User Manual for Zennio models including: ZPDEZTP, Motion detector with luminosity sensor for ceiling mounting

EyeZen TP

Joaquin

EyeZen TP - Zennio

EyeZen TP from Zennio is a device that aims at, among other functions, the detection of motion, the measurement and control of the room luminosity and the ...

EyeZen TP https://www.zennio.com Technical Support: https://support.zennio.com 4 1 INTRODUCTION 1.1 EYEZEN TP EyeZen TP from Zennio is a device that aims at, among other functions, the detection of motion, the measurement and control of the room luminosity and the detection of


File Info : application/pdf, 14 Pages, 1.08MB

PDF preview unavailable. Download the PDF instead.

Manual EyeZen TP EN v1.4 a
EyeZen TP
Motion detector with luminosity sensor for ceiling mounting
ZPDEZTP
Application program version: [1.4] User manual edition: [1.4]_a www.zennio.com

USER MANUAL

EyeZen TP
CONTENTS
Contents ........................................................................................................................................ 2 Document Updates ....................................................................................................................... 3 1 Introduction .......................................................................................................................... 4
1.1 EyeZen TP ...................................................................................................................... 4 1.2 Installation..................................................................................................................... 5 1.3 Start-Up and Power Loss ............................................................................................... 6 2 Configuration......................................................................................................................... 7 2.1 General .......................................................................................................................... 7 2.2 Motion Detector............................................................................................................ 9 2.3 Logic Functions ............................................................................................................ 10 ANNEX I. Communication Objects............................................................................................... 11

https://www.zennio.com

Technical Support: https://support.zennio.com 2

DOCUMENT UPDATES

EyeZen TP

Version
[1.4]_a

Changes
Changes in the application program: · Update of the Logic Functions, Heartbeat, Binary Inputs, and Presence Detector
· Reorganisation of ETS parameters.

Page(s)
-

https://www.zennio.com

Technical Support: https://support.zennio.com 3

1 INTRODUCTION

EyeZen TP

1.1 EYEZEN TP
EyeZen TP from Zennio is a device that aims at, among other functions, the detection of motion, the measurement and control of the room luminosity and the detection of occupancy within the room where it has been installed. It has been designed for ceiling or false ceiling mounting by means of the bundled accessories.
The most outstanding features of EyeZen TP are:
Sensor with configurable sensitivity. LED to indicate motion. Two colours of lenses: white and black. Motion detection:  6 motion detection channels.  Luminosity-dependent motion detection (optional).  Periodic and delayed sendings (binary, scene, HVAC, percentage). Occupancy detection:  1x occupancy detection channel.  Master / slave configuration.  Trigger upon door opening or closing.  Periodic and delayed sendings (binary, scene, HVAC, percentage). Luminosity measurement:  Configurable correction factor and offset.  Periodic sending or upon value change. 2 constant light control channels with configurable setpoints. Day / night configuration. 10 customisable, multi-operation logic functions. Heartbeat or periodical "still alive" notification.

https://www.zennio.com

Technical Support: https://support.zennio.com 4

1.2 INSTALLATION

EyeZen TP

EyeZen TP connects to the KNX bus through the on-board KNX connector.
Once the device is provided with power from the KNX bus, both the individual address and the associated application program may be downloaded.
This device does not need any additional external power since it is entirely powered through the KNX bus.

