LS ELECTRIC XGB XBE-TN32A Digital Output Module

For the latest prices, please check AutomationDirect.com.

Product Overview

The XBE-TN32A is a discrete output module from the LS ELECTRIC XGB series. It features 32 output points, operates at 12-24 VDC with a sinking output type, and has one common for all 32 points. Each point can handle up to 0.2A, with a total common current of 2A. This module requires the XTB-40H terminal block and a C40HH-xxSB-XBI cable for connection.

General Specifications

Item Specification
Input Point 32 point
Insulation Method Photocoupler insulation
Rated Load Voltage 12/24 VDC
Load Voltage Range 10.2 - 26.4 VDC
Maximum Load Current 0.2 A/point, 2A/1COM
Off Leakage Current 0.1 mA or less
Maximum Inrush Current 0.7 A/10ms or less
Maximum Voltage Drop (On) 0.4 VDC or less
Over Voltage Protection Zener Diode
Response Time (Off → On) 1ms or less
Response Time (On → Off) 1ms or less (rated load, resistive load)
Common Method 32 point / COM
Proper Cable Size 0.3 mm²
Current Consumption 120mA (when all point On)
External Power Supply 12/24 VDC ± 10% (ripple voltage 4 Vp-p or less)
Operation Indicator Output On, LED On
External Connection Method 40 pin connector
Weight 60g

I/O Module Configuration

The base rack slot number determines the Direct Variable name for the module. Each slot is automatically allocated 64 input points and 64 output points. The actual input Direct Variable assignments are used as follows:

Part Number PLC Memory Allocation Actual I/O Direct Variable
XBE-TN32A Input: %IX0.z.0 – %IX0.63
Output: %QX0.z.0 - %QX0.63
%QX0.z.0-%QX0.z.31

Note: "z" denotes the module slot (2 to 8).

For a quick start video on registering and configuring any Digital I/O Module, refer to the Digital Module Setup guide.

Wiring and Circuit Configuration

The XBE-TN32A module utilizes a 40-pin connector and requires an XTB-40H terminal block and a C40HH-xxSB-XBI cable.

Circuit Configuration

Module Pins XTB-40H Terminal Direct Variable Description
A1 B20 %QX0.z.0 Output 0
B1 B19 %QX0.z.1 Output 1
A2 B18 %QX0.z.2 Output 2
B2 B17 %QX0.z.3 Output 3
A3 B16 %QX0.z.4 Output 4
B3 B15 %QX0.z.5 Output 5
A4 B14 %QX0.z.6 Output 6
B4 B13 %QX0.z.7 Output 7
A5 B12 %QX0.z.8 Output 8
B5 B11 %QX0.z.9 Output 9
A6 B10 %QX0.z.10 Output 10
B6 B09 %QX0.z.11 Output 11
A7 B08 %QX0.z.12 Output 12
B7 B07 %QX0.z.13 Output 13
A8 B06 %QX0.z.14 Output 14
B8 B05 %QX0.z.15 Output 15
A9 B04 NC Not Connected
B9 B03 NC Not Connected
A10 B02 %QX0.z.16 Output 16
B10 B01 %QX0.z.17 Output 17
A11 A20 %QX0.z.18 Output 18
B11 A19 %QX0.z.19 Output 19
A12 A18 %QX0.z.20 Output 20
B12 A17 %QX0.z.21 Output 21
A13 A16 %QX0.z.22 Output 22
B13 A15 %QX0.z.23 Output 23
A14 A14 %QX0.z.24 Output 24
B14 A13 %QX0.z.25 Output 25
A15 A12 %QX0.z.26 Output 26
B15 A11 %QX0.z.27 Output 27
A16 A10 %QX0.z.28 Output 28
B16 A09 %QX0.z.29 Output 29
A17 A08 %QX0.z.30 Output 30
B17 A07 %QX0.z.31 Output 31
A18 A06 NC Not Connected
B18 A05 NC Not Connected
A19 A04 NC Not Connected
B19 A03 NC Not Connected
A20 A02 COM Common
B20 A01 COM Common

Note: In the I/O Direct Variable name, z=slot number.

