Ignition control replacement kit installation - Nortek Global HVAC

9 feb 2022 — Assembly, 100% lockout, required with vent damper. —. 257475 (1). Controller (UTEC #1003-638A). 257009 (1). —. Controller (UTEC #1003-514).


File Info : application/pdf, 4 Pages, 431.47KB

PDF preview unavailable. Download the PDF instead.

OPT-IGN-CNTRL (01-22) 134704-A
Revision: OPT-IGN-CNTRL (01-22) 134704-A Supersedes: CP-IGN CNTRL (05-17) PN134704R8
IGNITION CONTROLLER REPLACEMENT KIT INSTALLATION FOR DUCT FURNACES

UNITS WITH SERIAL NUMBER PILOT CODE 62, 63, 65, 66, OR 84
· Obsolete ignition controllers shown in Figure 1 and listed in Table 1 are no longer available from their manufacturer.

OBSOLETE

REPLACEMENT

PN 89488

PN 97547

PN 234012

PN 89314

PN 97782

PN 257010

PN 257009

Figure 1. Ignition Controllers

Pilot Code 62 66 63 65 84

Obsolete Manufacturer's No.
G67BG-2 G67BG-5 G67NG-2 G770NGC-4 G770NHC-1

Table 1.
PN 89314 97782 89488 97547 234012

Ignition Controllers

Replacement

Kit PN

Controller PN

Controller Description

257472

257009

Recycling without lockout--cannot be used with vent damper control

257473

257010

With lockout and 1-hour retry-- used with automatically-controlled vent damper

· Refer to the installation manual provided with the heater for important safety information.
· Refer to the replacement parts manual at www.reznorhvac.com for serial number information. All serial number codes apply to original equipment only.
· Ensure that all components listed in Table 2 are available before beginning installation.

Table 2. Ignition Controller Replacement Kit Components

Component

Description

Ignition control assembly
Wire assembly, TH (only one of these loose wires will be used) Controller mounting bracket assembly (used only on models F, FE, B, BE, RX, RG and X) Screw Label

Assembly, recycling without lockout Assembly, 100% lockout, required with vent damper Controller (UTEC #1003-638A) Controller (UTEC #1003-514) Wire assembly, red, 24V Wire assembly, black, MV Wire assembly, brown, MV/PV Wire assembly, blue, PV Wire assembly, green, GND BURNER Wire assembly, brown, 24V GND Wire assembly, red, SENSE Black Yellow Mounting bracket Screw, mounting bracket, #10 × 3/8 Control mounting, #8 × 3/8 Wiring

Kit PN

257472

257473

Component PN (Quantity)

257474 (1)

--

--

257475 (1)

257009 (1)

--

--

257010 (1)

--

173303 (1)

133108 (1)

98215 (1)

98214 (1)

257074 (1)

98215 (1)

257014 (1)

173307 (1)

122655 (1)

257012 (1)

96426 (2)

195638 (4)

257479 (1) 257478 (1)

INSTALLATION
 CAUTION 
Ignition controller PN 257010 with lockout is required on a unit with a vent damper. The controller has a safety feature such that once it is used with a vent damper, it will no longer operate a unit without a vent damper.

NOTE: Minimum flame proving signal strength is 0.2 microamps.
1. Turn OFF gas and electric power. 2. Open cabinet and mark and disconnect spark wire from spike connector on controller. 3. Leaving all other wires connected to ignition controller, disconnect other ends of wires from unit and remove
ignition controller. 4. For models F, FE, B, BE, RX, RG, and X, install controller mounting bracket and secure it to unit using two #10
× 3/8 mounting bracket screws. 5. Position replacement ignition controller in same orientation and mark and drill four 7/64-inch holes. 6. Secure replacement ignition controller to mounting bracket or to unit using four #8 × 3/8 screws. 7. Refer to Table 3 for special wiring instructions.

Reason
Replacing obsolete ignition controller PN 89488 or 89314
Replacing obsolete ignition controller on unit with automatic vent damper

Table 3. Special Wiring Instructions
Step 1. To connect ignitor lead to replacement controller, cut off Rajah connector (metal terminal) on spark wire. 2. Push back rubber boot and cut off terminal, cutting off no more than 1 inch of wire. 3. Remove rubber boot and push wire directly onto spike connector on controller. 1. Remove plug from controller. 2. Plug in wiring harness from vent damper. NOTE: The wiring harness electrically interlocks the vent damper to the controller. Unplugging either end results in a system shutdown.

8. Reconnect wires to replacement ignition controller as follows (see Figure 2): a. If unit has terminal block wiring, cut and strip ends as needed.
NOTE: All wires are connected to the ignition controller at the factory except to the TH terminal.
b. If existing wire from limit control is yellow, connect loose wire from yellow wire assembly from limit control to TH terminal. One wire from assembly will not be used.
c. If existing wire from limit control is black, connect loose wire from black wire assembly from limit control to TH terminal. One wire from assembly will not be used.
9. Affix wiring label: a. Select location for wiring label near current wiring diagram on unit. Do not put label on surface that will be hot when heater is operating and do not put it over existing wiring diagram. b. Wipe selected area with clean dry cloth, peel off backing, and adhere label.
10. Turn ON electric power and gas. 11. Follow lighting instructions with original ignition controller to relight heater. 12. Check for proper operation.
NOTE: Keep this manual for future reference.

2

OPT-IGN-CNTRL (01-22) 134704-A

Wiring Label 257478

Wiring Label 257479

Figure 2. Wiring Labels

OPT-IGN-CNTRL (01-22) 134704-A

3

Specifications and illustrations subject to change without notice or incurring obligations. Latest version of this manual is available at www.reznorhvac.com. ©2022 Nortek Global HVAC LLC, O'Fallon, MO. All rights reserved. OPT-IGN-CNTRL (01-22) 134704-A

