User Manual for Tekron models including: ITR Isolated Timing Repeater, ITR, Isolated Timing Repeater, Timing Repeater, Repeater

User Manual - Isolated Timing Repeater

A53463

User Manual - Isolated Timing Repeater


File Info : application/pdf, 17 Pages, 1.13MB

PDF preview unavailable. Download the PDF instead.

ITR Manual v1.7
ITR
USER MANUAL

because timing is everything

Level 1, 47 The Esplanade P.O.Box 31-285, Lower Hutt, New Zealand
Phone: +64 4 5667722 www.tekron.com

Page |1

Table of Contents
ITR............................................................................................................................................... 1 USER MANUAL............................................................................................................................ 1 Safety Symbols ........................................................................................................................... 3 Document Conventions.............................................................................................................. 3 Safety Warnings ......................................................................................................................... 4 Introduction................................................................................................................................ 5 Copper Input (Order Code D1) ................................................................................................... 5 Fiber Input (Order Code D2)....................................................................................................... 6 HV MOSFET (Order code D3) ..................................................................................................... 6 ITR Product Codes ...................................................................................................................... 8 LED Indicators........................................................................................................................... 10 ITR Inputs.................................................................................................................................. 10 Copper Inputs ........................................................................................................................... 10 Fiber Inputs............................................................................................................................... 10 ITR Outputs............................................................................................................................... 11 Copper Loop Output................................................................................................................. 11 Fiber Output ............................................................................................................................. 11 TTL Output................................................................................................................................ 11 RS422 /RS 485 Outputs ............................................................................................................ 11 RS 232 Output .......................................................................................................................... 11 MOSFET Output........................................................................................................................ 11 Optional AM IRIG-B Output...................................................................................................... 11 General User Guideline ............................................................................................................ 13 General Installation Guideline.................................................................................................. 14 Identification ............................................................................................................................ 14 Location .................................................................................................................................... 14 Power Supply............................................................................................................................ 14
Hazardous Voltage ............................................................................................................... 15 ITR Terminals ............................................................................................................................ 15 Earthing .................................................................................................................................... 17 Warranty .................................................................................................................................. 17 Contact ..................................................................................................................................... 17

because timing is everything

Page |2

Safety Symbols
The Safety symbols used on this product are: HAZARDOUS VOLTAGE Contact will cause electric shock or burn.
CAUTION Used to alert for important information.
PROTECTIVE EARTHING TERMINAL Protective Earthing Conductor 0.75mm2 shall be connected to GND terminal to protect against electric shock hazard. READ INSTRUCTION MANUAL Read the Instruction manual before installing or servicing this product.
Document Conventions
The Symbols used in this document are:
Is used to highlight additional information.
Is used to highlight any safety or regulatory points.

because timing is everything

Page |3

Safety Warnings
RESTRICTED ACCESS LOCATION The ITR should be installed in a Restricted Access location, accessible only using a lock and key or other means of security.
INSTALLATION ENCLOSURE The ITR should be installed on a DIN rail in an enclosure which acts as a Fire Enclosure and an Electrical Enclosure.
INSTALLATION PRACTICE The ITR should be installed by a suitably qualified personnel. Wiring, cable entries, conduit entries, knock-outs or glands should be installed in accordance with local wiring regulations.
HAZARDOUS VOLTAGE. Disconnect before working on product DC supply voltage up to 300V.
DUAL SUPPLY. Disconnect both supplies before working on the product Hazardous voltage may be present on DC supply and PR-, HV-SW-, HV-SW+ and PR+ terminals.
DISCONNECT DEVICE(S) Each Hazardous Voltage circuit which connects to the ITR shall incorporate a readily accessible disconnect device installed externally to the ITR. Disconnect devices shall have contact separation of at least 3mm.
HAZARDOUS VOLTAGE. Stray conductors or loose connections. Provide insulation and strain relief on all Hazardous Voltage terminations to protect against electric shock hazard.
OVERCURRENT PROTECTION ­ HV MOSFET Circuit from an external supply to HV MOSFET connections on the ITR shall be protected with an external 300 Vdc fuse rated at less than or equal to 200mA.
OVERCURRENT PROTECTION - POWER Circuit from an external supply to the PWR connections on the ITR shall be protected with 300 Vdc an external fuse rated at less than or equal to 1A.
PROTECTIVE EARTH The unit must be safety earthed whenever it is powered on, using the GND terminal as pictured above. The cable cross section must be equal to or greater than 0.75 mm2 (18 AWG).