Environmental Specifications

Item Specification Reference
Ambient Operating Temperature 0-55°C (32-131°F) IEC61131-3-2
Storage Temperature -25-70°C (-13-158°F)
Ambient Operating Humidity 5-95% relative humidity (non-condensing)
Storage Humidity 5-95% relative humidity (non-condensing)
Vibration¹ Occasional Vibration: 5 ≤ f < 8.4 Hz: 3.5 mm pulse width IEC61131-3-2
Continuous Vibration: 8.4 ≤ f < 150Hz: 1.75 mm pulse width
Shocks Peak Acceleration: 147 m/s² (15G)
Duration: 11ms
Pulse Wave Type: Half-sine (3 times each direction per each axis) LS Electric standard
Square Wave Impulse Noise 1,500VAC, 900VDC
Electrostatic Discharge Voltage: 4kV (contact discharge) IEC61000-4-2
Radiated Electromagnetic Field Noise 80-1,000 MHz, 10 V/m IEC61131-3-2, IEC61000-4-3
Environment Fast Transient / Burst Noise: Voltage 2kV IEC61131-3-2, IEC61000-4-4
Power Supply: 2kV
Digital/Analog Input/Output: 1kV
Communication Interface: Free from corrosive gases and excessive dust IEC61131-3-2
Attitude Less than 2,000m
Pollution Degree Less than 2 (see note 2)
Cooling Method Air-cooling

¹ Vibration of 10 times each direction (X, Y, and Z).

² Normally only nonconductive pollution occurs. Temporary conductivity caused by condensation is to be expected.

Available I/O Modules

The XGB Series offers a range of I/O modules. Below is a partial list including the XBE-TN32A:

Part Number Price Description Digital Input Digital Output Analog Input Analog Output Motion Bus Coupler Compatible Smart Link Required
XBE-DC08A $61ey: LS Electric XGB discrete input module, 8-point, 24 VDC, sinking/sourcing, 1 common(s), 8 point(s) per common. Removable terminal block included.
XBE-DC16A $;;5]4]: LS Electric XGB discrete input module, 16-point, 24 VDC, sinking/sourcing, 1 common(s), 16 point(s) per common. Removable terminal blocks included.
XBE-DC16B $;5]4?: LS Electric XGB discrete input module, 16-point, 12-24 VDC, sinking/sourcing, 1 common(s), 16 point(s) per common. Removable terminal blocks included.
XBE-DC32A $;;05]4,: LS Electric XGB discrete input module, 32-point, 24 VDC, sinking/sourcing, 1 common(s), 32 point(s) per common. Requires XTB-40H terminal block and C40HH-xxSB-XBI cable.
XBE-AC08A $;5]50: LS Electric XGB discrete input module, 8-point, 120 VAC, 2 common(s), 4 point(s) per common. Removable terminal blocks included.
XBE-RY08A $61eu: LS Electric XGB relay output module, 8-point, 125 VDC/250 VAC, (8) Form A, 1 common(s), 8 point(s) per common, 2A/point, 5A/common. Removable terminal block included.
XBE-RY08B $05]51: LS Electric XGB relay output module, 8-point, 125 VDC/250 VAC, 8 isolated common(s), 1 point(s) per common, 2A/point. Removable terminal blocks included.
XBE-RY16A $05]52: LS Electric XGB relay output module, 16-point, 125 VDC/250 VAC, (16) Form A, 2 isolated common(s), 8 point(s) per common, 2A/point, 5A/common. Removable terminal blocks included.
XBE-TN08A $61ev: LS Electric XGB discrete output module, 8-point, 12-24 VDC, sinking, 1 common(s), 8 point(s) per common, 0.5A/point, 2A/common. Removable terminal blocks included.
XBE-TN16A $5]54: LS Electric XGB discrete output module, 16-point, 12-24 VDC, sinking, 1 common(s), 16 point(s) per common, 0.5A/point, 2A/common. Removable terminal blocks included.
XBE-TN32A $05]55: LS Electric XGB discrete output module, 32-point, 12-24 VDC, sinking, 1 common(s), 32 point(s) per common, 0.2A/point, 2A/common. Requires XTB-40H terminal block and C40HH-xxSB-XBI cable.
XBE-TP08A $61ex: LS Electric XGB discrete output module, 8-point, 12-24 VDC, sourcing, 1 common(s), 8 point(s) per common, 0.5A/point, 2A/common. Removable terminal blocks included.
XBE-TP16A $5]56: LS Electric XGB discrete output module, 16-point, 12-24 VDC, sourcing, 1 common(s), 16 point(s) per common, 0.5A/point, 2A/common. Removable terminal blocks included.
XBE-TP32A $05]57: LS Electric XGB discrete output module, 32-point, 12-24 VDC, sourcing, 1 common(s), 32 point(s) per common, 0.2A/point, 2A/common. Requires XTB-40H terminal block and C40HH-xxSB-XBI cable.
XBE-DN32A $05]53: LS Electric XGB discrete combo module, Input: 16-point, 24 VDC, sinking/sourcing, Output: 16-point, 12-24 VDC, sinking, 0.2A/point, 2A/common. Requires XTB-40H terminal block and C40HH-xxSB-XBI cable.
XBE-DR16A $061e#: LS Electric XGB discrete combo module, Input: 8-point, 24 VDC, sinking/sourcing, Output: 8-point, 125 VDC/250 VAC, relay, (8) Form A (SPST) relays, 2A/point, 5A/common. Removable terminal blocks included.
XBF-PN04B $;;051,5: LS Electric XGB 4-axis positioning module, EtherCAT Master, 1 high-speed input point(s), sinking/line driver (differential), 1-channel, differential and single-ended encoder input(s), (1) Ethernet 100Base-TX (RJ45) port(s). For use with LS Electric XEM-DxxxHx PLCs.
XBF-PN08B $;;051,6: LS Electric XGB 8-axis positioning module, EtherCAT Master, 1 high-speed input point(s), sinking/line driver (differential), 1-channel, differential and single-ended encoder input(s), (1) Ethernet 100Base-TX (RJ45) port(s). For use with LS Electric XEM-DxxxHx PLCs.
XBF-HO02A $;05]5e: LS Electric XGB counter input module, 200 kHz maximum switching frequency, 2 high-speed input point(s), 5-24 VDC, sinking, 2-channel, single-ended encoder input(s), 2 high-speed output point(s), 5-24 VDC, sinking, external 24 VDC required.
XBF-HD02A $;;05]5f: LS Electric XGB counter input module, 500 kHz maximum switching frequency, 2 high-speed input point(s), 5-24 VDC, sinking, 2-channel, differential encoder input(s), 2 high-speed output point(s), 5-24 VDC, sinking, external 24 VDC required.