1

2

1. Detection LED indicator.

5

2. Retaining spring.

3. Test/Prog. button.

4. Test/Prog. LED.

5. KNX connector.

3 4
Figure 1. EyeZen TP. Elements
The main elements of the device are described next.
Programming button (3): a short press on this button sets the device into the programming mode, making the associated LED (4) light in red.
Note: if this button is held while plugging the device into the KNX bus, the device will enter the safe mode. In such case, the LED will blink in red every 0.5 seconds.
Detection notification LED (1): emits a red light flash when the sensor observes motion.
To get detailed information about the technical features of this device, as well as on the installation process and on security procedures, please refer to the corresponding Datasheet, bundled with the original packaging of the device and also available at www.zennio.com.

https://www.zennio.com

Technical Support: https://support.zennio.com 5

EyeZen TP
1.3 START-UP AND POWER LOSS
During the start-up of the device, the detection notification LED flashes red for one minute before the motion sensor is ready. Depending on the configuration, some specific actions will also be performed during the start-up. For example, the integrator can set whether the detection channels should start up enabled or disabled.

https://www.zennio.com

Technical Support: https://support.zennio.com 6

2 CONFIGURATION

EyeZen TP

2.1 GENERAL
After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by entering the parameters tab of the device.
ETS PARAMETERISATION From General screen it is possible to activate/deactivate all the required functionality.

Figure 2. General
Lens Color [White / Black]1: parameter to select the lens colour that EyeZen TP has installed, for correct sensor luminosity measurement.
Motion Detection [enabled]: enables the "Motion Detector" tab in the tree on the left. For more information, see section 2.2.
Logic Functions [enabled/disabled] enables or disables the "Logic Functions" tab in the tree on the left. For more information, see section 2.3.
Heartbeat (Periodic Alive Notification) [enabled/disabled]: incorporates a one-bit object to the project ("[Heartbeat] Object to Send `1'") that will be sent periodically with a value of "1" to notify that the device is still working (still alive).

1 The default values of each parameter will be highlighted in blue in this document, as follows: [default/rest of options].

https://www.zennio.com

Technical Support: https://support.zennio.com

7

EyeZen TP
Figure 3. Heartbeat
Note: the first sending after download or bus failure takes place with a delay of up to 255 seconds, to prevent bus overload. The following sendings match the period set.

https://www.zennio.com

Technical Support: https://support.zennio.com 8

EyeZen TP
2.2 MOTION DETECTOR
EyeZen TP incorporates six independent motion detection channels, two more for constant light control and one for occupancy detection.
Motion detection consists in sending objects to the bus whenever the device observes a moving body (or no longer observes it) in the environment of the room where it has been installed.
Constant light control consists in sending KNX orders to the dimmer device that controls the in-room luminaries so the ambient light level remains constant even if other light sources are present.
Occupancy detection is an algorithm that allows determining whether a particular space is under occupation no matter if the occupant moves or not (i.e., no matter if the device is detecting motion in the room or not).
It also allows setting different luminosity setpoints or object types for daytime and night time as well as activating or deactivating the motion indicator LEDs.
EyeZen TP can also set custom sensitivity of the motion sensor and measure the luminosity of the room by making certain adjustments. This measurement will be made according to the color of lens selected.
Please refer to the specific manual "Presence Detector" available in EyeZen TP product section at the Zennio website (www.zennio.com) for detailed information about the functionality and the configuration of the related parameters. Please note that references to presence detection in this manual in this case correspond to motion detection.

https://www.zennio.com

Technical Support: https://support.zennio.com 9

EyeZen TP
2.3 LOGIC FUNCTIONS
This module makes it possible to perform numeric and binary operations to incoming values received from the KNX bus, and to send the results through other communication objects specifically enabled for this purpose.
EyeZen TP can implement up to 10 different and independent functions, each of them entirely customisable and consisting of up to 4 consecutive operations.
The execution of each function can depend on a configurable condition, which will be evaluated every time the function is triggered through specific, parameterisable communication objects. The result after executing the operations of the function can also be evaluated according to certain conditions and afterwards sent (or not) to the KNX bus, which can be done every time the function is executed, periodically or only when the result differs from the last one.
Please refer to the "Logic Functions" user manual available under the EyeZen TP product section at the Zennio homepage (www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.

https://www.zennio.com

Technical Support: https://support.zennio.com 10

ANNEX I. COMMUNICATION OBJECTS

EyeZen TP

"Functional range" shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.

