APPLICATION DESIGN GUIDE

Install

LIBERTY - Visa Lighting

PDF preview unavailable. Download the PDF instead.

762381xx-reva
Drawing: 762381XX

Rev: A

APPLICATION DESIGN GUIDE
LVPC-DIM for Lighting Control in Elevated-Security Spaces GENERAL INFORMATION

1717 West Civic Drive Milwaukee, WI 53209 414-354-6600
Design Modification Rights Reserved © Visa Lighting 2016

Note: in this document "load" can refer to a single luminaire, a single circuit in a multi-function luminaire, or a group of two or more fixtures or luminaire circuits.
DO NOT CONNECT AC POWER TO ANY LVPC-DIM SWITCH INPUT OR DIMMING OUTPUT.
SEE LVPC-DIM USER GUIDE FOR MOUNTING REQUIREMENTS AND INPUT/OUTPUT RATINGS FOR CONNECTED LOADS AND CONTROL SWITCHES.
Independent Load Control with Dimming
The LVPC-DIM must be set to "MODE 4" in this configuration; see the LVPC-DIM User Guide for more information. See the appropriate wiring diagram in these instructions.
The LVPC-DIM can be used to control up to three loads independently. Up to two of the loads can be set up to "pushto-dim" where a short press of a control switch will turn the connected fixture on and off, and a long press will dim the fixture up or down. Loads must be 0-10V dimmable to use the push-to-dim function. These loads will be controlled by switches wired to the SWITCH 1 and SWITCH 2 control inputs on the LVPC-DIM. Fixtures connected to the third load output will have on/off control only via the SWITCH 3 control input.
Independent Load Control with Dimming and System Override
The LVPC-DIM must be set to "MODE 1" in this configuration; see the LVPC-DIM User Guide for more information. See the appropriate wiring diagram in these instructions.
The LVPC-DIM can also be used to control up to two loads independently, with an additional system override capability. Up to two loads can be set up to "push-to-dim" where a short press of a control switch will turn the connected fixture on and off, and a long press will dim the fixture up or down. Loads must be 0-10V dimmable to use the push-todim function. These loads will be controlled by switches wired to the SWITCH 1 and SWITCH 2 control inputs on the LVPC-DIM.
One or more additional switches can be connected to the SWITCH 3 control input to act as system override switches. A short press of an OVERRIDE switches will turn on all loads connected to the LVPC-DIM and force their output to 100%. All other load control switches will be deactivated until an OVERRIDE switch is pressed again.
Optional Switch Lock-Out Function (all configurations)
By adding a maintained on/off switch (typical rocker or toggle switch) to the SW COM wiring, one or more load control switches can be locked out if/as needed. When a maintained LOCK-OUT switch is ON the affected switches will operate normally, but when the maintained switch is OFF the affected switches will not affect the state of the connected loads. This functionality may be useful if certain switches should be deactivated based on time of day or other factors. It may be implemented with either control scheme detailed above and on the following pages.

Sheet: 1 of 3

Eng: CMG

Date Drawn: 9/29/2023

!When using electrical equipment, basic safety precautions should always be followed, including the following: · Read all instructions carefully before installing and save for future use. · Make sure all connections are in accordance with the National Electrical Code and local regulations. · To avoid possible electric shock, be sure the power supply is turned off before servicing or installing the fixture · Service should be performed by qualified personnel. · These instructions may not cover all details or variations. If additional information is needed, please contact Visa Lighting.

When using electrical equipment, basic safety precautions should always be followed, including the following: ! · Read all instructions carefully before installing and save for future use. · Make sure all connections are in accordance with the National Electrical Code and local regulations. · To avoid possible electric shock, be sure the power supply is turned off before servicing or installing the fixture · Service should be performed by qualified personnel. · These instructions may not cover all details or variations. If additional information is needed, please contact Visa Lighting.

1717 West Civic Drive Milwaukee, WI 53209 414-354-6600
Design Modification Rights Reserved © Visa Lighting 2016

Drawing: 762381XX

120-277VAC

S5 ON/OFF

Rev: A

Sheet: 2 of 3

Eng: CMG

HOT 120-277VAC
SW1 SW2 SW3 SW COM

NEUTRAL CONDUCTORS NOT SHOWN
LVPC-DIM CONTROLLER SET TO "MODE 4"
LVPC-DIM MUST BE INSTALLED IN SUITABLE ENCLOSURE (BY OTHERS)

LOAD 3 DIM2 0-10V/COM LOAD 2 DIM1 0-10V/COM LOAD 1
MAX 5A PER LOAD 10A MAX TOTAL LOAD

Date Drawn: 9/29/2023

LIGHT 1

LIGHT 2

LIGHT 3

APPLICATION DESIGN GUIDE
LVPC-DIM for Lighting Control in Elevated-Security Spaces INDEPENDENT 3-LOAD CONTROL (2 WITH DIMMING) AND OPTIONAL LOCKOUT

S1A MOM N.O.

S2A MOM N.O.

S3A MOM N.O.

S4 (LOCKOUT) ON/ OFF

WHEN MAINTAINED SWITCH S4 IS CLOSED ("ON") THE CONNECTED LIGHTS CAN BE CONTROLLED BY BOTH THE SWITCHES IN THE STAFF ZONE AND THE SWITCHES IN THE PATIENT ZONE.
WHEN S4 IS OPEN ("OFF") CONTROL OF THE LIGHTS IS ONLY POSSIBLE FROM THE STAFF ZONE AND THE SWITCHES IN THE PATIENT ZONE WILL HAVE NO EFFECT.

