Aldes MR Modulo: Adjustable Constant Airflow Regulator
READ AND SAVE THESE INSTRUCTIONS
SETTING THE AIRFLOW
Twist the rotating adjustment ring until the desired airflow is reached. Reference the correlation table at right and printed on the device. No tools required.
Illustration shows a small diameter Aldes MR Modulo device.
Illustration shows a hand rotating an adjustment ring on a larger diameter Aldes MR Modulo device to set the airflow.
Correlation Tables
P/N: 11016307 Ø 3" (80 mm) | ||||
---|---|---|---|---|
m³/h | CFM | m³/h | CFM | |
K | 20 | 12 | ||
J | 25 | 15 | ||
H | 30 | 18 | ||
G | 35 | 21 | 45 | 26 |
F | 40 | 24 | 50 | 29 |
B | 45 | 26 | 60 | 35 |
P/N: 11016308 Ø 4" (100 mm) | ||||
---|---|---|---|---|
m³/h | CFM | m³/h | CFM | |
L | 15 | 9 | ||
J | 20 | 12 | ||
H | 25 | 15 | ||
F | 30 | 18 | 70 | 41 |
E | 35 | 21 | 75 | 44 |
D | 40 | 24 | 80 | 47 |
C | 45 | 26 | 90 | 53 |
A | 55 | 32 |
P/N: 11016309 Ø 5" (125 mm) 10-50 CFM (15-90 m³/h) | ||||
---|---|---|---|---|
m³/h | CFM | m³/h | CFM | |
L | 15 | 9 | ||
H | 25 | 15 | 60 | 35 |
F | 30 | 18 | 65 | 38 |
E | 70 | 41 | ||
D | 45 | 26 | 75 | 44 |
B | 50 | 29 | 80 | 47 |
A | 85 | 50 |
P/N: 11016310 Ø 5" (125 mm) 60-110 CFM (100-190 m³/h) | ||
---|---|---|
m³/h | CFM | |
K | 100 | 59 |
J | 110 | 65 |
I | 120 | 71 |
H | 130 | 76 |
G | 140 | 82 |
E | 150 | 88 |
C | 160 | 94 |
A | 190 | 112 |
P/N: 11016311 Ø 6" (150 mm) | |||||
---|---|---|---|---|---|
m³/h | CFM | m³/h | CFM | ||
R | 100 | 60 | |||
P | 110 | 65 | |||
O | 120 | 70 | |||
M | 130 | 75 | |||
L | 140 | 80 | |||
K | 150 | 90 | |||
J | 160 | 95 | H | 170 | 100 |
G | 180 | 105 | |||
F | 190 | 110 | |||
E | 200 | 120 | |||
D | 210 | 125 | |||
A | 240 | 140 |
P/N: 11016313 Ø 8" (200 mm) | ||||
---|---|---|---|---|
m³/h | CFM | m³/h | CFM | |
U | 225 | 132 | ||
S | 250 | 147 | ||
Q | 275 | 160 | ||
N | 300 | 177 | ||
M | 325 | 191 | ||
J | 350 | 206 | ||
D | 400 | 235 |
P/N: 11016314 Ø 10" (250 mm) | ||
---|---|---|
m³/h | CFM | |
U | 300 | 175 |
R | 355 | 205 |
O | 400 | 235 |
L | 450 | 265 |
I | 500 | 295 |
G | 550 | 325 |
A | 650 | 385 |
Note: Certain letters correspond to two setpoints: one with the clip, and one without the clip.
INSTALLATION
The MR Modulo will push-fit into circular ducts in close proximity to a take-off or terminal. Orient the MR Modulo according to the airflow direction indicated on the device. Horizontal or vertical mounting is acceptable.
To avoid acoustic and aeraulic disturbance, provide the following distance between the device and the terminal (grille / diffuser / inlet):
- Exhaust Air: 1x the device diameter Ø
- Supply Air: 3x the device diameter Ø
Diagram illustrating recommended clearance distances for the MR Modulo in ductwork. For exhaust air, a distance of 1x the device diameter is shown. For supply air, a distance of 3x the device diameter is shown before the terminal (grille/diffuser/inlet).
MAINTENANCE
- MR Modulo performance is not altered by clogging, therefore it requires practically no special maintenance.
- If the intended application includes air heavily loaded with grease or dust, a fitting with an access panel or door, such as that used for flame dampers, should be used.
- Clean with soaped water. When cleaning, plug the hole on the plastic body, at the base of the bulb, to prevent any obstruction and any penetration of liquid or foreign body inside the bulb.
Diagram showing the Aldes MR Modulo device with a sticker. Text indicates to write the diameter and airflow setting on the provided sticker and place it directly onto the duct to show where the MR Modulo has been installed.
TYPICAL APPLICATIONS
Duct System
Diagram depicting a section of ductwork with multiple Aldes MR Modulo units installed in series.
Exhaust/Return Air
Illustrations showing the Aldes MR Modulo integrated into exhaust or return air duct systems, connecting to grilles or diffusers.
Supply Air
Illustrations showing the Aldes MR Modulo integrated into supply air duct systems, connecting to diffusers.