Installation Guide for ACI models including: BACnet Modbus ROOM SERIES, BACnet Modbus, ROOM SERIES

I0000926

BACnet / Modbus ROOM SERIES

Room Product Instruction

Room | WorkACI

Installation Instructions

BN2130-R2 - alpscontrols.com


File Info : application/pdf, 8 Pages, 227.98KB

PDF preview unavailable. Download the PDF instead.

I0000926 0 ?
BACnet / Modbus ROOM SERIES

Installation & Operation Instructions

Phone: 1-888-967-5224 Website: workaci.com

GENERAL INFORMATION
The BACnet MS/TP / Modbus RTU Room Series sensor is designed for use with electronic controllers in commercial heating and cooling building management systems. The ACI BACnet MS/TP / Modbus RTU Room Series sensor can be ordered to monitor temperature, RH, or temp/RH in Commercial Room environments. It uses BACnet MS/TP or Modbus RTU for physical connection to a BAS or controller, has dip switches to set addresses and baud rate, parity and stop bits (Modbus RTU only), and has on board end-of-line termination. There is no analog output.
WIRING INSTRUCTIONS
16 to 22 AWG two conductor shielded cable is recommended for powering the sensors.
PRECAUTIONS · DO NOT RUN THE WIRING IN ANY CONDUIT WITH LINE VOLTAGE (24/120/230VAC).
· Remove power before wiring. NEVER connect or disconnect wiring with power applied.
· It is recommended that you use an isolated UL-listed Class 2 transformer when powering the unit with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by the shared transformer.
· If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC Transorb or diode, connects to the positive side of the power supply. Without these snubbers, coils produce very large voltage spikes when de-energizing that can cause malfunction or destruction of electronic circuits.

FIGURE 1: LAYOUT
FRONT VIEW

TERMINAL BLOCKS

LED END OF LINE TERMINATION
EN DIS

64

ADDRESS BAUD

32

V GN D- D+

16

8

4

2

1

SW4

2

4

1

2

1

PAR
ON
ON
1234
OFF

BAC MOD NET BUS

RESET BUTTON

DIP SWITCH

TABLE 1: WIRING CONNECTIONS

TERMINAL BLOCKS +V GN DD+

CONNECTIONS
Power Supply Positive 8-34VDC / 10-28VAC Power Supply Common or Ground EIA-485 Data Negative EIA-485 Data Positive

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com

Page 1

Version: 3.0 I0000926

MOUNTING INSTRUCTIONS
ACI recommends using BELDEN 3105 for communication wiring. This wire has 120 ohm input impendence. The terminal blocks allow for (1) or (2) wires to be connected in each position for daisy chaining. Daisy chain the RS-485 wiring and do not use "Star" or "T" wiring.
Avoid running communication wires next to AC line voltage wires. These can be sources of noise that can affect signal quality.

FIGURE 2: ENCLOSURE DIMENSIONS
1.12" (28.36 mm)
2.75" (69.85 mm)

FRONT

4.50" (114.30 mm)

For optimal temperature measurement, follow these tips: · Do not install on external walls · Avoid air registers, diffusers, vents, and
windows · Avoid confined areas such as shelves, closed
cabinets, closets, and behind curtains · Eliminate and seal all wall and conduit
penetrations. Air migration from wall cavities may alter temperature readings. · Do not install near heat sources. eg: lamps, radiators, direct sunlight, copiers, chimney walls, walls concealing hot-water pipes · A thermally-insulated backing should be used when fitting to solid walls (concrete, steel, etc.). ACI part: A/ROOM-FOAM-PAD
Separate the cover from the base. Attach the base directly to the wall or to a standard 2" x 4" junction box using the (2) #6-32 x 1" screws that are provided.

BOTTOM

FIGURE 3: MOUNTING DIAGRAM

MOUNTING SCREW (#6-32 x 1")

OPTIONAL INSULATING GASKET

BACKPLATE

48" - 60"

CIRCUIT BOARD

(1.2 - 1.5 m)

COVER

Refer to the wiring instructions (p. 1-2) to make necessary connections. After wiring, attach the cover to the base by snapping the top of the cover on first and then the bottom. Tighten the cover down, using the (2) 1/16" Allen screws located in the bottom of the housing. A 1/16" Hex driver is needed to secure the cover to the base.