because timing is everything

Page |4

Introduction
The Isolated Timing Repeater (ITR) is a compact DIN rail mountable signal repeater providing 2.0kV electrical isolation between the power and I/O wiring and 3.5kV electrical isolation between input and earth for connected Intelligent Electronic Devices (IEDs).
The ITR performs several tasks including converting time sync signals from fiber to copper, (and vice versa), boosting signal strengths and converting one type of signal to another.
The ITR is available in multiple variants: Copper Input (Order Code D1)

 Takes a copper-based pulse or IRIG-B signal as input.  Provides a non-isolated loop output of the input signal.  Provides isolated TTL, RS232 and RS422 as standard outputs  Provides isolated AM IRIG-B as an optional output.

because timing is everything

Page |5

Fiber Input (Order Code D2)

 Takes a copper or Fiber based pulse or IRIG-B signal as input.  Provides isolated Fiber, TTL, RS232 and RS422 as standard outputs  Provides isolated AM IRIG-B as an optional output.
HV MOSFET (Order code D3)

 Takes a Copper or Fiber based pulse or IRIG-B signal as input.  Provides isolated Fiber and HV MOSFET output as standard.
For the HV MOSFET wiring use a slow blow fuse with a 300V dc voltage rating, and no greater than a 200mA current rating.
Note: For the HV MOSFET ITR option, high voltage may be present on the HV terminals as well as the PWR input terminals. For this reason, there is a DUAL SUPPLY label affixed to warn of this as pictured above.
All three configurations can be ordered with a low, medium or high voltage power supply option with typical power drain of 5W max. The power to I/O isolation is 2kV.

because timing is everything

Page |6

For further reading you can refer to the following documents on the Tekron website www.tekron.com

 ITR Datasheet  Typical Installation Guide  Declaration of Conformity  RoHS Statement  Order Code Guide

https://tekron.com/dmsdocument/109 https://tekron.com/dmsdocument/103 https://tekron.com/dmsdocument/260 https://tekron.com/dmsdocument/110 https://tekron.com/dmsdocument/108

because timing is everything

Page |7

ITR Product Codes

The tables below summarize the ITR order options.

Copper

ITR Order Code Guide

Product Type

Description ITR Signal Repeater (Copper Version)

Order Code D1 - X X D1

Power Supply Options

Description Low Voltage Medium Voltage High Voltage

Connector Type 2 pin screw terminal
2 pin screw terminal
2 pin screw terminal

Specification

14 - 36 Vdc (360 ­ 140 mA)

1

20 - 75 Vdc (250 ­ 80 mA)

2

90 - 300 Vdc (56 ­ 17 mA)

3

Description TTL Output RS232 Output RS422 Output

Connector Type 2 pin screw terminal
2 pin screw terminal
2 pin screw terminal

Specification
0-5V, 150mA Fused
±10V (Typical unloaded), 15mA (max) ±5V, 50 RS422 Loads (RS485 Compatible)

Description

Connector

Signal

Specification

Type

Type

Options

DC IRIG-B to AM IRIG-B

2 pin screw

AM IRIG- 8V pk-pk, Internal

J

Converter

terminal

B

impedance:120

No Secondary Output

N/A

N/A

N/A

K

Fiber

ITR Order Code Guide

Product Type

Description ITR Signal Repeater (Fiber Version)

Description

Power Supply Options

Low Voltage Medium Voltage

High Voltage

Standard Outputs

Description Fiber

TTL Output RS232 Output RS422 Output

Options

Description
DC IRIG-B to AM IRIG-B Converter No Secondary Output

Order Code D2 - X X D2

Connector Type 2 pin screw terminal 2 pin screw terminal 2 pin screw terminal
Connector Type ST Fiber Connection
2 pin screw terminal 2 pin screw terminal 2 pin screw terminal
Connector Type 2 pin screw terminal N/A

Specification
14 - 36 Vdc (360 ­ 140 mA) 20 - 75 Vdc (250 ­ 80 mA)
90 - 300 Vdc (56 ­ 17 mA)

Specification

Multi-mode 50/125 µm, 62.5/125um, 100/140 µm, and 200 µm HCS cable supported,  = 820 nm
0-5V, 150mA Fused

±10V (Typical unloaded), 15mA (max) ±5V, 50 RS422 Loads (RS485 Compatible)

Signal Type AM IRIG-B
N/A

Specification
8V pk-pk, Internal impedance:120 N/A

1 2 3
J K

because timing is everything

Page |8

HV MOSFET

ITR Order Code Guide

Product Type

Description ITR Signal Repeater (HV MOSFET Version)

