Potter PPAD100-MIM Micro Input Module - Fire Alarm Resources - Free fire alarm PDF manuals, documents, installation instructions, and technical specifications


File Info : application/pdf, 2 Pages, 1.02MB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676759154
Features
· One Class B contact monitoring input · Small size allows mounting in most electrical boxes · SLC Class a, Class X & Class B · 6" pigtail wiring connections · product includes a 5 year warranty · UUKL Listed for Smoke Control

PAD100-MIM
Micro Input Module

Description
The paD100-MIM is used to monitor the status of an initiating device(s) that contain a normally open set of dry contacts. The module is enclosed in a plastic case to protect against inadvertent shorts and ground faults. The case can be mounted using a single screw. The paD100-MIM has a status indicator LED to indicate communication and alarm condition. In normal condition, the LED flashes when the device is being polled by the control panel. When the input is activated, the LED will flash at a fast rate.
Application
The micro input module (paD100-MIM) is compatible with potter's IPA and AFC/ARC series addressable fire alarm control panels. generally the paD100-MIM is used to monitor pull stations and other devices where the module is installed in an electrical box or enclosure behind the device being monitored.

Technical Specifications

Operating Voltage Max SLC Standby Current Max SLC alarm Current IDC Input Circuit Wiring Max Wiring Resistance of IDC Max Wiring Capacitance of IDC EOL Resistor Operating Temperature Range Operating Humidity Range Max no. of Module per Loop
Dimensions

24.0V 200A 200A Class B 100  1F 5.1K  32 to 120ºF (0 to 49ºC) 0 to 93% (non-condensing)
127 units 1.75" (44.5mm)L × 1.36" (34.5mm)W× .43" (11mm)D

Mounting Options

2-1/2" (64mm) deep single-gang box

Shipping Weight

0.3 lbs

potter Electric Signal Company, LLC · St. Louis, MO · phone: 800-325-3936 8830079 - REV D · 12/18
firealarmresources.com

· www.pottersignal.com
pagE 1 OF 2

PAD100-MIM
Micro Input Module
Setting the Address
Each addressable SLC device must be assigned an address. The address is set using the DIp switch located on the front of the paD100-MIM. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device: 1. power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits.
Wiring Diagram
Fig 1

FROM FACP OR PREVIOUS DEVICE AND TO NEXT DEVICE

Ordering Information

Model paD100-MIM

Description Micro Input Module

Stock No. 3992700

TO NORMALLY OPEN MONITORED DEVICE 5.1K OHM REQUIRED Part #3005013

potter Electric Signal Company, LLC · St. Louis, MO · phone: 800-325-3936 · www.pottersignal.com

8830079 - REV D · 12/18

pagE 2 OF 2