Take care when mounting. Check local code for mounting height requirements. Typical mounting heights are 48-60"(1.22-1.52m) off the ground and at least 1.5'(0.5m) from the adjacent wall. The sensor should be mounted in an area where air circulation is well mixed, and not blocked by obstructions.

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com

Page 2

Version: 3.0 I0000926

BACnet MS/TP and Modbus RTU INTERFACE
The BACnet Master-Slave/Token-Passing (MS/TP) and Modbus Remote Terminal Unit (RTU) data link protocol uses EIA-485 as a two-wire, daisy chain network. A branch is a discrete chain of devices connected to a controller. The max number of devices per segment is 32, as per the BACnet and Modbus specifications. 4000 ft (1219.2 m) is the maximum recommended length for a segment, which includes all devices from the controller to the last device in the daisy chain.
BACnet or Modbus RTU protocol selection is done via SW4 switch. Place dipswitch #4 to the OFF position for BACnet and the ON position for Modbus. Refer to FIGURE 4.
ACI's BACnet sensors are master devices. Only master nodes are allowed to send and receive tokens on the MSTP network.
ACI's Modbus RTU sensors are slave devices. Only one master is connected to the bus and several slave nodes are connected to the same trunk. The Master initiates communication. The slave nodes only respond to a request from the Master. Slave nodes do not communicate with each other.
Each branch must have all devices connected with (+) connected to (+) and (-) connected to (-). If a shielded cable is used, this is not to be connected to the devices. The shield cable should only be connected on one end to earth ground, usually at the controller. The start and end of each branch should have a termination resistor at the device level or at the controller.
Each device must be configured for the correct baud rate and have a unique address in each branch. The baud rate for the branch is set by the controller. This product has auto-baud for ease of network configuration but setting the baud rate using the DIP switches is recommended. Note: Auto-baud feature does not function when Modbus is the selected protocol.

FIGURE 4: SW4 DIPSWITCH SETTINGS

ON ON OFF 1 2 3 4

SW4

DIP 1 ­ PAR2 (only applies to Modbus) DIP 2 ­ PAR1(only applies to Modbus) DIP 3 ­ OPEN (For Future Use) DIP 4 -- OFF is BACNET, ON is MODBUS

BAUD RATE SELECTION
By default, BACnet Protocol and Auto-Baud is factory set. If the sensor is field adjusted for Modbus RTU, the baud rate should be selected at this time to match the Master configuration. If Modbus RTU protocol is selected it is recommended the sensor unique address is selected at this time. Switches 8-10 are used to set the BACnet and Modbus baud rate. Refer to TABLE 2 for switch settings. Where (0) is OFF and (1) is ON. If the system's baud rate is known, it is recommended to set the specific baud rate to match the system. If the device is powered when a change is made, the device must be power cycled or reset for changes in baud rate to be made.

TABLE 2: BAUD RATE SELECTION

BAUD RATE Auto-Baud 9600 19200 38400 57600 76800 Reserved

SW 8 0 0 0 0 1 1 1

SW 9 0 0 1 1 0 0 1

SW 10 0 1 0 1 0 1 0

**Note: Auto-Baud not available for Modbus RTU.

EOL TERMINATION RESISTANCE SELECTION
RS-485 requires that the last device in a chain have a termination resistor. This is controlled using a jumper in the EN (enabled) position marked on FIGURE 5. When the jumper is set to EN (enabled), a 120 resistance is added in parallel to the data line. When the jumper is set to DIS (disable), the resistance is not added. By default, the jumper is placed in the DIS (disabled) position.