Power Supply Options

Description Low Voltage
Medium Voltage

High Voltage

Connector Type
2 pin screw terminal 2 pin screw terminal 2 pin screw terminal

Order Code D3 - X D3

Specification

14 - 36 Vdc (360 ­ 140 mA)

1

20 - 75 Vdc (250 ­ 80 mA)

2

90 - 300 Vdc (56 ­ 17 mA)

3

Output

Description Fiber
HV MOSFET Output ­ Screw Terminals

Connector Type ST Fiber Connector
2 pin screw terminal

Specification Multi-mode 50/125 µm, 62.5/125um, 100/140 µm, and 200 µm HCS cable supported,  = 820 nm 300 Vdc (+0V tolerance), 100mA

If 300V is used for both the supply and the HV MOSFET, then the input voltage tolerance must match that of the HV MOSFET = 300V +0V tolerance.

because timing is everything

Page |9

LED Indicators
ITRs have two green LEDs: PWR: On solidly when the correct power is supplied to the ITR. SIG: Lit when the input signal is at a logic high level. Normally this LED will flicker at a 100Hz rate when an IRIG-B signal is fed to the ITR.
ITR Inputs
Copper Inputs All ITR types can take a TTL level signal fed into the Input terminals at the top right of the ITR. The polarity of this driving signal must match that on the ITR label.
Note: The copper input signal can be any TTL signal such as DLCS IRIG-B, or it can be pulsed at TTL Levels (for example Pulse per second). The current loading at 5V is 2mA maximum.
If the ITR is part of a daisy-chained string of devices, the LOOP terminals on the Copper ITR can be used to wire to the next device in the daisy-chain. For the other ITR types, both the incoming and outgoing IRIG-B signals can be wired to the same Input terminals.
If the ITR is the last device in the daisy-chain, then the TERM connections can be shorted which will terminate the incoming IRIG-B signal with 120. This will correctly terminate a 120 balanced line recommended for signal distribution.
The input to earth isolation is 3.5kV minimum.
The ITR is designed with balanced inputs and outputs which allow the use of twisted pair cabling to distribute time synchronization signals and provide excellent noise immunity from induced voltages in a noisy substation environment.
Fiber Inputs The Fiber ITR types can take both a TTL copper input as well as a Fiber input signal. These two signal sources are fed to a logic AND gate. The output of this AND gate is then used to generate the ITR's Fiber signal and the Isolated copper output signals.
If both the copper and fiber inputs are used, the output is therefore the logical AND of the two input signals. Usually only one input is used at a time, or the two inputs need to be identical for meaningful outputs.
The fiber connection is ST Fiber,  = 820 nm, and multi-mode. 50/125 µm, 62.5/125 µm, 100/140 µm, and 200 µm HCS cable is supported.
The receiver sensitivity is -24 dBm.

because timing is everything

P a g e | 10

ITR Outputs
Typical input to Copper / Fiber output delays are 85±10nS.
Copper Loop Output The copper loop output from the ITR is wired in parallel with the ITR's copper input. It is therefore not electrically isolated from the copper input. Shorting the Term connection terminals will add a 120 resistor across the copper input effectively terminating the copper line.
Fiber Output The Fiber output signal mirrors the input from either the copper input or Fiber input signal. If both are present at the same time, then the Fiber output signal will be the logic AND of the two signals.
The fiber output is  = 820 nm, and multimode. 50/125 µm, 62.5/125 µm, 100/140 µm, and 200 µm HCS cable is supported.
Assuming 62.5/125 µm cable is used, and another Tekron device is receiving the fiber signal, the optical power budget is: 10.4 dB typical, 5 dB worst case.
The output delivers -15dBm of power in the typical case, -19 dBm in the worst case.

TTL Output The TTL Output is a 0 to 5V Pk signal capable of driving up to 150mA loading. This output is internally protected with a PTC self-resetting fuse.
RS422 /RS 485 Outputs The RS422/RS485 output is ±5V, or 50 RS422 unit loads (RS485 Compatible).
RS 232 Output The RS232 output is ±10V (typical unloaded), and capable of driving 15mA maximum.
MOSFET Output The HV MOSFET option provides a 300Vdc (+0V tolerance), 100mA, high speed MOSFET, fused with reverse polarity and ESD protection. The internal signal delay from input to HV MOSFET output is 60uS typically.