Note: See "Smart Link I/O System" on page tLSE-131 for the XTB-40H terminal block and cables. See "XGB PLC Replacement Terminals" on page tLSE-149 for replacement removable terminal blocks.

Smart Link I/O System, Terminals and Cable Connections

The Smart Link I/O system is a breakout wiring system for high-density I/O modules in the LS Electric XGB PLC series. It is required for all modules with a 40-pin connection and consists of a Smart Link cable with an XTB-40H terminal block.

XGB Accessories

Part Number Price Description Length Compatible With
XTB-40H $;-5]51: LS Electric XGB terminal block, 40-pin screw type. For use with LS Electric XGB series high-density modules. n/a n/a
XTB-40H-LABEL $61e_: Automation Direct terminal label sheet, printed with terminal names for LS Electric XGB series modules. Package of 8. For use with XTB-40H terminal block. n/a n/a
C40HH-05SB-XBI $;-5]5i: LS Electric XGB PLC I/O cable, 1.6ft/0.5m cable length, 40-pin connector to 40-pin connector. For use with LS Electric XGB series high-density modules. 0.5 m All LS XGB series PLCs and modules with 40-pin connectors
C40HH-10SB-XBI $;-5]5j: LS Electric XGB PLC I/O cable, 3.2ft/1m cable length, 40-pin connector to 40-pin connector. For use with LS Electric XGB series high-density modules. 1m All LS XGB series PLCs and modules with 40-pin connectors
C40HH-15SB-XBI $;5]5k: LS Electric XGB PLC I/O cable, 4.9ft/1.5m cable length, 40-pin connector to 40-pin connector. For use with LS Electric XGB series high-density modules. 1.5 m All LS XGB series PLCs and modules with 40-pin connectors
C40HH-20SB-XBI $;5]50: LS Electric XGB PLC I/O cable, 6.5ft/2m cable length, 40-pin connector to 40-pin connector. For use with LS Electric XGB series high-density modules. 2m All LS XGB series PLCs and modules with 40-pin connectors
C40HH-30SB-XBI $;5]5p: LS Electric XGB PLC I/O cable, 9.8ft/3m cable length, 40-pin connector to 40-pin connector. For use with LS Electric XGB series high-density modules. 3m All LS XGB series PLCs and modules with 40-pin connectors