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com

Page 3

Version: 3.0 I0000926

FIGURE 5: EOL TERMINATION JUMPERS

END OF LINE TERMINATION ENABLED

END OF LINE TERMINATION DISABLED

EN DIS

EN DIS

RESET
The reset button can be used to reset the device without disconnecting power. The location of this button is shown in FIGURE 1 P.1 .
LED INFORMATION
One LED indicates four statuses. Solid green shows that power is good, but no data is transmitting. A solid Amber indicates that auto-baud is set and no data has been received to set a baud rate. Green/Amber flashing indicates data is being transmitted or received. Solid Red LED status indicates an error state, usually loss of communication on the network. If BACnet is the selected protocol, and this status remains for 10 times the APDU timeout, the device will automatically reset. If this state remains longer than that, reset the device.
ADDRESS SELECTION
Switches 1-7 are used to set the BACnet and Modbus addressing. Refer to TABLE 3 for switch settings. Each device in a network branch must have a unique address. The value of each position is printed on the board. By default, the address is (0). Note: (0) cannot be used if Modbus RTU protocol is selected and will require a unique address. If the device is powered when a change is made, the device must be power cycled or reset for changes in address to be made.

TABLE 3: ADDRESS SELECTION

SW SW SW SW SW SW SW 1 2 3 4 5 67 ADDRESS (64) (32) (16) (8) (4) (2) (1)

0

0 0 0 0 0 00

1

0 0 0 0 0 01

12

0 0 0 1 1 00

DEVICE CONFIGURATION THROUGH BACnet
DEVICE INSTANCE
The Device Instance, by default, is 1035000 plus the Address. For example, an Address of 21 results in a default address of 1035021. This can be changed once the device is connected to the network, but each device instance must be unique within the network, not just this segment.
DEVICE NAME
By default, the device name is based on the type of device and the address. The device name can be a character string up to 32 characters in length. This can be changed once the device is connected to the network. For example: Temperature Sensor - 034. The device name must be unique throughout the entire BACnet network, not just this segment.
TEST MODE BACnet
For the Sensor objects (AI0 and AI1), a test mode can be set by writing the Boolean value true to the "out-of-service" property. Then the present-value can be set to any valid test value the user requires. This allows a user to test reactions to specific values returned by this device.
DEVICE LOCATION
The device location is optional but is intended to allow for further definition of the device's location. The device location can be a character string up to 64 characters in length.
DEVICE DESCRIPTION
By default, the device description is optional but is intended to allow for further information about the device or its environment. The device location can be a character string up to 64 characters in length.

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com

Page 4

Version: 3.0 I0000926

TEMPERATURE UNITS CONFIGURATION
For temperature, the units of measure can be configured using BACnet. By writing to the units property of the temperature sensor (AI0), the reported temperature units can be changed. TABLE 4 shows the values to write.

TABLE 4: UNIT SETTING

UNITS °F K °C

VALUE 64 63 62

TEMPERATURE AND RH OFFSET
This device allows for a temperature offset of +/-5C (9F) and an RH offset of +/-10%. By default, these values are set to 0, meaning no offset is added.
These are set by writing to the present value of the Temperature Calibration Offset (AV0) or RH Calibration Offset (AV1). The value written must be within the specified range or an error will be returned. To set back to factory settings, write any changed values to 0.

TABLE 5: BACnet OBJECT TABLE

OBJECT TYPE OBJECT ID

Device

- - - - - - - - - -

Analog

AI-0

Inputs

AI-1

Analog

AV-0

Values

AV-1

OBJECT NAME

RANGE BACnet ENGINEERING UNITS

BN11x0

0-4194302 - - - - - - - - - - - - - - - - - - - - - - - - - -

Temperature Sensor 34.7 - 122.0 degrees-Fahrenheit (64) - default

RH Sensor

0.0 - 95.0 percent-relative-humidity (29)

Temperature

-9.0 - 9.0 delta-degrees-Fahrenheit (120)

Calibration Offset

RH Calibration Offset -10.0 -10.0 percent-relative-humidity (29)

PIC STATEMENT QR

Note: The table shows all objects for Temperature and RH. If you have a Temperature only model, the RH objects(AI-1 and AV-1) will not be present. If you have a RH only model, the Temperature objects (AI-0 and AV-0) will not be present.