Number 1 2 3 4 5 6
7 8 9
10
11
12 13
14
15 16 17 18

Size 1 Bit 1 Byte 1 Byte

I/O Flags C - - T -
I C-W-C - - T -

2 Bytes I/O C R W - -

2 Bytes 2 Bytes 1 Byte

I/O C R W - O CR-TO CR-T-

2 Bytes I/O C R W - -

2 Bytes 2 Bytes 1 Byte
1 Bit 1 Bit 1 Bit

I/O C R W - O CR-TO CR-TI C-W-I C-W-I C-W--

1 Bit

I C-W--

1 Bit 1 Bit 1 Byte

O CR-TC - - T -
O CR-T-

Data type (DPT) DPT_Trigger
DPT_SceneNumber DPT_SceneControl
1.xxx
1.xxx DPT_Value_Lux
DPT_Scaling
1.xxx
1.xxx DPT_Value_Lux
DPT_Scaling DPT_DayNight DPT_DayNight
DPT_Enable
DPT_Enable
DPT_Switch DPT_Start DPT_Scaling

1 Byte O C R - T -

DPT_HVACMode

1 Bit
1 Bit 2 Bytes 2 Bytes

I C-W--
I C-W-I C-W-I C-W--

DPT_Window_Door
DPT_Start DPT_TimePeriodSec DPT_TimePeriodSec

Functional Range 0/1
0 - 63 0-63; 128-191
0/1
0/1
0% - 100%
0/1
0/1
0% - 100% 0/1 0/1 0/1
0/1
0/1 0/1 0% - 100% 1=Comfort 2=Standby 3=Economy 4=Building Protection
0/1
0/1 0 - 65535 0 - 65535

Name

Function

[Heartbeat] Object to Send '1' Sending of '1' Periodically

Scene Input

Scene Value

Scene Output

Scene Value

Correction Factor - Internal Sensor

[0, 80] x0.1

Offset - Internal Sensor

[-200, 200] Luxes

Luminosity - Internal Sensor Luxes

Luminosity - Internal Sensor %

Correction Factor - Additional Sensor

[0, 80] x0.1

Offset - Additional Sensor

[-200, 200] Luxes

Luminosity - Additional Sensor Luxes

Luminosity - Additional Sensor %

Day/Night

0 = Day; 1 = Night

Day/Night

0 = Night; 1 = Day

Detection LED

0 = Disable; 1 = Enable

Detection LED

0 = Disable; 1 = Enable Only During the Day

Occupancy: Output (Binary) Binary Value

Occupancy: Slave Output

1 = Motion Detected

Occupancy: Output (Scaling) 0-100%

Occupancy: Output (HVAC)

Auto, Comfort, Standby, Economy, Building Protection

Occupancy: Trigger
Occupancy: Slave Input Occupancy: Waiting Time Occupancy: Listening Time

Binary Value to Trigger the Occupancy Detection 1 = Detection from slave device 0-65535 s. 1-65535 s.

https://www.zennio.com

Technical Support: https://support.zennio.com 11

19
20 21 22 23 24
25, 35, 45, 55, 65, 75
26, 36, 46, 56, 66, 76 27, 37, 47, 57, 67, 77

1 Bit 1 Bit 1 Bit 1 Byte 1 Byte 1 Byte 1 Byte
1 Bit
1 Bit 1 Byte

I C-W-I C-W-O CR-TI C-W-I C-W-I C-W-I C-W--
I C-W--
O CR-TO CR-T-

DPT_Enable DPT_Enable DPT_Occupancy DPT_Scaling DPT_Scaling DPT_Scaling DPT_Scaling
DPT_Start
DPT_Switch DPT_Scaling