S1B MOM N.O.

S2B MOM N.O.

S3B MOM N.O.

EXTERNAL (STAFF) ZONE

ROOM (PATIENT)
ZONE

SWITCH

FUNCTION

REQUIRED?

S1A, S1B

MOMENTARY PRESS TURNS LOAD 1 ON/OFF INEDPENDENTLY.

YES

HELD PRESS WHEN LOAD IS ON DIMS LOAD 1 UP/DOWN (IF EQUIPPED).

S2A, S2B

MOMENTARY PRESS TURNS LOAD 2 ON/OFF INDEPENDENTLY.

IF LOAD 2 IS

HELD PRESS WHEN LOAD IS ON DIMS LOAD 2 UP/DOWN (IF EQUIPPED). PRESENT

S3A, S3B

MOMENTARY PRESS TURNS LOAD 3 ON/OFF INDEPENDENTLY.

IF LOAD 3 IS PRESENT

S4

WHEN CLOSED (ON) ALL SWITCHES FUNCTION NORMALLY.

(LOCKOUT) WHEN OPEN (OFF) SWITCHES IN ROOM ZONE ARE LOCKED OUT.

OPTIONAL

S5

MASTER SYSTEM POWER (SWITCH OR DISCONNECT).

AS REQ'D

LINE VOLTAGE 0-10V DC DIMMING 5VDC CONTROL

When using electrical equipment, basic safety precautions should always be followed, including the following: ! · Read all instructions carefully before installing and save for future use. · Make sure all connections are in accordance with the National Electrical Code and local regulations. · To avoid possible electric shock, be sure the power supply is turned off before servicing or installing the fixture · Service should be performed by qualified personnel. · These instructions may not cover all details or variations. If additional information is needed, please contact Visa Lighting.

1717 West Civic Drive Milwaukee, WI 53209 414-354-6600
Design Modification Rights Reserved © Visa Lighting 2016

Drawing: 762381XX

Rev: A

Sheet: 3 of 3

Eng: CMG

Date Drawn: 9/29/2023

120-277VAC

S5 ON/OFF

HOT 120-277VAC
SW1 SW2 SW3 SW COM

NEUTRAL CONDUCTORS NOT SHOWN
LVPC-DIM CONTROLLER SET TO "MODE 1"
LVPC-DIM MUST BE INSTALLED IN SUITABLE ENCLOSURE (BY OTHERS)

LOAD 3 (NO CONNECT) DIM2 0-10V/COM LOAD 2 DIM1 0-10V/COM LOAD 1
MAX 5A PER LOAD 10A MAX TOTAL LOAD

LIGHT 1

LIGHT 2

LVPC-DIM for Lighting Control in Elevated-Security Spaces INDEPENDENT 2-LOAD (WITH DIMMING) WITH OPTIONAL OVERRIDE AND LOCKOUT

APPLICATION DESIGN GUIDE

S1A MOM N.O.

S2A MOM N.O.

S3 (OVER RIDE) MOM N.O.

S4 (LOCKOUT) ON/ OFF

WHEN MAINTAINED SWITCH S4 IS CLOSED ("ON") THE CONNECTED LIGHTS CAN BE CONTROLLED BY BOTH THE SWITCHES IN THE STAFF ZONE AND THE SWITCHES IN THE PATIENT ZONE.
WHEN S4 IS OPEN ("OFF") CONTROL OF THE LIGHTS IS ONLY POSSIBLE FROM THE STAFF ZONE AND THE SWITCHES IN THE PATIENT ZONE WILL HAVE NO EFFECT.

S1B MOM N.O.

S2B MOM N.O.

WHEN S3 IS PRESSED, LIGHTS 1 AND 2 WILL COME ON AT FULL OUTPUT AND ALL OTHER MOMENTARY SWITCHES (BOTH INSIDE AND OUTSIDE THEPATIENT ZONE) WILL BE LOCKED OUT UNTIL S3 IS PRESSED AGAIN.

EXTERNAL (STAFF) ZONE

ROOM (PATIENT)
ZONE

SWITCH S1A, S1B

FUNCTION

REQUIRED?

MOMENTARY PRESS TURNS LOAD 1 ON/OFF INDEPENDENTLY. HELD PRESS WHEN LOAD IS ON DIMS LOAD 1 UP/DOWN (IF EQUIPPED).

YES

S2A, S2B

MOMENTARY PRESS TURNS LOAD 2 ON/OFF INDEPENDENTLY. HELD PRESS WHEN LOAD IS ON DIMS LOAD 2 UP/DOWN (IF EQUIPPED).

IF LOAD 2 IS PRESENT

S3

MOMENTARY PRESS TURNS LOADS 1 AND 2 ON AT FULL OUTPUT AND

(OVERRIDE) LOCKS OUT ALL OTHER SWITCHES UNTIL S3 IS PRESSED AGAIN.

OPTIONAL

S4

WHEN CLOSED (ON) ALL SWITCHES FUNCTION NORMALLY.

(LOCKOUT) WHEN OPEN (OFF) SWITCHES IN ROOM ZONE ARE LOCKED OUT.

OPTIONAL

S5

MASTER SYSTEM POWER (SWITCH OR DISCONNECT).

AS REQ'D

LINE VOLTAGE 0-10V DC DIMMING 5VDC CONTROL