XTB-40H Specifications

Item Specification
Number of Pins 40 pin
Terminal Pitch 7.0 mm
Connector Type MIL-C-83503
Applicable Wires AWG22-16 (1.5mm²/MAX)
Insulation Resistance 100MΩ (500VDC)
Dielectric Strength 500VAC 1 minute
Screw M3 x 8L
Screw Torque 1.2N.m (12kgf.cm)
Ambient Temperature -10°C to +50°C (no freezing)
Material
Case Modified PPO
Protective Cover Polycarbonate
PCB Epoxy 1.6t

Module to Cable to Terminal Pinouts

This section provides detailed pinout information for connecting the module to the terminal block via the cable.

Module Pins | C40HH-xxSB-XBI Cable | XTB-40H Terminal

B20 | HIROSE HIF3BA-40D-2.54R (Module Side) | A1

B19 | HIROSE HIF3BA-40D-2.54R (Module Side) | B1

B18 | | A2

B17 | | B2

B16 | | A3

B15 | | B3

B14 | | A4

B13 | | B4

B12 | | A5

B11 | | B5

B10 | | A6

B09 | | B6

B08 | | A7

B07 | | B7

B06 | | A8

B05 | | B8

B04 | | A9

B03 | | B9

B02 | | A10

B01 | | B10

A11 | | A11

B11 | | B11

A12 | | A12

B12 | | B12

A13 | | A13

B13 | | B13

A14 | | A14

B14 | | B14

A15 | | A15

B15 | | B15

A16 | | A16

B16 | | B16

A17 | | A17

B17 | | B17

A18 | | A18

B18 | | B18

A19 | | A19

B19 | | B19

A20 | | A20

B20 | | B20

PDF preview unavailable. Download the PDF instead.

xbetn32a

Related Documents

Preview LS Electric Factory Automation Solutions
Explore LS Electric's comprehensive range of factory automation products, including PLCs, HMIs, Motion Controllers, Servo Systems, and Gearboxes. Discover solutions for smart factory integration and efficient industrial operations.
Preview LS ELECTRIC XGB EtherCAT Multi-Axis Positioning Modules: XBF-PN04B and XBF-PN08B
Detailed specifications and wiring examples for LS ELECTRIC XGB series EtherCAT multi-axis positioning modules, including the XBF-PN04B (4-axis) and XBF-PN08B (8-axis). Covers general specifications, encoder input details, pin assignments, variable assignments, setup examples, and wiring configurations for line driver, open collector, and totem pole encoder types.
Preview LS ELECTRIC H100 Extension I/O Module User Manual
Comprehensive user manual for the LS ELECTRIC H100 Extension I/O module (model EIOE-H100). This guide details installation, configuration, operation, and safety for extending LSLV-H100 series inverter capabilities with digital and analog I/O.
Preview LS Electric XGB PLC: Advanced Automation, Affordable Price
Discover the LS Electric XGB PLC, a compact and powerful programmable logic controller offering advanced motion control, IEC 61131 programming, extensive I/O options, and free software. Learn about its versatility, reliability, and cost-effectiveness for industrial automation.
Preview LS XGB Cnet XBL-C21A, C41A Programmable Logic Controller Installation Guide
This guide provides essential information for installing and operating the LS XGB Cnet XBL-C21A and XBL-C41A Programmable Logic Controllers. It covers safety precautions, operating environment, software compatibility, wiring, module installation, and warranty details.
Preview LS ELECTRIC H100 Extension IO2 Module User Manual
User manual for the LS ELECTRIC H100 Extension IO2 module, detailing installation, specifications, operations, and parameters for LSLV-H100 series inverters.
Preview LS Smart I/O Pnet GPL-DV4C/DC4C Programmable Logic Controller Installation Guide
Installation guide for LS ELECTRIC's Smart I/O Pnet Programmable Logic Controllers (PLCs), models GPL-DV4C and GPL-DC4C. Covers safety precautions, operating environment, specifications, wiring, and warranty information.
Preview LS ELECTRIC G100 PROFIBUS-DP Communication Module User Manual
This manual provides detailed information on the LS ELECTRIC G100 PROFIBUS-DP communication module, including its features, technical specifications, installation, operation, and troubleshooting. Learn how to connect the LSLV-G100 inverter to a PROFIBUS network for enhanced automation and control.