, short circuit, polarity inversion). Check connection terminals.
>>>>Above measurement rangeCheck configuration (signal type, linearization, resistance range, scaling).
---Rupture (sensor/line)
Polarity inversion
Check configuration (signal type, linearization, resistance range, scaling). In case of error, the regulator switches to manual mode.

a Depending on the signal type (sensor); see "Technical Characteristics".

4.4 Additional Information

Detailed information on configuration and device operation can be found in the commissioning notice, interface description (Modbus), and ST editor notice. Refer to section 1.9 "Available Technical Documentation".

Ethernet Interface (Option): Ethernet interface settings are made using the Lantronix CPR Manager software. On-device or Setup software configuration is not required. Further information is available in the Modbus interface description.

5. Technical Characteristics

5.1 Analog Input

Thermocouples

The document lists various thermocouple types (Fe-CuNi, Cu-CuNi, NiCr-Ni, NiCr-CuNi, NiCrSi-NiSi, Pt10Rh-Pt, Pt13Rh-Pt, Pt30Rh-Pt6Rh) with their corresponding Type, Norm, ITS standard, measurement range, and precision.

Resistance Sensors

Details for Pt100, Pt1000, and KTY sensors are provided, including connection type (2/3 wires), ITS standard, measurement range, precision, and measuring current.

Rheostat and Resistance/Potentiometer

Specifications for Rheostats and Resistance/Potentiometers are given, including measurement range, precision, measuring current, ambient temperature influence, connection type, and line resistance.

Tension, Current (Normalized Signals)

Specifications for voltage (0-10 V, 2-10 V) and current (4-20 mA, 0-20 mA) signals are provided, including measurement range, precision, and input resistance/load voltage.

5.2 Digital Inputs

Input for Dry Contact: Closed contact: input active (Ron < 1 kΩ). Open contact: input inactive (Roff > 50 kΩ). Sampling cycle: 150 ms.

5.3 Analog Output

5.4 Digital Outputs

5.5 Interfaces

5.6 Display

18-segment LCD Displays:

5.7 Electrical Characteristics

5.8 Environmental Influences

5.9 Housing

a Maximum permissible ambient temperature is valid only for mounting with vertical display orientation.

6. China RoHS

Product Group: 702110, 702111, 702112, 702113, 702114.

China EEP Hazardous Substances Information:

Component NameLead (Pb)Mercury (Hg)Cadmium (Cd)Hexavalent Chromium (Cr(VI))Polybrominated Biphenyls (PBB)Polybrominated Diphenyl Ethers (PBDE)
Housing000000
Process connection000000
Nuts000000
Screw000000

This table is prepared in accordance with SJ/T 11364. 'o' indicates that hazardous substances are below the GB/T 26572 limit. 'X' indicates that hazardous substances exceed the GB/T 26572 limit in at least one homogeneous material.


File Info : application/pdf, 32 Pages, 1.73MB

PDF preview unavailable. Download the PDF instead.

RAYCHEM-IM-EU1715-TCONTROL05-FR ?srsltid=AfmBOorGAdC8-PEUn2PIEZJdWo Q EuRRr0dmvep8fnRDhpA8hkFPJjp

References

Adobe PDF Library 17.0 Adobe InDesign 20.3 (Windows)

Related Documents

Preview Raychem HWAT-T55 Thermostat User Manual
This document provides comprehensive information on the Raychem HWAT-T55 thermostat, including product description, features, functional description, installation, getting started, operation modes, temperature settings, parameter adjustments, troubleshooting, and technical data. It details how to use the thermostat for maintaining hot water pipe temperatures.
Preview Raychem Elexant 4010i: Single-Point Heat-Tracing Controller Specifications
Comprehensive technical specifications and overview of the Raychem Elexant 4010i, a touch-screen single-point heat-tracing controller designed for freeze protection and process temperature maintenance. Details features, control algorithms, monitoring capabilities, installation, communication, and ordering information.
Preview Raychem ETS-05 Electronic Thermostat Installation and Operation Guide
This guide provides detailed information on the Raychem ETS-05 electronic surface sensing thermostat, including its features, specifications, installation instructions, wiring diagrams, and maintenance procedures. The ETS-05 is designed for accurate temperature control of heating cables.
Preview Raychem HTC-915 Universal Heat Tracing Control System - Technical Specifications
Detailed technical specifications, application, electrical properties, and configuration guide for the Raychem HTC-915 Universal Heat Tracing Control System. Includes product overview, installation notes, and maintenance information.
Preview Raychem Flex Series NGC-30/NGC-40 System Panels and Skids for Heat Tracing Control
Comprehensive technical specifications and configuration details for Raychem's Flex Series NGC-30 and NGC-40 heat tracing control and monitoring systems, designed for reliable operation in hazardous and non-hazardous industrial environments.
Preview Raychem 1500-EX User Interface Terminal Installation Manual
Comprehensive installation guide for the Raychem 1500-EX user interface terminal, detailing its features, specifications, certifications, mounting, connections, and data communication for Raychem NGC systems.
Preview Raychem QTVR Self-Regulating Heating Cables: Product Overview and Specifications
Detailed information on Raychem QTVR self-regulating heating cables for electrical process temperature maintenance in nonhazardous and hazardous locations. Includes specifications, approvals, performance data, and ordering details.
Preview Raychem Elexant 4020i Installation Guide: Heat Tracing Control Module
Comprehensive installation guide for the Raychem Elexant 4020i, a touch-screen heat-tracing control module. Covers specifications, approvals, wiring diagrams, mounting, and safety conditions for electric heat tracing (EHT) applications.