28, 38, 48, 58, 68, 78

1 Byte O C R - T -

DPT_HVACMode

29, 39, 49, 59, 69, 79 30, 40, 50, 60, 70, 80 31, 41, 51, 61, 71, 81 32, 42, 52, 62, 72, 82 33, 43, 53, 63, 73, 83
85, 101
86, 102 87, 103 88, 104
89, 105
90, 106 91, 107 92, 108 93, 109
94, 110

1 Bit 1 Bit 1 Bit 1 Bit 2 Bytes 2 Bytes 1 Byte

I C-W-I C-W-I C-W-I C-W-I/O C R W - O CR-TO CR-T-

1 Bit

I C-W--

1 Bit 1 Bit 1 Bit 1 Bit 2 Bytes 2 Bytes 1 Byte 1 Byte 2 Bytes 1 Byte 1 Byte 2 Bytes 2 Bytes 1 Byte

I C-W-I C-W-I C-W-I C-W-I C-W-I C-W-I C-W-I C-W-I C-W-I C-W-O CR-TI/O C R W - O CR-TO CR-T-

1 Bit

I C-W--

DPT_Enable DPT_Enable DPT_Start DPT_Start DPT_TimePeriodSec DPT_Value_Lux DPT_Scaling
DPT_Start
DPT_Enable DPT_Enable DPT_Start DPT_Start DPT_Value_Lux DPT_Value_Lux DPT_Scaling DPT_Scaling DPT_Value_Lux DPT_Scaling DPT_Scaling DPT_TimePeriodSec DPT_Value_Lux DPT_Scaling
DPT_Switch

https://www.zennio.com

0/1 0/1 0/1 0% - 100% 0% - 100% 0% - 100% 0% - 100%
0/1
0/1 0% - 100% 1=Comfort 2=Standby 3=Economy 4=Building Protection
0/1 0/1 0/1 0/1 0 - 65535
0% - 100%
0/1
0/1 0/1 0/1 0/1
0% - 100% 0% - 100%
0% - 100% 0% - 100% 0 - 65535
0% - 100%
0/1

EyeZen TP

Occupancy: Lock

0 = Unlock; 1 = Lock

Occupancy: Lock

0 = Lock; 1 = Unlock

Occupancy: Occupancy State 0 = Not Occupied; 1 = Occupied

Sensor Sensitivity

1-100%

Sensor 2 Sensitivity

1-100%

Sensor 3 Sensitivity

1-100%

Sensor 4 Sensitivity

1-100%

[Cx]

External

Motion

Detection

1 = Motion detected external sensor

by

an

[Cx] Output (Binary)

Binary Value

[Cx] Output (Scaling)

0-100%

[Cx] Output (HVAC)

Auto, Comfort, Standby, Economy, Building Protection

[Cx] Lock Status

0 = Unlock; 1 = Lock

[Cx] Lock Status

0 = Lock; 1 = Unlock

[Cx] Force State

0 = No Detection; 1 = Detection

[Cx] External Switch

0 = No Detection; 1 = Detection

[Cx] Length of Detection

1-65535 s.

[Cx] Luminosity

Luxes

[Cx] Luminosity

%

[CLCx] External Motion Detection

1 = Motion detected by an external sensor

[CLCx] Lock Status

0 = Unlock; 1 = Lock

[CLCx] Lock Status

0 = Lock; 1 = Unlock

[CLCx] Force State

0 = No Detection; 1 = Detection

[CLCx] External Switch

0 = No Detection; 1 = Detection

[CLCx] Setpoint

Setpoint Value (1-2000)

[CLCx] Setpoint During Day Setpoint Value (1-2000)

[CLCx] Setpoint

Setpoint Value (1-100)%

[CLCx] Setpoint During Day Setpoint Value (1-100)%

[CLCx] Setpoint During Night Setpoint Value (1-2000)

[CLCx] Setpoint During Night Setpoint Value (1-100)%

[CLCx] Dimming Value

Dimming Value (%)

[CLCx] Length of Detection 1-65535 s.

