Instructions for RAB models including: X17FA140SF, X17, FA Field Adjustable Dusk to Dawn LED Flood Light, X17FA140SF X17 FA Field Adjustable Dusk to Dawn LED Flood Light, X17 FA Field Adjustable Dusk to Dawn LED Flood Light, Field Adjustable Dusk to Dawn LED Flood Light, Adjustable Dusk to Dawn LED Flood Light, Dusk to Dawn LED Flood Light, LED Flood Light, Flood Light

Download PDF Instruction Manual

RAB X17FA35 35W LED Floodlight, 5034 Lumens, 120-277V, 3000K, 4000K and 5000K Color Temperature, 80 CRI, Bronze

Installation Instructions

Floodlights 13243/14129/13616 Lumens X17 105W Field Adjustable Cc | Crescent Electric Supply Company

X17 Flood Field Adjustable 80W LED 120-277V 3000K-4000K-5000K Knu | Crescent Electric Supply Company


File Info : application/pdf, 2 Pages, 438.17KB

PDF preview unavailable. Download the PDF instead.

rab-x17fa80-installationinstructions-22
INSTRUCTIONS
X17TM FA FIELD ADJUSTABLE INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

15-35W 60-80W

60-80W 105-140W

60-80W 105-140W

IMPORTANT

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE. RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside.
WARNING: Do not use an electric generator to test LED fixtures.
WARNING: Min 75°C SUPPLY CONDUCTORS.

KNUCKLE MOUNT

SLIPFITTER MOUNT

(suitable for 15W, 35W, 60W, 80W)
To ensure weatherproof seal, apply weatherproof silicone sealant around the edge of the junction box (not supplied). This is especially important with an uneven wall surface.
1. Secure the fixture to a 1/2" NPS hole in the junction box or landscape post as shown in Fig. 1. Seal arm thread using Teflon® tape or silicone sealant.
2. Make appropriate wire connections per NEC in an approved enclosure (not included) see Fig. 8.
3. The Knuckle Arm allows 180° of vertical aiming adjustment depending on the mounting position as shown in Fig. 2.

(suitable for 60W, 80W, 105W, 140W)
1. Place the Slipfitter over the Tenon and secure the Fixture with the Screws on the side of the Slipfitter as shown in Fig. 3.
2. Make appropriate wire connections per NEC in an approved enclosure (not included) see Fig. 8.
3. Loosen the Locking Bolt and swivel Fixture to desired angle.
4. Tighten the Locking Bolt.
90°

Fixture

Locking Bolt

Knuckle Arm Pole

Slipfitter Mount
Fig: 3

Fig: 1

Fig: 2

Suport Wire

TRUNNION MOUNT
(suitable for 60W, 80W, 105W, 140W)
To adjust the angle of the Fixture using the Trunnion (Fig. 4): 1. Loosen the Pivot Bolts and Angle Locking Screws. 2. Make appropriate wire connections per NEC in a approved
enclosure (not included) see Fig. 8. 3. Adjust fixture to desired angle. 4. Tighten Pivot Bolts and Angle Locking Screw.

Angle Locking Screw

Fig: 4

Pivot Bolts

INSTRUCTIONS
X17TM FA FIELD ADJUSTABLE INSTALLATION

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

FIELD ADJUSTMENT
Follow instructions below to change fixture Color Temperature (CCT) from the factory settings and Photocell On/Off option.
Factory Settings: 4000K (CCT)
1. Remove Selector Switch Caps by turning counter clockwise using a flat head screwdriver Fig. 5.
2. Locate the Selector Switches on the fixture Fig. 6,7. 3. Select Color Temperature (CCT) by sliding the respective switch
to the desired value.
4. Select Photocell On/Off option by sliding respective switch to the desired value.

Fig: 5

Selector Switch Caps

0-10V DIMMABLE WIRING

Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. Units ordered with /480 suffix are 480V. For 0-10 Dimming, follow the wiring directions as shown in Fig. 8.
1. Connect the black/brown fixture lead to the LINE supply lead.
2. Connect the white/blue fixture lead to the COMMON supply lead.
3. Connect the green/yellow wire from fixture to supply ground. Do NOT connect the GROUND of the dimming fixture to the output.
4. Connect the purple fixture lead to the DIM V+ lead.
5. Connect the pink/gray fixture lead to the DIM V- lead.
6. Cap the yellow fixture lead, if present. Do NOT connect.

Fig: 8

LINE

BLACK/BROWN

COMMON

WHITE/BLUE

(+) DIM V+

PURPLE

(-) DIM V-

PINK/GRAY

15W, 35W, 60W

GROUND

GREEN/YELLOW

Fig: 6

CCT Selector Switch

Photocell Selector Switch

105W, 140W

CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized. 1. Clean glass lens with non-abrasive glass cleaning solution. 2. Do not open the fixture to clean the LED. Do not touch the LED.

TROUBLESHOOTING

Fig: 7

1. Is the fixture grounded properly?

CCT Selector Switch Photocell Selector Switch

2. It is recommended to wear gloves to avoid injury during installation.
3. If any smoke or spark, please turn off the power immediately.

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

Easy Answers

© 2021 RAB LIGHTING Inc.