DEVICE CONFIGURATION THROUGH MODBUS RTU

MODBUS RTU DATA BITS, PARITY, AND STOP BITS SELECTION
Confirm Modbus Protocol is selected via dipswitch #4 on SW4 - see FIGURE 5. The device that requests information is called the Modbus Master and the devices giving the information are Modbus Slaves. The Modbus sensors are slave devices and the number of Data Bits needs to be the same as in the Master device configuration. ACI's Modbus RTU sensors utilize 8 data bits during communication exchange.

Parity and stop bit selection is performed via the SW4 switch located on the board. Dipswtiches #1 and #2 are adjusted to select the Parity and stop

TABLE 6: PARITY AND STOP BITS

PAR 2

PAR 1 Mode (Databits-Parity-Stop Bits)

0

0

8-Even-1

0

1

8-Odd-1

1

0

8-None-2

1

1

8-None-1 (Non-Standard)

bits - see TABLE 6. Where (0) is OFF and (1) is ON. If BACnet protocol is selected these dipswitches are irrelevant.
TEST MODE Modbus RTU
There are 5 data values in test mode. Coil 1001, Holding Registers (HR) 1001 and 1002, and the Input Registers (IR) 0003 and 0004 for Temp and RH values. When Coil 1001 is enabled, reading IR 0003 and 0004 will respond with the values in HR 1001 and 1002, other wise they will respond with the actual sensor values. General process for this is to write initial test values to HR 1001 and 1002, Enable Coil 1001 and then read as normal from IR 0003 and 0004. While Coil 1001 is enable, it is possible to write a change of value to IR 1001 and 1002, which will be reflected in the next read from IR 0003 and 0004. When testing completed, disable Coil 1001. The status of Coil 1001 and HR 1001 and 1002 are not persistent between reset/power cycle.

Page 5

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com

Version: 3.0 I0000926

MODBUS RTU MODEL
Modbus data model: Four (4) primary data tables (addressable registers) · Discrete Input (read only bit). · Coil (read / write bit). · Input register (read only 16 bit word, interpretation is up to application). · Holding register (read / write 16 bit word).

MODBUS RTU MAP

REFERENCE 1001
1

ADDRESS 1000
0

NAME Test Mode Enable

DESCRIPTION
COILS CL
0 = Disable Test Mode. IR3 and IR4 will read with current Sensor Value. 1 = Enable Test Mode. IR3 and IR4 will read with the values stored in HR1001 and HR1002 .

Sensors Present

INPUT REGISTER IR
For each bit location: 0 = Sensor not present 1 = Sensor present

2 3
4
2001
2002
2003 2004 9001
9002
9003 Thru 9006 9007 Thru 9010 9011 Thru 9016
1

1 2
3
2000
2001
2002 2003 9000
9001
9002 Thru 9005 9006 Thru 9009 9010 Thru 9015
0

Reserved
Temperature Sensor Value

Bit 0 - Temperature Sensor Bit 1 - RH sensor N/A
For example, a value of 312 would represent 31.2 Degrees of the units selected in HR1. Signed Integer.

RH Sensor Value

For Example: A value of 429 would represent 42.9% Relative Humidity.

Temperature Range Temperature range Minimum value (Tenths). Signed Integer. Min

Temperature Range Max RH Range Min RH Range Max Unsigned Integer Test Value

Temperature range Maximum value (Tenths). Signed Integer.
Relative Humidity range Minimum value (Tenths) Relative Humidity range Maximum value (Tenths) Always reads a value of 12345. For testing proper communication and interpretation of values.

Signed Integer Test Always reads a value of -12345. For testing proper communication

Value

and interpretation of values.

Test String Test Value Always reads a string value of "-123.45" (Null terminated). For testing proper communication and interpretation of values.