Optional AM IRIG-B Output
The Optional AM IRIG-B output provides an Amplitude modulated IRIG-B output signal nominally 8 V pk-pk with 120 output impedance.

because timing is everything

P a g e | 11

because timing is everything

P a g e | 12

General User Guideline
The ITR should only be maintained by suitably qualified personnel.
The safety considerations outlined in the following installation guideline should be followed and not compromised in any way. Fuses and protection devices should be replaced only with the same rated components. Protective earths should not be disconnected or removed.
The ITR does not generate any high voltages, but instead may have one or more high voltages fed to it as a power supply or for switching - as is the case for the HV MOSFET option. The operator should familiarise themselves with how to isolate all voltages fed to the ITR before working on it.
Once installed, the ITR requires no adjustments or setup. The unit has two LEDs that indicate the power supply is present and an input signal is present.

because timing is everything

P a g e | 13

General Installation Guideline
Identification Each ITR unit is shipped with an identification label on its side. This label provides details of the ITR product code, the power supply requirement and serial number.
Check the identification label on the side of the unit to ensure that the correct model has been supplied before proceeding with the installation!
Location INSTALLATION ENCLOSURE The ITR should be installed on a DIN rail in an enclosure which acts as a Fire Enclosure and an Electrical Enclosure.
RESTRICTED ACCESS LOCATION The ITR should be installed in a Restricted Access location, accessible only using a lock and key or other means of security.
INSTALLATION PRACTICE The ITR should be installed by suitably qualified personnel. Wiring, cable entries, conduit entries, knock-outs or glands should be installed in accordance with local wiring regulations.

Power Supply
The input voltage range is marked on the product label on the side of the ITR. Do not apply voltage outside this range. Note that either supply polarity is acceptable due to internal rectification.

OVERCURRENT PROTECTION ­ HV MOSFET Circuitry from an external supply to the HV MOSFET on the ITR shall be protected with a 300 Vdc fuse rated at  200mA.

OVERCURRENT PROTECTION - POWER For the power supply protection fuse:  Use a slow blow fuse  Calculate the fuse current rating using the following formula: -

Fuse

current

rating

=











  

Amps

Fuse voltage rating = At least the maximum supply voltage

For example, if using a 300V power supply, the rating should be =
33mA, so a 40mA (or above current) slow blow fuse rated at or above 300V dc would be suitable.

because timing is everything

P a g e | 14

Hazardous Voltage
HAZARDOUS VOLTAGE - Disconnect before working on product DC supply voltage up to 300V, (+0V tolerance). DUAL SUPPLY - Disconnect both supplies before working on the product Hazardous voltage may be present on DC supply and PR-, HV-SW-, HV-SW+ and PR+ terminals. DISCONNECT DEVICE(S) Each Hazardous Voltage circuit which connects to the ITR shall incorporate a readily accessible disconnect device installed externally to the ITR. Disconnect devices shall have contact separation of at least 3mm.
ITR Terminals

because timing is everything

P a g e | 15

HAZARDOUS VOLTAGE. Stray conductors or loose connections. Provide insulation and strain relief on all Hazardous Voltage terminations to protect against electric shock hazard.
The screw clamp terminals on the ITR accept 30 to 12 AWG solid or stranded cable (1.5mm Ø max). Please ensure that the wiring is terminated without exposing any bare copper wire.
Ensure all wiring to the ITR is done in a way so that if one screw termination becomes loose, then the wire will not be able to come in contact with other terminals. Each individual wire requires a secondary fixing method.
This can be achieved by securing all three power wires together, (+, - and GND), and similarly, for the wiring to the HV MOSFET option secure up to 4 wires as required.
An example of one way to achieve this is to terminate individual wires into crimp pin terminals (e.g. Multicomp MC29483), then heat shrink the crimped wires together so they support each other.

INSTALLATION ENCLOSURE The ITR should be installed on a DIN rail in an enclosure which acts as a Fire Enclosure and an Electrical Enclosure.
INSTALLATION PRACTICE The ITR should be installed by suitably qualified personnel. Wiring, cable entries, conduit entries, knock-outs or glands should be installed in accordance with local wiring regulations.

because timing is everything

P a g e | 16

Earthing
PROTECTIVE EARTH The unit must be safety earthed using the GND terminal (as pictured above) whenever it is powered on. The cable cross section must be equal to or greater than 0.75 mm2 (18 AWG).
Warranty
For terms and conditions of Tekron's Warranty see the Web Site http://tekron.com/about-tekron/warranty
Contact
The ITR is manufactured in New Zealand by Tekron International Limited. To contact Tekron please visit https://tekron.com/contact-us/

because timing is everything

P a g e | 17



References

Microsoft: Print To PDF