[CLCx] Luminosity

Luxes

[CLCx] Luminosity

%

[CLCx] Manual (Input)

Control:

On/Off

1-Bit

Control

Technical Support: https://support.zennio.com 12

EyeZen TP

95, 111

4 Bit

96, 112 97, 113

1 Byte 1 Bit

98, 114

4 Bit

99, 115

1 Bit

100, 116

1 Bit

117, 118, 119, 120, 121, 122, 123, 124, 125, 126, 127, 128, 129, 130, 131, 132, 133, 134, 135, 136, 137, 138, 139, 140, 141, 142, 143, 144, 145, 146,
147, 148 149, 150, 151, 152, 153, 154, 155, 156, 157, 158, 159, 160,
161, 162, 163, 164 165, 166, 167, 168, 169, 170, 171, 172, 173, 174, 175, 176,
177, 178, 179, 180 181, 182, 183, 184, 185, 186,
187, 188
189, 190, 191, 192, 193, 194, 195, 196, 197, 198

1 Bit
1 Byte
2 Bytes
4 Bytes 1 Bit 1 Byte
2 Bytes 4 Bytes 1 Byte 2 Bytes 2 Bytes

I C - W - - DPT_Control_Dimming

I C-W-O CR-T-

DPT_Scaling DPT_Switch

O C R - T - DPT_Control_Dimming

I C-W-O CR-T-

DPT_Enable DPT_Enable

0x0 (Stop) 0x1 (Dec. by 100%)
... 0x7 (Dec. by 1%)
0x8 (Stop) 0xD (Inc. by 100%)
... 0xF (Inc. by 1%)
0% - 100%
0/1
0x0 (Stop) 0x1 (Dec. by 100%)
... 0x7 (Dec. by 1%)
0x8 (Stop) 0xD (Inc. by 100%)
... 0xF (Inc. by 1%)
0/1
0/1

[CLCx] Manual Control: Relative Dimming (Input)

4-Bit Control

[CLCx] Manual Control: Absolute Dimming (Input)

1-Byte Control

[CLCx] Manual (Output)

Control:

On/Off

1-Bit

Control

[CLCx] Manual Control: Relative Dimming (Output)

4-Bit Control

[CLCx] Manual Control
[CLCx] Manual Control (Status)

0 = Disable; 1 = Enable 0 = Disabled; 1 = Enabled

I C-W--

DPT_Bool

0/1

[LF] (1-Bit) Data Entry x

Binary Data Entry (0/1)

I C - W - - DPT_Value_1_Ucount

0 - 255

[LF] (1-Byte) Data Entry x

1-Byte Data Entry (0-255)

I C-W--

1.xxx

0/1

[LF] (2-Byte) Data Entry x

2-Byte Data Entry

I C - W - - DPT_Value_4_Count

O CR-T-

DPT_Bool

O C R - T - DPT_Value_1_Ucount

O C R - T - DPT_Value_2_Ucount

O C R - T - DPT_Value_4_Count

O CR-T-

DPT_Scaling

O C R - T - DPT_Value_2_Count

O CR-T-

9.xxx

-2147483648 - 2147483647 [LF] (4-Byte) Data Entry x

0/1 0 - 255 0 - 65535 -2147483648 - 2147483647 0% - 100% -32768 - 32767 -671088.64 - 670433.28

[LF] Function x - Result [LF] Function x - Result [LF] Function x - Result [LF] Function x - Result [LF] Function x - Result [LF] Function x - Result [LF] Function x - Result

4-Byte Data Entry
(1-Bit) Boolean (1-Byte) Unsigned (2-Byte) Unsigned (4-Byte) Signed (1-Byte) Percentage (2-Byte) Signed (2-Byte) Float

https://www.zennio.com

Technical Support: https://support.zennio.com 13

Join and send us your inquiries about Zennio devices:
https://support.zennio.com
Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain). Tel. +34 925 232 002. www.zennio.com info@zennio.com


Microsoft Word 2016