Serial Number

Non-null terminated character string of the Serial Number. For example, "12345678"

Firmware Version

Non-null terminated character string of the Firmware Version. For example, "02.00.000.90"

HOLDING REGISTER HR

Temperature Units

Value - Units: 62 - Degrees Celsius 63 - Degrees Kelvin 64 - Degrees Fahrenheit

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com

Page 6

Version: 3.0 I0000926

2
3
1001 1002 9001 Thru 9016 9017 Thru 9048
9049 Thru 9080

1
2
1000 1001 9000 Thru 9015 9016 Thru 9047
9048 Thru 9079

HOLDING REGISTER HR

Temperature Offset Value
RH Offset Value
Test Mode Temperature Value

Temperature Offset Value (Tenths) Signed Integer. User can set an offset that will be added to Temperature sensor and reflected in IR3. Range of -5.0 to 5.0 degrees Celsius/degrees Kelvin (-9.0 to 9.0 degrees Fahrenheit). For example, writing -16 would add an offset of -1.6 degrees.
Relative Humidity Offset (Tenths)
User can set an offset that will be added to RH sensor and reflected in IR4. Range of -10.0 to 10.0 %RH.
For example, writing -16 would add an offset of -1.6 %RH. User can set what temperature value (Tenths) that would be returned when reading IR3 and Test Mode is Enabled in CL1001. For Example -400 would be -40.0.

Test Mode RH Value User can set what RH value (Tenths) that would be returned when reading IR4 and Test Mode is Enabled in CL1001.

Device Name

Device Name, Device Location, and Device Description are user settable character strings (Null terminated) that can be used to allow for system customization and device identification.

Device Location

For example:
Device Name (Modbus 9001 thru 9016) could be set to a system ID: "S2253"

Device Location (Modbus 9017 thru 9048) could be set to: Device Description "Building 5, Floor 2, Duct 3"

Device Description (Modbus 9049 thru 9080) could be set to: "Cold air return sensor"

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com

Page 7

Version: 3.0 I0000926

PRODUCT SPECIFICATIONS

Supply Voltage: Current Consumption: Temperature Measurement Range: Temperature Measurement Accuracy: Temperature Calibration Offset: RH Measurement Range: RH Measurement Accuracy: RH Calibration Offset: Temperature / RH Update Rate: Communication Protocol: Sensor Addresses:
Supported Baud Rates:
Device Instance Number: Parity (Modbus RTU) Stop Bits (Modbus RTU) Data Bits (Modbus RTU) Connections / Wire Size: Terminal Block Torque Rating: Operating Temperature Range: Storage Temperature Range: Operating Humidity Range: Enclosure Material / UL Flammability:

12 to 36 VDC / 24 VAC +/- 10%, 50/60 Hz (Reverse Polarity Protected) 25 mA maximum (0.67 VA) 35 to 122°F (1.5 to 50°C) @ 77°F (25°C): +/- 1.0°F (+/- 0.5°C) +/- 9°F (+/- 5°C) (Field Configurable) 0 to 100% @ 77°F (25°C): +/- 2% from 10 to 90% RH +/- 10% RH (Field Configurable) 4 seconds BACnet MS/TP or Modbus RTU = Field Selectable; EIA RS-485 0 to 127 (0 (Default - Must be changed if Modbus RTU is selected protocol); Field Selectable) Auto Baud (Default, BACnet Only), 9600, 19200, 38400, 57600, 76800, 115200 (Field Selectable) 1035000 + Address (example: Address 127 = 1035127; Field Configurable) None/Even/Odd = Field Selectable 1 or 2 = Field Selectable 8 Screw Terminal Blocks / 16 AWG (1.31 mm2) to 22 AWG (0.33 mm2) 0.45 lbf-in (0.5 Nm) nominal 35 to 122°F (1.5 to 50°C) -40 to 185°F (-40 to 85°C) 10 to 95% RH, non-condensing ABS Plastic / UL94-HB

WARRANTY
The ACI BACnet and Modbus RTU Room Series temperature sensors are covered by ACI's Five (5) Year Limited Warranty, which is located in the front of ACI'S SENSORS & TRANSMITTERS CATALOG or can be found on ACI's web site: www.workaci.com.

W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with household waste. Do not burn.

BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI). BTL is a registered trademark of BACnet International.

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com

Page 8

Version: 3.0 I0000926

